Anda di halaman 1dari 3

MEMORIAL DE CALCULO DO SISTEMA DE HIDRANTES

End: Rua Jaime Benvolo, 14321 - Ftima Municipio: Fortaleza/CE


Ocupao: A-2 Risco: BAIXO (300MJm2)
Proprietrio: Condomnio Gizela
Resp. Tcnico: Eng. Adam Sales Silva CREA: 50.376/D
Norma adotada: NT 006- CBM/CE

Sistema Tipo 2 C tubo 120 Tubo Ao galvanizado Esguicho (mm) 16


mangueira (mm) 40 C mang: 140 comp. 30 K esguicho 33
RECALQUE SUCO
Vazo minima esguichos vazo mangueira C= 140 tubulaao C= 120 desn.
press. Req. vel. k
Trecho Tabela 2-NT 6 pressao diam. adotada diam. compr. J (m/m) H. mang. diam. C.real C. eq. C total J (m/m) H tubo (+ -)
H1-A 250 l/ min 57.4 16 250 40 30 0.290 8.70 65 2.2 16 18.2 0.036 0.66 2.2 68.95 1.26 33
H2-A 243 l/ min 54.44 16 243 40 30 0.276 8.29 63 5.2 20.3 25.5 0.040 1.03 5.2 68.95 1.30 33
PA-BI 493 63 1 19.4 20.4 0.149 3.03 -0.1 71.88 2.64 33
BI-RI H1+H2 493 75 2.7 10.6 13.3 0.064 0.85 0.5 73.23 1.86

Dados bomba de incndio Reserva tcnica de incendio PA PONTO A


Potncia minima 10.707 Cv ( x ) Elevado BI BOMBA DE INCNDIO
Bomba adotada 10 Cv ( ) Subterrneo H1 HIDRANTE 1 MAIS DESFAVORVEL
Presso 73.23 mca ( ) Ao nivel do solo H2 HIDRANTE 2 MAIS DESFAVORVEL
Vazo 493 L/min
Rendimento Bomba 75 % volume 6,9 m *OBS: Lembrar de transformar l/min em m/h

_________________________________________
ADAM SALES SILVA
Engenheiro Civil