The supporter is flat and horizontal and can afford the weigh of
1. INSTALLATION PRECAUTION outdoor unit, without noise and vibration.
To install properly, please read this manual at first. The noise and the outlet air will not influence your neighbor.
When installing the indoor unit or its tubing, please follow this Place convenient for piping and wiring.
manual as strictly as possible.
Please keep away from the following places, or malfunction may
When all the installation work is finished, please turn on the power be caused.(if unavoidable, please consult the professionals):
only after a thorough check.
There is mineral oil like the oil of cutting machine.
No further announcement if there is any change of this manual
caused by product improvement. There is much salty air. (Near the coast)
installation manual
1
NOTE 3 Mounting screw
No other equipment has to be connected with this power Never throw or beat the controller.
line.
Before installation, operate the remote controller to determine
For detailed installation acceptance, please refer to your its location in a reception range.
contract with the power supplier if restrictions do apply for
products like washing machines, air conditioners or Keep the remote controller at least 1m apart from the nearest
electrical ovens. TV set or stereo equipment. (It is necessary to prevent image
disturbances or noise interferences.)
For power details of the air conditioner, refer to the rating
plate of the product. Do not install the remote controller in a place exposed to direct
sunlight or close to a heatingsource, such as a stove. Note that
For any question contact your local dealer. the positive and negative poles are in right positions when
loading batteries.
3. ACCESSORIES
Table.3-1
4. INDOOR UNIT INSTALLATION
Name of Installing 10 Hanging Screw Bolts (4 Bolts)
Qty Outline Usage
Accessories
Please refer to the following figure for the distance measurement
Installation manual 1 (This manual)
between the screw bolts.
Wired controller Control the
1
air-conditioner Please install with screw bolts.
42-48MBH 2 The handling to the ceiling varies from the constructions, consult
Pipe insula- Heat insulation the construction personnels for the specific procedures.
tion material 75-96MBH 4
Water outlet joint 1 For drainage The size of the ceiling to be handled.Do keep the ceiling flat.
Consolidate the roof beam for possible vibration.
Chucking the joint which
42-48MBH
connect the drain hose Cut off the roof beam.
Clasp 1
and the outlet of indoor
unit Strengthen the place cut off, and consolidate the roof beam.
Water connec-
1 To connect drain pipe Carry out the pipe and line operation in the ceiling after finishing
ting pipe
75-96MBH the installation of the main body. While choosing where to start
Adhesive tape
1 To connect drain pipe the operation, determine the direction of the pipes to be drawn
for seal
out. Especially in case there is a ceiling, position the refrigerant
The indoor unit which at the
pipes, drain pipes, indoor & outdoor lines to the connection
terminal of communication places before hanging up the machine.
Network matching wire 1 system shouldconnect a
impedance between port The installation of hanging screw bolts.
P and port Q
42-48MBH 1 Use for pipe connection Wooden construction
Copper nut of engineering installation
75-96MBH 2 Put the square timber traversely overthe roof beam, then
install the hanging screw bolts. (Refer to Fig.4-1)
The following are selectable accessories
Remote controller & Its Frame Timber over the beam
1. Remote controller....................................1
Ro of beam
Ce iling
Fig.4-2
installation manual
2
For original concrete bricks
Use embeding screw bold, crock and stick harmness (refer
to Fig.4-3)
Steel bar
Supporting
Hanging bolts angle steel
Fig.4-4
Overhang the indoor unit onto the hanging screw bolts with
block.
Position the indoor unit in a flat level by using the level indicator,
unless it may cause leakage.
Fig.4-7
Screw nut
washer
Overhang part
Hanging
screw bolt
Fig.4-5
Clean the air filter (Vacuum cleaner or pure water may be The positioning of ceiling hole and indoor unit and hanging
used to clean the air filter. If the dust accumulation is too screw bolts
heavy , please use soft brush and mild detergent to clean it
and dry out in cool place). Routine method of installation: the size of installation for indoor
unit following Fig.4-9
The air-in side should face down when using water.
(See Fig.4-7) Please install with 10 hanging screw bolts.
Carry out the pipe and line operation in the ceiling after finishing
The air-in side should face up when using vacuum cleaner. the installation of the main body. While choosing where to start
(See Fig.4-8) the operation, determine the direction of the position the
refrigerant pipes, drain pipes, indoor & outdoor lines and
line-controlled lines to the connection places before.
installation manual
3
The positioning of ceiling hole and indoor unit and hanging screw bolts
routine method of installation: the size of installation for indoor unit following the Fig.4--9 and Fig.4-10
29
56
82
82
249
420
270
PLASTIC COVER
68 24
46 ELECTRICAL CONTROL BOX
1148
137 800 90 169
CONNECTING POINT OF
15
15
69
50
DRAIN PIPE
52
136
4-5 HOLES FOR AIR
179
AIR INTAKE DUCT FLANGE
189
14
123
11
123
638
600
638
691
REFRIGERANT-PIPE FLANED
CONNECTION 16(5/8)
253
61 6-5 HOLES FOR AIR
AIR OUTLET DUCT FLANGE OUTLET DUCT CONNECTION
37
15
75
35
17
65 400 400
136
SAFETY DRAIN CONNECTING PIPE 125
1148
1300
AIR OUTLET
339
82
82
31
Fig.4-9
64 1073
48 MBH 952
214
85
420
PLASTIC COVER
AIR INTAKE
4-12*25 OBLONG SUSPENTION BOLT HOLES
CONNECTING POINT OF
800
DRAIN PIPE
189
189
REFRIGERANT-PIPE FLANED 43
CONNECTION 9.52(3/8)
44
REFRIGERANT-PIPE FLANED
CONNECTION 16(5/8)
123
123
690
642
26
253
Fig.4-10
65 722 65
installation manual
4
Fig.4-11
Position A
Water Tray
Position B
12 Screw
For fixing the safety drain tray
Fig.4-12
CAUTION
1. Please shut down the unit and cut off power cable before maintain the motor.
2. Dont heavy pull the foam tray, when dismounting; otherwise the foam tray would break.
installation manual
5
The method of installation: Adopt following method if the air-conditionings size of installationsite is limited and the indoor unit cant put into the
installtionsite.
48 MBH
Fig.4-13
Position A
Water Tray
Position B
11-Screw
CAUTION
1. Please shut down the unit and cut off power cable before maintain the motor.
2. Dont heavy pull the foam tray, when dismounting; otherwise the foam tray would break.
installation manual
6
maintenance of motor
4 Bolts
For fixing the fan assembly
Filter
Motor Assembly
Fig.4-15
Inside of structure
Front view of fan assembly installation state
Side view of fan assembly
installation state
Pothook
Scroll
Move
CAUTION
1. Please shut down the unit and cut off power cable before maintain the motor.
2. Before dismount the fan assembly, you must remove the motor and electric control box, as well as connective wires between motor and
capacity assembly.
3. Fan subassembly is very heavy, please be careful during maintaining, otherwise physical injury would be caused.
installation manual
7
maintenance of motor
motor
4 Bolts
For fixing the fan assembly
FIiler
Fortified panel
Motor Asseembly
4 Screw
For fixing the reinforced panel
Inside of structure
Front view of fan assembly installation state
Scroll
Pothook
Fig.4-18
The state after fan assembly is taken off
1. Refer to Fig.4-17, remove all 11 bolts from safety drain tray, and take off the safety drain tray.
2. Refer to Fig.4-17, remove all 4 bolts from reinforced panel, and take off the panel.
3. Refer to Fig.4-17, remove all 4 bolts from fan assembly, see Fig.4-18, according to which orders to take off the fan assembly.
4. Refer to Fig.4-18, horizontal pushing the fan assembly, until it cannot not move any further, and then lift up slightly and take down to remove it.
5. After motor maintenance, reinstall the fan assemblies as per the reverse above orders. And connect the motor with electric control box,
as motor with power cable of capacity.
CAUTION
1. Please shut down the unit and cut off power cable before maintain the motor.
2. Before dismount the fan assembly, you must remove the motor and electric control box, as well as connective wires between
motor and capacity assembly.
3. Fan subassembly is very heavy, please be careful during maintaining, otherwise physical injury would be caused.
installation manual
8
75 MBH
85 MBH
96 MBH 1121 75
60
96
343
Entrances and exits
for communication
lines of indoor and outdoor
Air outlet
4-12*25 oblong
suspention 1443
470
bolt holes
Electrical
parts box 4-10 hanging screw
Air outlet
(configure on spot)
duct flange
810
Refrigerant-pipe flared Connecting point
connection9.52(3/8) of drain pipe
Air intake
duct flange
66
Refrigerant-pipe flared
69
connection16(5/8)
55
Air intake
936 200
378
50
Fig.4-19
The method of installation: adopt following method if the air-conditionings size of installation site is limited and the indoor unit cant put into
the installation site.
Fig.4-20
screw
cover plate B
cover plate A
A
Part A of
indoor unit A
bolt C
B
bolt A C Fig.4-21
installation manual
9
1 The indoor unit show as Fig.4-20 NOTE
2 Following Fig.4-21 twist-off the screws, along the direction of A During teardown and installation, the scroll was allowed direct
get off the cover plate A and cover plate B. support by hand
3 Dismounting bolt A
Fan subassembly is more weightiness, please take careful
4 Dismounting bolt C during teardown and installation, and keep from hurt by fan
subassembly.
5 Along the direction of B and C divided the part B and part C of
indoor unit.
6 The part A and part B of indoor unit individual put into the
positionsite, then install the indoor unit following the reverse
order of step 2,3,4 and 5.
5. INSTALLATION SPACE
Maintenance of motor
500mm or mo re
Maintenance roomage
bolt
600mm or mo re
Maintenance roomage
600mmX600mm
checking orifice
motor
assembly
Fig.5-1
bottom
cover plate
screw
pothook
Confirm the minimum
drain tilt is 1/100 or more
checking orifice Fig.5-2
Panel installation
Inside frame
Knob
3 Support the fan subassembly from the bottom, then litter up,
get down fan subassembly.
installation manual
10
6. HIGH STATIC PRESSURE TYP
75MBH(50hz) 75MBH(60hz)
P(Pa)
P(Pa)
300 300
280 280
260 260
160 160
Low speed
Low speed
140 140
120 120
100 100
80 80
60 60
40 40
20 20
0 0
1000 1500 2000 2500 3000 3500 4000 4500 5000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000
Q(m3/h) Q(m3/h)
Fig.6-4
Fig.6-1
75MBH(60hz)
P(Pa)
42MBHkW(50hz)
P(Pa)
300
280
48MBH(50hz)(Two Air Outlet)
300
260
280
160
Low speed 180 Midium speed
140 160
80 100
60 80
40 60
20 40
0 20
1500 2000 2500 3000 3500 4000 4500 5000 5500 6000
0
Q(m /h)
3
500 1000 1500 2000 2500 3000 3500 4000
Q(m3/h)
Fig.6-2 Fig.6-5
85MBH(50hz) 42MBH(60hz)
P(Pa)
P(Pa)
96MBH(50hz) 48MBH(60hz)
300 300
280 280
260 260
220
220 High speed
200 Midium speed
200
180
180 Midium speed
160 Low speed
160
140 Low speed
140
120
120
100
100
80
80
60
60
40
40
20
0 20
2000 2500 3000 3500 4000 4500 5000 5500 6000
0
Q(m3/h) 500 1000 1500 2000 2500 3000 3500 4000
Q(m3/h)
Fig.6-3
Fig.6-6
installation manual
11
Heat insulated components
P(Pa)
Provided at field
48MBH(50hz)(One Air Outlet)
300
Heat insulated components Intake flange Intake flange
280 Provided at field Provided at fieldProvided at field
260
240
High speed Outer wall
220
Slope down Main body
200
Midium speed
180
Low speed
Air blowout side Air intake side
160
140
Cover cap Canvas fan duct
120
(Provided at field) (Provided at field)
100
80
60
Fig.7-2
40
20
The air filter is not the standard accessory, but please must be
0
800 1000 1200 1400 1600 1800 2000 installed air filter in the air intake side of the fan duct system. Use
Q(m3/h)
the dust arrest efficiency (use gravimetric method) with above
50%.
Fig.6-7
Make sure the air intake side of fan duct slope down. Then it can
prevent water logging.
Select the fan duct, and make the intake side can intake the
outside air.
7. DUCT DESIGN Otherwise, the units can not run normally.
Please heat insulating the fan duct for avoiding condensation.
(Material: glass wool or polyethylene foamed, thickness: 25mm)
If use the mental fan duct to make through the mental iron wire,
Cover the pipe before connecting to keep rubbish, dust or other iron net or mental panel of the wooden building, then it must do the
impurities out. (electronic) insulating for the fan duct and the wall.
Outer wall
Isolation booth
Air outlet Isolation booth
checking orifice
Air dust filter
9. CONNECTION CONDITION
Fig.7-1
The total connected capacity of the standard indoor units and fresh
air treatment units must be between 50% and 100% of the capacity
8 Installation of fan duct of the air conditioning outdoor units. the connected capacity of the
Connect the fan duct as the following. (Refer to Fig.7-2 ) (Air intake fresh air treatment units must not exceed 30% of the capacity of the
side) air conditioning outdoor units.
Connecting air duct and intake flange Provided at field not exceed 30% of the capacity of the air conditioning outdoor units.
Use aluminum adhesive tapes etc. to seal the connecting Then fresh air treatment unit can also be used exclusively. the
parts of the intake flange and fan duct, for avoiding air leakage. connected capacity of the fresh air treatment unit must bebetween
(Air blowout side) 50% and 100% of the capacity of the air conditioning outdoor unit.
Connecting air duct and blowout flange Attached by main body Only connectable to outdoor unit.
Use aluminum adhesive tapes etc. to seal the connecting parts
of the blowout flange and fan duct, for avoiding air leakage. System example: check that system connected capacity
Use the bolts (Accessory 8) to connect the blowout flange with the is within the appropriate range.
units.
installation manual
12
fresh air Be sure to use two wrenches simultaneously when you connect
5HP treatment unit or disconnect the pipes.
Total connected capacity of standard indoor units and fresh air Notices For Benable pipe.
treatment unit does not exceed 100%. system capacity of 20 HP =
indoor unit capacity of 20 HP. The bending angle should not exceed 90
Connected capacity of fresh air treatment unit does not exceed
30% of this since system capacity of 20 HP x 0.3 = 6 HP > fresh air Bending position is preferably in the bendable pipe. The larger
treatment unit capacity = 5 HP the better it is .
14kW indoor unit (one air outlet) should be matched with a 14kW
outdoor unit. Do not bend the pipe more than three times.
Check whether the height drop between the indoor unit and
outdoor unit, the length of refrigerant pipe, and the number of
Bend the pipe with thumb
the bends meet the following requirements:
The max height drop and The length of refrigerant pipe deponding
on the ouotdoor unit.(If the height drop is more than 10m, you
had better put the outdoor unit over above the indoor unit.)
Fig.11-2
The number bends fewer than 15.
Do not let air, dust, or other impurities fall in the pipe system Make the ends
straight
during the time of installation.
Fig.11-3
The connecting pipe should not be installed until the indoor and
outdoor units have been fixed already.
Keep the connecting pipe dry, and do not let moisture in Locate The Pipe
during installation.
Drill a hole in the wall (suitable just for the size of the wall conduit,
The Procedure of Connecting Pipes 90mm in general), then set on the fittings such as the wall conduit
Measure the necessary length of the connecting pipe, and make and its cover.
it by the following way.
Bind the connecting pipe and the cables together tightly with
Connect the indoor unit at first, then the outdoor unit. binding tapes. Do not let air in, which will cause water leakage
by condensation.
Bend the tubing in proper way. Don,t harm them.
Pass the bound connecting pipe through the wall conduit from
Daub the surfaces of the flare pipe and the joint nuts with frozen outside. Be careful of the pipe all ocation to do no damage to the
oil, and wrench it for 3~4rounds with hands before fasten the tubing.
flare nuts. (Refer to Fig.11-1)
Connect the pipes.
installation manual
13
Then, open the stem of stop valves of the outdoor unit to make
the refrigerant pipe connecting the indoor unit with the outdoor
45+_2
unit fluently flow.
90+4
A
_
Be sure of no leakage by checking it with leak detector or soap Fig.12-3
water.
Cover the joint of the connecting pipe to the indoor unit with the
Table.12-1
sound proof/insulating sheath (fittings), and bind it well with the
tapes to prevent leakage. A(mm)
Outside diameter
Max Min
Fig.12-4
Table.12-2
6.4mm 14.4~17.2N.m
12.7mm 49.5~60.3N.m
12.2 Check The Leakage 15.9mm 61.8~75.4N.m
Check all the joints with the leak detector or soap water. (See 19.1mm 92.7~118.6N.m
Fig.10-6 as a reference illustration)
Be sure to with insulating materials cover all the exposed parts Loosen and remove the maintenance nuts of stop valves A and
of the flare pipe joints and refrigerant pipe on the liquid-side and B, and connect the charge hose of the manifold valve with the
the gas-side. Ensure that there is no gap between them. maintenance terminator of stop valve A. (Be sure that stop
valves A and B are both closed)
Incomplete insulation may cause water condensation.
Connect the joint of the charge hose with the vacuum pump.
installation manual
14
Turn on the vacuum pump. At the beginning of pumping, loosen With the connection part to the indoor unit, please be noted
the maintenance terminator nut of stop valve B a little to check not to impose pressure on the side of indoor unit pipes.
whether the air comes in (the sound of the pump changes, and
the indicator of compound meter turns below zero). Then fasten When the declivity of the drain pipe downwards is over 1/100,
there should not be any win ding.
the nut.
The total length of the drain pipe when pulled out traversely
When the pumping has finished, close the Lo-lever of the manifold
shall not exceed 20m, when the pipe is over long, a prop stand
valve completely and turn off the vacuum pump.
must be installed to prevent winding.
When you have pumped for over 15 minutes, please confirm Refer to the figures on the right for the installation of the pipes.
that the indicator of multimeter is on -1.0X105Pa (-76cmHg)
Loosen and remove the quadrangle cover of stop valves A and 1.5M~2M
B to open stop valve A and B completely, then fasten them.
Bend Fig.13-1
Manifold valve
S shap
Multi-meter Pressure meter
-76 cmHg
Hi-lever
Lo-lever
Put as deep as possible
Charge hose (about 10mm)
Charge hose
Caution: While connecting the drain pipe, please use the drain pipe
connect to the secondary water holder simultaneously, for avoiding
All the stop valves should be opened before test operation. there are little condensate water deposit in the unit when the machine
Each air conditioner has two stop valves of different sizes on is running under the high humidity working condition.
the side of the outdoor unit which operate as Lo-stop value,
respectively. (Refer to Fig.10-6)
Flare nut
14. WIRING
Stopper
Cap
Attaching wiring
Valve body
Fig.12-6
Valve stem
The air conditioner should use separate power supply with rated
voltage.
13. CONNECT THE DRAIN PIPE The wiring work should be done by qualified persons according
to circuit drawing.
CAUTION The wiring attached to this air conditioner is 10m long. Be sure
to prolong it with wiring of the same type and proper length
The drain pipe of indoor unit must be heat insulated, or it will if necessary. Generally, do not twist two wiring together unless
condense dew, as well as the connections of the indoor unit. the joint is soldered well and covered with insulator tape.
Hard PVC binder must be used for pipe connection, and make Do not turn on the power until you have checked carefully after
sure there is no leakage. wiring.
installation manual
15
The Specification of Power Terminal board diagram
Table.14-1
Please refer to the indoor unit wiring diagram for the detailed
wiring. In accord with the communication wiring, terminal board
Phase 1-Phase
wiring is different according to the horsepower of air-condictioners.
Power
Frequency and volt 220-240V~50Hz 208-230V~60Hz
The wiring of model 42 and 45, please refer to Fig.14-3,
and Fig.14-4 is the wiring for model 75,85 and 96.
42/45(Two Air Outlet)
Capacity(MBH) 45(One Air Outlet)
75/85/96 42/45(Two Air Outlet) 75/85/96
INDOOR UNIT
YELLOW/GREEN
OUTDOOR UNIT
XT2 XT3
PQE L N
COMPUTER
Fig.14-1
15. CONTROL
OUTDOOR UNIT
Horsepower set
PQE
INDOOR UNIT INDOOR UNIT INDOOR UNIT INDOOR UNIT Base on different purposes to set the switch codes on the main
XT2 XT3 XT2 XT3 XT2 XT3 ...... XT2 XT3
PQE PQE boards of indoor unit, Once finish the setting, please cut off the
main power, and then switch on the power again. Otherwise,
XYE XYE
setting functions could not work.
CENTRAL CONTROL
MONITOR (CCM)
Horsepower code
POWER_S
F1F2E
COMPUTER
F 012
BC E
3456
D
789A
Fig.14-2
ENC1
Fig.15-1
installation manual
16
Table.15-1 SW 1 Difinition
SW1 1 means factory test mode
ENC1 Toggle switch For set horsepower ON 0 means auto addressing mode
1234 (default setting)
Code Capacity(Horsepower)
SW1 1 means DC fan is chosen
0 7000 BTU(0.8HP) ON 0 means AC fan is chosen
1234
1 9000 BTU(1.0HP)
SW1 0 0 means DC fanstatic pressure
2 12000 BTU(1.2HP) ON
is 0 (reserved)
1234
Note: 3 15000 BTU(1.5HP)
The horsepower has SW1
0 1 means DC fanstatic pressure
been set before 4 18000 BTU(2.0HP) ON
is 1 (reserved)
leaving the factory, 1234
5 24000 BTU(2.5HP)
anyone cant modify SW1
it except the 10 means DC fanstatic pressure
6 27000 BTU(3.0HP) ON
maintenance person. is 2 (reserved)
1234
7 31000 BTU(3.2HP)
SW1
34000 BTU(4.0HP) ON 11 means DC fanstatic pressure
8 1234 is 3 (reserved)
38000 BTU(4.0HP)
J1
with jumper " J1 " f or
non-auto restart function
NOTE
J2
r eserve d
75MBH: Please dial switch ENC1 to 8 (both system A and B).
85MBH: Please dial switch ENC1 to 9 for system A and 8 for
system B. SW 2 Difinition
96MBH: Please dial switch ENC1 to 9 (both system A and B).
SW2 00 means shutting down the unit
ON to stop cold air at 15
1234
SW2 01 means shutting down the unit
Network Address Setting
ON to stop cold air at 20
1234
When outdoor unit set the code to be found address SW2 10 means shutting down the unit
automatically, the new indoor unit do not need to set the ON to stop cold air at 24
indoor unit address, at this time the outdoor unit will 1234
distribute different addresses for indoor units
SW2 11 means shutting down the unit
automatically.
ON to stop cold air at 26
When outdoor unit set the code to be found address 1234
non-automatically, all the indoor units must set the system SW2 00 means the time of stopping
addresses by remote controller first (For the setting system ON TERMAL fan is 4 mintue
address of indoor unit which has two or more main boards, 1234
it has to separate use the display board connected with SW2
ten-core connecting wire to set the address for each 01 means the time of stopping
ON
mainboard). TERMAL fan is 8 mintue
1234
The setting of network address is through the SW2
10 means the time of stopping
ON
communication of indoor and outdoor units, its address is TERMAL fan is 12 mintue
the same as the indoor unit system address, and not need 1234
to set separate. SW2 11 means the time of stopping
ON TERMAL fan is 16 mintue
When all indoor units are TVR 4G series indoor unit, the 1234
central controlling of indoor unit can be finished in the
outdoor unit, and not need to make central control in the
SW 5 Difinition
indoor unit, the detail please refers to the TVR 4G outdoor
unit instruction manual. SW5
ON 00 means temp. compensation value
is 6 under heat mode (reserved)
For the previous indoor units central control function, can 12
use (X, Y, E) terminal to connect and form the central SW5
01 means temp. compensation value
control group, at this time there is not need to set the ON
network address, and also can use outside setting network
is 2 under heat mode (reserved)
12
module, mainboard (CN20) to form network.
SW5
10 means temp. compensation value
ON
Mainboard codes indication label is 4 under heat mode (reserved)
12
SW5 11 means temp. compensation value
ON
is 8 under heat mode (reserved)
12
installation manual
17
SW6 Difinition
SW6 16. TROUBLE SHOOTING
ON 1 means old display panel
0 means new display panel
123 Table.16-1
SW6 1 means auto air blow under
ON auto mode (reserved) NO. Type Contents Digital LED display Remarks
0 means auto air blow under
123 non-auto mode (reserved)
SW6 The evaporator
ON sensor check
reserved Error code After the malfunctions
Malfun- point is abnomal
123 1 H1,H2,H3, disappear, it restores
ction or room temp.
E2,E3 or E4 automatically.
sensor is
SW7 Difinition 0/1 Difinition abnormal.
SW7
ON standard Indoor/outdoor unit Error code After the malfunctions
ON means 0 Malfun- communication
configuration 2 E1 disappear, it restores
12 ction is abnormal. automatically.
SW7 last unit of
ON ON means 1
the network After the malfunctions
12 Malfun- Outdoor unit Error code
3 disappear, it restores
ction abnormal Ed
automatically.
If the malfunctions
CAUTION cant be solved in
Malfun- Water level switch Error code three min. all the
4 ction is abnormal EE indoor alarm lamps
Please adjust the code ENC1 to the suitable position (both
system A and B should be adjusted for Model 75,85 and 96). flash at 0.5Hz.Turn
off the power to restore.
For the same indoor unit, every mainboard must be differ- The indoor unit Error code After the malfunctions
ent indoor unit addresses and network addresses. without an add- FE disappear, it restores
7 Alarm ress when it is
automatically.
When using central controller to control the indoor unit, first time electri-
please pay attention to the address setting, as the model fied
75, 85 and 96 have two or more mainboards. We suggest
setting the neighbor address for the mainboards in the
same indoor unit. When using a central controller for
controlling, mainboards in the same unit must be opened PRE-DEF indicator(cooling and heating type)
and closed at the same time, for avoiding the unexpected Temporary button or fan only indicator(cooling only type)
incident. Infrared signal receiver
Fig.16-1
Connective Pipe 1
Connective Pipe 2
Fig.17-1
installation manual
18
There is no obstacle at the outlet and inlet of the outdoor and
18. INSTALL BRANCH PIPE indoor and indoor units
Install vertically Whether the buttons on the remote controller works well.
Main pipe is vertical
to horizontal plane
Whether the air flow louver moves normally.
Install horizontally
A
Whether the indicator lights normally.
B
Whether the temporary buttons works well.
CAUTION
19. TEST OPERATION
Protection function will delay the startup of compressor for 3 minutes
in case the unit is turned on immediately after power on or restarted
after shutdown.
The test operation must be carried out after the entire installation
has been completed.
The length of the tubing and the added stow capacity of the
refrigerant have been recorded.
The power voltage fits the rated voltage of the air conditioner.
installation manual
19