TABLE OF CONTENTS
II. Description 4
`
Operation Manual
GENERAL INFORMATION
IMPORTANT
Before installing or operating the generator control panel, read this
instruction book thoroughly.
Transportation Damage:
Immediately upon receipt of the generator control panel, an examination should be made
for any damage or loss sustained during transportation. If damage or rough handling is
evident, a damage claim should be filed at once with the transportation company and the
Enercon Systems International, LLC, sales office should be promptly notified.
Unpacking:
The generator control panel should be unpacked as soon as possible after being received.
Failure to do so may cause difficulty in making claims for damage not evident upon receipt.
Care should be used in unpacking in order to avoid damaging any of the generator control
panel components. Be sure that no loose parts are missing or left in the packing material.
Blow out any dirt or foreign material that may have accumulated on and in the generator
control panel or its components.
Storage:
If the generator control panel is not to be installed in its permanent location at once, it
should be stored in an upright position in a clean and dry environment.
Interconnection:
Control wire interconnections between the generator control panel and all external
equipment are illustrated in the interconnection diagram. All wiring shown with solid lines
are connection made by Enercon. All connections shown with dashed lines are connections
that the user must make, to complete the installation. Unless otherwise noted on the
interconnect drawing, all control wiring is to be #14 AWG or larger.
Be sure to observe minimum wire sizes when they are called out. If the Engine-Generator is
located over one hundred (100) feet from the Generator Control Panel, special
consideration must be given to the control wire size.
If revisions or changes are made to the current transformers (CT), be sure the white dot is as
shown on the drawings, that the black leads are grounded, and the phase rotation is as
indicated on the drawings.
Cable entrance area and component locations are all given on the outline drawing.
Page 1 ES-1032
Operation Manual
GENERAL INFORMATION
WHEN TO INSPECT:
Since maintenance requirements are low, it is recommended that a routine inspection
be performed at the end of the first six months of operation.
Inspect at least once a year thereafter or if the initial inspection indicates, then more
often.
CAUTION:
NEVER WORK ON ENERGIZED ELECTRICAL EQUIPMENT.
Disable switchboard by shutting down all generators.
INSPECTION:
Clean all dust and debris, which could lead to future dielectric problems from the
interior and exterior of each cubicle with a vacuum cleaner or non-metallic brush.
Inspect all internal components and wiring for signs of excessive heating and/ or
deteriorated insulation, especially at high stress points such as door cables.
Check 'plug-in' relays for proper seating in sockets.
Manually operate all control circuit breakers two or three times, checking operation
for any abnormality.
Correct all defects found during inspection.
Page 2 ES-1032
Operation Manual
GENERAL INFORMATION
AFTER INSPECTION:
Before re-energizing the generator control panel, connect battery cables first, and
then apply the A.C. power to the battery charger to prevent damage to electronic
components and engine electronic governor systems.
Reconnect any AC power which was previously disconnected in preparation for
maintenance.
Functional test the entire generating system in accordance with this manual.
Place all control switches and the Engine Control Switch in the recorded positions.
INITIAL SETUP
1. If the frequency (speed) is other than the nominal frequency, use the Raise/ Lower
Toggle Switch (90S-CS) of the manual speed control at the GCP Panel to either raise
or lower the frequency of the generator to the nominal frequency.
2. If the Voltage is other than the nominal voltage, use the Raise/ Lower Toggle Switch
(90V-CS) of the manual voltage control at the GCP Panel to either raise or lower the
voltage of the generator to the nominal voltage.
Page 3 ES-1032
Operation Manual
DESCRIPTION
DESCRIPTION
This project is designed for two (2) Cummins Diesel Engine Generator rated 2160kW,
2700kVA, 3 phases, 142 Amps at 11,000V, 50Hz.
The system is comprises of two separate Generator Control Panel (GCP837501A &
GCP837501B) that will control two units of Diesel Generators. The GCP contains the
following components: Human Machine Interface (HMI), Programmable Logic Controllers,
Electronic Generator Control Module (EGCM), Generator Multi-function Protection Relay
(MFR), Lockout Relay, Dual AVR, set of control Auxiliary Relays, control Circuit Breakers,
Synchroscope and Synch Indicating Lights, control Selector Switches and Pushbuttons,
Ammeter-Voltmeter selector switch, Analog meters, Emergency Stop Pushbutton (ESPB),
Status Indicating Lights and Alarm horn.
The control system is designed to run the Diesel Engine Generator in Isochronous mode, in
Baseload mode or in Droop mode via ECMS Signal transmitted to the Generator Control
Panel.
The system is designed to operate in Manual and Auto mode of operation. In Auto, automatic
starting of the Generator can be done in two ways: loss of main power and remote start via
ECMS. While Manual operation, Generator starting is initiated using the Normal Start/ Stop
Switch (44-CS) or using the EGCM start pushbutton in the event of PLC failure.
When the two Generators are running in parallel, the load will be shared equally via CAN
bus connected to the EGCM controller. Any load fluctuations shall be distributed equally
among the two Generator sets.
In any mode of operation when the protection detects any fault on the system, it will
automatically trip the breaker and/ or shutdown the Essential Diesel Engine Generator.
Page 4 ES-1032
Operation Manual
ELECTRONIC GENERATOR CONTROL MODULE FUNCTION
Metering includes:
- Phase Voltage
- Phase-Neutral Voltage
- Ampere
- Frequency
- KW
- KVAR
- KVA
- Power factor
Page 5 ES-1032
Operation Manual
ELECTRONIC GENERATOR CONTROL MODULE FUNCTION
Auto Mode: Starting of the engine is initiated and automatic closing of Circuit breaker is
carried out.
Manual Mode: Starts the engine in this position and manual closing of Circuit breaker can
be done via circuit breaker push button or an external breaker Control
Switch.
Stop Mode: Stops the engine if it is running after a preset cooldown period or prevent the
engine from starting. Also trips the Generator circuit breaker if it is closed.
For more details, Electronic Generator Control Module (EGCM) operations and
functions can be found in Woodward Easygen 3000 - Generator Control Operation
Manual.
Page 6 ES-1032
Operation Manual
GENERATOR MULTIFUNCTION RELAY FUNCTION
Page 7 ES-1032
Operation Manual
GENERATOR CONTROL SWITCHES & ANALOG METERING FUNCTION
OFF: Stops the engine if it is running after a preset cooldown period or prevents the
engine from starting.
Also trips the generator circuit breaker if it is closed.
START: It will initiate immediate starting of the engine provided the Engine Control
Switch (10-SS) is in Manual mode.
STOP: Stops the engine if it is running after preset cooldown time delay becomes
zero.
AUTO: In this position, the Generator breaker will close automatically when
Generator voltage is available at the incoming bus (dead bus condition) and/or
incoming Generator voltage is in-phase with the Bus voltage and frequency.
MANUAL: In this position, the Generator breaker will be close manually by the station
operator when Generator voltage is available at the incoming bus (deadbus
condition) and/or incoming Generator voltage is in-phase with the Bus voltage
and frequency.
POSITIONS:
TRIP (left): Trips and locks out the Generator Circuit Breaker.
AUTO (center): Arms the automatic closing circuit of the Generator circuit breaker.
CLOSE (right): Close the Generator circuit breaker manually when the condition for
closing has been met.
Page 8 ES-1032
Operation Manual
GENERATOR CONTROL SWITCHES & ANALOG METERING FUNCTION
IN: It will stop the engine and will keep it lockout until the operator manually
resets. It will also trip the Generator circuit breaker.
AC ANALOG AMMETER
This meter will display the Generator phase currents.
AC ANALOG VOLTMETER
This meter will display the Generator phase voltages.
DUAL AC VOLTMETER
This meter will display the voltage of Generator and Bus for comparison during manual or
auto synchronization.
SYNCHROSCOPE:
It indicates the degree to which two AC power systems (Generator or Other Source) are
synchronized with each other.
SYNC LAMPS:
Two lamps are in series between same phase A of incoming and bus bar. Indicates the
generator and bus bar AC synchronized with each other when in darkness.
DC ANALOG AMMETER
This meter will display the charging current of the battery charger.
DC ANALOG VOLTMETER
This meter will display the battery system voltage of the control panel.
ALARM HORN:
It provides audible alarm for any fault and warning.
Page 10 ES-1032
Operation Manual
GENERATOR CONTROL INDICATING LIGHTS
INDICATING LIGHTS:
Indicating lights are classified as status, warning, or faults. The abbreviation for the
light is in parenthesis after the name.
STATUS INDICATORS:
READY TO START LIGHT (RTSL): It indicates that the Generator is ready to start.
CIRCUIT BREAKER OPEN LIGHT (CBOL): It indicates that the circuit breaker is in
open position.
CIRCUIT BREAKER CLOSED LIGHT (CBCL): It indicates that the circuit breaker is in
closed position.
UNIT RUNNING LIGHT (URL): It indicates that the engine is in running condition.
FAULT INDICATORS:
PLC BYPASSED LIGHT (PBPL): The programmable logic controller is not running or
in faulty condition.
PLC BYPASSED SHUTDOWN LIGHT (PBPSDL): It indicates that the ESD Bypass
switch is enabled to allow the switching of 24VDC control voltage of the GCP.
CIRCUIT BREAKER TRIP LIGHT (CBTL): It indicates that the breaker is trip due to an
overcurrent.
EXTERNAL SHUTDOWN ACTIVATED LIGHT (EXSDL): It will activate this light when
an external signal is received.
LOCAL SHUTDOWN SWITCH ACTIVATED LIGHT (LSDL): It will activate this light
when abnormal condition is detected in the engine enclosure.
LOCAL FIRE SUPPRESSION ACTIVATED LIGHT (LFSL): It will activate this light
when a fire is detected in the engine enclosure.
FIRE & GAS SYSTEM BYPASSED LIGHT (FGBPL): It will activate this light when the
Fire and Gas system bypassed is activated.
Page 11 ES-1032
Operation Manual
GENERATOR CONTROL TOUCHSCREEN OPERATIONS
TOUCHSCREEN OPERATION
The touchscreen allows the station operator to visually monitor the status and its associated
circuit breaker, electrical parameter readings, active fault and alarm. Every screen contains
an upper tab for user access (default setting: Username: master, PASSWORD: control) and
lower tab for screen switching such as System Overview, Alarm List 1 and Alarm List 2,
Alarm Log, Engine Parameter and Engine Auxiliary.
1) SYSTEM OVERVIEW B
A C
2 4 6 D
1 3 5
GOTO PUSHBUTTON:
These pushbuttons when press will navigate to selected menu screen:
1. SYSTEM OVERVIEW Button
2. ALARM LIST 1 Button
3. ALARM LIST 2 Button
4. ALARM LOG button
5. ENGINE PARAMETER Button
6. ENGINE AUXILIARY button
Page 12 ES-1032
Operation Manual
GENERATOR CONTROL TOUCHSCREEN OPERATION
UPPER TAB:
(A) SCREEN NAME WINDOW:
This window shows the current screen being shown.
BREAKER STATUS:
52G OPEN (CLOSED)
Display the current position of the Generator Circuit Breaker (open or closed).
GENERATOR STATUS:
ENGINE NOT RUNNING
It will display if the Generator is in Standby or Stop mode.
ENGINE RUNNING
It will display if the Generator is in running condition.
ENGINE ON-LINE
It will display if the Generator is running, the Generator Circuit Breaker is closed and
taking load from the bus.
UNLOADING
The Electronic Generator Control Module (EGCM) is unloading the Generator set prior
to its removal from the bus.
SYSTEM WARNING
It will display if the Generator have common engine warning.
SYSTEM FAULT
It will display if the Generator is being shutdown due to an Engine fault or an electrical
fault.
COOLING DOWN
It will display if the Generator is running on cooldown mode prior to shutdown.
Page 13 ES-1032
Operation Manual
GENERATOR CONTROL TOUCHSCREEN OPERATIONS
STARTER SELECTION:
SYSTEM 1/ SYSTEM 2
This pushbutton will be activated to select the starter type to be used in the Engine start
up.
OFF: It will show the OFF status of the Engine Control Switch being selected to Off
position.
MANUAL: It will show the MANUAL status of the Engine Control Switch being selected to
Manual position.
MANUAL: It will show the MANUAL status of the Synch Selector Switch being selected to
Manual position.
SYSTEM STATUS:
SYSTEM IN AUTO
It indicates that the Auto mode of operation is selected.
Page 14 ES-1032
Operation Manual
GENERATOR CONTROL TOUCHSCREEN OPERATIONS
ENGINE START
It indicates that the Engine has been started.
ENGINE CRANK
It indicates that the Engine has been cranked.
EXCITATION START
It indicates that the Engine Excitation has been started.
Page 15 ES-1032
Operation Manual
GENERATOR CONTROL TOUCHSCREEN OPERATIONS
CURRENT (PHASE A)
Displays the Generators line current on Phase A
CURRENT (PHASE B)
Displays the Generators line current on Phase B
CURRENT (PHASE C)
Displays the Generators line current on Phase C
FREQUENCY
Display the Generators frequency in Hz.
POWER FACTOR
Display the power factor of the Generator. (Value with LEAD indicates capacitive
power factor, value with LAG indicates inductive power factor).
Page 16 ES-1032
Operation Manual
GENERATOR CONTROL TOUCHSCREEN OPERATIONS
If a fault occurred during operation, the logic sequence is to trip the Generator circuit
breaker and stop the Diesel Engine Generator from which any operation of running again
the Generator and closing the breaker is not possible unless the cause of fault has been
reset. In case alarm was triggered, it will only sound the annunciation to give warning to the
operator and logically will not affect the existing operation. Prior to start up the Generator,
active alarm should be reset first. These faults and alarms are below:
ELECTRICAL WARNING
The MFR relay has reached the warning set points programmed into the unit. The GCP
will initiate an alarm sound but no shutdown will occur.
Page 17 ES-1032
Operation Manual
GENERATOR CONTROL TOUCHSCREEN OPERATIONS
ELECTRICAL FAULT
The MFR relay has reached the trip set points programmed into the unit. The GCP will
initiate a tripping signal to the Generator breaker and will shutdown the engine to
prevent from further damage to the unit.
If the Electrical Fault indicating light is active, a separate screen will be displayed (By
pressing the icon on the left side adjacent to the Electrical Fault text) to list down the
specific fault occurred including the last fault value, the Date and Time. See list below:
NOTE:
Press this button to return to the Alarm List Screen 1
Page 19 ES-1032
Operation Manual
GENERATOR CONTROL TOUCHSCREEN OPERATIONS
ENGINE OVERCRANK
The Engine Control Module has indicated that the engine has failed to start within the
preset cranking time at the Engine Local Control Panel.
Page 20 ES-1032
Operation Manual
GENERATOR CONTROL TOUCHSCREEN OPERATIONS
Page 21 ES-1032
Operation Manual
GENERATOR CONTROL TOUCHSCREEN OPERATIONS
HEAT DETECTED
The Heat Detector installed in the Engine Generator Enclosure had been activated due to
excessive heat inside the enclosure during operation. The GCP will initiate a tripping
signal to the Generator breaker and will shutdown the Generator.
EXCITATION CB TRIP
The Circuit Breaker for the Generator Excitation has been trip due to an overload. The
GCP will initiate an alarm sound but no shutdown will occur.
OVEREXCITATION
The Generator has reached the above normal set points during the operation. At this
condition, the GCP will initiate a shutdown signal to the Engine.
PUSHBUTTONS
SILENCE PUSHBUTTON
Silences the alarm horn, and acknowledges an alarm condition.
RESET PUSHBUTTON
Resets the Generator fault windows if a fault condition is activated and provided it has
been cleared.
Page 23 ES-1032
Operation Manual
GENERATOR CONTROL TOUCHSCREEN OPERATIONS
Page 25 ES-1032
Operation Manual
START
When this pushbutton is pressed, it will enable the four pushbutton functions (ACK, ACK
ALL, ROLL UP, ROLL DOWN).
ACK
When this pushbutton is pressed, it acknowledges the selected alarm in the alarm
history list. The color of the alarm text will be changed from Red into Bright Green.
ACK ALL
When this pushbutton is pressed, it acknowledges all the selected alarms in the alarm
history list. The color of the alarm text will be changed from Red into Bright Green.
Page 26 ES-1032
Operation Manual
ROLL UP
When this pushbutton is pressed, it allows the operator to scroll up the alarm history.
ROLL DOWN
When this pushbutton is pressed, it allows the operator to scroll down the alarm history.
ACTIVE LIGHT
It indicates that the Alarm is still active.
ACKNOWLEDGE LIGHT
It indicates that the Alarm has been acknowledged by the operator.
RECOVERED LIGHT
It indicates that the Alarm has been acknowledged and reset by the operator.
Page 27 ES-1032
Operation Manual
This screen displays the Diesel Engine Generators parameters to allow the operator to
monitor the engine status.
SCREEN DISPLAY:
ENGINE COOLANT TEMPERATURE (deg. C)
ENGINE OIL TEMPERATURE (deg. C)
ENGINE OIL PRESSURE (kPa)
EXHAUST RIGHT MANIFOLD TEMPERATURE (deg. C)
EXHAUST LEFT MANIFOLD TEMPERATURE (deg. C)
GENERATOR FRONT BEARING TEMPERATURE (deg. C)
GENERATOR REAR BEARING TEMPERATURE (deg. C)
GENERATOR PHASE A, B & C WINDING TEMPERATURE (deg. C)
AIR INLET TEMPERATIRE (deg. C)
Page 28 ES-1032
Operation Manual
AIR OUTLET TEMPERATIRE (deg. C)
ENGINE SPEED
GENERATOR CONTROL TOUCHSCREEN OPERATIONS
This screen displays the Diesel Engine Generators auxiliaries to allow the operator to
monitor the enclosure and engine status.
SCREEN DISPLAY:
FUEL TANK LEVEL (in Liters)
GREEN LIGHT
It indicates that the Radiator Fan is available and ready to run.
Page 29 ES-1032
Operation Manual
BLUE LIGHT
It indicates that the Cooler Fan is in running condition.
GENERATOR CONTROL TOUCHSCREEN OPERATIONS
BLUE LIGHT
It indicates that the Jacket Water Heater is in running condition.
GREEN LIGHT
It indicates that the Jacket Water Heater is available and ready to run.
BLUE LIGHT
It indicates that the Space Heater is in running condition.
Page 30 ES-1032
Operation Manual
OPERATING PROCEDURES
LEGEND:
Selector Switches and Pushbutton Switches
Device Switch Function Description
10 - SS Auto Off - Manual Engine control Selector key Switch
25 - SS Auto - Manual Synchronizing Selector Switch
42 - CS Trip - Auto - Close Breaker Control Switch (Close only applicable when
25-SS is in Manual)
44-CS Normal Start/ Stop Control Switch, momentary, spring return to centre
position for manual starting and stopping of engine
25ES-PB Emergency Stop Emergency Stop Pushbutton
Pushbutton
25DB-PB Dead Bus Close Permissive Dead Bus Close permit Push button
90V-CS Voltage Raise - Lower Voltage Raise/Lower Toggle switch (only applicable
when 25-SS is in Manual)
90S-CS Speed Raise - Lower Speed Raise/Lower Toggle switch (only
applicable when 25-SS is in Manual)
On sensing the loss of main power, and after a pre-set time delay, each Generator Control
Panel (GCP837501A and GCP837501B) starts its EDG simultaneously provided the
conditions above had been met.
Both the Generator sets (GEN837501A and GEN837501B) will start and attains the nominal
voltage and frequency. The Generator Control Panel will then proceed with the automatic
synchronization.
Page 31 ES-1032
Operation Manual
The GCP of the first Generator set (GCP837501A or GCP837501B) to attain the voltage and
frequency will automatically close its Generator Incoming Breaker (52-68 or 52-67) on to the
Deadbus.
If the voltage is now available on the other bus section (SWG823501 or SWG823502) with the
Tie Breaker (52-24) in CLOSED position, the GCP of the other Generator set (GCP837501B
or GCP837501A) will automatically synchronize with the voltage on its bus section
(SWG823501 or SWG823502) and close its Generator Breaker (52-68 or 52-67) when
synchronization conditions had been met.
If the voltage is not available on the other bus section (SWG823501 or SWG823502) with the
Tie Breaker (52-24) in OPEN position, the GCP (GCP837501A or GCP837501B) will
automatically close its Generator Incoming Breaker (52-68 or 52-67) on to the Deadbus.
Both Generator sets will run on Isochronous mode when running in the Island mode.
Note:
Restoration of main power, when at least one Gas Turbine Generator (GTG) is ready to take
load, is performed manually by Operations personnel. The Generator Control Panel of both
EDG had no role to play in this.
Once normal power is restored, the Operator may either stop the EDG at the Generator
Control Panel or remotely at the ECMS operators terminal.
Page 32 ES-1032
Operation Manual
For Further operation, all Emergency pushbuttons need to be released and the GCP
needs to be reset the station Operator.
On sensing the loss of main power, and after a pre-set time delay, each GCP starts its EDG
simultaneously provided the conditions above had been met.
Both the Generator sets (GEN837501A and GEN837501B) will start and attains the nominal
voltage and frequency. The Generator Control Panel will wait the command from the
operator to execute the manual synchronization. The Operator can decide as to which EDG
is to be brought on line first.
Accordingly, the Operator can now close the Generator Incoming Breaker (52-67 or 52-68)
on to the Dead bus or Live bus using the Breaker Control Switch (42-CS) on the Generator
Control Panel.
For Manual closure of breaker on to the Dead bus, the Operator must simultaneously
depress the Dead Bus Close Permissive Pushbutton (25DB-PB) while operating the Breaker
Control Switch (42-CS) to the Close position. The Generator set will run on Isochronous
mode when running in the Island mode.
The bus section (SWG823501 or SWG823502) is now live from EDG (GEN837501A or
GEN837501B). If the Bus tie Breaker (52-24) is CLOSED, the other bus section will also be
live.
If the Bus tie Breaker (52-24) is OPEN and the bus section (SWG823501 or SWG823502) is
dead, the Operator can directly close the Generator Incoming Breaker (52-68 or 52-67) on to
the Dead bus using the Dead Bus Close Permissive Pushbutton (25DB-PB) and the Breaker
Control Switch (42-CS) on the Generator Control Panel. The GCP ensures that Generator
Incoming Breaker (52-68 or 52-67) cannot be closed if the bus section (SWG823501 or
Page 33 ES-1032
Operation Manual
SWG823502) is live and the voltages are not in synchronism with the Generator set
(GEN837501A and GEN837501B) voltage.
If the bus section (SWG823501 or SWG823502) is Live, the Operator can then perform
Manual synchronizing by increasing or decreasing the Generator voltage using Voltage
Raise/ Lower Toggle Switch (90V-CS) and increasing or decreasing the Generator
frequency using Speed Raise/ Lower Toggle Switch (90S-CS) on the Generator Control Panel
in order to match with the corresponding bus voltage and frequency.
Once in synchronism, the Operator can now be closed the Generator Incoming Breaker (52-
68 or 52-67) on to the Live bus using the Breaker Control Switch (42-CS) on the Generator
Control Panel (GCP837501A or GCP837501B).
Now both the Generator sets are running in synchronism and they will both run in
Isochronous/ Load sharing mode. Both the Generators continue to supply power to the bus
(SWG823501 or SWG823502) until such time as Normal Power is restored.
For Further operation, all Emergency pushbuttons need to be released and the GCP
needs to be reset the station Operator.
On receipt of a normal stop command, the EDG will go into cooldown stop. If at any
time during cooldown shutdown period, the normal power is lost then the GCP,
provided the Engine Control Switch (10-SS) is in AUTO cancels the cooldown
shutdown timing. If the Synch Selector Switch (25-SS) is also in AUTO then the
Generator Control Panel (GCP837501A or GCP837501B) will automatically close the
Page 34 ES-1032
Operation Manual
Generator Incoming Breaker on to the dead bus or synchronize with the other EDG
should it achieve dead bus closure first.
For proper Generator Operation, follow the Control Switches position and condition
requirements below:
Engine Control Switch (10-SS) - MANUAL mode
Synch Selector Switch (25-SS) - MANUAL mode
Lock-out relay (86) on the respective Generator incomer breaker (52-67 or 52-68)
shall not be operated.
No abnormal condition exists (i.e. Emergency Shutdown Switch or Emergency Stop
Pushbutton activated) on Generator Control Panel (GCP837501A/ GCP837501B) or
Essential Diesel Generator (GEN837501A and GEN837501B).
The Operator has to initiate a start command on Normal Start/ Stop Control Switch (44-
CS) on the GCP by placing the switch in START position. The Generator set will be
started and keep running on no load until the Operator decided to initiate a normal stop
at GCP or remotely from ECMS Terminal.
For proper Generator Operation, follow the Control Switches position and condition
requirements below:
Engine Control Switch (10-SS) - MANUAL mode
Synch Selector Switch (25-SS) - AUTO mode
Lock-out relay (86) on the respective Generator incomer breaker (52-67 or 52-68)
shall not be operated.
No abnormal condition exists (i.e. Emergency Shutdown Switch or Emergency Stop
Pushbutton activated) on Generator Control Panel (GCP837501A/ GCP837501B) or
Essential Diesel Generator (GEN837501A and GEN837501B).
The Operator has to initiate a start command on Normal Start/ Stop Control Switch (44-
CS) on the GCP by placing the switch in START position. The Generator set will be
started and attain the nominal voltage and frequency. The EDG (GEN837501A or
GEN837501B) voltage and frequency will automatically synchronize with the voltage and
frequency on the corresponding bus section (SWG823501 or SWG823502) and the
corresponding Generator Incoming Breaker (52-68 or 52-67) will close.
Page 35 ES-1032
Operation Manual
NOTE: Now the EDG will run in synchronism with the GTG and the Generator set
defaults to Baseload mode, taking the load from the bus base on the pre-set kW set
points on the GCP.
For proper Generator Operation, follow the Control Switches position and condition
requirements below:
Engine Control Switch (10-SS) - MANUAL mode
Synch Selector Switch (25-SS) - MANUAL mode
Lock-out relay (86) on the respective Generator incomer breaker (52-67 or 52-68)
shall not be operated.
No abnormal condition exists (i.e. Emergency Shutdown Switch or Emergency Stop
Pushbutton activated) on Generator Control Panel (GCP837501A/ GCP837501B) or
Essential Diesel Generator (GEN837501A and GEN837501B).
The Operator has to initiate a start command on Normal Start/ Stop Control Switch (44-
CS) on the GCP by placing the switch in START position. The Generator set will be
started and attain the nominal voltage and frequency. The Generator Control Panel will
wait the command from the Operator to execute the manual synchronization. The
Operator can decide as to which EDG is to be synchronized with the Gas Turbine
Generator (GTG).
The Operator can then perform Manual synchronizing by increasing or decreasing the
Generator voltage using Voltage Raise/ Lower Toggle Switch (90V-CS) and increasing or
decreasing the Generator frequency using Speed Raise/ Lower Toggle Switch (90S-CS)
on the Generator Control Panel in order to match with the corresponding bus voltage
and frequency.
Once in synchronism, the Operator can now be closed the Generator Incoming Breaker
(52-68 or 52-67) on to the Live bus using the Breaker Control Switch (42-CS) on the
Generator Control Panel (GCP837501A or GCP837501B).
The load test is stopped by the station Operator initiating a normal stop by placing the
Normal Start/ Stop Control Switch (44-CS) to Stop position at the Generator Control Panel
(GCP837501A or GCP837501B) or remotely from the ECMS Terminal.
NOTE: Now the EDG will run in synchronism with the GTG and the Generator set
defaults to Baseload mode, taking the load from the bus base on the pre-set kW set
points on the GCP.
Page 36 ES-1032