Controll System Model Design Functions For MRV For Super Controll System Model Design Functions For MRV For Super
units Match units units Match units
Central
Gateway
Match with YCZ-A003
IGU05
Control
Single unit control All All
Every system need one IGU05
Group control, max.16 units Cassette, Cassette,
Weekly timer
convertible, duct convertible, duct Max.32 IGU02 units to be connected
YR-E16 Clock
Mode: cooling, heating, auto, air flow, type, built-in floor type, built-in floor Local control Max.40 indoor units connected for
every system
dehumidification
Temperature, fan speed, fan direction
standing standing
version Total connected indoor units
BMS system: quantity is Max.400
on/off, fan speed, temperature
HCM-01 All /
(RS485&232 control
Operation mode control
converter+ Schedule timer (weekly, monthly)
86*86mm,same size with the switch; Cassette, Cassette, Modbus rtu interface (only
Wired Thickness only 13.05mm, super slim convertible, duct convertible, duct software) display, without control)
YR-E17 Touch Screen, back up light Electricity charge report
controller Easy installation, user friendly
type, built-in floor type, built-in floor
Max.4 groups system; Every system
standing standing Remote can connect max.20 IGU02 units; Every
monitoring IGU02 can connect max.40 indoor units
Total connected indoor units quantity is
version3 BMS Max.1000
system: on/off, fan speed, temperature
HCM-03 control All /
Single unit control
Group control, max.16 units Cassette, Cassette,
IPC(Industrial Operation mode control
Clock convertible, duct convertible, duct
personal Schedule timer (weekly, monthly)
Electricity charge report
YR-E14 Timer
type, built-in floor type, built-in floor
computer) Interface: BACnet ip, Modbus ip, Modbus rtu
Mode: cooling, heating, auto, air flow,
standing standing Building + software Many users remote moniotoring
History record and curve
dehumidification
Individual
Temperature, fan speed, fan direction
Management Monitor and Control to the whole
System Remote MRV system, max 250 indoor units
Controlle Third party interface: BACnet IP and
Single unit operation Wall mounted, console monitoring Modbus
HCM-05 New designed user friendly interface All /
Infrared
Cool, heat, dry, quiet operation button type
Clock version5 BMS Change the pulse meter to 485 meter
YR-HD / (optional controller for
controller
History record and curve
system:
Timer
Mode: cooling, heating, auto, air flow, cassette, convertible Development cooperation with
dehumidification and duct type) Honeywell
Wired
Honeywell
Match with
contoller RE-02 Realize infrared control for duct type Duct Duct HCM-01,HCM-03,HCM-05, HCM-05A
reciever Every system need one IGU02
Max.40 indoor units connected for
Gateway IGU02 every IGU02 All /
CONTROLLER
Cassette, Cassette, Protocol adapter
Simple YR-F02
Single unit control convertible, duct convertible, duct
Electricity charge data
collection, calculation, allocation and
controller Group control, max.16 units
type type storage
Modbus rtu
Connect the outdoor unit to change
Single unit control Modbus IGU06
the homebus protocol to modbus
protocol All /
Group control, max.32 units, Individual
Cassette, Cassette, Gateway And then match with the IGU07 to
Group Group
control to each unit
convertible, duct convertible, duct realize the lonworks gateway
YCZ-G001 Weekly timer
BMS function
Controller Controller Clock
Mode: cooling, heating, auto, air
type, built-in floor type, built-in floor
Interface
standing standing Lonworks protocol gateway
flow, dehumidification Every outdoor system adopt one
Lonworks
Temperature, fan speed, fan direction IGU07+IGU06
IGU07 In one system, total connected All /
Touch
Single unit control Gateway indoor units quantity is Max.32
Central control, max.128 units The longate need connect external
Central screen Weekly timer 24V DC power supply
YCZ-A003 Zone control
central
All All
Control Can be connected the third party
Adapter Adapter SUPER MATCH indoor units can be
interface: Modbus rtu YCJ-A002 controlled in one system with MRV
controller (Detector) (Detector)
All All
Max.32 IGU05 units can be connected outdoor units
with one YCZ-A003
129 130
CONTROL SYSTEM CONTROLLER
YR-E16 YR-E17
86*86mm, same size with the switch;
thickness only 13.05mm, super slim
Touch screen, back up light
Easy installation, user friendly
User Friendly-design
User Friendly-function
CONTROLLER
Built in weekly timer function: When a power failure occurs, all settings remain stored up to 72 hours
Mode memory function
Energy saving and the child lock function, to meet the individual needs of different places and populations
Wired control and group control, Max.16 indoor units
User Friendly-installation
Push-pull structure
Using plug interface to fix the connection wire without screw, easy installation without tools
131 132
CONTROL SYSTEM CONTROLLER
No.1
No.1
acNet /IP
BacNet
~
No.2
No.2
4 groups
Ammeter
Max-
Max.32 .20sets of
sets of IGU-02
IGU-05
YCZ- A003 HCM- 03
No.20
No.32
Ammeter
BAC net A/C Management System [HCM-05+IGU02; HCM-05A+IGU02] Smart A/C Management [HCM-01 + IGU02]
Monitor
Software IGU02
Max. 40 sets of indoor units for one IGU02
CONTROLLER
Ammeter No.1 No.2 No.40
Max. 32 sets of
Ammeter
IGU02
IGU02 HCM- 01
HCM-05: Max.250 indoor units available No.32
HCM-05A: Max.500 indoor units available
Ammeter
HCM-05
133 134
CONTROL SYSTEM ACCESSORIES CONTROLLER
IGU06
Max. 32 sets of indoor units for one IGU06 Gather pipe HZG-20A Refrigerant gathering 2 outdoor units
Refrigerant gathering
Gather pipe HZG-R20A
RS-485 max.1000m
Refrigerant distribution
Manifold pipe FQG-B1350A for heat pump MRV
Total indoor units capacity
bigger than 73,000W
CONTROLLER
Total indoor units capacity less than
Manifold pipe
Refrigerant distribution
FQG-RB730A for heat recovery MRV
73,000W, but equal or bigger than
50,600W
Manifold pipe
Refrigerant distribution Total indoor units capacity
FQG-RB1350A for heat recovery MRV bigger than 73,000W
135 136