Display
Panel
J28 Connector
FIGURE 1. REMOTE HMI220 CONTROL PANEL
J29 Connector
GENERAL PRECAUTIONS
Read these installation instructions completely and
become familiar with safety warnings, cautions, and
the installation procedure before starting.
Incorrect installation can result in
WARNING
severe personal injury or death and/or equip-
ment failure or damage. This kit must be
FIGURE 2. REMOTE HMI320 CONTROL PANEL installed by service personnel who are trained
and experienced to perform electrical and me-
Verify that the following items are included in the kit. chanical service.
J29
TB15
1
B B
2
B+ B+
3
FIGURE 4. HMI CONNECTIONS RS-485+
4
RS-485
J28 Connections 5 F2
BI_DIR WAKEUP
J28 is used for power connections. RXEF025
CON1X5
(In the control board) MOLEX_39870_0505
CON2X2
FIGURE 8. TB15 PINS
AMP_1_770174_0
B TABLE 3. TB15 PIN ASSIGNMENTS
FUNCTION /
PIN DESCRIPTION
FIGURE 5. J28 WIRING CONNECTS TO
TB15-1 RS-485 Shield Network Shield
2 1 TB15-2 N/A
TB15-3 RS-485 Data Network Data A
A/Modbus
TB15-4 RS-485 Data Network Data B
4 3 B/Modbus
J28-1
B+ Return
J28-3 TB1-10
6. If the HMI is installed more than 200 feet (61 tween the HMI and the terminal block for
meters) from the generator set, a terminal the J29 connector and pin 3 on the J28
block must be installed (see Figure 10). connector.
a. Install a terminal block near the remote c. Install socket contact pins on the ends of
HMI. all wires that will be installed on the J28
and J29 connectors.
b. Cut 16 AWG (1.31mm2) wire of the ap-
propriate length for the connections be- d. Install the wires with the contact pins in the
tween the HMI and the terminal block. appropriate locations on the J28 and J29
connectors (see Figure 13).
c. Install socket contact pins on the ends of
e. Install wires of the appropriate size (see
the wires that will be installed on the J28
Table 1) from the terminal block to the con-
and J29 connectors.
trol base board (see Figure 13) for the J29
d. Install the wires with the contact pins in the and J28-3 connections. Connect J28-3 to
appropriate locations on the J28 and J29 TB1-10.
connectors (see Figure 13). f. Use 16 AWG (1.31mm2) wire, connect wir-
e. Connect the other ends of the wires to the ing from the J28-3 to Iso() and J28-1 to
terminal block. Iso(+) on the isolated power supply.
8. Plug the J28 connector into the HMI and apply
f. Install wires of the appropriate size (see power to the HMI through the J28 connector.
Table 1) from the terminal block to the con-
trol base board (see Figure 13). 9. With J28 connected and J29 disconnected, ac-
cess the Cummins Power Generation InCal
7. If the HMI is installed more than 500 feet from website (http://www.cumminspower.com) and
the generator set, an isolated power supply download the latest InCal calibration file for
must be installed (see Figure 11). your HMI.
a. Install a terminal block near the remote You must update the remote HMI cal-
HMI. libration with the same part number as
the local HMI!
b. Cut 16 AWG (1.31mm2) wire of the ap-
propriate length for the connections be- 10. Plug the J29 connector into the HMI.
J28-1
(Power +)
Internal
Ground
NOTE: REMOTE HMI220 WILL NOT WORK WITH THE 3.3 CONTROL.
REMOTE HMI320 WILL WORK WITH THE 2.2/2.3/3.3 CONTROLS.
REMOTE HMI320 WILL NOT WORK WITH THE 1.1/1.2 CONTROLS.
6mm 276mm
212mm
110.4mm
4.3mm
142.3mm
288mm
FIGURE 14. HMI CUTOUT TEMPLATE