Electrical Estimator's Manual

How to Estimate Electrical Construction Projects

Including Everyday Labor Installation Rates

William Penn

Houston, Texas
Copyright 0 2005 by Gulf Publishing Company, Houston, Texas. All rights reserved.
No part of this publication may be reproduced or transmitted in any form without the prior
written permission of the publisher.

Gulf Publishing Company


2 Greenway Plaza, Suite 1020
Houston, TX 77046

10 9 8 7 6 5 4 3 2 1

Printed in the United States of America.

Printed on acid-free paper.

Text design and composition by Ruth Maassen.

ISBN 0-9765113-2-0
Preface

his guide of instructional and informative material plans will lay out the services to the building, the site and
T has been developed for the individual who would
like to add estimating of electrical construction projects to
interior lighting, various devices, voiceldata communica-
tion, the fire alarm system, and mechanical equipment
their skill set. Electrical workers, apprentices, contractors, electrical requirements.
draftspersons, engineers, architects, material handlers, The sample estimate herein includes a recapitula-
salespeople, and instructors of electrical contracting tion sheet of the sample estimate that depicts all of the
courses who are involved in the electrical construction job expenses, nonproductive labor, materials, and labor
industry can benefit by studying and applying the infor- hours for a complete installation cost. Contractor over-
mation in this guide. head as well as profit is allowed for, and these percent-
An explanation of bidding procedures, project spec- ages will be set by the contractor.
ifications, and construction plans is laid out with step- Electrical contractors are constantly searching for
by-step instructions using drawings, notations, detail qualified, experienced estimators as well as junior esti-
sheets, and a complete sample estimate. Blank esti- mators for their companies. By thoroughly studying
mating sheets for the estimators use when estimating this guide, you will enhance your job marketability to
are included. electrical contractors.
The guide begins by explaining the various sections A section of this guide includes more than 2,500 easily
and divisions of a sample projects bid specifications. We accessed labor units on a wide array of electrical materi-
also review each trades installation responsibilities (for als, along with charts, miscellaneous formulas, and rules
example, general construction, plumbing, HVAC, and of thumb. The labor units included herein have been
electrical). Partial floor plans and site plans have been developed by this author after more than 45 years in the
developed for the electrical installation. These partial electrical construction industry (see About the Author).

ix
Contents

Preface ix Site Plan 5


Foundation Plans 5
About the Author xi Finish Schedule Sheet 6
Architectural Plans 6
Introduction xiii Structural Plans 6
Mechanical and Electrical Site Plans 6
CHAPTER 1 How to Estimate Electrical Plumbing Plans 6
Construction Projects 1 Heating, Ventilating, and Air-conditioning
Plans 6
Contractors Library: Reference Material for the
Electrical Plans 7
Estimator 1
Estimators Tools Required 1
Section 1: Preparing Estimates from Plans, CHAPTER 2 Electrical Material and Labor
Specifications, and Related Documents 2 Takeoff 9
Step 1: What Documents to Look for and Typical Electrical Symbol List 9
Examine 2 Ceiling Finishes 11
Invitation to Bid 2 Text Introduction to Fixtures Takeoff 1 2
Form of Proposal or Bid Form 3 Text Recap of Fixtures Takeoff 1 2
Project Specifications 3 Text Introduction to Devices Takeoff 1 2
General Conditions 3 Ceiling Finishes Partial Floor Plan 13
Supplementary Conditions 3 Fixture Legend 15
Special Conditions for the Mechanical and Lighting Fixtures Partial Floor Plan 16
Electrical Trades 3 Fixtures Rough Takeoff Sheet 18
General Construction Division 3 Estimate Sheet of Fixtures Labor Hours 20
Structural Steel Division 4 Devices Partial Floor Plan 22
Plumbing Division 4 Devices Rough Takeoff Sheet 24
Heating, Ventilating, and Air-conditioning Estimate Sheet of Devices Labor Hours 25
Division 4 Text Introduction to Site Lighting Takeoff 26
Electrical Division 4 Site Lighting Partial Plan 27
Step 2: The Bid Drawings and Estimate 4 Site Lighting Rough Takeoff Sheet 29
Title Sheet 4 Estimate Sheet of Site Lighting Labor Hours 30
vi Contents

Text Introduction to Branch Wiring Takeoff 32 Field Installation of Raceways and Associated
Text Introduction to Communications Fittings for RGC 82
Takeoff 32 Field Installation of Rigid Conduit Associated
Branch Wiring Rough Takeoff Sheet 33 Fittings 84
Estimate Sheet of Branch Wiring Labor Field Installation of Rigid Conduit and
Hours 34 Associated Explosion-Proof Fittings 86
Communications Partial Floor Plan 35 Field Installation of Wireways and Fittings 88
Communications Rough Takeoff Sheet 37 Field Installation of Cable Tray and
Estimate Sheet of Communications Labor Fittings 89
Hours 38 Field Installation of Flexible Conduit and
Text Introduction to Fire Alarm Takeoff 39 Fittings 92
Text Introduction to Mechanical Equipment Field Installation of Motor Whip
Takeoff 39 Connections 93
Text Introduction to Services to Building, Field Installation of Raceways and Associated
Feeders, Panels, and Transformers 39 Fittings for EMT 94
Fire Alarm Partial Floor Plan 40 Field Installation of Raceways and Associated
Typical Fire Alarm Riser Diagram 4 2 PVC Fittings 95
Fire Alarm Rough Takeoff Sheet 4 3 Field Installation of Under Floor Ducts and
Estimate Sheet of Fire Alarm Labor Hours 44 Fittings 97
Mechanical Equipment Partial Floor Plan 45 Field Installation of Trench Duct and
Mechanical Equipment Rough Takeoff Sheet 4 7 Fittings 98
Estimate Sheet of Mechanical Equipment Labor Field Installation of Metal Wiremold and
Hours 48 Fittings 99
Typical Power Riser Diagram 49 Field Installation of Mineral Insulated Cable
Estimate Sheet of Panels and Transformers 600V 100
Labor Hours 50 Section 2: Devices, Boxes, Plates, and
Site Services Partial Plan 52 Flat Wiring 102
Feeder Schedule 54 Field Installation of Devices and Plates 102
Estimate Sheet of Feeders Labor Hours 55 Fie1d Ins tall a tion of Poke- Through Fittings/
Typical Details Rough Takeoff Sheet 57 Devices/Covers 103
Rough Takeoff Sheets to Estimate Sheets 59 Field Installation of Sheet Metal Outlet and
Recapitulation Sheet 61 Junction Boxes 104
Estimate Sheet of Equipment Prices Field Installation of Cast Outlet and Junction
Needed 63 Boxes 105
Recapitulation of Estimate Sheets 64 Field Installation of Under Carpet Flat- Wiring
Estimate Sheets: System 106
Feeders Labor Hours 65 Section 3: Light Fixtures 107
Panels and Transformers Labor Hours 66 Field Installation of HID Lighting Fixtures 107
Indoor Feeders Labor Hours 68 Field Installation of Lighting Fixtures
Branch Wiring Labor Hours 69 (Incandescent, Exit, Emergency) 108
Site Lighting Labor Hours 70 Field Installation of Fluorescent Fixtures 109
Fixtures Labor Hours 72 Field Installation of Track Lighting
Devices Labor Hours 74 Systems 110
Communications Labor Hours 75 Field Installation of Preassembled Quick Wiring
Fire Alarm Labor Hours 76 Systems 1 1 1
Mechanical Equipment Labor Hours 77 Field Installation of Area Lighting 1 1 3
Field Installation of Wood Poles 1 1 4
Section 4: Emergency Generators 115
CHAPTER 3 Labor Rate Schedules and Forms, Field Installation of Emergency Generator
Charts, and Diagrams 79 Sets 115
Section 1:Raceways and Fittings 82 Section 5: Grounding 1 1 7
Contents vii

Field Installation of Grounding 1 1 7 Field Installation of Multiconductor Copper


Section 6 : Bus Ducts 118 Cables 147
Field Installation of Copper Bus Ducts 118 Field Installation of Low-Voltage and
Field Installation of Copper Bus Ducts and Multiconductor Cables 149
Plug-in Units 119 Section 11: Voice and Data Wiring 150
Section 7: Distribution Equipment 120 Field Installation of Voice/Data Systems 150
Field Installation of Nonfused Disconnect Section 12: Miscellaneous HVAC Devices 151
Switches: 250 Volts 120 Field Installation of Wiring for Miscellaneous
Field Installation of Nema 1 Motor Control HVAC Devices 151
Centers 121 Section 13: Light Bases 1 5 2
Field Installation of Starters, Contactors, and Field Installation of Concrete Bases 152
Controls 122 Section 14: Voltage Drop Tables 153
Fiel d In stallation of High - Voltage Transformers Voltage Drop Tables for Low-Voltage
124 Circuits 153
Fiel d Installa tion of Low- Voltage Transformers Section 15: Miscellaneous 154
126 Miscellaneous Information, Formulas 154
Field Installation of Incoming Service and AC Motor Connections 155
Distribution Sections 2 28 Motor HP and Ampere Ratings
Field Installation of Meter Sockets and (Single Phase) 156
Stacks 129 Motor HP and Ampere Ratings
Field Installation of Meter Stacks 130 (Three Phase) 157
Field Installation of Indoor Surface Panel Typical Motor Control Circuits 158
Boards 131 Conversion Factors 160
Field Installation of Indoor Surface-Mounted Ampere Ratings of Resistance Loads (Single
Panels 132 Phase) 166
Field Installation of Circuit Breakers 133 Ampere Ratings of Resistance Loads (Three
Field Connection of Preinstalled Circuit Phase) 167
BreakerdPressure Switches and Single- Wire Transformer Connections (Delta to Wye) 168
Terminations 134 Transformer Connections (Delta to Delta) 169
Field Installation of Circuit Breaker Enclosures Transformer KVA and Ampere Ratings (Single
and Circuit Breakers 136 Phase) 170
Section 8: Fire Alarm and Miscellaneous Transformer KVA and Ampere Ratings (Three
Systems 137 Phase) 171
Field Installation of Fire Alarm System Lighting Design/Footcan dle
Equipment 137 Recommendations 172
Field Installation of Miscellaneous Systems 138
Section 9: Electric Heating 139 CHAPTER 4 Sample Estimate and Forms 175
Field Installation of Electric Heating 139 Estimators Check Sheet 176
Field Installation of Snow Melting Mats, Sample Estimate 179
Snow Melting Cable, and Heat Tracing Blank Forms 199
Cable 141 Recapitulation Sheet
Section 10: High- and Low-Voltage Cables 143 Estimate Sheet
Field Installation of High-Voltage Cable in Change Order Recapitulation Sheet
Conduit 143 Rough Takeofl Sheet
Field Installation of Copper Wire and Feeder Schedule
Cable 144 Request for Information
Field Installation of Multiconductor Tray Work A u th orization Form
Cables 146 Time and Material Work Order
Introduction

he electrical construction industry has evolved someone else) who shows responsibility, good work
T from the rudimentary adage black is the hot leg
and white is the neutral. Although this is still true and
habits, dependability, and enjoys their work. The con-
tractor might encourage that employee to begin to learn
the theory is the same, much has been discovered and the estimating process; this was my personal experi-
expanded on. When you visit or speak with an electri- ence with a contractor whom I worked for as an electri-
cal contractor today about estimating, bidding, buying, cian and who led me to develop this knowledge.
etc., it is nearly the same as it was 50 years ago. Yes, the The following text has been developed after my many
estimating hardware, so to speak, has evolved from years of experience in the electrical construction indus-
handheld counters and individual wheel map measures try. The contents have been designed in such a way that
to electronic probes that count and measure and at the electrical instructors, electricians, electrical engineers,
same time keep a running total. New devices have architects, blueprint readers, etc. can draw some benefit
come into the market to make the estimating task faster from it, even if only for reference material. Those indi-
and more accurate, which, in theory, reduces the cost to viduals who have some electrical experience and want to
produce an estimate. This is all true, yet there is one advance themselves into the electrical estimators circle
factor that has survived all these years and will con- should study the material contained herein. The entire
tinue to survive-the hands-on ESTIMATOR. format has been designed with the beginner as well as
The ESTIMATOR has the ability to transform a set of the seasoned estimator and others in mind.
electrical construction plans and documents into a total Included are step-by-step instructions on how to
cost of labor, materials, and job expenses. All of the new interpret construction plans and specifications, what to
probes, markers, and gadgets cannot attend a prebid site look for, and why you should read all of the specifica-
investigative walk-through or actually interpret bidding tions, even those for the roofing, woodwork, wall con-
documents. This always has been, is now, and will be struction materials, plumbing, etc. Many times there
performed by a human being-an ESTIMATOR. will be items in these categories of the specifications
Estimators are constantly being sought out by elec- that impact an electrical contractors bidding price.
trical contractors and are in great demand. Many times Partial plans of a typical office building are in-
a contractor will have an employee (an electrician or cluded to show the utilities coming into the building,
xiv Introduction

the site lighting, interior lighting, panels and power- and installations. These have been time-tested in the
distribution devices, safety and communication devices, field and applied by many contractors whom I con-
mechanical equipment, and electrical services to prop- sulted for in the past (see About the Author).
erly depict the various electrical materials in place. A complete sample estimate has been included here
Rough takeoff sheets have been developed for all of to show exactly how a professional estimate is formu-
the electrical materials shown on the partial plans and lated. Although the prices of the individual materials
associated materials required for a complete installa- are not shown on the estimate pricing sheets, there
tion. This book will show you how to transfer all of the have been allowances inserted on the final recapitula-
materials shown on the rough takeoff sheets to estimat- tion sheet so that you can go through this sheet from
ing sheets for inserting prices and labor hours. The next beginning to final bidding price,
step shown is to total all of the labor (material is not At the end of this book there is a miscellaneous sec-
priced here due to each contractors specific pricing tion of formulas, charts, schematics, conversions, light-
structure) and transfer the hours to a final recapitula- ing levels for most common places, and blank estimat-
tion sheet. This final recapitulation sheet will include ing and related business forms.
all pricing, labor hours, nonproductive labor, job ex- There are many aspects to the electrical construc-
penses, hourly labor rates, overhead, and profit. tion industry and the feeling here is that estimating is
Following the job estimate, there is a section on the heart and soul of a successful company.
actual labor rates for thousands of items of materials
CHAPTER 1

How to Estimate Electrical


Construction Projects

Reference material on installations of other trades


T his information and instructional material is de-
signed for those who have experience as an electri-
cal contractor, electrician, electrical draftsperson, or
Pads of rough takeoff, estimate, feeder, recapitu-
lation, and change-order sheets
electrical engineer in the construction industry, and
also for those who want to increase their knowledge of Estimator's Tools Required
the estimating field. If you have some knowledge of Triangular architect's rule
blueprint reading, electrical materials, and field instal- Triangular engineer's rule
lations on construction projects, this material will be
Miscellaneous drafting tools (angles, protractor,
easier to learn and then apply. After you complete this
templates)
book, you will need to have access to the essential refer-
ence materials and tools that are listed below, whether Manual hand counter
you are a beginning or a seasoned estimator. Map measuring wheels (1 inch, % inch, and M
inch to the foot)
Electronic probe counter and measurer in lieu of
Contractor's Libray: Reference Material
manual counter and wheels
for the Estimator
Walking measuring wheel
Latest edition of the National Electrical Code
A 100-foot tape measure
Latest edition of the National Fire Prevention
Highlighter markers
Code
Access to a computer is recommended
Latest edition of the BOCA Code and local codes
in the area of construction
Estimating is the art of translating blueprints, scopes
Catalogs and digests of electrical materials of work, prebid field inspections, and verbal requests for
Material pricing references proposals into costs of materials and labor required to
Labor unit manual for electrical materials produce a complete electrical installation with an ade-
(enclosed within Chapter 3 preferred) quate profit margin. Although there are various types of

1
2 How to Estimate Electrical Construction Projects

estimating, such as the square-foot method or the assem- A site plan and partial site services plan show the
bly method, this course will use the labor-unit ap- site lighting poles and fixtures, the wall and floor open-
proach. There may be instances where the estimator ings for the electrical service, and communications and
uses methods other than the labor-unit approach to pro- site lighting that the builder installed in the concrete
duce a budget or ballpark price. This often occurs when bearing walls below grade. Also shown are details on the
time does not allow for a labor unit estimate, but the site lighting pole bases and conduits for the service, in-
contractor feels compelled to submit a proposal to the cluding wire size, conduit size for the communications,
requesting party. These proposals are often costly to the and conduit size with wire sizes for the site lighting. The
contractor and have a negative effect on the relationship location of the temporary electric service for the project's
between both parties and perhaps others who have an construction and staging area is also shown.
interest in the project. Included in the bid package are the plans, contract
specifications including a scope of work, and a form of
SECTION 1: Preparing Estimates from Plans, proposal to be used by the bidder when submitting his
Specifications, and Related Documents or her price. The scope of work defines what is to be
For this exercise, let us assume that a shell of a 5,000- included in each contractor's proposal. There is also a
square-foot (50' x 100') building has been erected for bulletin #1 (sometimes referred to as an addendum)
future office space. The floor has been poured with 4 that is to be acknowledged as received, and any cost
inches of reinforced concrete, the exterior walls are impact must be included with the contractor's pro-
constructed with cement blocks, and the roofing mate- posal. Bulletins and addenda often arise in response to
rial is supported by steel bar joists on 4-foot centers. questions of clarification asked by the contractors. This
There is a main front entrance and side and rear exit method keeps all of the bidders aware of any changes in
doors. The building will be heated by natural gas and their scope of work, which may affect their proposal.
will be fully air-conditioned by four roof-mounted, Bulletin #1 is issued to change the bid due date only.
prepackaged HVAC units. The men's and women's rest-
rooms will have a roof-mounted exhaust fan and their STEP 1: What Documents to Look for
walls will be constructed of cement blocks. The entire and Examine
building will have an automatic wet fire-sprinkler sys- Invitation to Bid
tem. The finished ceiling will be constructed with sus- The invitation may come to the bidder in the form of a
pended tee bars and acoustical ceiling tiles sized at 2' x letter, postcard, newspaper advertisement, facsimile,
4' and 2' x 2' as required. The interior walls will be steel email, or by telephone. Let us assume it was delivered
studs with sheet rock. A utility room with exposed ceil- to the bidder by letter, requesting a proposal for his or
ing construction has been provided for the electrical her portion of the work. In this case, it is for the electri-
equipment, building maintenance items, and communi- cal installation of the proposed office space. The invita-
cation space for voice and data distribution. tion usually provides a project description along with,
There are electrical floor plans that show the electri- but not limited to, other related information such as the
cal panels, lighting fixtures, switches, receptacles, ex- physical size of the building, its present condition,
haust fans, HVAC units, exit and emergency light units, location, owner, a time and date for a prebid meeting at
time clocks, fire alarm panel, fire bells, fire pull sta- the site for all the bidders (sometimes attendance is
tions, smoke detectors, telephone and data outlets, and mandatory), and a time and place to receive the bids.
detailed riser diagrams for power, fire alarm, and com- This invitation may be sufficient for the contractor to
munications systems. Most estimators will review the either submit or decline to submit a proposal. In this
electrical plans immediately and notify the various case, we will review the invitation along with the form
major material suppliers of the need for pricing and of proposal (bid form) prior to proceeding with the
the date their prices are required. decision to submit a proposal.
How to Estimate Electrical Construction Projects 3

Form of Proposal or Bid Form tractor with specific requirements for the completion of
This will give the contractor information on bonding their work. Here the contractor will review information
requirements, among other things. Is there a bid bond, let- on all of the contractors obligations for their work. A
ter of surety, or performance and payment bond required, scope of work is outlined, and also information on in-
and to what percentage are the performance and the pay- surance requirements, time of completion, payments to
ment bonds rated? This is important for the contractor to contractors (including a schedule of values), damages,
know prior to investing time and dollars in an estimate. conflicts, disputes, arbitration, progress scheduling
The contractor may or may not be able to acquire addi- (either by a bar chart or a more complex critical path
tional bonding for this project for various reasons. Per- method), temporary facilities required, inspection re-
haps the contractor has a limit on the dollar amount of ports, cooperation with other trades, cleanup, storage
volume the bonding company (also referred to as the facilities, shop drawings, etc.
surety) has predetermined to be the limit of liability.
There are many different ways a total estimated price Supplementary Conditions. Not all projects will re-
might be requested. Instead of asking for just one total quire this type of supplement. These are used primarily
price for the contractors entire scope of work, the bid when a generic set of general conditions is used for a
request might require a breakdown of the total price by project. This reduces the cost of designing a whole new
tasks within the scope of work. Thus, there will be many set of general conditions. As each project stands on its
different forms of proposal that the contractor will be ex- own as to conditions, it is more cost effective to use sup-
posed to. The estimator must prepare the estimate ac- plements along with a generic set of general conditions.
cording to the requirements as described in the proposal
form. Special Conditions for the Mechanical and Electrical
Note: It is the estimators responsibility to inform Trades. These trades require specific instructions be-
the contractor of bidding and bonding requirements as cause each trade either supplies electrical materials for
soon as possible, to give the contractor ample time to installation by others, or is obligated to supply and in-
make an intelligent decision as to whether to bid on the stall certain items requiring electrical power supply in
project or decline. This also gives everyone concerned one form or another. It is very important that the electri-
ample time to complete their tasks prior to the date cal estimator read the requirements of all the mechani-
fixed for submitting proposals. cal trades to ascertain the responsibility of the electrical
Now that we have examined the invitation to bid contractor. Examples of items that would need to be
and the form of proposal, the contractor has made the clarified are motor controls, disconnect switches, duct
decision to submit a proposal on the project. heaters, automatic temperature control systems, han-
dling of motors, fire-pump controls, and the like.
Project Specifications
Contained within the specifications are the general con- General Construction Division. Although we will be
ditions, the supplementary conditions, and the special assuming that a shell of a building is in place and the
conditions for the mechanical and the electrical trades. scope of work will govern, it is necessary to become
Next we will follow the various trade divisions of the familiar with all building specifications that follow.
work. Let us look at each division for the items that This section will discuss who is responsible for the
may impact the estimators price structure. following: site clearing and preparation, civil work,
drainage, roadways and parking areas, surveying, exca-
General Conditions. These apply to all the prospec- vation, forms, reinforced concrete work, masonry units,
tive contractors who may be contracted to install a por- roofing materials, miscellaneous metal, insulation,
tion of the construction project. A scope of work, which weatherproofing, partitions and interior wall finishes,
is part of the general conditions, will provide each con- windows, glazing, interior and exterior doors, magnetic
4 How to Estimate Electrical Construction Projects

door holders for the fire alarm system, hardware, floor electrical contractor. The specifications will define all
covering, painting, suspended ceilings, acoustical treat- of the electrical components as to type, installations,
ment, carpentry, openings for other trades, and other sizes, manufacturers, shop drawing requirements, etc.
miscellaneous items. When the specifications and plans conflict, a general
rule of thumb would be that the plans take precedence
Structural Steel Division. This section will not be as over the specifications. The thought behind this is that
detailed as the general construction division. The esti- the plans are drawn for a particular project, while the
mator should review this and look for such items as specifications are used by many electrical engineers for
openings in the roof material and bar joist construction. many different projects.
There may be specific loading and or hanging require- If a major conflict is detected and a cost impact is
ments allowed from these joists, in addition to other apparent, the electrical estimator should write to the
agencies having jurisdiction. electrical engineer, with a copy to the architect, asking
for a clarification. Beware of seeking answers in phone
Plumbing Division. Do not overlook this division by conversations. Too often, phone calls are forgotten and
assuming that plumbing has no significant impact on in the general conditions this type of communication
the electrical work. There are items that may require will not be honored if challenged. Always put all of
electrical power such as, but not limited to, sewage your job-related concerns, questions, and statements in
ejector pumps, sump pumps, water pumps, boilers, writing to all the interested parties. Send copies to the
certain gas-fired units, water connections to emer- owners representative, inspectors, the architect, engi-
gency power generators, motor controls, fire pumps neers, the general contractor, subcontractors, and any
and related flow switches, and tamper switches and other persons who would be directly involved with
controllers. So, be sure to review this division as well your concern, question, or statement.
as the supplementary conditions for the mechanical
and electrical trades to learn who is responsible for fur- STEP 2: The Bid Drawings
nishing, installing, and connecting such items. and Estimate
Let us begin with a set of bid drawings issued along
Heating, Ventilating, and Air-conditioning Division. with the previous bid documents. The drawings include
In this division, there will be many items that will re- a title sheet, which will list the project name and ad-
quire coordination with the electrical contractor. There- dress, the owners name and address, the designer archi-
fore, it is absolutely necessary for the estimator to re- tect, engineers, the date, and a list of drawings included.
view each section of this division where there are items By having a complete set of drawings, the bidders on the
that require electrical power and perhaps control wiring. various sections will have all of the building informa-
These specifications will define who furnishes, installs, tion necessary to submit a sound proposal. Unfortu-
and connects the materials necessary for this division. nately, there will be times when you will only receive
Review in detail the sections on roof fans and blowers, the electrical floor plans and perhaps a site plan. This
prepackaged gas-fired rooftop heating and air-condi- creates a list of exclusions you will need to submit along
tioning units, automatic temperature control systems, with your proposal. But let us continue with the prem-
connections to heat-supplying light fixtures, duct- ise you have all of the bid drawings.
mounted fire detectors with probes, motorized louvers,
electric heat units, motor controls, and the like. Title Sheet
This sheet offers important information such as a list of
Electrical Division. You should read these sections in the drawings for each main section of the work, the
their entirety; along with all the other divisions and number of drawings, revisions with their dates, and the
sections, these form the written requirements for the contact information for the architects and engineers.
How to Estimate Electrical Construction Projects 5

The estimator must compare each drawing number, oversight by the affected trades. Landscaping contrac-
date, and revision to the title sheet list of drawings. tors generally investigate their planting areas as they
This will assure the estimator that the drawings bound relate to utilities that may be buried there. Keep this in
in the bid set are the appropriate bidding documents. If mind when preparing your estimate.
the estimator discovers any discrepancies in the bid Look for the water meter, which may be located in a
drawings, he or 5 he should immediately ask the archi- pit on the exterior of the building or in the building.
tect for clarification, in writing, with copies to the This water meter may require a continuous bonding
owner's representative and the engineer. If the proposal jumper around the meter to prevent loss of continuity of
is being made to a general contractor, the request for the metal water service conduit if the meter is removed.
clarification would go to that contractor. Remember, all The local inspecting agency will be able to answer any
communications by telephone must be followed up in questions regarding grounding andlor bonding that they
writing to avoid under- or overbidding. require. Remember that the National Electric Code
(NEC) provides the minimum requirements for electrical
Site Plan installations, but the local electrical inspecting agency
Now that we have verified that all of the drawing num- may enforce a higher level of requirements. Question
bers and dates bound in the bid documents are correct, the local electrical inspector. Locate the sleeves that the
we can proceed with a scan of all the drawings, begin- general contractor built into the walls below grade for
ning with the site plan. A typical site plan will show the electric service, telephone, data communications,
the building(s), roads, driveways, sidewalks, parking and site lighting. You will need to connect to these and
areas, utilities, landscaping, lighting, and various other list this work in the estimate. Review the site lighting
details. Note the scale on the site plan for future refer- fixtures and bases. Look for any details on the site light-
ence and highlight it with a marker. Consider repeating ing fixtures, bases, and their description schedule that
the scale in large numbers with a colored marker in an may be on this sheet. If there are no details here, they
open area on all the plans so you can't miss it. Take will be located on the electrical plans. This plan may
note of the compass heading in reference to the build- also show where temporary services are to be located,
ing for your information when placing photocells for such as electric, water, telephone, and staging and stor-
exterior lighting, if specified. age areas for the contractors.
The main road that provides access to the project
will be the most likely area where all services will be Foundation Plans
accessed. Regarding the electric, telephone, and data Not all bid sets will contain separate foundation plans.
services to the building, you will need to pay close The architect may decide to incorporate this informa-
attention to various elements such as the topography, tion on the architectural plans. If you encounter foun-
landscaping, other utilities, paving, and curbs. All dation plans, you should scan them for possible utility
these factors have a direct impact on the electrical pro- sleeves or windows below grade in the foundation
posal. If the conduits that supply these services need to walls. Here you will find the depth and sizes of the
be buried at a depth of 42" minimum, then the topogra- footings, and the width of the foundation walls and
phy will need to be examined closely for rises and grade beams. Take note of the elevation of the top of the
declines of the rough graded area. You may have to footings. This will determine whether you need to stay
excavate 60" of depth in some areas of the direction of above or below the footings with your conduits enter-
the conduits to maintain 42" minimum depth of these ing the building from the exterior. This plan might also
conduits, Locate any landscaping that may affect the include a list of test borings showing the earth compo-
direction and depth of these conduits, and report any sition at different levels made in various areas of the
depth and direction conflicts to the architect. I have site. This will help you andlor your subcontractor in
seen many auger bits chew up conduits because of the estimating your excavation costs for trenches, manholes,
6 How to Estimate Electrical Construction Projects

handholes, site lighting pole bases, etc. that may be Mechanical and Electrical Site Plans
required. Some engineers will prefer to add this plan rather than
try to incorporate all of their designs onto the archi-
Finish Schedule Sheet tects site plan. This plan will lay out such items as the
This sheet will list every floor, wall, and ceiling finish electrical and communications services, site lighting
within the building. This will guide you in selecting with their details, temporary services locations, cooling
the proper floor outlets, wall outlet boxes, ceiling outlet towers, condensers for air conditioning, motor-driven
boxes, recessed or flush-mounted ceiling fixture frames pumps, emergency power units, fuel tanks, etc. Coordi-
or rings. The architect may specify special colored de- nate this plan with other site plans in the bid package.
vices and plates to match wall finishes. You will not
know what colors may be special without reviewing the Plumbing Plans
finish schedule, so the finish schedule has a direct Here again, the total number of plans that are numbered
impact on the electrical estimate. This sheet may also P-1, P-2, P-3, etc. will be determined by the mechanical
incorporate the door finish schedule. This will need to engineer. Although you may think that reviewing the
be reviewed for any electrically operated overhead-type plumbing plans are not so important, you do need to
doors, entry doors, roll-up windows, etc. for their elec- review these plans just as you would review the other
tric requirements. plans. Where is the water meter if not shown some-
where else? The fire pump and associated equipment
Architectural Plans will be shown here, as well as any sprinkler flow and
The total number of plans that are numbered A-1, A-2, tamper switches. Sump pumps, condensate pumps, hot
A-3, A-4, etc. will be determined by the architect and water pumps, chilled water pumps, cooling towers, etc.,
the complexity of the project. These plans will be used and all of their associated electrical equipment will be
to construct the project. All of the information needed shown here as well. Some engineers will include a
by the general contractor will be incorporated therein. schedule of all the mechanical equipment, the name-
The electrical estimator should review all of these plate data, and the contractors responsibilities.
drawings to become familiar with all the different Other engineers will list all of these requirements in
rooms, halls, multistory stairways, exits, entrances, the specifications rather than on the plans. The plumb-
details of wall sections, and ceiling details. A reflected ing specifications may indicate that all control wiring is
ceiling plan will be included in these A-drawings.

to be furnished and installed by others. Seldom will the
This plan may show the ceiling lighting fixtures. The plumbing specifications require that the control wiring
electrical engineer will use the reflected ceiling plan to be furnished and installed by the plumbing contractor.
design the fixtures and circuiting. Note the details on Most times it would be the responsibility of the electri-
the suspension system of all the suspended ceilings. cal contractor.

Structural Plans Heating, Ventilating, and Air-conditioning


Again, the total number of plans that are numbered S-1, Plans
S-2, S-3, etc. will be determined by the structural engi- The total number of plans that are numbered HVAC-1,
neer in coordination with the architect. It is important WAC-2, WAC-3, etc. will be determined by the mechan-
to review all of these plans and the associated details ical engineer. The HVAC plans may be the most impor-
for slab thickness, foundation and footing design, struc- tant plans that the electrical contractor reviews, other
tural steel layout, bar joist placement, roof steel, and than the architectural and electrical plans. These plans
decking. Do not overlook these plans, as many ques- will show where all of the heating, ventilating, and air-
tions can be answered here. conditioning equipment are located. You should review
How to Estimate Electrical Construction Projects 7

the sheet-metal duct drawing to know the various sizes of Now that we have reviewed all of the bid plans, we will
the supply and, if any, the return ducts. This will also lay review the electrical plans and prepare to do a system-
out the rooftop multizone or single-zone HVAC units, atic estimate. Keep in mind that we have previously
roof fans, cooling tower, duct-mounted reheat units, ther- asked the various material suppliers and subcontractors
mostats, ATC zone valves, lighting unit boot attachments for their quotations on such items as interior and exte-
for air-handling fixtures, etc. The floor plans will locate rior light fixtures, electrical distribution panels, fire
the motorized dampers as required for the ventilation alarm equipment, communication equipment, precast
design, piping details, unit heaters, unit ventilators, sill- concrete bases, and excavation on this project. Many
line heat units, etc. Some engineers may include a sched- suppliers will meet with the electrical estimator and
ule of all equipment with the electrical requirements, review all of the equipment that will need pricing.
along with who is responsible for furnishing, installing, Some electrical supply houses, if asked, will supply the
and wiring it all. Other engineers will spell it all out in estimator with prices on the total amount of power and
their specifications. The plumbing and the HVAC de- communication cable, raceways, and devices. Look
sign engineering are generally performed by the same over each plan and become familiar with the layouts of
engineering company. In some instances, the plumbing, all the devices and equipment. We will begin an electri-
heating/ventilating/air conditioning, and electrical will cal material takeoff in Chapter 2 by turning to the Typ-
be designed by the same engineering company. ical Electrical Symbol List, which has three pages of
common electrical symbols. (Note: There are symbol
Electrical Plans lists on the other contract plans that the estimator can
The total number of plans that are numbered E-1, E-2, refer to when there is equipment furnished by other
E-3, etc. will be determined by the electrical engineer. trades that require electrical connections.)
CHAPTER 2

Electrical Material and Labor Takeoff

Typical Electrical Symbol List


The symbols shown below are generic in nature, but them handy rather than keep fumbling through plans.
they give the estimator a guide while doing a takeoff. Each engineer has symbol lists they use that may vary
Review this list and become familiar with the symbols. with others, but basic symbols are the same throughout
Some estimators will photocopy the symbols and keep the industry and will be on all symbol lists.

s Single-pole switch, amp, and volt rating in specs


s2 Two-pole switch, amp, and volt rating in specs
s 3 Three-way switch, amp, and volt rating in specs
s4 Four-way switch, amp, and volt rating in specs
s, Single-pole switch with lighted handle, amp, and volt rating in specs
Wp Weather proof (nema rating as shown on plans and in specs)
dim Dimmer switch rating, voltage, type, and incandescent or fluorescent in specs
eXpl0 Explosion proof (class and division ratings in specs)
0 Duplex receptacle, amp, and volt rating in specs
@ Single (simplex) receptacle, amp, and volt rating in specs
@ Special receptacle, amp, and volt rating in specs
F Duplex receptacle in a floor box, amp, volt, and type in specs
tifmn: Duplex receptacle-2 gang floor box with combo cover for receptacle and communication jack, in specs
Enclosed circuit breaker as shown on plans and in specs
Disconnect switch; I-,2- or 3-pole amp and volt as shown on plans and in specs
Combination disconnect and starter as shown on plans and in specs
Starter as shown on plans and in specs
Sm Single-pole manual motor starter as shown on plans and in specs
Sm, Single-pole manual motor starter with pilot light as shown on plans and in specs
1 Control station with buttons, switches, and/or lights as shown on plans and in specs

9
10 How to Estimate Electrical Construction Projects

Contactor as shown on plans and in specs


l i me clock as shown on plans and in specs
Photocell as shown on plans and in specs
Relay as shown on plans and in specs
E
1Motor control center as shown on plans and in specs
0 Single-phase electric motor as shown on plans and in specs
Three-phase electric motor as shown on plans and in specs
Unit heater as shown on plans and in specs
Cabinet heater as shown on plans and in specs
Heating, ventilating, and air-conditioning unit as shown on plans and in specs
4 Ground connection as shown on plans and in specs
6 Transformer as shown on plans and in specs
1-1 Switchboard as shown on plans and in specs
Main distribution panel as shown on plans and in specs
F l Power panel as shown on plans and in specs
Lighting panel as shown on plans and in specs
w\ Receptacle panel as shown on plans and in specs
Manhole as shown on plans and in specs
Handhole as shown on plans and in specs
- Raceway exposed as shown on plans and in specs
--- Raceway concealed in slab or below grade as shown on plans and in specs
7 Raceway or cable concealed above finished floor as shown on plans and in specs
- - SR Surface raceway as shown on plans and in specs (metal or nonmetal)
- - MI Mineral insulated cable as shown on plans and in specs
-TC- Tray cable as shown on plans and in specs
Cable tray as shown on plans and in specs [include bends, hangers, drops, grounds, couplings, etc.)
Feeder bus duct as shown on plans and in specs (include all associated components)
Plug-in bus duct as shown on plans and in specs (include all associated components)
Bus plug-in disconnect/circuit breaker as shown on plans and in specs
Patch panel floor stand as shown on plans and in specs
[171 64-port patch panel as shown on plans and in specs
- Shelf for patch panel and wire manager as shown on plans and in specs
m F Floor box with data outlet as shown on plans and in specs
VD Wall box with data outlet as shown on plans and in spec3
B F Floor box with voice outlet as shown on plans and in specs
mV Wall box with voice outlet as shown on plans and in specs
mF Two-gang floor box with data and voice outlet as shown on plans and in specs

- 100 pair #llO-voice block for voice communications as shown on plans and in specs
Communication backboard, size as shown on plans and in specs
VPT Wall box for public telephone connection as shown on plans and in specs
0 e Incandescent light fixture recessed "TYPE"as shown on plans and in specs
0 4 Incandescent light fixture wall-mounted "TYPE" as shown on plans and in specs
@ Exit light fixture ceiling-mounted "TYPE" as shown on plans and in specs

-0
Exit light fixture wall-mounted "TYPE" as shown on plans and in specs
Incandescent light fixture recessed "TYPE" as shown on plans and in specs
Fluorescent light fixture 12" to 24" long surface-mounted "TYPE" as shown on plans and in specs
-
Electrical Material and Labor Takeoff 11

Fluorescent fixture 48" long surface I recessed I lay-in I suspended "TYPE" as shown on plans and in specs

-
Fluorescent fixture 24" x 24" surface I recessed I lay-in I suspended "TYPE"as shown on plans and in specs
0 Fluorescent fixture 24" x 48" surface I recessed I lay-in I suspended "TYPE" as shown on plans and in specs

n Fluorescent fixture 48" x 48" surface I recessed I lay-in I suspended "TYPE" as shown on plans and in specs

Fluorescent fixture 8' long surface I recessed I suspended "TYPE"as shown on plans and in specs
Light-track surface-mounted "TYPE" and length as shown on plans and in specs
Light-track fixture "TYPE" as shown on plans and in specs
Chandelier suspended "TYPE" as shown on plans and in specs
Emergency battery unit "TYPE" as shown on plans and in specs
Emergency remote light "TYPE" as shown on plans and in specs
HID lighting fixture "TYPE" as shown on plans and in specs
HID lighting fixture "TYPE" as shown on plans and in specs
Bollard for walkway "TYPE" as shown on plans and in specs
Site lighting pole and one fixture "TYPE" as shown on plans and in specs
Site lighting pole and two fixtures "TYPE" as shown on plans and in specs
Site lighting pole and four fixtures "TYPE" as shown on plans and in specs

In ground flagpole light as shown on plans and in specs


Fire alarm panel with battery backup
Fire alarm remote annunciator
FAmanual pull station
Lr# FA combination horn and light
-P FA outdoor combination horn and light
0 SD FA smoke detector
0 HD FAheat detector
ODD FAduct detector with sampling tube
~ I FAremote
L indicating light
wl FA data gathering panel
laahl FAremote module
FAflow switch
FA tamper switch
FA electro/magnetic door holder

Ceiling Finishes Reviewing the ceiling finishes prior to counting the


As suggested previously, a good procedure for the esti- light fixtures will save many headaches when purchas-
mator to follow is to review the architectural plan for ing the light fixtures and fixture frames for recessed
the ceiling finishes. Let us look at the ceiling finishes light fixtures, pendants for suspended light fixtures,
partial floor plan (Fig. 2-1, p. 13). hold-down clips for lay-in light fixtures, shade aligners
You will see that all ceiling finishes are type "A" unless for light fixtures with RLM-type shades (reflectors), and
noted otherwise. A type "A" ceiling finish is to be a 2' x 4' airplane-type steel cable for suspended light fixtures.
suspended grid with 2' x 4' acoustical ceiling tiles. A type The estimator should transfer the ceiling finishes in-
"B" ceiling finish is to be a 2' x 2' suspended grid with 2' formation to the electrical plans. Here is where colored
x 2' acoustical ceiling tiles. A type "C" ceiling finish is to highlighters will help the estimator-you can color code
be a suspended framework for a sheetrock finish. Finally, the various ceiling types on the electrical plans. Perhaps
a type "D" ceiling finish is to be exposed construction. the ceiling finish with the greatest percentage of the
12 How to Estimate Electrical Construction Projects

ceiling construction would not be color coded; just color all the light fixtures have been counted, we total them
code the smaller ceiling areas. This will make the light and list all of the associated items needed to have a
fixture takeoff easier and more accurate than hurrying complete working lighting system for the building.
the takeoff and omitting some of the associated light fix- Each fixture will have lamps, outlet boxes, junction
ture accessories. This color-coding method will avoid boxes, flexible whips, etc. Other necessary items may
serious and costly mistakes. be hold-down clips, suspension materials (pendants,
chains, cables, etc.), splicing materials, fixture wire,
Text Introduction to Fixtures Takeoff and labor for testing and tagging. A flexible whip is
Before beginning to count the light fixtures, the estimator allowed for each lay-in and recessed fixture. Wall-
should have pencils, blank rough takeoff sheets, a few mounted fixtures will require a wall outlet box, as will
different colored highlighters, and a manual or electronic some ceiling-mounted fixtures. The estimator should
counter. These are essential for the estimator to keep investigate which fixtures may be furnished with an
handy at all times. As you begin to count the items, make outlet box and check all notes and the specifications for
a small colored slash mark on each item and record each possible spare lamps and fixtures. There are occasions
item with the counter. It is a good idea to select a color when the engineer will specify that a percentage of all
for each division of the takeoff, such as fixtures, devices, types of lamps be turned over to the owner as spares at
and their wiring in orange, fire alarm systems in red, the completion of the project. The estimator must allow
communications voice in green, data in yellow, etc. This a sum of money for this requirement in the estimate.
method will ensure that each item will be counted only The estimate sheets (Figs. 2-4A, B , pp. 20, 21) will
once (Figs. 2-2A, B, pp. 1 5 , 16). Note that there are many show how all of the fixtures and associated materials are
products on the market that can color and count at the to be listed for pricing and the hours required for each
same time. Use whatever you find most comfortable. material. The prices are not included due to each contrac-
All of the fixtures are listed on the top section of the tors price structure with the material suppliers and actual
fixtures rough takeoff sheets (Figs. 2-3A, B, pp. 18,19).By price fluctuation in the markets. A few of the items such
listing the fixture type, size, mounting, lamps, voltage, as hold-down clips, supports, splicing, tags, testing, etc.
etc., the estimator has a snapshot of the most important are allowance items of money and hours. These amounts
facts about the fixtures. Beginning with type A fixtures, will vary according to the size of each project.
count all of them on the floor plan and enter the total in
the block under the description. Note that in the left-most Text Introduction t o Devices Takeoff
column the estimator will list which plan the fixtures In order to count all the devices, we need to turn again
were counted from. There is a reason we takeoff the elec- to the lighting fixtures partial floor plan (see Fig. 2-2B,
trical items and list them according to which plan they p. 16) to count the switches. This plan will show you
were counted from. For example, if after the contracts are that some of the switches are ganged together as re-
awarded, the owner requests that all of the type B light quired (meaning more than one is utilized). When you
fixtures on the first floor be changed to another style or count these switch locations, count them as you see
deleted, the estimator can turn to the rough takeoff sheets them; for example, SSS is a three-gang box and plate
and very quickly respond to the request. This saves over- with three switches. Counting the switches this way
head time and money. The estimator does not have to will not only give you the switch count, but will give
open the plans and do another count on that type of fix- you the count of the boxes (single or ganged) and the
ture. This method applies to all of the takeoffs. matching plate(s). These switch totals are listed on the
devices rough takeoff sheet (Fig. 2-6, p. 24). Also on
Text Recap of Fixtures Takeoff this sheet is a count of the receptacles shown on the
This concludes the light fixture counting and com- partial device floor plan (Fig. 2-5, p. 22). You should
pletes the takeoff of all the building light fixtures. After check the specifications to see if any special covers or
Electrical Material and Labor Takeoff 13
14 How to Estimate Electrical Construction Projects

NOTES
Electrical Material and Labor Takeoff 15

FIXTURE LEGEND

SYMBOL -
TYPE DESCRlPTlON

A FLUORESCENT 277V LAY-IN 2' X 4' 3/32W CWRS LAMPS


A- 1 II II
I' 2 ' X 4' 2/32W CWRS LAMPS
II II
B I' 2' X 2' 2/32W U CWRS LAMPS
C II II
I' 4 ' X 4' 6/32W CWRS LAMPS
II
D II
RECESSED 1' X 4' 2/32W CWRS LAMPS & FRAME
E EXIT LIGHT UNIVERSAL MOUNT 277V W/ LAMPS AND BATTERY
F FLUORESCENT 277V RECESSED HIGH HAT W/ 1 PL LAMP
II I'
G WALL MOUNTED W/1 PL LAMP
H HI-PRESSURE SODIUM 277V W/P WALL MOUNTED W/ 1 70W LAMP
J TRACK LIGHT FIXTURE 120V W/ 1 75W PAR LAMP
J-1 4' LONG TEE BAR MOUNTED LIGHTTRACK 120V 1 CIRCUIT & HARDWARE
K FLUORESCENT 120V UNDER COUNTER PLUG IN FIXTURE 24" LONG
L II
277V SUSPENDED FIXTURE W/ 2 32W CWRS LAMPS
M INCANDESCENT FIXTURE W/P W/ 1 1OOW IF 130V LAMP & BOX
N I1 II I'
W/ 1 150W PAR 38 FLOOD LAMP & PE
EM EMER' B A T UNIT 277V 2 HEADS WALL MTD.
EM II II I1
I' 1 HEAD II II

RH REMOTE EMER. BATT' HEAD

Figure 2-2A

colors for the devices are required. Normally the cata- The estimate sheet (Fig. 2 - 7 , p. 2 5 ) will show how
log numbers of the devices are listed in the electrical all of the devices and associated materials are to be
specifications or on the symbol list. The architect may listed onto the estimate sheet for pricing and the hours
note special colors for all wall devices on the architec- required for each item.
tural plans: they might not be found elsewhere. This is The prices are not included due to each contractor's
why we stress the need for reviewing all the bidding price structure with the material suppliers and actual
documents for possible items that will affect the electri- price fluctuation in the markets. A few of the items
cal estimate. Be assured that this will come up in your such as the metal wall stud box supports are an allow-
estimating at some point, so do not overlook the review ance of money and hours. These amounts will vary ac-
of all the bidding documents. cording to the size and type of project.
16 How to Estimate Electrical Construction Projects
Electrical Material and Labor Takeoff 17

NOTES
EST. NO: 10/01/03-1

Lighting Fixtures 2x4' lay-ir


-
IXTURES
Type "A-1'
2x4' lay-ir
Type '8'
2'x2 lay-in
ROUGH TAKEOFF SHEET
Type 'EM"
wall batt uni
SHEETNO: 1 OF:
DATE: 10/1/0:
Type 'G'
fluor' wall
2

Type 'H'
wlp wall
ITEMS & 3-32~
cw 2-32~
cw 2-32wU cw 2 heads 1 pl lamp 1 - 7 0 hpS
~
LOCATION 277 volt 277 volt 277 volt 277 volt 277 volt 277 volt
~
emer unit (sconce)

1 2 1 5 3 1 8 3 4

0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0
0 1
0 0 0 0 0 I 0 0

-- --
0 0

1
0

2
0

1
0

5w/f rm's
- 0

3
0

3
0

T
14
Figure 2-3A
EST. NO: 10/01/03-1
w Type "J"
8' track surf
F
-
Type "J-I"
4' track surf
"J" fittings
internal 90
"J" fittings
live end
"J" fittings
couplings
'J" fittings
'T" bar clips
"J" heads
cylinders
Type "K"
2 surf
Type 'L"
4' susp'd
Type "M"
w/p globe
Type 'N"
w/p spot &
1 circuit 1 circuit feed in with each with under cab' rlm reflect'r w/ box motion sent Remote en
120 volt 120 volt outlet cover par20 75w 1-1 8w cw 2-32w cw 1-1 00 w if 1-1 50w par head
for "T" bar lamps 120 volt 277 volt 130 volt 120 volt

Plan E-1 Lighting 0 1 0 1 0 3 2 0 4 0 1 2

0 0 0 0 0 0 0 1 0 4 0 0

Plan E-3 TeVData 0 0 0 0 0 0 0 0 0 0 0 0


Panels &
0 0 0 0 0 0 0 0 0 0 0 0

>2 0 1
0

0
0

1
0

0
0

3
0

2
0

1
0

4
0

4
0

1
0

.---- -----
32 WAIT 32 WAIT U 18WAl-r IOOWATT 75WAlT 18WAIT 150WATT 70WAlT FIXTURE FIXTURE .FIXTURE FLEXIBLE
COOL WHT COOL WHT DUAL PL INCAND PAR 20 COOL WHT PAR 38 FL HPS BD OUTLET OUTLET JUNCTION FIXTURE
hips FLUO LAMF FLUO LAMF LAMPS LAMPS LAMPS FLUORLAMP LAMPS CLEAR BOXES BOXES BOXES WHIPS
120 v 120 v 120 v LAMP WALL IN CEIL'NG 4"SQ&COV

rTOTALS 74 4 11 4 2 1 1 4

Allow materials for independently supporting all light fixtures mounted in or on suspended ceilings.

Allow for hold-down clips on lay-in fixtures, splicing materials tags, testing, etc.
17 20 a

I
33

TOTALS

Figure 2-3B
20 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office bldq' #lo0 Utown, USA PAGENO: 1 OF 2


Estimate Sheet of Fixtures Labor Hours

ESTIMATED BY: F S.T. CHCKDBY: Sr. DATE: 10101103

1
2

3
4

5
6
7
8
9
10

11
12
13
14
15

16

17
18

19

20
21
22
23
24
25

26
27
28

29
30

31
32

Figure 2-4A
Electrical Material and Labor Takeoff 21

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office bldq' #lo0 Utown, USA PAGENO: 2 OF 2


Estimate Sheet of Fixtures Labor Hours

ESTIMATED BY: M C CHCKDBY: Sr. DATE: 10/01/03

I DESCRIPTION OF MATERIALS

1 -FIXTURE OUTLET BOXES FOR WALL


I
QUANTITY

17
I
MATERIALS
I UNITCOST I PERI
I
EA
I
i
AMOUNT I
i
LABOR t
UNIT I PEF

0.35
i
EA
2 FIXTURE OUTLET IN CEILING SPACE 20 EA 0.35 EA
3 4" SQ' BOXES W1 BLANK COVERS 8 EA 0.35 EA
4 FLEXIBLE FIXTURE WHIPS W/WIRE 33 EA 0.1 EA
5

6 HOLD-DOWN CLIPS FOR LAY-IN FIXTURES ALLOW


7 INDEPENDENT SUPPORTS FOR LAY-IN FIXT'S ALLOW 7
8 8

10
og
11

12 12

13 13
14 14

15 15

16 16

17 17

18 aving out a price or hours are 18


greatly reduced. Get in the habit of making a line from the
19 19
quantity column to the labor hours amount column. Leave
20 open only those spaces that require material prices and labor 20
hours! This applies to all estimate sheets of the estimate from
21 e recapitulationsheet to the last estimate sheet. 21

22 22

23 23

24 24

25 25

26 26
"7 I 27

I
~

28 28

29 I 29

30 I 30

31
I
I 31

32 32

EA = Each
TOTAL TOTAL 1 21.55

Figure 2-4B
N
N

DEVICES PARTIAL FLOOR PLAN SHEETNO: 1 OF 1


DATE: 10/01/03

6-pole contactor

tl
I
I
i
i
I
I
i
'. ' i
'
0
Note: These items are located on the roof.
Typical for 4 locations.

Notes: The type M fixture is a w/p globe complete with a photocell & box. Provide a suitable support for mounting
the fixture to. Mount the w/p receptacle on the same support.
Branch circuiting to run beneath in the hung ceiling space.
Coordinate roof penetrations with the general contractor and architect.
*Provide a single pole switch at the roof hatch to control the lights and outlets. NOT TO SCALE

Figure 2-5
Electrical Material and Labor Takeoff 23

NOTES
24 How to Estimate Electrical Construction Projects
.:. :..
Electrical Material and Labor Takeoff 25

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office bldg' #lo0 Utown, USA PAGENO: 1 OF 1


Estimate Sheet of Devices Labor Hours

ESTIMATED BY: Mr. E S T . CHCKDBY: Sr. DATE: 10/01/03

DESCRIPTION OF MATERIALS MATERIALS I LABORHOURS


QUANTITY I UNITCOST AMOUNT I
IPERI UNIT I PERIAMOUNT

1 1
2 2

3 3
4 4
5 5
6 6
7 7
8 8

9 9

10 10
11 11
12 12
13 13
14 14

15 15
16 16
17 17

18 18

19 19
20 20
21 21

22 22

23 / 23

24 I
I I
24

26 I 26

27
-,
I
I
I
I
27

29 I 29

30 I
I I
I 30
31 I I I I I I 31
I I 32
32
EA = Each
INC = Included TOTAL TOTAL 30.85

Figure 2-7
26 How to Estimate Electrical Construction Projects

Text Introduction to Site Lighting Takeoff of the totals accumulated from the site plan as you
measure all distances between poles and building.
The site lighting partial plan (Fig. 2-8, p. 27) gives us a
Items not to overlook in the estimate:
view of the building, site light fixtures, site lighting pole
base detail, parking areas, sidewalks, driveways, road
1. Excavation, stone base, backfilling, and tamping
locations, utility pole, utility transformer, lighting con-
for the precast concrete bases (allow for the
tactor, time clock, and photo cell. Begin the takeoff by
removal or spreading of excess earth).
listing the site lighting pole types on the rough takeoff
sheet (Fig. 2-9, p. 29). The poles have single or multiple 2. Delivery of bolt circles, anchor bolts, precut PVC

fixtures on them and are laid out for driveway and park- ground rod sleeves, and preassembled PVC race-
ing area illumination. When we count the pole types, we ways to the precast manufacturer. Determine
will also be counting the fixture heads, lamps, and con- whether the precast manufucturer will set the bases
crete bases at the same time. As listed on the sheet, there in the holes or in one staging area upon delivery.
are many items that will be required for the fixtures, but If all the bases are delivered and unloaded in one
not seen, such as fuses, splicing, direct burial warning place, the estimator must allow time and money
tape, wire in the poles, and ground lugs. The concrete to move the bases into place and set them.
bases have a $9' PVC sleeve in the center to accommodate 3. Allow money for a boom truck to pick up the
the installation of a ground rod after the base is set in poles and set them on their bases. Preassemble
place. The precast contractor will place the anchor bolts, the pole arms, fixtures, and wiring, and test the
sleeves for wiring, and the ground rod. They will not pole assembly on the ground prior to lifting it
need a labor factor applied, just delivery charges to the into place. Allow money for leveling material
precast company for their installation. The conduit sys- and allow for labor.
tem will be 1%''schedule 40 PVC with copper wire sizes 4. Allow money to lay out the pole locations with
and types as shown. To determine the footages of the the site engineer. Request a quotation from other
PVC, wire, trenching, and warning tape, you will need a civil engineers, also.
scaled rule or map measurer. Measure each run of PVC
and enter the totals as shown on the rough takeoff sheet The estimate sheets (Figs. Z-lOA, B, pp. 30, 31) will
(see Fig. 2-9, p. 29). List all of the PVC raceways, elbows, show how all of the site lighting poles and all associ-
couplings, and PVC cement. The excavation and associ- ated materials are to be listed for pricing and the re-
ated items required for the site lighting wiring are also quired labor hours for all material. The prices are not
listed. The estimator can request a quotation from exca- included due to each contractor's price structure with
vators or do this work with in-house workers and in- the material suppliers and actual price fluctuation in
house equipment. coordinate the raceway installation the markets. A few items such as in-line fuse holders
with the site contractor to avoid problems with curbs, (with fuses), ground lugs, wirenuts, etc. will be allow-
sidewalks, other utilities, and the like. ance items of money and hours. Some of the material
You can use the back of the sheet to list all of the will be required in the specifications and not shown on
individual footages of the PVC, wire, trench, warning the electrical plans. It is important for the estimator to
tape, etc. and then transfer the totals (as shown on the review the specifications repeatedly to avoid missing
sheet) to the face of the sheet. This will provide backup specified materials.
EST. NO: 1O/O1/03-1 SITE LIGHTING SITE LIGHTING PARTIAL PLAN SHEETNO: 1 OF
DATE:
-
10/01/03
1
JOB: Office bldq #lo0 Utown, USA

Pwrl Co. Term Pole


Primary electric service to xfm'r
2#8 & 1#10 in 1 Communications conduit to building

......
*.
.....
See site services plan for details

......
I
2#0 1#10 in 1 1/epvc -$
A
............... d P w r ' co'transf'

Type 3
6-pole Igt contactor 30a 480v &

. I -
Time clock for outside lighting

SITE LIGHT POLE BASE DETAILS


2#6 & 1#10 in 1 1/4"pvc anchor bolt ca e
*and rd sleve
OFFICE
Type 1 BUILDING 1 /e!
\ 3,' I
G* -
2#8 &1#10 in 1 1/4"wc

typical
conduit
-f. Type 1 + ' I space

I' I NOTTOSCALE
as reqd

NOTE: Anchor bolt size & circle


will be per pole mfg' spec's.

Figure 2-8
N
U
28 How to Estimate Electrical Construction Projects

NOTES
Type "1" Type "2" Type " 3 400 wan 400 wan in-line #12 thhn cu wirenuts ground lugs, 7'precast 1/2"x10 1/2"x7'
Site Lighting 2 0 alum pole 2 0 alum pole 20' alum pole fixt heads hps lamps fuse holders in poles tape & etc. attach to conc' bases copper clad pvc conduit
ITEMS & 2 40Ow fix 4 40Ow fix 1 400w fix w/ballasts base horz. w/ fuses from feeder to splice to pole pyramid type gnd rods for sleeves
LOCATION 26arms 43'arms 16'arm 480 volt up to fixt. feeds in pole 3 above grd' w/clamps precasted
480 volt hps 480 volt hps 480 volt hps 480 volt hps 4' below ard' into bases

Plan MEP-1 6 4 4 32 32 64 1.500 allow $$$ 14 14 14 *14


A good rule to follow when measuring the conduit and wire between the building panel and each pole light is as follows: Begin by numbering (1, 2, 3,4, etc.) or lettering
(A, B, C, etc.) each pole light. Then measure from the panel to the first pole and record that on the back of this sheet. Continue until you measure between each pole
light and then transfer all that info to this side of the rough takeoff sheet as shown below. The estimator may want to use a separate rough takeoff sheet and not use the
back of this sheet, whichever is more comfortable for the estimator ....

astrodial Itg contactor photo cell


time clock 6p 30a 600v 277v
2p 20a 277v 277v coil
n/l enclo n/l enclo

1 1 1

Figure 2-9
N
W
30 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office bldg' #lo0 Utown, USA PAGENO: 1 OF 2


Estimate Sheet of Site Linhtina Labor Hours

ESTIMATED BY: Mr. E S T . CHCK'D BY: Sr. DATE: 10/01/03

Figure 2-10A
Electrical Material and Labor Takeoff 31

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office bldg' #lo0 Utown, USA PAGENO: 2 OF 2


Estimate Sheet of Site Lighting Labor Hours

ESTIMATED BY: Mr. E.S.T. CHCKDBY: Sr. DATE: 10/01/03

1
2

3
4

6
7
8 # l o thhn 600v copper wire stranded 1,800' M 10 M 18
9
10 Direct buried electrical lines warning tape 1,500' M 4 M 6
I1

12

13

14

15
16
17
18

19
20
21

22
23
24

25
26

27
28

29

30
31

32

Figure 2-10B
32 How to Estimate Electrical Construction Projects

Text Introduction to Branch Wiring Takeoff The data patch panel floor stand with the patch panel
are also located in the utilities room. There are three
In order to takeoff the branch wiring, you need to refer to
locations that have a combination voice and data outlet.
a few of the electrical plans. On the lighting plan (see
These three outlet locations will require one category
Fig. 2-2B) you will find the circuiting for the lighting fix-
# 3 plenum-rated cable for voice and one category #5
tures and for the associated switching of these fixtures.
plenum-rated cable for data. Both cables will terminate
On the devices plan (see Fig. 2-5) you will find the cir-
in the utilities room on their respective voice block or
cuiting for the receptacles and the 1 2 0 V feed to the fire
data panel. The outlets at the wall will consist of one
alarm control panel from the RP panel. In our example
single-gang wall box, one voice connector, one data
here, MC cable is permitted on this project for all branch
wiring within the building. There is no wiring in the connector, and one single-gang combination wall plate
floor, as it had been poured prior to the contracts being to accommodate both voice and data connectors. The
awarded. There may be a need to install a short amount single-voice outlet in the utilities room will require an
on EMT in the utilities and restrooms (less than 50 feet), outlet box, a voice connector, and a single wall plate.
but we will make an allowance for this small amount of As you can see on the floor plan, the cables run to-
EMT and wire required. On the branch wiring rough gether through the suspended ceiling from the outlet to
takeoff sheet (Fig. 2-11, p. 33), the MC cable and associ- the utilities room. These cables will be supported by
ated fittings have been listed according to the plan num- J hooks and through the wall sleeves as required at all
ber. As described above, we takeoff the material and list penetrations. Patch cords are provided for both voice
it according to the plan number, which serves as a check and data. All cables, plates, blocks, and panels will be
that a plan was not overlooked in the takeoff procedure. tagged with the appropriate markings. Field testing
The estimate sheet (Fig. 2 - 1 2 , p. 34) will show how must be performed on all cables and a record of the
all of the branch circuit wiring and associated materials tests turned over to the proper authority. All penetra-
are to be listed for pricing and the hours required for tions of walls and partitions require sleeves to accom-
each item. The prices are not included due to each con- modate the voice and data cables. The estimator must
tractors price structure with the material suppliers and count and list all the components required for the voice/
actual price fluctuation in the markets. A few items data system on the rough takeoff sheet (Fig. 2-14, p. 37).
such as wall stud sleeves, splicing materials, tape, tags, The estimate sheet (Fig. 2-15, p. 38) will show how
junction boxes, etc. will not be shown on the plans, but all of the communication items and the associated mate-
will be required. It is important for the estimator to rials are to be listed for pricing and the required labor
visualize the installation of the cable and listing the hours. The prices are not included due to each contrac-
material and labor allowances in the estimate. tors price structure with the material suppliers and
actual price fluctuation in the markets. As listed above,
many materials for the communication system are not
Text Introduction to Communications Takeoff shown on the plans but will be necessary for a complete
The partial communication floor plan (Fig. 2-13, p. 35) system. Some of these materials may be patch cables,
shows the communications equipment for the voice grounding, a cable support system, labels, testing, etc.
and data wiring required. The voice backboard and The specifications will also specify the various compo-
110-punch-down block are located in the utilities room. nents required for a complete communication system.
SHEETNO: 1 OF: 1
DATE: 10/01/03
SPLICING WALL STUD 4 & 5
TAPE SLEEVES SQ BOXE!
TAGS Wl BLANK
COVERS

ALLOW I 40 I 25

ALLOW I 50 I 25

ALLOW I 90 I 50

Figure 2-1 1
W
W
34 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office bldg' #lo0 Utown, USA PAGENO: 1 OF 1


Estimate Sheet of Branch Wirinq Labor Hours

ESTIMATED BY: Mr. F S.T. CHCKDBY Sr. DATE: 10/01/03

I
1 2/c
DESCRIPTION OF MATERIALS

#12 MC cable
QUANTITY

3,000
I
MATERIA1
UNITCOST

1
2 3/c #12 MC cable 1,000 2

3 4/c #12 MC cable 400' 3


4 2/c #10 MC cable 100' 36 4

5 3/c #10 MC cable 300' 15 5


6 4/c #lo MC cable 750' 55 M 41.25 6
7 7
a MC cable connectors 374 8
9 MC cable hangers and SupportsMastners Allow 9
10 I I I10
11 Metal stud wall sieves 90 I 11
121 -I 12
13 4" and 5" square boxes with blank covers I 50 13
14 I I
I 14
15 Misc. splicing, tags, tape, ty-raps, etc. Allow I I- 15
16
I
I I 16

17 Allowance for misc' EMT and wire I Allow I I I- 17


ia ia
19 19
20 20
21 21
22

23
24
25 25
26 I I 26

27

28

2g
30
29
30
31
32 I I 32
M = Per Thousand EA = Each

I C = Per Hundred TOTAL I ITOTAL 1 324.35

Figure 2-12
Electrical Material and Labor Takeoff 35
I
I
I
i
I
3
I
I
- I
@ I
\, *
c
\
\
t .-..-.--I
\
/
L
36 How to Estimate Electrical Construction Projects

NOTES
EST. NO: 10/01/03-1 VOICE-DATA COMM' ROUGH TAKEOFF SHEET
VD
data
wall outlet
vvoice/data
wD
wall outlet
I-IHP
telephone
voice/data patch panel
64 pori
data patch
I-shelf for
patch panel
box & plate box & plate backboard floor stand panel 8 wire mng'r
& connector I connectors 4x8' & qnd conn

0 3 1 1 1 1

voice cable **. cat' 5 cat' 3 'J' hooks test all


*.** for cables cables
punch down data cable voice cable
e..*
at 110 plenum plenum
a
.
*
.
block 3x100 4x10 0
m
e
4
$.
E
3
2
%.
E
P
3
P
5
0
4
d
x
e
0
3

Figure 2-14 W
U
38 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office bldd #lo0 Utown, USA PAGENO: 1 OF 1


Estimate Sheet of Communications Labor Hours

ESTIMATED BY: Yr. F S.T. CHCKDBY: Sr. DATE: 10/01/03

C = Per Hundred PR = Per Pair TOTAL I TOTAL 27.9

Figure 2-15
Electrical Material and Labor Takeoff 39

Text Introduction t o Fire Alarm Takeoff p. 45). All automatic temperature control wiring is to be
The fire alarm partial floor plan (Fig. 2-16, p. 40) lays furnished and installed by the HVAC contractor. All
out the fire alarm devices required for this portion of motor controllers and controls are to be furnished by
the building. The typical fire alarm riser diagram (Fig. the HVAC contractor. The electrical contractor shall
2-17, p. 42) provides the estimator with the wiring and
receive, mount, and wire line the voltage wiring of
zones required. The main fire alarm panel is located in starters. Coordinate all wiring and installations with
the utility room along with the sprinkler flow and the HVAC contractor. Here again we list all of this mate-
tamper switches. The remote annunciator panel should rial on the rough takeoff sheet (Fig. 2-21, p. 47).
be located near the entrance to give the first responders The estimate sheet (Fig. 2-22, p. 48) will show how
the immediate location that initiated the alarm. The all of the mechanical equipment requirements are listed
duct detectors will be mounted on the HVAC duct work for pricing and the required labor hours for the project.
in accordance with the local authorities codes. The The electrical contractor will be responsible for certain
length of the sampling tubes for the detector will need items in accordance with the plans and specifications.
to be measured after a location has been determined. The estimator will need to go back through the
Coordinate the installation of the tube and detector HVAC specifications and read what that contractor is to
with the HVAC duct installer. The estimator should ver- furnish (e.g., fans, rooftop HVAC units, etc.). Coordi-
ify the wiring requirements and device quantities for nate this information with the electrical specifications.
each zone with the fire alarm equipment supplier. The If there are any conflicts, seek clarifications prior to bid
detector zones may incorporate manual stations as well submission.
as automatic detectors. The estimator should request a
Text Introduction to Services to Building,
floor plan from the fire alarm equipment supplier show-
Feeders, Panels, and Transformers
ing the locations of the devices, wiring, and zones. Here
again we list all of this material on the rough takeoff The following partial floor plans and estimate sheets
sheet (Fig. 2-18, p. 43). (Figs. 2-23-2-27B, pp. 49-56) include the utility serv-
The estimate sheet (Fig. 2-19, p, 44) will show all of ices to the building, the main service electrical equip-
the fire alarm system materials and associated items ment, the electrical panels, and the feeders to the elec-
that are to be listed for pricing and the required labor trical panels and HVAC equipment. The typical power
hours for all the material. The prices are not included riser diagram on this page depicts the feeders to the var-
due to each contractors price structure with the mate- ious panels, the transformer, and mechanical equip-
rial suppliers and actual fluctuation in the markets. ment. The estimator should review this riser and list
the feeders shown on a feeder schedule (Fig. 2-26, p.
There are various items that are not shown on the plans
54), which is included herein. Take note that all of the
but will be required for a complete fire alarm system;
some of these may be junction boxes, hangers and sup- interior feeders will be installed above the suspended
ports, wall sleeves, splicing materials, and labels and ceiling and exposed in the utilities room. The raceways
tags. The estimator will find that the specifications will outside of the building walls are installed underground,
specify many of these items, but not all; the estimator as shown on the riser. The panels and transformer are
shown here as well as the mechanical equipment.
must allow for these unseen items.

Text Introduction t o Mechanical


Equipment Takeoff Sheet
Allow for splicing, tagging, tape, testing, etc. Locate the
ATC panel and furnish it with a 120 V circuit (Fig. 2-20,
40 How to Estimate Electrical Construction Projects
I
3 i
a I
5
0
I
1
LL
i
a i
F
U i
\
a
a \
--v
D
H \
9
a
\
w )
n. \
a 0 /
E
-b
.-
C

,
Electrical Material and Labor Takeoff 41

NOTES
Next Page

EST. NO: 10/01/03-1 (FIRE ALARM) TYPICAL FIRE ALARM RISER DIAGRAM SHEETNO: 1 OF: 1
JOB: Office bldg #lo0 Utown, USA DATE: 10/01/03

SYMBOLS: A= 4/c #16 plenum rated fire alarm cable


B= 2/c #16 plenum rated fire alarm cable
FA= manual pull station; mount on recessed wall box
VH= visual & audio alarm; mount on recessed wall box
SD= ceiling mounted smoke detector; mount on ceiling outlet box
DD= duct mounted detector w/ sample tube mounted in retum duct (keep distance from all duct bends, see specs)
NOTE: The flow and tamper switches are furnished & installed by others.

Figure 2-17
Previous Page

EST. NO: 10/01/03- FIRE ALARM ROUGH TAKEOFF SHEET SHEETNO: 1 OF: 1

12 coup's 1 common
14 clamDs (25x100)
Plan E-3 1,500' 500' 42 allowance allowance allowance allowance 90' 2,500'

TOTALS

Figure 2-18
44 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office blda' #lo0 Utown, USA PAGENO: 1 OF 1


Estimate Sheet of Fire Alarm Labor Hours

ESTIMATED BY: Mr. F S.T. CHCK'D BY Sr. DATE: 10/01/03

Figure 2-19
EST. NO: 10/01/03-1 MF(3-I' FQUIP' LAYOUT MECH EQ PARTIAL FLOOR PLAN SHEETNO: 1 OF 1
JOB: Office blda #lo0 Utown. USA DATE: 10/01/03

Mount all motor controls in utility room

Panel PLP-1

I I L4 #12s

i
I
'. i
'J i

NOTES:
All motor controls shall be furnished by the HVAC contractor and turned over to the electrical contractor for installation and power wiring.
(All ATC wiring to be furnished and installed by the HVAC contractor.)
All exhaust fans are to be furnished with electric power safety disconnect devices.
All motor controllers shall be furnished with the proper-sized overload heaters.
The HVAC contractor shall furnish and install all equipment supplied, except as noted otherwise.

Figure 2-20
46 How to Estimate Electrical Construction Projects

NOTES
EST. NO: 10/01/03-1 MECHANICAL EQUIP' ROUGH TAKEOFF SHEET SHEETNO: 1 OF: 1

Figure 2-21
48 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office bldg' #lo0 Utown, USA PAGENO: 1 OF 1

Estimate Sheet of Mechanical Equipment Labor Hours


ESTIMATED BY: F S.T. CHCKDBY: Sr. DATE: 10/01/03

EA= Each
FIBO= Furnished & Installed by Others TOTAL TOTAL 38.15

Figure 2-22
EST. NO: 10/01/03-1 (FEEDERS) TYPICAL POWER RISER DIAGRAM SHEET NO: 1OF: 1
JOB: Office blda #lo0 Utown, USA DATE: 10/01/03

Roof Line

**

trans'fr

;-El
Y- Exterior building wall NOT_
. TO SCALE
_ _ ~

"F-l"= 2- 4" Schld 80 pvc conduits in trench for power co. feeder. Use galv' UR sweep ells. Install drag lines. Min' bury @ 4 8 b.f.g.

Feel
er #
'F-2"= 3- 4" Rigid galv' conduits in trench for secondary service to bldg' each with 4 #500 mcm thhn copper cables and 1 #3/0bare copper
"F-3"= 1 1/4" c with 4 #2 awg thhn copper cables
"F-4"= 1 1/4" c with 4 #2 awg thhn copper cables * = 60 amp- 600 volt- no fuse- w/p disc. (w/gnd lug)
"F-5"= 1 1/4" c with 3 #1 awg thhn copper cables + = Jbox w/ term' block for feeders, taps 8 gnds.
"F-6"= 2" c with 4 #3/0awg thhn copper cables =k= Ground to building steel
"F-7"= 1" c with 3 #4 8 1 #8 awg thhn copper cables
"F-8"= 1" c with 3 #4 8 1 #8 awg thhn copper cables
"F-9= 3/4" c with 3 #8 8 1 #10 awg thhn copper cables
& = Roof pitch pocket furnish and install
= Foundationwall seal sleeves for feeders
Note: See plans for all panel schedules, transformer, etc.

**
Notes: Trenching, backfill, tamping, sand layers, burial warning tape, excess earth removal and layout by the EC.
Foundation wall sleeves/windows for all electrical penetrations to be furnished and installed by the GC. The EC to coordinate all locations.
EC to coordinate location and requirements with the utility company on their transformer, pad, and grounding.
EC to check with the local inspection authority on the grounding requirementsfor the electrical equipment.

Figure 2-23
50 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office bldq' #lo0 Utown, USA PAGENO: 1 OF 2


Estimate Sheet of Panels & Transformers Labor Hours

ESTIMATED BY: F S T. CHCK'D BY: Sr. DATE: 1OlOllO3

1
2

5
6
7

9
1 10

1 11

1 12

1 13
1 14
1 15
1 16
1 17
1 18
1 19
2 20
2 21
2 22
2 23
2 24
2 25
2 26
2 27
2 20
2 29
3 30
3 31
3 32

Figure 2-24A
Electrical Material and Labor Takeoff 51

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office bldg' #lo0 Utown, USA PAGENO: 2 OF 2


Estimate Sheet of Panels & Transformers Labor Hours

ESTIMATED BY: Mr. F S.T. CHCKD BY: Sr. DATE: 10/01/03

1
2

3
4

8
9
10
11

12

13
14

15

16

17
18
19
20
21
22

23
24

25

26
27
28
29

30
31

32

AL = Allowance TOTAL I ITOTAL I 38.1

Figure 2-24B
EST. NO: 10/01/03-1 SFRVICFS 1 AYOUT SITE SERVICES PARTIAL PLAN SHEETNO: 1 OF 1
JOB: Office bidq #lo0 Utown. USA DATE: 10/01/03
r--------------
Trench 24"w x 48"d to terminal pole I
for power & comm's. I

NOTE: 1- Verify all requirements for both power , \""'


2 - 4 PVC conduits o utility terminal pole

'.
below finish grade
and communications with all
agencies prior to installations!
2- Review specs for all requirements
1-4" PVC to pole for
'
1-
I.
I
Staging area
Locate temp srvs here &
office/storage trailers here
on the materials for installation and
the power riser diagram.
3-4" RGC ea w/ 4 #500 mcm cu

I l l

I I

/ IHVAC-']
\

The electrical service and secondary conduits and wire are


listed on the feeder sheet rough takeoff. Also included is
the communications empty conduit. All of the panel and
mechanical equipment feeders, the subcontracting, asso-

.'
--
PLP-2 RP-112
ciated material, and labor are shown here also. From this
feeder sheet rough takeoff the materials listed are trans-
ferred to the estimate sheets (2) for pricing and the required
'. ' labor hours.

["""-"j I
'---.
.' 0. -. -. -.
4 . I
'. 0.
i
' *'/*
0- -. - a \ .
NOT TO SCALE

Figure 2-25
Electrical Material and Labor Takeoff 53

NOTES
54 How to Estimate Electrical Construction Projects

EST. NO: 10/01/03-1 Feeders FEEDER SCHEDULE SHEETNO: 1 OF 1


JOB: Office blda #lo0 Utown. USA DATE: l O / O x

p/r= pvc to rigid adapter p=pvc


gb= ground bushing r=ngid
w/p flex=3 sealtight wiconn's 4.)" pitch pockets to install and seal.
f l e x 3 greenfield w/conn s
br=bare copper Ir=long radius
rgc=ngtd galvanized conduit

NOTE:
The following two estimate sheets will show how all of the feeders and associated materials are to be listed for pricing
and required labor hours. Many of these are not on the plans but are necessary for a complete power system. Turn to the
Estimate Sheet of Feeders Labor Hours for pricing and hours input.

Figure 2-26
Electrical Material and Labor Takeoff 55

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office bldd #lo0 Utown, USA PAGENO: 1 OF 2


Estimate Sheet of Feeders Labor Hours

ESTIMATED BY: Mr. E.S.T. CHCKDBY: Sr. DATE: 10/01/03

I
EA = Each M = Per Thousand Q = Quotation
II 1I
IC = Per Hundred AL = Allowance TOTAL I TOTAL 117.5

Figure 2-27A
56 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office blda' #lo0 Utown, USA PAGENO: 2 OF 2


Estimate Sheet of Feeders Labor Hours

ESTIMATED BY Mr. F S.T. CHCKDBY Sr. DATE: 10/01/03


w

-
-
1

- 2
3
4
5
6

7
0
9
10
11
12
13
14

15
16
17

10
19

20
21

22
23
24
25
26
27
28
29
30
31
32 I I I I 32
EA = Each M = Per Thousand
C = Per Hundred TOTAL TOTAL 81.75 -
Figure 2-27B
EST. NO: 10101/03-1 TYPICAL DETAILS ROUGH TAKEOFF SHEET SHEETNO: 1 OF 2
#loo 1o/01/03-
DATE:
TYPICAL WALL MOUNTED FIXTURE DETAIL (EXTERIOR) TYPICAL WALL MOUNTED FIXTURE DETAIL (INDOOR)
( Metal Stud wlsheetrock 2 sides )
Concrete block wall Suspended acoustic ceiling tile

wall -
& One gang Masonry wall box +MC cable or emt
/

MC cable or EMT
g dry wall box & bar support
4" sq' JB in bldg' ceiling space
A
,.dded supports if req'd.
EMT short nipple wlconn's.
Provide sealant I caulking as req'd.
Mor MC cable
FSl Typical anchor

EMT (or MC cable in interior walls) Outlet box, device, plate (typ')
Outlet box, device, plate (typ) Switch, recept', other devices
Switch, recept', other devices Height as spec'd.
Height as spec'd.

DETAIL 1 DETAIL 2

TYPICAL LAY-IN FIXTURE TYPICAL RECESSED HI-HAT TYPE FIXTURE


Structural bar ioist Structural bar ioist
- n
. _

- e' ,4- safety wire I


Suspended t-bar system Suspend d t-bar system
-4 supportwires support wires -b

T-bar T-bar G e x i b l e I
J
Hold-dohn clip Light fixture Hold-down cbp
t
Recessed light fixture

DETAIL 3 DETAIL 4

Figure 2-28A VI
U
EST. NO: 10/01/03-1 TYPICAL DETAILS ROUGH TAKEOFF SHEET SHEETNO: 2 OF: 2
1 DATE: -
0
3

ir-
,

Typical suspended light fixture support Typical detail of recept' & "M" fixture on roof and
typical roof pitch pocket for conduit penetrations
Conduit & j-box for branch circuit
+Type "M' fixture

1 rigid conduit

1" cast outlet box + /P GFCl


11W x 1' bell reducer

T ical pitch pocket & sealant


Fluorescentlight fixture
k
Secure frame to roof -*Angle iron welded frame for support
Typical lighting panel with main lugs only rigid conduit & roof devices
lamp conduit as req'd.

0 0
Connect to circuit conductors
A 0 B 0 C0 J-box

Typical panel interior


with main circuit breaker
and feed thru lugs circuit breaker
0 0

Neutral
0 0

Figure 2-28B
Electrical Material and Labor Takeoff 59

Rough Takeoff Sheets to Estimate Sheets Figure 2-29H, p. 6 9 , lists the materials and work re-
Now that we have listed all electrical devices, light fix- quired for the branch circuits. This information was
tures, service equipment, raceways, and wire on the gathered from rough takeoff sheets of the project. On the
rough takeoff sheets, we move all of the items from the branch wiring rough takeoff sheet (see Fig. 2-11, p. 33)
rough takeoff sheets to the estimate sheets for material we listed all of the material onto another estimate sheet.
pricing and labor rates (Figs. 2-29A-P, pp. 61-77). As you can see on the estimate sheets of this estimate
Figure 2-29D, p. 6 5 , lists the materials and work re- there are items of material not shown on the plans but
quired for the empty conduits for the utility company necessary for a complete installation. The estimator
feeders and the communications for the project, trans- must be aware of these types of materials and make all
former pad requirements, secondary feeders to the MDP allowances of labor and material costs in the estimate.
in the building, excavation, grounding, etc. This infor- Figures 2-291-7, pp. 70-71, list the site lighting poles,
mation was gathered from the feeder schedule for the fixtures, wiring, etc. This information was gathered from
project (see Fig. 2-26, p. 54). rough takeoff sheets of the estimate. On the site lighting
Here we see the PVC raceways, the excavation re- rough takeoff sheet (see Fig. 2-9, p. 29) we listed all of
quirements, rigid conduits up the terminal pole, drag the materials onto another estimate sheet. This rough
lines, grounding, direct burial warning tape, utility com- takeoff sheet lists all of the site lighting as shown on the
pany transformer pad requirements, and all conduit fit- partial site plan and all of the unseen but necessary
tings. On the feeder schedule (see Fig. 2-26, p. 54) we material and labor for a complete installation.
listed the material required. The estimate sheet allows the Figures 2-29K-L, pp. 72-73, list the light fixtures,
estimator to list all the items and apply pricing and labor lamps, whips, boxes, etc. This information was gathered
hours necessary for their purchase and their installation. from rough takeoff sheets of the estimate. On the fixtures
In order to apply the labor hours for all the materials the rough takeoff sheets (see Figs. 2-3A, B, pp. 18, 19) we
estimator will need a reliable labor unit reference manual listed all of the materials onto another estimate sheet (or
such as the labor rates included in this book. sheets). There are a few allowances that must be included
Figures 2-29E-F, pp. 66-67, list the service equip- here again. The estimator should be aware of the unseen
ment, panels, transformers, grounding, etc. This infor- material and any associated labor hours necessary for a
mation was gathered from the riser and plan of the proj- complete installation and include them in the estimate.
ect. On the feederlriser and panel schedule (see Fig. Figure 2-29M, p. 74, lists the devices, boxes, and
2-23, p. 49) we listed all of the materials onto another plates. This information was gathered from rough take-
estimate sheet (or sheets). The format for the estimate off sheets of the estimate. On the devices rough takeoff
sheets listing this equipment allows the estimator to sheet (see Fig. 2-6, p. 24) we listed all of the materials
apply labor to each item as needed. Project specifica- onto another estimate sheet (or sheets).
tions will describe all of the equipment details. Figure 2-29N, p. 7 5 , lists all of the materials for a
Figure 2-29G, p. 68, lists feeders that service distribu- voice and data communications system. This informa-
tion equipment, transformers panels, and the mechanical tion was gathered from rough takeoff sheets of the esti-
equipment. This information was gathered from the riser mate, On the communications rough takeoff sheet (see
and panel schedule of the estimate (see Fig. 2-23, p. 49). Fig. 2-14, p. 37) we listed all of the voice and data out-
On the feeders one-line diagram (see Fig. 2-23, p. 49) we lets, backboard, patch panel and stand, cables, patch
listed all the conduit, cable, junction boxes, flex, etc. cords, punch-down block, connectors, etc. onto another
onto another estimate sheet. There will be items required estimate sheet (or sheets).
such as hardware, clamps, hangers, splicing materials, Figure 2 - 2 9 0 , p. 76, lists all of the materials for a fire
and lugs not seen on the plans but that must be ac- alarm system. This information was gathered from rough
counted for in the estimate. takeoff sheets of the estimate. On the fire alarm rough
60 How to Estimate Electrical Construction Projects

takeoff sheet (see Fig. 2-18, p. 43) we listed the fire alarm shop drawings submittal dates, etc. The supplier with
panel, annunciator, stations, signals, detectors, resistors, the lowest quotation in accordance with all of the plans
flow and tamper switches, cable, boxes, raceways, wire, and specifications should be entered into the estimate
etc. onto another estimate sheet (or sheets). where required.
Figure 2-29P, p. 7 7 , lists all of the materials required During this time frame the estimator should prepare
for the mechanical equipment. This information was gath- the recapitulation of the estimate sheets. The recapitu-
ered from rough takeoff sheets of the estimate. On the lation sheet (or sheets) will list all of the estimate sheets
mechanical equipment takeoff sheet (see Fig. 2-21, p. 47) and their totals of labor hours and material (Fig. 2-29C,
we listed the various items furnished by the electrical con- p. 64). Upon completion of the recapitulation sheet (or
tractor and the mechanical equipment that requires elec- sheets) the total of the material cost (less quotations)
trical connections onto another estimate sheet (or sheets). and the total of hours will be transferred forward to the
NOTE: As the estimate sheets are developed a page final recapitulation cover sheet (Fig. 2-29A, p. 61). Now
number should be placed on them. This will help the that the material prices and the labor hours for the en-
estimator to keep track of how many pages there are tire estimate have been entered onto the final recapitula-
and will reduce the loss of a sheet. If they are numbered tion sheet, the estimator prepares the equipment prices
sequentially, a missing estimate sheet will be avoided. needed recapitulation sheet (Fig. 2-29B, p. 63). On this
The sequence of the pages can be adjusted and when recapitulation sheet (or sheets) the estimator enters all the
doing so the number should also be changed to match quotations of the major items for the project. Such mate-
the sequence (some use the A, B , C, etc. method then rial may be the light fixtures in the building as well the
change to numerals). site lighting, power distribution equipment, life-safety
The next step is to assemble all of the estimate sheets equipment, communications equipment, civil work sub-
in numerical order and begin to apply the prices and labor contractor, precast concrete items, etc.
hours to all of the materials and necessary allowances Once all of the quotations have been entered onto
where they are needed. In order to apply the labor rates, the equipment prices needed recapitulation sheet (or
the estimator will need a labor rate reference guide to sheets) and totaled, the estimator will transfer this total
refer to. This book contains a section devoted to material onto the final recapitulation sheet. On the final recapit-
labor rates used herein (see Chapter 3). Refer to the sam- ulation sheet we now have all of the material prices
ple estimate to see how the labor rate units are applied to entered and the total of the labor hours required to
the materials listed on the estimate sheets. Upon comple- complete the project installation (see Fig. 2-29A, p, 61).
tion of the individual labor units and their mathematical The final estimate in a completed form follows (see
extensions, the sheets should be totaled. Fig. 2-29A-P, pp. 61-77). The cover recapitulation sheet
Pricing the material and allowances on each estimate includes all anticipated costs of material, labor, job ex-
sheet is delegated to different persons in contracting penses, nonproductive labor, overhead, and profit.
companies. Some will have the estimator do it, some NOTE: You will see spaces on the estimate sheets
will have a purchasing agent do it, and some contractors with a Q and a space in the material column high-
will perform the task themselves. No matter who does lighted (any color highlight will work here). The high-
the pricing of the material, the estimator should be the light is a reminder to the estimator that a price quote is
one responsible for assembling the estimate sheets after needed. If one lump sum is received for multiple items,
all of the labor hours and prices are completed and to- the estimator will enter the lump sum on that estimate
taled. All major material suppliers quotations should be sheet and write inc. (included) in each space that is
reviewed for any exclusions, quantities, delivery dates, included in the lump sum.
Electrical Material and Labor Takeoff 61

RECAPITULATION SHEET ESTIMATE NO: 10/01/03-1


JOB OFFICE BLDG' #lo0 UTOWN, USA SHEETNO: 1 OF 1

ESTIMATED BY MR. E.S.T. CHECKED BY Sr. DATE: 10/01/03

(contin u es)
Figure 2-29A
62 How to Estimate Electrical Construction Projects

RECAPITULATION SHEET (BACK)


1. THE CONTRACTOR MUST INVESTIGATE THE REQUIREMENTS OF EACH GOVERNMENT AGENCY AS IT
RELATES TO SALES TAXES ON BOTH MATERIALS AND LABOR AND INCLUDE ALL OF THESE COSTS IN EACH
PROPOSAL!
2. Nonproductive labor section contains various areas of costs that are affected by noninstallation labor factors. These
items may or may not apply to all proposals but remind the contractor that there may be labor costs beyond the actual
labor cost associated with the project. This may also remind the contractor that there may be other items of nonpro-
ductive labor cost that should be addressed in the proposal.
3. Job expense section contains important direct project-related costs. These dollar costs may or may not be applicable to
each proposal submitted by the contractor. This may also remind the contractor that there may be additional job-
related expenses to be considered.
4. Labor hour section allows the contractor to apply different labor rates as they may apply to the level of grade of the
workers who physically install or direct the installations.
5. Taxes section allows the contractor to include such taxable items of labor as they may apply to the project.
6. Overhead section is a cost of doing business for the contractor. This cost may include insurances, office supplies,
postage, contractors building facility, utilities, office personnel payroll, telephone, association fees, periodicals, facil-
ity maintenance, rolling stock upkeep and fuel, rental of office equipment, support programs costs, etc. Include any
other costs that are fixed as they relate to the business inside the contractors facilities.
7. Profit is relative to the size of the proposal and the amount the contractor anticipates.
8. Bond section gives the contractor the ability to include the cost of a bid bond, performance bond, andlor payment
bonds.

Figure 2-29A continued


Electrical Material and Labor Takeoff 63

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office bldc1' #lo0 Utown, USA PAGENO: PN-1 OF 1

EQUIPMENT PRICES NEEDED


ESTIMATED BY: MR. EST. CHCKDBY Sr. DATE: 10/01/03

I
1 Civil work
DESCRIPTIONOF MATERIALS

EST. PAGE #67


QUANTllY
QUOTE
I
MATERIAL!
UNITCOST
D 1

2 MDP, panels, transformer EST. PAGE #63 & 64 QUOTE D 2


3 Site lighting fixtures EST. PAGE #43 QUOTE D 3
4 Boom truck allowance EST. PAGE #43 QUOTE D 4
5 Civil work EST. PAGE #43 & 44 QUOTE D 5

6 Light fixtures EST. PAGE #33 QUOTE D 6

7 Fire alarm EST. PAGE #56 QUOTE D 7


8 8
9

10
11
12 12
13 13
14 14

15
16 16
17 - 17

18
19
20
211 I I 21
22

23
24
I I
25

~::
- 6 2
27

~::
29
30
31

32

TOTAL

Figure 2-29B
64 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office bldq' #lo0 Utown, USA PAGENO: RE-1 OF 1

RECAP OF ESTIMATE SHEETS


ESTIMATED BY: MR. E S T . CHCKDBY: Sr. DATE: 10/01/03

1 1
2 2

3 3
4 4

5 5
6 6

7 7
8 8
9 9
10 10
11 11
12 12
13 13

14 14
15 15
16 16
17 17
18 18
19 19

20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27

28 28

29 29
30 30
31 31
32 32

Figure 2-29C
Electrical Material and Labor Takeoff 65

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office bldg' #lo0 Utown, USA PAGENO: 1 OF 13


Estimate Sheet of Feeders Labor Hours

ESTIMATED BY: W . E.S.T. CHCKDBY: Sr. DATE: 10/01/03

Figure 2-290
66 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office bid@#lo0 Utown, USA PAGE NO: 2 OF 13


Estimate Sheet of Panels & Transformers Labor Hours

ESTIMATED BY: Mr. F~S.T. CHCKDBY: Sr. DATE: 10/01103

Q = Quotation EA = Each
AL = Allowance TOTAL TOTAL 107.8

Figure 2-29E
Electrical Material and Labor Takeoff 67

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office blda' #lo0 Utown, USA PAGENO: 3 OF 13


Estimate Sheet of Panels & Transformers Labor Hours

ESTIMATED BY: Mr. E S T . CHCK'D BY: Sr. DATE: 10/01/03

IAL = Allowance TOTAL I ITOTAL I 38.1

Figure 2-29F
68 How to Estimate Electrical Construction Projects

1
2
3
4
5
6
7
8
9
10
11

12
13
14

115
'16
'17
118
19
20
21
22
23
24
25
26
27
28
29
I I
30 30
31 31
32 32
EA = Each M = Per Thousand
C = Per Hundred TOTAL TOTAL 81.75

Figure 2-296
Electrical Material and Labor Takeoff 69

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office blda' #lo0 Utown, USA PAGENO: 5 OF 13


Estimate Sheet of Branch Wiring Labor Hours

ESTIMATED BY: Mr. E.S.T. CHCK'D BY: Sr. DATE: 10/01/03

Figure 2-29H
70 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office blda' #IO0 Utown, USA PAGENO: 6 OF 13


Estimate Sheet of Site Lighting Labor Hours

ESTIMATED BY: Mr. F S.T. CHCK'D BY: Sr. DATE: 10/01/03

Figure 2-291
Electrical Material and Labor Takeoff 71

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office bldg' #lo0 Utown, USA PAGENO: 7 OF 13


Estimate Sheet of Site Liqhting Labor Hours

ESTIMATED BY: Mr. F S.T. CHCKDBY: Sr. DATE: 10/01/03

1 1
2 2

3 3
4 4

6 #6 thhn 600v copper wire stranded 1,500' M 14 M 21 6


7 #8 thhn 600v copper wire stranded 3,000' M 12 M 36 7

8 #10 thhn 600v copper wire stranded 1,800 M 10 M 18 8


0 1 9

i o Direct buried electrical lines warning tape I 1,500' I M 4 M 6 10


9, I 1 I I 1 11

1 12

1 13
1 14
1 15

1 16

17 I I 17
18 I. 18

20 I 20

21 I I 21
22 1 - I 22

--
24 I I 24
25 I
I
I
I
25

27 I I 27
28 I
I
I
I
28

30 I I 30
31 I I 31
32 1 1 32

M = Per Thousand Q = Quotation


C = Per Hundred TOTAL TOTAL 107.3

Figure 2-29J
72 How to Estimate Electrical Construction Projects

30 150 WATT PAR 38FL LAMPS 1 Q 0.03 EA 0.05 30


31 70 WAlT HID HPS BD LAMPS 4 Q 0.1 EA 0.4 31
32 32
Q = Quotation
EA = Each TOTAL TOTAL 76.95

Figure 2-29K
Electrical Material and Labor Takeoff 73

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office blda' #lo0 Utown, USA PAGE NO: 9 OF 13


Estimate Sheet of Fixtures Labor Hours

ESTIMATED BY: tytr, E.S.T. CHCK'D BY: Sr. DATE: 10/01/03

1 1
2 2
3 3
4 4

5 5
6 6

7 7

8 8

9 9
10
I I I ."
in

18 18
19 19
20 I I 20

22 I I 22
23
1
I
I
I 1
23

25

26
27

28
29
30

I I I I I I 31
32 I I
I J
32
EA = Each
21.55

Figure 2-291.
74 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office bldd #lo0 Utown, USA PAGENO: 10 OF 13


Estimate Sheet of Devices Labor Hours

ESTIMATED BY: Mr. F S.T. CHCK'D BY: Sr. DATE: 10l01I03

DESCRIPTION OF MATERIALS MATERIALS I LABORHOURS


QUANTIW II UNITCOST IPERI AMOUNT I UNIT I PERI
AMOUNT
I 1 I I 1

1 S - 20 amp 277v sinQle-pole switch 6 EA 0.7 EA 4.2 1

.
2 SS - 2-20amp
3 SSS - 3-20 amp "
'I

"
"
"
I' 0
1 EA
I
1.4 EA 1.4
2
3

4 S3 - 20 amp 277v 3-way switch 4 EA 0.75 EA 3 4


5 S3S3 - 2-20 amp It 0 5
6 54 - 20 amp 277v 4-way switch 0 6
7
8
9
10
11
12
13
14
15
16
I
17 I 17
18 Price and labor the devices with a box and plate
I 18
1 1 I I 1
1 SI I I
~ ~~
I10

20 Metal stud wall box supports Allow INC - 20


21 I -71

22 22
23 I
I I
23

26
27
28
29
30
31
32
EA = Each
INC = included TOTAL TOTAL 30.85

Figure 2-29M
Electrical Material and Labor Takeoff 75

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office bid@ #IO0 Utown, USA PAGE NO: 11 OF 13


Estimate Sheet of Communications Labor Hours

ESTIMATED B Y Mr. F S.T. CHCKDBY Sr. DATE: 10/01/03

Figure 2-29N
76 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office bldg' #lo0 Utown, USA PAGENO: 12 OF 13


Estimate Sheet of Fire Alarm Labor Hours
~~~ ~~~

ESTIMATED BY: Mr. F S T. CHCKDBY: Sr. DATE: 10/01/03

I C = Per Hundred INC = Included TOTAL I I TOTAL

Figure 2-290
Electrical Material and Labor Takeoff 77

ESTIMATE SHEET ESTIMATE NO: 10/01/03-1

JOB: Office blda' #lo0 Utown, USA PAGENO: 13 OF 13

Estimate Sheet of Mechanical Equipment Labor Hours


ESTIMATED BY: Mr. E S T . CHCKD BY: Sr. DATE: 10/01/03

1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 0 Prepackaged HV AC rooftop units b
4 FIBO- 4 EA 4 8
9 (3-phase 480 v w/p prewired) 9
10 I I I
I i. n_
I
I I I I I I
11 (Conduit and wire, flex connections, roof pockets 11
I I I I I I
12 are included on the feeder estimate sheets.) I I I 12
I
13 Misc' splicing, tags, tape, testing I Allow I I I I 8
14 1 I I

18 I 18
19
I
I
I I I
19

32 I 1 I I I I 32
EA = Each
FIB0 = Furnished & Installed by Others TOTAL TOTAL 38.15

Figure 2-29P
CHAPTER 3

Labor Rate Schedules and Forms,


Charts, and Diagrams

his section contains electrical construction materi- tures, civil work, life-safety systems, voice and data
T als and associated installation labor units along
with a sample estimate of a combination office and
systems, etc.). This facilitates returns of quotations
prior to the bid date.
warehouse. The estimate lays out the project in orderly STEP 1:Review the fixture schedule, count the fix-
steps, such as the installation of the projects incoming tures, and list them on a takeoff sheet along with the
electric service. You should understand that in order to lamps, flexible whips, hangers, hold-down clips, fix-
have service delivered to the project, a variety of elec- ture outlet boxes, and miscellaneous items. This allows
trical materials will be necessary. A power company the estimator to visit areas of the project and it familiar-
will require raceways, drag lines, and grounding among izes the estimator with the project, which will assist in
related items. To prepare a coherent itemized quantity the takeoff. After this section of the takeoff is on the
of material, you will need to review the contract docu- estimate sheet, refer to the sections of the manual
ments including plans, specifications and all adden- where the labor units are listed. Apply labor units as
dums that may be included. they relate to the fixtures listed on the estimate sheet.
TAKEOFF: The estimator should begin the takeoff of STEP 2: Follow STEP 1 for the remaining sections of
all electrical materials required by examining all the the project, as the sample estimate would show (see
plans including building, steel, plumbing, HVAC, elec- Chapter 4). NOTE: The sample estimate does not in-
trical, and communications plans. Review the specifi- clude pricing, as each contractor will have their own
cations that help to describe the makeup of all the pricing structure arrangements with their suppliers and
materials. After the estimator has reviewed the docu- market fluctuations.
ments, a plan should be developed and the takeoff After the estimator has compiled all of the estimate
should begin. It is recommended that each section of sheets they will need to be listed on a separate estimate
the project should be listed on rough takeoff sheets and sheet referred to as a recap of estimate sheets. Next, the
be assembled by sections (see sample estimate in Chap- estimator will need to prepare a price quotations
ter 4). Consider counting and listing all of the items that needed sheet. This should list all of the quotations that
would require a specific quotation price (e.g., sw. gear, have been received from the various manufacturers of
panels, transformers, disconnect switches, lighting fix- required equipment.

79
80 How to Estimate Electrical Construction Projects

The final sheet will be the recapitulation sheet. Refer Section 3


to the sample sheet for the final assembly of all the asso- Light Fixtures
ciated sheets (see Fig. 4-1A). Along with all of the sheets,
Hid, incandescent, exit, and emergency lights
the estimator should alert his superiors of all associated
(Figs. 3-27 and 3-28)
costs that will be required in the complete installation of
the work required. The estimator should review the com- Fluorescent fixtures (Fig. 3-29)
pletion schedule and calculate the amount of workers Track lighting and associated components (Fig.
whom will be required to complete the work contracted 3-30)
for and any nonproductive labor required. Preassembled quick wiring system (Figs. 3-31 and
The actual costs of materials, labor, overhead, and 3-32)
profit will be determined by the estimators superiors. Area lighting (Fig. 3-33)
But, the estimator should be prepared to provide the
Wood pole installation (Fig. 3-34)
necessary information to those who will have the final
responsibility in developing the final selling price.
Section 4
Included here are blank forms for the estimator to
Emergency Generators
use in preparing estimates.
Emergency generator sets (Figs. 3-35 and 3-36)
Section 1
Raceways and Fittings Section 5
Rigid galvanized conduit (Figs. 3-1 and 3-2) Grounding
Rigid conduit associated fittings (Figs. 3-3 and 3-4) Grounding, cadwelding, and associated fittings
(Fig. 3-37)
Rigid conduit associated fittings, explosion proof
(Figs. 3-5 and 3-6)
Section 6
Wireways and fittings (Fig. 3-7)
Bus Ducts
Cable tray and fittings (Fig. 3-8 and 3-9)
Copperfaluminum ducts and associated devices
Flexible conduit and fittings (Figs. 3-10 and 3-11) (Figs. 3-38 and 3-39)
Flexible motor whips (Fig. 3-12)
EMT raceways and fittings (Fig. 3-13)
Section 7
PVC raceways and fittings (Figs. 3-14 and 3-15)
Distribution Equipment
Fused and nonfused disconnect switches (Fig. 3-40)
Under floor ducts and fittings (Fig. 3-16)
Motor control centers (Fig. 3-41)
Trench duct and fittings (Figs. 3-17 and 3-18)
Starters, contactors, and controls (Figs. 3-42 and
Wiremold and fittings (Fig. 3-19)
3-43)
Mineral insulated (MI) cable 600 volt (Figs. 3-20
High-voltage transformers (Figs. 3-44 and 3-45)
and 3-21)
Low-voltage transformers (Figs. 3-46 and 3-47)
Section 2 Incoming service and distribution sections (Fig. 3-48)
Devices, Boxes, Plates, and Flat Wiring Meter stacks (Figs. 3-49 and 3-50)
Devices and plates (Fig. 3-22) Indoor surface panels (Figs. 3-51 and 3-52)
Poke-through fittings (Fig. 3-23) Circuit breakers and terminations (Figs. 3-53, 3-54,
Outlet and junction boxes (Figs. 3-24 and 3-25) and 3-55)
Under carpet flat-wiring system (Fig. 3-26) Enclosures and circuit breakers (Fig. 3-56)
Labor Rate Schedules and Forms, Charts, and Diagrams 81

Section 8 Section 13
Fire Alarm and Miscellaneous Systems Light Bases
Fire alarm devices and cables (Fig. 3-57) Concrete light bases built in place (Fig. 3-72)
Clock, sound, doorbell, nurse call, and cctv/
Section 14
public systems (Fig. 3-58)
Voltage Drop Tables
Section 9 6- and 12-volt voltage drop tables (Fig. 3-73)
Electric Heating
Section 15
Baseboard, wall, radiant, panels, and explosion
proof units (Figs. 3-59 and 3-60) Miscellaneous
Snow melting mats and roof gutter cables (Figs. 3-61 Formulas, tables, conversion factors, etc.
and 3-62) (Fig. 3-74)
AC motor connections
Section 10 Single-phase motor HP and ampere ratings
High- and Low-Voltage Cables (Fig. 3-75)
High-voltage cables installed in raceways Three-phase motor HP and ampere ratings
(Fig. 3-63) (Fig. 3-76)
600-volt cables installed in raceways (and reel Typical motor control circuits (Figs. 3-77, 3-78,
setup) (Figs. 3-64 and 3-65) 3-79, and 3-80)
Multiconductor tray cables (Fig. 3-66) Conversion factors (Fig. 3-81)
Multiconductor copper cables (Figs. 3-67 and 3-68) Ampere ratings of single- and three-phase resist-
Low-voltage and multiconductor cables (Fig. 3-69) ance loads (Figs. 3-82 and 3-83)
Diagrams of three-phase transformer connections
Section 11 (Figs. 3-84 and 3-85)
Voice and Data Wiring Transformer KVA and single- and three-phase
Category 3 and 5 cables, devices, and terminations ampere ratings (Figs. 3-86 and 3-87)
(Fig. 3-70) Lighting design/footcandle recommendations
(Fig. 3-88)
Section 12
Miscellaneous HVAC Devices
ATC controls and fan units (Fig. 3-71)
82 How to Estimate Electrical Construction Projects

Section 1: Raceways and Fittings

1
RGC LABOR HRS TO INSTALL PER "C"
CONDUIT RGC RGC RGC RGC RGC
SIZES COND COND COND COND MFG BENDS
(EXPI (SLAB) TRENCH PAINT 90,45, ETC.

112" 5 3 2.5 1 10

314" 6 4 3 1 15

1" 7 5 3.5 1.2 20

1-114" 8 6 4 1.2 30

1-112" 10 NIA 5 1.5 40

2" 12 NIA 6 2 60

2-112" 17 NIA 8.5 2.5 80

3" 20 NIA 10 3 100

3-112" 25 NIA 12.5 3.3 125

4" 30 NIA 15 4 200

5" 40 NIA 20 4.5 2.5

6" 50 NIA 25 5 3

Figure 3-1
Labor Rate Schedules and Forms, Charts, and Diagrams 83

FIELD INSTALLATION OF RACEWAYS


AND ASSOCIATED FllTlNGS FOR RGC
RGC LABOR HRS TO INSTALL
CONDUIT RGC RGC RGC RGC RGC
SIZES MFG 90 ELLS MFG 90 ELLS CLAMPS & TERMS MFG
48" RADIUS 60" RADIUS SUPPORTS LOCWBUSH NIPPLES

112" ***** *****


10 10 10

314" ***** ***** 10 10 10

1I' ***** ***** 15 10 15

1-114" ***** ***** 15 10 20

1-1/2" ***** ***** 15 15 25

2" ***** ***** 20 15 25

2- 112" ***** ***** 20 15 35

3 125 150 25 25 50

3-112" 150 175 25 25 50

4" 250 300 50 25 75

5" 300 400 75 35 75

6" 350 500 75 45 75

NOTES:
Add 25% to labor hours to install above 15' up to 25'.
Parallel runs: 2nd run x 75%; 3rd run x 70%; 4th run x 65%; above 4th x 50%.
Coupling labor is included with conduit labor.
Trapeze hangers add 1.25 hrs each (add 15% each foot if longer than 3').
Drill and set concrete anchors at 1 0 minutes each (add 100% if in overhead).
Deduct 15% if installing aluminum raceways and fittings.
Add for assembly and removal of scaffolding if required (+I- 8 hrs total for 316' sections).
Add 25% to exposed RGC hours if using PVC-coated conduit.
Allow 2-4 hrs per 1,000' for direct burial marker tape (hr rate per M depends on job conditions).

Figure 3-2
84 How to Estimate Electrical Construction Projects

FIELD INSTALLATION OF RIGID CONDUIT ASSOCIATED FITTINGS


RGC LABOR HRS TO INSTALL PER "C"
CONDUIT RGC RGC RGC RGC RGC RGC RGC
SIZES GROUND SERVICE THREADED CONDULET CONDULET CONDULET CONDULET
BUSHING HEAD HUB 1 HUB "LB" & COV "T" & COV "X"& COV

112" 10 20 20 20 30 60 80

314" 10 25 20 20 40 60 80

1'I 10 35 25 25 50 75 100

1-114" 10 40 35 35 70 100 140

1- 112" 15 45 45 45 90 130 180

2" 15 50 60 60 120 180 240

2-112" 20 60 85 85 170 250 340

3" 25 75 125 125 250 375 500

3-112" 25 85 175 175 300 400 *****

4" 35 100 250 250 375 500 *****

5" 40 125 375 ***** ***** ***** *****

6" 50 150 450 ***** ***** ***** *****

Figure 3-3
Labor Rate Schedules and Forms, Charts, and Diagrams 85

FIELD INSTALLATION OF RIGID CONDUIT ASSOCIATED FllTlNGS


RGC LABOR TO INSTALL PER "C"
CONDUIT RGC RGC RGC RGC RGC RGC
SIZES REDUCING 3-PIECE RISER FLOOR SPLIT FLOOR
BUSHING COUPLING CLAMPS FLANGE COUPLING SLEEVE

112" ***** 30 15 25 30 *****

314" 7.5 35 15 25 35 *****

45 *****
1II 10 45 15 25

1-114" 12 60 20 35 60 50

1-112" 15 70 20 35 70 50

2" 20 95 25 40 95 50

2-112" 25 125 25 40 125 50

3" 30 150 35 50 150 100

3-1/2" 50 175 50 50 175 100

4" 80 200 50 75 200 100

5" 100 250 75 100 250 100

6" 150 300 100 100 300 100

NOTES:
Labor on reducing bushings is size to be reduced (e.g., 314'' labor is to reduce to 1/2", etc.).
Floor flange labor includes anchors.
Floor sleeve labor includes layout.
Core bore concrete floor 4" thick up to 4" diameter allow 1.5 hrs each (this includes layout, setup, and removal). Add
extra labor to catch core material if required on floor below.

Figure 3-4
86 How to Estimate Electrical Construction Projects

FIELD INSTALLATION OF RIGID CONDUIT AND


ASSOCIATED EXPLOSION-PROOF FllTNGS

1 1
RGC RGC RGC RGC RGC
SIZES UNYIUNF LBY EYSIEY2 EYD ECLK LBH
EWPF EWPF EWPF EWPF EWPF EWPF

30 35 40 50 45

35 40 45 55 45

L L 1-114"
40

50
50

65
55

75
70

85
55

80

3"

3-112"
160

175
60
*****

*****
*****

tf***
1 1 1 ::: 1
80

110

145

175

200
90

120

210
95

125

*****
100

130

265
185

320

4" 200 ***t*


225 235 *****
400

5" ***** ***** *t*** ***** *****


250
***** ***** ***+* *****
6" 300 ***t*

NOTES:
Above units include layout, fitting to conduit, and covers (guj-type also).
Sealing of seal fittings is included.
Installation of drain is included on drain fittings.
Add for any "special" supports of fittings.
Average labor based on lengths up to 24" for eclk-type flex.
"Exp prf' = explosion prooflhazardous locations.
Add 15% to hours if using PVC-coated conduit.

Figure 3-5
Labor Rate Schedules and Forms, Charts, and Diagrams 87

FIELD INSTALLATION OF RIGID CONDUIT AND


ASSOCIATE D EXPLOSION- PROOF FlTTlNG S

RGC LABOR HRS TO INSTALL PER "C"


COND RGC I RGC I RGC I
RGC I RGC I RGC
SIZES GUAE GUAC GUAUB GUAT GUAX GUASC
EWPF EWPF EWPF EWPF EWPF EWPF

112" 20 40 40 60 80 10

314" 20 40 40 60 80 10

1'I 25 50 50 75 100 10

1-1/4" ***** 70 70 100 140 *****

1-112" ***** 90 90 130 180 *****

***** 120 120 180 240 *****


2"

NOTES:
Above units include layout, fitting to conduit, and covers (guj-type also).
Installation of drain is included on drain fittings.
Add for any "special" supports of fittings.
"Exp prf" = explosion prooflhazardous locations.
Add 15% to hours if using PVC-coated conduit.

Figure 3-6
88 How to Estimate Electrical Construction Projects

FIELD INSTALLATION OF WIREWAYS AND FllTlNGS

I yEE I
SIZES
HRS
PER
EACH
WMI
COUP'
LABOR HRS TO IN$
WMI
FACTORY
WNV
TEE
WNV
CROSS
FOOT CON" BEND FllTlNG FllTlNG

2.5" x 2.5" 0.2 0.05 0.1 0.12 0.15

4 " x 4" 0.25 0.08 0.12 0.15 0.18

6 " x 6" 0.35 0.08 0.12 0.18 0.2

8 " x 8" 0.4 0.1 0.15 0.2 0.25

12" x 12" 0.5 0.15 0.2 0.25 0.35

WIREWAY LABOR HRS TO INSTALL EACH


INDOOR W/W 1 WNV WNV 1 WNV
SIZES BLANK PANEL FACTORY UNIVERSAL
END ADAPTER REDUCER HANGER

2.5" x 2.5" 0.05 0.45 0.1 0.1

4 " x 4" 0.08 0.45 0.12 0.1

6 " x 6" 0.08 0.5 0.12 0.15

8 " x 8" 0.1 0.6 0.15 0.15

12" x 12" 0.15 0.75 0.2 0.2

NOTES:
Add 25% to hrs to install above 15' up to 25'.
Add 25% to hrs to install Nema 1 2 - and 3R-types wireway and fittings.
Add .35 hrs per hanging rod and clamp.
Add 1.25 hrs per trapeze hanger (add 15% each foot if longer than 3').
Drill and set concrete anchors at 10 minutes each (add 100% if in overhead).

Figure 3-7
Labor Rate Schedules and Forms, Charts, and Diagrams 89

FIELD INSTALLATION OF CABLE TRAY AND FllTlNGS

ALUM INUM LABOR HRS TO INSTALL EACH


TRAY ALUM ALUM ALUM ALUM
SIZES TRAY 90 DEG 90 DEG TEE
LENGTH ELL ELL FTNG
12' LONG 12" RAD 24" RAD 12" RAD

3" D X 12" W 1.55 1.65 1.75 3.55

3" D X 24" W 1.75 2.95 3.15 3.95

4" D X 6" W 1.45 1.55 1.65 3.55

4" D X 12" W 1.55 1.65 1.85 3.75

4" D X 18" W 1.75 2.45 2.65 4.15

4" D X 24" W 1.85 2.95 3.25 4.75

6" D X 12" W 2.25 1.85 2.05 3.95

6" D X 24" W 2.75 3.15 3.35 5.15

NOTES:
Add 75% to the above labor rates if tray is steel.
Trapeze hangers add 1.25 hrs each as required [add 15% each foot if longer than 3').
Drill and set anchors overhead at 20 minutes each.
Pairs of splice plates included in tray labor.
Hold-down clips included in tray labor.
Add 5 hrs per hundred feet for divider strip.
Add .50 hrs each for divider strips in fittings.
Add .25 hrs each for tray ground clamp.

Figure 3-8
90 How to Estimate Electrical Construction Projects

ALUMINUM LABOR HRS TO INSTALL EACH


TRAY ALUM ALUM ALUM ALUM ALUM
SIZES TEE CROSS END DROP TRAY
FTNG FTNG FTNG OUT BOX
24"RAD FTNG CONN

3"D X 12"W 3.95 4.45 0.55 0.55 0.35

3"D X 24"W 4.35 5.55 0.75 0.75 0.45

4"D X 6"W 3.95 4.45 0.45 0.45 0.35

4"D X 12"W 4.25 4.85 0.55 0.55 0.45

4"D X 18"W 4.45 5.15 0.75 0.75 0.55

4"D X 24"W 5.15 5.65 0.85 0.85 0.65

6"D X 12"W 4.45 5.15 0.75 0.75 0.55

1 6"D X 24"W 5.65 6.15 1.15 1.15 0.75


Labor Rate Schedules and Forms, Charts, and Diagrams 91

DESCRIPTION LABOR HRS TO INSTALL PER "C"


METAL FLEX
SIZES 318" 112" 314" 1" 1- 114" 1-112''

FLEX COND 3.5 3.5 4 7.5 10 12

STR CONN 5 5 6 8.5 14 18

ANGL CONN 5.5 5.5 7 10 16 20

FLEX TO RGC 5 5 6 8.5 14 18

STRAPICLAMP 5 5 5 10 10 15

DESCRIPTION LABOR HRS TO INSTALL PER "C"


SEALTITE
SIZES 318" 112" 314" 1'I 1-114" -
1 112"

SEALTITE 5.5 5.5 7.5 11 15.25 18.75

STR CONN 10 10 14 18.5 25 31

ANGL CONN 10 10 14 18.5 25 31

SEALTITWRGS 35 35 40 50 60 70

STRAP/CLAMP 6 6 6 11 11 16

NOTES:
Drill and set anchors at 10 minutes each (add 100% if overhead).
For short whips 3' to 6' long, add 15% to above flex-conduit labor units.

Figure 3-10
92 How to Estimate Electrical Construction Projects

SIZES 2" 2-112" 3" 3- 112" 4"

FLEX COND 15 20 28 34 40

STR CONN 25 30 40 50 75

ANGL CONN 30 40 50 60 85

FLEX TO RGC 25 30 40 50 75

STRAP/CLAMP 15 20 25 25 50

DESCRIPTION LABOR HRS TO INSTALL PER "C"


SEALTITE
SIZES 2" 2-112" 3" 3- 112" 4"

SEALTITE 28 30 34 44 50

STR CONN 43 55 70 94 120

ANGL CONN 43 55 70 94 120

SEALTITWRGS 82 88 95 110 130

STRAPICLAMP 16 22 30 30 65

Figure 3-11
Labor Rate Schedules and Forms, Charts, and Diagrams 93

FIELD INSTALLATION OF MOTOR WHIP CONNECTIONS


MOTOR
SIZE 1 0PHASE 3 0 PHASE
HP MOTOR MOTOR

1 HP 0.75 1

2 HP 0.75 1.5

r
3 HP 1 1.5

1.25 1.75

7.5 HP 1.5 2

10 HP 1.75 2.5

15 HP 2 3

20 HP 2.25 3.25

25/30 HP 2.75 3.5

40 HP 3 3.75

50160 HP 3.25 4

75 HP ***** 4.5
***** 5
100 HP

125 HP ***** 5.25


***** 5.5
150 HP
***** I 6
200 HP

NOTES:
Labor units include the makeup of flexible whips that include:
a. flexible whip with connectors.
b. appropriate wire size and connections of each end.
Handling and/or setting of motors is not included.

Figure 3-12
94 How to Estimate Electrical Construction Projects

EMT LABOR HRS TO INSTALL PER "C"


CONDUIT EMT EMT EMT EMT EMT EMT EMT
SIZES CONDUIT CONN'. MFG CLAMPS SERVICE LB' & T'&
BENDS STRAPS HEADS COVER COVER

112" 4 5 3 5 16 5 7

314" 5 5 3 5 16 5 7

1(I 6 10 5 10 20 10 12

1-114" 8 10 10 10 25 10 12

1-112" 9 10 10 15 25 10 15

2" 12 15 20 15 35 15 18

2- 112" 14 15 20 20 40 15 18

3" 16 20 25 25 50 20 25

3-112" 18 25 40 25 75 25 35

4" 18 25 50 50 75 25 35

NOTES:
Add 25% to labor hours to install above 15' up to 25'.
Parallel runs: 2nd one x 75%; 3rd one x 70%; 4th one x 75%; above 4th x 50.
Trapeze hangers add 1.25 hrs each (add 15% each foot if longer than 3').
Coupling labor is included with all raceways.
Drill and set concrete anchors at 10 minutes each (add 100% if in overhead).
Add for assembly and removal of scaffolding if required (+/- 8 hrs total for 3/6' sections).

Figure 3-13
Labor Rate Schedules and Forms, Charts, and Diagrams 95

AND A

PVC LABOR HRS TO INSTALL "C"


CONDUIT PVC 40 PVC 80 ADAPTERS MFG BEND
SIZES CONDUIT CONDUIT PVC 40180 PVC 40180
EXPOSED EXPOSED MALE I FEMALE (REG 45/90)

112" 4 4.4 10 10

314" 4 4.4 10 10

1 I' 5 5.5 10 10

1-114" 6 6.6 20 20

1-112" 6 6.6 20 20

2" 7 7.7 30 30

2- 112" 8 8.8 35 35

3" 10 11 35 35

3-112" 10 11 40 40

4" 12 13.2 80 80

5" 16 17.6 90 90

6" 20 22 100 100

NOTES:
For PVC in trench reduce hourly rate by 50%.
Chair labor rate at 5 hrs per "C."
Add for field bending as required (hot box or blanket).
Add for special stakes and tie downs to avoid floating when encased with concrete.
Raceway labor is based upon 10'lengths.
End-bell labor (bell ends) same as adapter labor.
Coupling labor included with raceway labor.
Allow 2-4 hrs per 1,000'for direct burial marker tape (hrrate per M depends on job conditions).

Figure 3-14
96 How to Estimate Electrical ConstructionProjects

FIELD INSTALLATION OF RACEWAYS AND ASSOCIATED PVC FlTlNGS

PVC LABOR HRS TO INSTALL "C"


CONDUIT MFG BEND MFG BEND PLUGS
SIZES PVC 40180 PVC 40180 PVC
(48" RAD.) (60'' RAD.) (& CAPS)

112" 11 12.1 3

314" 11 12.1 3

1" 11 12.1 3

1-114" 22 24.2 4

1-112" 22 24.2 4

2" 33 36.3 5

2-112" 38.5 42.35 5

3" 38.5 42.35 5

3- 112" 44 48.4 5

4" 88 96.8 6

5" 99 108.9 6

6" 110 121 6

NOTE:
Coupling labor included with raceway labor.

Figure 3-15
Labor Rate Schedules and Forms, Charts, and Diagrams 97

1 POWER FLOOR DUCT 10' LONG .80HRS EA. LENGTH


1 COMMUNICATION FLOOR DUCT 10' LONG .85 HRS EA. LENGTH

2 POWER FLOOR DUCTS: 10' LONG .85 HRS EA. LENGTH

3 POWER FLOOR DUCTS: 10' LONG -90 HRS EA. LENGTH

1 POWER & 2 COMMUNICATION FLOOR DUCTS: 10' LONG 1.OO HR EA. LENGTH

1 POWER & 2 SUPER COMMUNICATION FLOOR DUCTS: 10' LONG 1.2 HRS EA. LENGTH

COMBINATION SUPPORT / COUPLING 5 0 HRS EACH

SINGLE-LEVEL FLOOR DUCT JUNCTION BOX 1.5 HRS EACH

TWO-LEVEL FLOOR DUCT JUNCTION BOX 2.5 HRS EACH

VERTICAL 90-DEG' ELL FOR POWER DUCT .75 HRS EACH

VERTICAL 90-DEG' ELL FOR COMMUNICATION DUCT (STND & SUPER) 1.OO HR EACH

HORZ' 90-DEG' ELL FOR POWER DUCT -75HRS EACH

HORZ' 90-DEG' ELL FOR COMMUNICATION DUCT (STND & SUPER) 1.OO HR EACH

SINGLE CONDUIT ADAPTER -25 HRS EACH

MULTICONDUIT ADAPTER -50 HRS EACH

RED' COUP'/ELL ENTER PULL BWY" FIlTING/CAB' CON" 1.OO HR EACH

CLOSURE PLATES .10 HRS EACH

_AFTER INSERT I 1.3 HRS EACH


98 How to Estimate Electrical ConstructionProjects

TRENCH LABOR HRS TO INSTALL EACH


DUCT DUCT COVER DUCT DUCT DUCT
SIZES 10' 24" DIVIDER SUPPORT END
LONG LONG 5' LONG CHANNEL BLANK

6" 4 0.35 0.15 0.5 1

9" 4 0.35 0.15 0.5 1

12" 5.25 0.5 0.15 0.5 1.25

18" 7 0.75 0.15 0.75 1.75

24" 8 1 0.15 0.75 2

30" 8.75 1.3 0.15 1 2.5

36" 9 1.5 0.15 1 2.85

Figure 3-17

TRENCH LABOR HRS TO INSTALL EACH


DUCT DUCT RISER + REDUCER: GROMMETS
SIZES VERT' CAB1NET SIZE TO BE PLASTIC &
ELL CONN REDUCED METAL

6" 2.75 3 *****


0.25

9" *****
3 3 0.25

12" 3.5 3.5 0.5 0.4

ia" 4 4.15 1 0.5

24" 4.75 4.9 1.5 0.65

30" 6 6 2 0.75

36" 6.5 7.75 2.75 0.75

Figure 3-18
Labor Rate Schedules and Forms, Charts, and Diagrams 99

FIELD INSTALLATION OF METAL WIREMOLD AND FITTINGS

W/M LABOR HRS TO INSTALL PER "C"


SIZES FEET STRAPS 90-DEG TEE& CEIL'G DEVICE COMBO' DEVICE BOX
ELLS CROSS BOX BOXlG FIT'NG BRCK'T CON"

200 4.5 10 10 15 25 25 25 ***** *****

500 5 10 10 15 25 25 25 ***** *****

700 6 10 15 18 25 25 25 ***** *****

1,000 7 12 15 18 ***** ***** ***** ***** *****

8 15 15 20 ***** ***** ***** ***** *****


2,100

8.5 15 18 22 ***** ***** ***** ***** *****


2,600

10 18 25 35 ***** ***** ***** 25 25


3,000
***** ***** ***** 25 25
4,000 12 20 25 40

NOTE:
Deduct 50% of using nonmetallic surface raceways and fittings.

Figure 3-19
100 How to Estimate Electrical Construction Projects

" MII'
LABOR HRS TO INSTALL PER "C"
CABLE "MI" "MI" "MI" "MI" "MI"
COND' CABLE CABLE CABLE CABLE CABLE
SIZES 1 2 3 4 7
COND' COND' COND' COND' COND'

#12 4.8 5.5 6.25 7 7.5

#lo 5 5.75 7 7.85 8.5

#8 5.5 7 a 8.55 *****

#6 6 7.75 9 9.75 *****

#4 7.25 a 9.25 ***** *****

#2 8 ***** ***** ***** *****

#1 8.5 ***** ***** ***** *****

#1/0 9 ***** ***** ***** *****

#2/0 9.5 ***** ***** ***** *****

#3/0 10 ***** ***** ***** *****

#4/0 12 ***** ***** ***** *****

Figure 3-20
Labor Rate Schedules and Forms, Charts, and Diagrams 101

FIELD INSTALLATION OF MINERAL INSULATED CABLE 600V


"MI" LABOR HRS TO INS
CABLE "MI" "MI" "MI" "MI" "MI"
COND' CABLE CABLE CABLE CABLE CABLE
SIZES l/COND' 2/COND' 3/COND' 4/COND' 7/COND'
TERM TERM TERM TERM TERM

#12 1 1.25 1.55 1.75 2.5

#10 1 1.35 1.65 1.9 3

1.15 1.45 1.75 2.15 *****


#8

#6 1.25 1.65 1.9 2.25 *****

#4 1.35 1.75

#2 1.5 *****

1.7 ***** ***** ***** *****


#1
***** ***** ***** *****
#1/0 1.9

2.1 ***** ***** ***** *****


#2/0

2.25 ***** ***** ***** *****


#3/0
***** ***** ***** *****
#4/0 2.5

NOTES:
Add 25% to labor to install above 15' up to 25'.
Trapeze hangers add 1.25 hrs each (add 15% each foot if longer than 3').
Drill and set concrete anchors at 10 minutes each (add 100% if in overhead).
Allow for assembly and removal of scaffolding if required (+/- 8 hrs total for 3/6' sections).

Figure 3-21
102 How to Estimate Electrical Construction Projects

Section 2: Devices, Boxes, Plates, and Flat Wiring

FIELD INSTALLATION OF DEVICES AND PLATES

SINGLE-POLE SWITCH W/ PLATE (15 & 20 AMP) 35 HRS PER "C"

SINGLE-POLE SWITCH & PILOT LIGHT W/ PLATE (15 & 20 AMP) 40 HRS PER "C"

PILOT LIGHT W/ PLATE (120 VOL T) 25 HRS PER "C"

2-POLE SWITCH W/ PLATE (15 & 20 AMP) 45 HRS PER "C"

3-WAY SWITCH W/ PLATE (15 & 20 AMP) 40 HRS PER "C"

4-WAY SWITCH W/ PLATE (15 & 20 AMP) 45 HRS PER "C"

SINGLE RECEPTACLE W/ PLATE (15 & 20 AMP) 35 HRS PER 'IC"

DUPLEX RECEPTACLE W/ PLATE (15 & 20 AMP) 35 HRS PER "C"

GFCl RECEPTACLE W/ PLATE (15 & 20 AMP) 40 HRS PER "C"

2-POLE 3-WIRE RECEPTACLE W/ PLATE (15 & 20 AMP) 35 HRS PER "C"

3-POLE 4-WIRE RECEPTACLE W/ PLATE (15 & 20 AMP) 45 HRS PER "C"

2-POLE 3-WIRE RECEPTACLE W/ PLATE (30 AMP) 40 HRS PER "C"

3-POLE 4-WIRE RECEPTACLE W/ PLATE (30 AMP) 45 HRS PER "C"

2-POLE 3-WIRE RECEPTACLE W/ PLATE (40 AMP) 50 HRS PER "C"

3-POLE 4-WIRE RECEPTACLE W/ PLATE (40 AMP) 50 HRS PER "C"

2-POLE 3-WIRE RECEPTACLE W/ PLATE (50 AMP)a 70 HRS PER "C"

3-POLE 4-WIRE RECEPTACLE W/ PLATE (50 AMP)a 75 HRS PER "C"

2-POLE 3-WIRE RECEPTACLE W/ PLATE (60 AMP)a 70 HRS PER "C"

3-POLE 4-WIRE RECEPTACLE W/ PLATE (60 AMP)a 75 HRS PER "C"

.2-POLE 3-WIRE RECEPTACLE W/ PLATE (100 AMP)a 100 HRS PER 'IC"

3-POLE 4-WIRE RECEPTACLE W/ PLATE (100 AMP)a 100 HRS PER "C"

Figure 3-22
Labor Rate Schedules and Forms, Charts, and Diagrams 103

FIELD INSTALLATION OF POKE-THROUGH FITTINGS / DEVICES /COVERS

POKE-THROUGH FllTlNG W/ A SIMPLEX OR DUPLEX RECEPTACLE 150 HRS PER "C"

POKE-THROUGH FllTlNG W/ TWO SIMPLEX OR DUPLEX RECEPTACLE 175 HRS PER "C"

POKE-THROUGH FllTlNG W/ HOLE FOR FLEX' CONDUIT 125 HRS PER "C"

POKE-THROUGH FITTING W/ RECEPTACLE AND HOLE FOR FLEX' CONDUIT 150 HRS PER "C"

POKE-THROUGH POWER OR COMMUNICATIONS DIVIDER KIT 25 HRS PER "C"

SERVICE FllTlNG W/ 1 SIMPLEX OR DUPLEX RECEPTACLE 75 HRS PER "C"

SERVICE FITTING W/ 2 RECEPTACLES 105 HRS PER "C"

SERVICE FllTlNG FOR VOICE / DATA 50 HRS PER "C"

NOTES:
Labor includes complete installation of receptacles and covers/plates.
Allow additional time to layout and core drill floor holes.
Allow additional time for flexible conduit as required.
Allow additional time for voice or data connections.

Figure 3-23
104 How to Estimate Electrical Construction Projects

FIELD INSTALLATION OF SHEET METAL OUTLET AND JUNCTION BOXES

9NE GANG METAL WALL BOX / NEW OR EXIST' WORKa 35 HRS PER "C"

3NE GANG METAL MASONRY WALL BOXb 35 HRS PER "C"

3NE GANG METALTHROUGH 4" WALL BOX FOR NEW WORK 45 HRS PER "C"

3NE GANG METAL THROUGH 8" WALL BOX FOR NEW WORK 45 HRS PER "C"

METAL HANDY BOXd 30 HRS PER "C"

4" SQUARE METAL BOX 1-1/2" DEEPqd 25 HRS PER "C"

4" SQUARE METAL BOX 2-1/8" DEEPCid 40 HRS PER "C"

4-11/16" SQUARE METAL BOX 1-1/2" 35 HRS PER "C"

4-11/16" SQUARE METAL BOX 2-1/8" DEEPCid 50 HRS PER "C"

4" ROUND METAL BOX OR EXTENSION BOXd 25 HRS PER "C"

METAL HUNG CEILING BOX WITH 24" BAR SUPPORT 50 HRS PER "C"

ONE GANG METAL FLOOR BOX W/ COVER (ADJUSTABLE) 125 HRS PER "C"

METAL JUNCTION BOX W/COVER 6"x6"x4" DEEP (144/256 cu. in.) 100 HRS PER "C"

METAL JUNCTION BOX W/COVER 12"xl2"x4" DEEP (556 cu. in.) 150 HRS PER "C"

METAL JUNCTION BOX WEOVER 18"xl8"x6" DEEP (1,944 cu. in.) 200 HRS PER "C"

METAL JUNCTION BOXES 2,000 cu. in. to 4,000 cu. inee 300 HRS PER 'IC"

NOTES:
"angable type add 15 hrs per "C" for additional gang in sheetrock.
bAdd 10 hrs per "C" for each added gang and 10 hrs per "C" for box partitions.
'Add 10 hrs per "C" for blank cover and 10 hrs per "C" for 1 and 2 gang tile covers.
dAdd 10 hrs per 'IC" for blank covers.
.75 hrs for each additional 1,000 cu. in. up to 12,000 cu. in.
Add for cutting into existing masonry and 15 hrs per "C" for box supports.
Add 1 . 2 5 hrs for each 1,000 cu. in. above 12,000 cu. in.

Figure 3-24
Labor Rate Schedules and Forms, Charts, and Diagrams 105

FIELD INSTALLATION OF CAST OUTLET AND JUNCTION BOXES

ONE GANG, ONE HUB OUTLET BOXa 50 HRS PER "C"

TWO GANG, ONE HUB OUTLET BOXa 65 HRS PER "C"

ONE GANG FLOOR OUTLET BOX 100 HRS PER "C"

TWO GANG FLOOR OUTLET BOX 135 HRS PER "C"

THREE GANG FLOOR OUTLET BOX 175 HRS PER "C"

JUNCTION BOX W/COVER 6"x 6"x 4" DEEP (144 CU IN) 200 HRS PER "C"

JUNCTION BOX W/COVER 8" x 8" x 4" DEEP (256 CU IN) 200 HRS PER "C"

JUNCTION BOX W/COVER 12" x 12" x 4" DEEP (576 CU IN)b 300 HRS PER "C"

NOTES:
15 hrs per "C" for each additional hub.
bAdd 1.5 hrs per "M" cu. in. for boxes 600 cu. in. up to 10,000 cu. in.
Add 10 hrs per "C" for cover plate and 1 5 hrs per "C" for wlp cover.
Add 50 hrs per "C" for wlp bubble cover.
Deduct 15% if using aluminum.
Add 15% if using 2 gang box made in tandem.
Add 2 hrs per "M" cu. in. for boxes above 10,000 cu. in.

Figure 3-25
106 How to Estimate Electrical Construction Projects

FIELD INSTALLATION OF UNDER CARPET FLAT-WIRING SYSTEM


FLAT LABOR HRS TO INSTALL PER "C"
CABLE CABLE CABLE CABLE CABLE TO SINGLE DUAL
SIZES W/SHLD'S SPLICE TEE POWER FLOOR FLOOR
TRANS' RECEP RECEP

3/c #12 4 24 40 12 65 75

I 4/c #12 5 24 40 12 65 75

5/c #12 6 24 40 12 65 75

3/c #10 6 26 42 12 65 75

4/c #10 7 26 42 12 65 75

5/C #10 8 26 42 12 65 75

FLAT FLAT SHLD'S WALL FLOOR FLOOR


TELEPH DATA BOlTOM TRANS' TELE DATA
CABLE CABLE & TOP BOX FTNG' FTNG'
25PR. 25lC

16 16 4 200 100 100

Figure 3-26
Labor Rate Schedules and Forms, Charts, and Diagrams 107

Section 3: Light Fixtures

FIELD INSTALLATION OF HID LIGHTING FIXTURES

FLUSH-MOUNTED HID LIGHT FIXTURE 100 WATT 2.50 HRS EACH

FLUSH-MOUNTED HID LIGHT FIXTURE 250 WATT 2.50 HRS EACH

FLUSH-MOUNTED HID LIGHT FIXTURE 400 WATT 2.80 HRS EACH

FLUSH-MOUNTED HID LIGHT FIXTURE 1000 WATT 4.00 HRS EACH

FLUSH-MOUNTED HID LIGHT FIXTURE 1500 WAlT **********

*SURFACE-MOUNTED HID LIGHT FIXTURE 100 WATT 3.00 HRS EACH

*SURFACE-MOUNTED HID LIGHT FIXTURE 250 WATT 3.00 HRS EACH ~

*SURFACE-MOUNTED HID LIGHT FIXTURE 400 WATT 3.30 HRS EACH

SURFACE-MOUNTED HID LIGHT FIXTURE 1000 WATT 4.30 HRS EACH

SURFACE-MOUNTED HID LIGHT FIXTURE 1500 WATT 4.75 HRS EACH

HIGH OR LOW BAY HID LIGHT FIXTURE 100 WATT 2.00 HRS EACH

HIGH OR LOW BAY HID LIGHT FIXTURE 250 WATT 2.00HRS EACH

HIGH OR LOW BAY HID LIGHT FIXTURE 400 WATT 2.00 HRS EACH

HIGH OR LOW BAY HID LIGHT FIXTURE 1000 WATT 2.25 HRS EACH

HIGH OR LOW BAY HID LIGHT FIXTURE 1500 WATT 2.25HRS EACH

NOTES:
*Add 100% to labor for explosion proof.
All labor units are based upon ceiling height of 12' or less.
Add 25% to labor for each 5' increase in ceiling height.
Add 1 hr for each remote-mounted HID ballast.
Allow for added hangers for fixtures if required for independent suspension.
Add .50 hrs each for pendants (max 24") and -10 hrs for each foot over 24".
Add flex fixture whips at 10 hrs per "C."
High/low bay HID prewired with cord and male cap and furnished with loop and hook.

Figure 3-27
108 How to Estimate Electrical Construction Projects

FIELD INSTALLATION OF LIGHTING FIXTURES


(INCANDESCENT, EXIT, EMERGENCY)

SURFACE-MOUNTED PORCELAIN LAMP HOLDER .035HRS EACH

*SURFACE-MOUNTED INCAND. FIXTURE 100 WATT MAXIMUM .075HRS EACH

'SURFACE-MOUNTED INCAND. FIXTURE 300 WAlT MAXIMUM 1.25 HRS EACH

*WALL-MOUNTED INCAND. FIXTURE 200 WATT MAXIMUM 1-00HRS EACH

INCAND. LAMP HOLDER FOR "PAR" OR "R" TYPE LAMPS 0.50 HRS EACH

'PENDANT-MOUNTED INCAND. RLM FIXTURE 300 W A T MAXIMUM 1S O HRS EACH

LOW VOLTAGE AND LINE VOLTAGE HI-HATS 1.00 HRS EACH

I
I
EXIT LIGHT CEILING /WALL MTD 1 FACE .75 HRS EACH
-1
EXIT LIGHT CEILING / WALL MTD 2 FACE 1.OO HRS EACH

COMBO EXIT/EMERG LIGHT CEILINGMIALL MTD 1 FACE 1.50 HRS EACH

COMBO EXIT/EMERG LIGHT CEILINGMIALL MTD 2 FACE 1.50 HRS EACH

EXIT LIGHT EXPLOSION PROOF 2.25 HRS EACH

EMERG BATTERY LIGHT UNIT EXPLOSION PROOF 3.00 HRS EACH

REMOTE EMERG LIGHT EXPLOSION PROOF 2.25 HRS EACH

Figure 3-28
Labor Rate Schedules and Forms, Charts, and Diagrams 109

FIELD INSTALLATION OF FLUORESCENT FIXTURES


FLUSH- LABOR HRS TO INSTALL EACH
MOUNTED
FlXTURE 2' LONG 2' x 2' 4' 2' x 4' 8' 4' x 4'

1 LAMP 0.75 1 1 ***** 1.25 *****

2 LAMP 0.75 1 1 1.1 1.25 1.5

3 LAMP ***** 1.25 1.25 1.3 1.5 1.75

4 LAMP ***** 1.25 1.25 1.3 1.5 1.75

SURFACE- LABOR HRS TO INSTALL EACH


MOUNTED
FIXTURE 2' LONG 2' x 2' 4' 2' x 4' 8' 4' x 4'

1 LAMP 0.35 0.5 0.65 ***** 1 *****

2 LAMP 0.35 0.5 0.65 0.8 1 1.25

3 LAMP ***** 0.65 0.8 1 1.25 1.5

4 LAMP ***** 0.65 0.8 1 1.25 1.5

PENDANT- LABOR HRS TO INSTALL EACH


MOUNTED
FIXTURE 2' LONG 2' x 2' 4' 2' x 4' 8' 4' x 4'
***** 1.25 *****
1 LAMP 0.5 0.75 0.75

2 LAMP 0.5 0.75 0.75 1 1.25 1.75

3 LAMP ***** 1 1 1.25 1.5 2

4 LAMP ***** 1 1 1.25 1.5 2

NOTES:
All labor units are based upon ceiling height of 12' or less.
Add 25% to labor for each 5' increase in ceiling height.
Add 1 hr for each remote-mounted emergency battery for fluorescent fixtures.
Allow for additional fixture support if required for independent suspension.

Figure 3-29
110 How to Estimate Electrical Construction Projects

TRACK , LABOR HRS TO INSTALL EACH


LIGHT 1CKT 2CKT 1CKT 2CKT 1CKT 2CKT 1CKT 2CKT 1CKT 2CKT
LENGTH TRACK TRACK END END CENTER CENTER THRU THRU FLEX FLEX
FEED FEED FEED FEED COUP COUP COUP COUP-

2' 0.5 0.6 0.25 0.4 0.35 0.5 0.15 0.2 0.2 0.25

4' 0.65 0.75

8' 1 1.25

12' 1.5 0.175

1CKT 2CKT 1CKT 2CKT 1CKT 2CKT TRACK LOW LINE LINE
4-WAY 4-WAY TEE TEE 90-DEG 90-DEG MTG VOLT VOLT HID
FllTlNG FITTING FITTING FllTlNG FITTING FllTlNG CLIP FlXT FlXT FlXT

0.35 0.5 0.25 0.4 0.2 0.35 0.1 0.5 0.65 1

Figure 3-30
Labor Rate Schedules and Forms, Charts, and Diagrams 111

FIELD INSTALLATION OF PREASSEMBLED QUICK WRING SYSTEMS

HRS TO
QUICK WIRING COMPONENTS INSTALL

FIXTURE CONVERTER: HARD WIRE TO CABLE SYSTEM 0.25

HARDWIRE TO CABLE CONVERTER: 3 WIRE 0.25

HARDWIRE TO CABLE CONVERTER: 4 WIRE 0.3

HARDWIRE TO CABLE CONVERTER: 5 WIRE 0.35

CABLE SPLITTER: CABLE IN AND 2 CABLES OUT 0.2

PREASS'LD CABLE COMBO' HARDWIRE END & FIXT' CONVERTER END 9' 0.35

PREASS'LD CABLE COMBO' HARDWIRE END & FIXT' CONVERTER END 15' 0.5

PREASS'LD CABLE SWITCH DROP HARDWIRE END & 3-WAY CABLE RECEPT' 7' 0.35

PREASS'LD CABLE SWITCH DROP HARDWIRE END & 3-WAY CABLE RECEPT' 9' 0.35

PREASS'LD CABLE DROP: HARDWIRE TO CABLE SYSTEM 0.25

PREASS'LD CABLE #12 AWG CONVERTER END TO FIXTURE END 9' 0.25

PREASS'LD CABLE #10 AWG CONVERTER END TO FIXTURE END 9' 0.3

PREASS'LD CABLE #12 AWG CONVERTER END TO FIXTURE END 15' 0.25

PREASS'LD CABLE #10 AWG CONVERTER END TO FIXTURE END 15' 0.3

PREASS'LD CABLE #12 AWG CONVERTER END TO FIXTURE END 21' 0.35

PREASS'LD CABLE #10 AWG CONVERTER END TO FIXTURE END 21' 0.4
112 How to Estimate Electrical Construction Projects

HRS TO
QUICK WIRING COMPONENTS INSTALL
EACH
PREASS'LD CABLE #12 AWG CONVERTER END TO FIXTURE END 25' 0.35

PREASS'LD CABLE #10 AWG CONVERTER END TO FIXTURE END 25' 0.4

PREASS'LD CABLE #12 AWG CONVERTER END TO FIXTURE END 31' 0.35

PREASS'LD CABLE #10 AWG CONVERTER END TO FIXTURE END 31' 0.4

PREASS'LD CABLE FIXTURE TO FIXTURE 5'

PREASS'LD CABLE FIXTURE TO FIXTURE 7'


I o.2
0.2

PREASS'LD CABLE FIXTURE TO FIXTURE 9' 0.25

PREASS'LD CABLE FIXTURE TO FIXTURE 11' 0.25

PREASS'LD CABLE FIXTURE TO FIXTURE 13' 0.3

PREASS'LD CABLE FIXTURE TO FIXTURE 15' 0.3

PREASS'LD CABLE EXTENDER 5' 0.2

PREASS'LD CABLE EXTENDER 9' 0.2

PREASS'LD CABLE EXTENDER 11' 0.25

PREASS'LD CABLE EXTENDER 15' 0.3

PREASS'LD CABLE EXTENDER 21' 0.35

NOTES:
The items referenced above are similar to RELOP by Lithonia.
Add 25% to labor hrs to install above 1 5 ' up to 25'.
Trapeze hangers add 1 . 2 5 hrs each (add 15% each foot if longer than 3').

Figure 3-32
Labor Rate Schedules and Forms, Charts, and Diagrams 113

* SITE HOURS HOURS HOURS HOURS HOURS


LIGHTING EACH EACH EACH EACH EACH
POLES 12' 18' 25' 30' 50'

STEEL 3 4 5 6 a

,
ALUMINUM 2 3 4 5 6

WOOD 2 2.5 3 4 5

**lo0 WATT HID FIXTURE ON POLE 1.5 HRS EACH

**250 WAlT HID FIXTURE ON POLE 2.0 HRS EACH

**400WATT HID FIXTURE ON POLE 2.5 HRS EACH

, **lo00 WATT HID FIXTURE ON POLE 3.0 HRS EACH

**1500 WATT HID FIXTURE ON POLE 4.0 HRS EACH

*'POLE TOP TO FIXTURE ADAPTER 1.O HRS EACH

**POLE TOP YOKE FITTING FOR 2 FIXTURES 1.5 HRS EACH

**POLE TOP YOKE FITTING FOR 3 FIXTURES 2.0 HRS EACH

**POLE TOP YOKE FllTlNG FOR 4 FIXTURES 2.5 HRS EACH

**POLE ARM UP TO 3' LONG 2.0 HRS EACH

'*POLE ARM UP TO 6' LONG 3.0 HRS EACH

] WALKWAY BOLLARD (42" high) set on concrete base I 2.5HRSEACH

NOTES:
*Allow for use of bucket truck, or the like, to set and connect.
**Labor rates are intended for dressing up pole prior to setting.
Allow for in-line fuse holders with fuses and shims for leveling poles as required.
Allow extra labor for remote ballast (average at 1.5 hrs each).

Figure 3-33
114 How to Estimate Electrical Construction Projects

FIELD INSTALLATION OF WOOD POLES


LABOR HRS TO INSTALL EACH
WOOD I WOOD I WOOD I WOOD I WOOD I WOOD 1 WOOD I WOOD

SET IN

'D P

LABOR HRS TO INSTALL EACH


WOOD I WOOD I WOOD I WOOD I WOOD I WOOD I WOOD I WOOD I WOOD
POLE POLE POLE POLE POLE POLE POLE POLE POLE
20' 25' 30' 35' 40' 45' 50' 55' 60'
SET IN SET IN SET IN SET IN SET IN SET IN SET IN SET IN SET IN
ROCK ROCK ROCK ROCK ROCK ROCK ROCK ROCK ROCK
3' DEEP 3.5' DEEP 3.5' DEEP 4' DEEP 4' DEEP 4.5' DEEP 4.5' DEEP 5' DEEP 5' DEEP

7 7 8 8 9 10 12 14 16

LABOR HRS TO INSTALL EACH

I
R ! $ : :
CROSS I
I R!&
t I ARM&
HRD'WR
I
CROSS I CROSS I ANCHOR
&GUY
HRD'WR
I
I ANCHOR
&GUY
HRD'WR
I
48" 60" 72" I
INSOIL I IN ROCK

NOTES:
Allow for the rental of auger and bucket trucks as needed.
Add 6" deeper at corners, dead ends, etc.
Dig hole with 4" clearance (e.g.,30" pole butt should have 38" diameter hole).
Backfill and tamping is included.

Figure 3-34
Labor Rate Schedules and Forms, Charts, and Diagrams 115

Section 4: Emergency Generators

FIELD INSTALLATION OF EMERGENCY GENERATOR SETS

GENERATOR SETS LABOR HRS TO INSTALL EACH


KW SIZES GAS I GASOLINE DIESEL
277V l480V I 3 0 277V I 480V I 3 0

10 50 *****

15 55 55

30 62 62

***** 88
50

70 88 *****

*****
75 102

85 102 *****

***** 124
100

124 *****
115

***** 132
125

150 ***** 142

148 *****
170

***** 152
175

NOTES:
Installation includes receiving, handling, setting, and leveling generator (lifting equipment
charges not included).
Installation includes automatic transfer switch, battery, charger, and critical silencer (muffler).
Sheet metal and damper requirements are not included.
Concrete work, water, fuel, and exhaust piping are not included.
Day tank and remote control wiring are not included.
Main fuel tank and installation are not included.

Figure 3-35
116 How to Estimate Electrical Construction Projects

FIELD INSTALLATION OF EMERGENCY GENERATOR SETS

GENERATOR SETS LABOR HRS TO INSTALL EACH


KW SIZES GAS I GASOLINE DIESEL
277V 1480V 277V l480V
***** 160
200
***** 172
250
***** 188
300
***** 196
350
***** 216
400
***** 240
500

NOTES:
Installation includes receiving, handling, setting, and leveling generator (lifting equipment charges
are not included).
Installation includes automatic transfer switch, battery, charger, critical silencer (muffler).
Sheet metal and damper requirements are not included.
Concrete work, water, fuel, and exhaust piping are not included.
Day tank and remote control wiring are not included.
Main fuel tank and installation are not included.

Figure 3-36
Labor Rate Schedules and Forms, Charts, and Diagrams 117

COPPER LABOR HRS TO INSTALL EACH


CLAD GND RD GND RD GND RD GND RD GND RD GND RD GND RD
GROUND a' LONG 10' LONG 12' LONG 15' LONG COUP CLAMP DRIVE
RODS IN EARTH INEARTH INEARTH INEARTH ( acorn ) STUDS

1/2" 1.4 1.6 1.8 2 0.1 0.25 0.1

518" 1.6 1.a 2 2.25 0.1 0.25 0.1

314'' 1.a 2 2.25 2.5 0.1 0.25 0.1

1 GROUND CLAMP FOR PIPES: 1/2" TO 1" .75 HR EA

GROUND CLAMP FOR PIPES: 1-1/4"TO 2" 1.OO HR EA

GROUND CLAMP FOR PIPES: 2-1/2"TO 4" 1.25 HR EA

GROUND CLAMP FOR PIPES: 5" TO 8" 1.65 HR EA

GROUND CLAMP FOR PIPES: 10"TO 12" 2.00 HR EA

#a -ARMORED BARE COPPER GROUND WIRE 4 HRS PER "C" FEET

#6 -ARMORED BARE COPPER GROUND WIRE 5 HRS PER "C" FEET

#4 -ARMORED BARE COPPER GROUND WIRE 6 HRS PER "C" FEET

CADWELD GROUND WIRE (#2/0 TO #4/0) TO GROUND ROD 1.50 HR EA

CADWELD GROUND WIRE (#2/0 TO #4/0) TO BUILDING STEEL 1.75HR EA ,

.CADWELD GROUND WIRE (#2/0 TO #4/0) TEE OR THRU JOINT 1.75 HR EA

Figure 3-37
118 How to Estimate Electrical Construction Projects

Section 6: Bus Ducts

BUS HRS TO INSTALL EA FT' HRS TO INSTALL EACH


DUCTS PLUG IN FEEDER 90-DEG' TEE CABLE SWBD TO END WALL
COPPER 3P14W 3Pl4W ELBOW FITTING TAP BOX PNL' STUB BOX FLANGE
NEMA 1 STRAIGHT STRAIGHT 3P/4W 3Pl4W 3Pl4W 3Pl4W 3Pl4W 3Pl4W

225 AMP 0.48 I.. t.


3.25 5 4 4 0.5 2
.*.**
400 AMP 0.56 3.75 6.5 5.5 4.5 0.5 2.25

600 AMP 0.64 0.56 4.75 8 7 5.25 0.75 2.5

800 AMP 0.8 0.72 5.5 10 8 6.75 0.75 3

1,000 AMP 0.88 0.8 6 12 10 7.25 0.75 4

1,200 AMP 0.96 0.88 7 14 12 7.75 1 4

1,600 AMP 1.28 1.12 8 16 16 8.5 1 5

2,000 AMP 1.76 1.52 10 18 18 9.5 1 6

2,500 AMP 1.92 1.92 12 24 24 12 1 7

AMP 7 64 7 64 14 30 30 16 1 8

Figure 3-38
Labor Rate Schedules and Forms, Charts, and Diagrams 119

FIELD INSTALLATIONOF COPPER BUS DUCTS AND PLUG-IN UNITS

BUS DUCT HRS PER FT HRS TO INSTALL EACH PLUG-IN HRS TO INSTALL EA
AMPERE ADD MFG' HANGER SPRING SERVlCE SWITCH & 3 POLE 3 POLE
COPPER GND BUS CLAMP SUPPORT HEAD CIR. BRKR. 3 WIRE 4 WIRE

225 0.035 0.5 1 4 30 AMP 1 1.25

400 0.055 0.5 1.5 5 60 AMP 1.25 1.5

600 0.055 0.5 1.5 6.5 100 AMP 1.5 1.75

800 0.085 0.5 1.75 7 200 AMP 2.5 3.25

1,000 0.085 0.75 1.75 8 400 AMP 5 5.5

1,200 0.01 1 2 10 600 AMP 7 9

1,600 0.12 1 2 12 800 AMP 10 12

2,000 0.16 1.25 3 16 1,200 AMP 16 20

2,500 0.185 1.5 3 18 1,600 AMP 24 28

3,000 0.2 2 4 24

NOTES:
Add 20/0 to above for weatherproof installation if required.
Add 35% to labor hours to install above 15' up to 25'.
Trapeze hangers add 1 . 7 5 hrs each (add 15% each foot if longer than 5').
Single-rod hanger labor at 65% of trapeze labor.
Drill and set concrete anchors at 20 minutes each.
Deduct 15% for using aluminum ducts.
Labor rates for plug-in switch and circuit breaker includes terminations of wire.

Figure 3-39
120 How to Estimate Electrical Construction Projects

Section 7: Distribution Equipment

30 AMP 60 AMP 100 AMP 200 AMP 400 AMP 0 to 200 200 to 600 600 to 1,200
2P 3w 2P 3w 2P 3w 2P 3w 2P 3w AMP AMP AMP
NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 FUSE FUSE FUSE
DISC. SW. DISC. SW. DISC. SW. DISC. SW. DISC. SW. ***** ***** *****

0.8 1.6 2.8 4.5 7.5 0.03 0.05 0.1


I I I 1 I I 1 I I

2-pole sw
see note
below for
600 volt

3-pole sw
see note
below for
600 volt

r r
LABOR HRS TO INSTALL EACH
30 AMP 60 AMP 100 AMP 200 AMP 400 AMP 600 AMP 800 AMP 1,200 AMP
3 P 4w 3 P 4w 3 P 4w 3 P 4w 3 P 4w 3 P 4w 3 P 4w 3P 4w
NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1
DISC. SW. DISC. SW. DISC. SW. DISC. SW. DISC. SW. DISC. SW. DISC. SW. DISC. SW.

1.2 2 3.3 5 8 12 16 20

NOTES:
Add 25% for Nema 3R enclosures.
Add 1 5 % for 600-volt enclosures.
Add 10% for fusible enclosures.

Figure 3-40
Labor Rate Schedules and Forms, Charts, and Diagrams 121

FIELD INSTALLATION OF NEMA 1 MOTOR CONTROL CENTERS

Motor Control Center Section, Class B Wiring 600 V

Approx. size: 72"H x 20"W x 20"D (8 hours each


section
Receive, unload, unwrap, set, and connect together units
NOTES:
Allow for lifting equipment costs as required.
Allow for raised pad and leveling channels.
Allow for grounding as required.

Starter unit up to size 1 factory installed FVNR .75 HR EA


II I1 IIII II II
size 2 'I 1.0
II I1
II ,I I l l 1
size 3 I' 1.3
I, ,I IIII
size 4 'I
II II
1.6 I' 'I

II II IIII
size 5 'I
I1 II
1.8 I' I'

I1 II II
II IIII
size 6 I' 2.0"

NOTES:
Add 100% to starter units for FVR.
Add .25 each to connect PBs, HOAs, PLs, and INTLKs.

Disconnectkircuit breaker unit up to 30 amps factory installed -75 HR EA

It I, II I I I I I I
400 I'
I, I,
1.8 'I 'I

II
II II II I I I I I I
600 'I
II
2.0"
II
II ,I II I I I I I I
800 I'
II
3.0" I'

Figure 3-41
122 How to Estimate Electrical Construction Projects

FIELD INSTALLATION OF STARTERS, CONTACTORS, AND CONTROLS


1 STARTER

I
SIZES N/1 600V STWSTP HOA PILOT
ENCLOSED BUlTON sw LGT
NO PB'S IN COV'R IN COV'R IN COV'R

2 0.5 0.75 0.5

:O 2

2.35

2.75
I 0.5

0.5

0.5
I 0.75

0.75

0.75
I 0.5

0.5

0.5

0.75 0.5

0.75 0.5

0.75 0.5

0.75 0.5

0.75 0.5
1

0.75 I 0.5

CONTACTOR HRS TO INSTALL DEVICES HRS TO


AMP RATING N/1 600V N/1 600V INSTALL
ENCLOSED ENCLOSED STOP BUTTON 0.5
ELECT. HELD MECH. HELD
START BUlTON 0.5
30 1.75 1.75
HOA SWITCH 0.75
60 2.25 2.25
ON-OFF SWITCH 0.5
100 3 3
PILOT LIGHT 0.5
200 4.5 4.5

300 6 6

400 8 8

600 10 10

NOTES:
Add 25% for Nema 3R enclosures.
Add 100% for explosion-proof enclosures,

Figure 3-42
Labor Rate Schedules and Forms, Charts, and Diagrams 123

FIELD INSTALLATION OF STARTERS, CONTACTORS, AND CONTROLS

ENCLOSURES ONLY HRS TO


INSTALL

1 PUSH BUTTON NEMA 1 ENCLOSURE 0.5

2 PUSH BUTTON NEMA 1 ENCLOSURE 0.5

3 PUSH BUTTON NEMA 1 ENCLOSURE 0.65

. 4 PUSH BUTTON NEMA 1 ENCLOSURE 0.65

6 PUSH BUTTON NEMA 1 ENCLOSURE 1

.12 PUSH BUTTON NEMA 1 ENCLOSURE 1.5

16 PUSH BUTTON NEMA 1 ENCLOSURE 1.75

20 PUSH BUTTON NEMA 1 ENCLOSURE 2

. 2 4 PUSH BUTTON NEMA 1 ENCLOSURE 2.5

Figure 3-43
124 How to Estimate Electrical Construction Projects

FIELD INSTALLATION OF HIGH-VOLTAGETRANSFORMERS


KVA LABOR HRS TO INSTALL EACH
SIZE OF DRY TYPE LIQUID FILLED LIQUID FILLED
XFORMR'S 3 0 PAD MTD 3 0 PADMTD 1 0 POLE MTD
5 & 15 KV PRI 5 & 15 KV PRI 5 TO 25 KVA PRI
2771480~SEC 2771480~SEC 120 TO 480V SEC
*t*t* ttt**
10 12
I**** t
.
15 16

25 ***** ,...t
18
ttt*f
37.5 ,
.
t
19
*ttt* ttttt
50 22
ttttt
75 *t*tt
32

100 *.*** tCtt.


40

167 .**** *****


56
I r l t t t
250 ...t t
76

333 *..*+ **tt.


108

112 21 ttttt *****

150 28 32 *****

NOTES:
The above labor includes primary, secondary, and ground terminations. (Cable end preparation
is not included. See high-voltage cable section.)
Mounting of the transformers is relative to each installation.
Allow for rigging, lifting if conditions require.
Allow for grounding, bonding as required.
Allow for leveling channels for pad-mounted transformers.
Allow for line/bucket truck as required.

Figure 3-44
Labor Rate Schedules and Forms, Charts, and Diagrams 125

FIELD INSTALLATIONOF HIGH-VOLTAGE TRANSFORMERS


KVA LABOR HRS TO INSTALL EACH.
SIZE OF DRY TYPE LIQUID FILLED LIQUID FILLED
X FORMR'S 3 0 PADMTD 3 0 PADMTD 1 0 POLE MTD
5 & 15 KV PRI 5 & 15 KV PRI 5 TO 25 KVA PRI
2771480V SEC 277148OV SEC 120 TO 480V SEC
+++++
225 35 38

41 46 ++***
300

500 58 52 *****

+++*+
750 65 55

70 80 ++***
1,000
+++++
1,500 77 86
+++++
2,000 88 103

112 112 **+++


2,500

120 124 ***+*


3,000
++++* 132 +**+*
3,750

NOTES:
The above labor includes primary, secondary, and ground terminations. (Cable end preparation
is not included. See high-voltage cable section.)
Mounting of the transformers is relative to each installation.
Allow for rigging, lifting if conditions require.
Allow for grounding, bonding as required.
Allow for leveling channels for pad-mounted transformers.
Allow for linelbucket truck as required.

Figure 3-45
Next Page
126 How to Estimate Electrical Construction Projects

FIELD INSTALLATION OF LOW-VOLTAGE TRANSFORMERS

KVA
SIZE OF BUCWBOOST BUCWBOOST "ISOLATING" "ISOLATING" 1 0 3 0
X FORMR'S 1 0 3 0 1 0 3 0 240/480V PRI 240/480V PRI
120/240V PRI 240/208V 120/240 V PRI 120/240V PRI 120/240V SEC 120/208V SEC
12/24V SEC 120/240V SEC 120/208V SEC

1 ***** ***** ***** 1 *****


0.1
***** ***** ***** 1 *****
0.25 1
***** ***** *****
0.5 1.5 1.75 1.5
***** ***** ***** *****
0.75 2 1.5
***** 3.75 ***** 2 *****
1 3.75

2 4.5 *I***
6 ***tt
2 *****

3 6 ***.* 6.5 ***tf


3 4

5 8 ***** 7.5 ***** 4 *****

6 ****+ ***** ***** ***** ***** 7

7.5 tt*** *****


8 ***** 6 *****

9 ***** ***** ***** ***** ***** 8

10 ***** +**** 9 ***** 7 +****

****e ****e
15 8 14 8 10
***** ***** ***** *****
25 16 9
*****
30
I l2
*e***
I *****
I *****
I *****
I l2
*****
37.5 *t**t
21 I****
11

NOTES:
Primary, secondary, and ground connections labor are included.
Allow for grounding, bonding as required.
Labor hours are based upon floor or wall mounting. Allow for rigging, lifting if required.
Allow for special supports, trapeze hangers, framing, etc.

Figure 3-46
Previous Page
Labor Rate Schedules and Forms, Charts, and Diagrams 127

FIELD INSTALLATION OF LOW-VOLTAGETRANSFORMERS

LABOR HRS TO INSTALL EACH


-
SIZE OF BUCWBOOST BUCWBOOST I ISOLATING I ISOLATING 1 0 3 0
XFORMR'S 1 0 2401480V PRI 240/480V PRI
120124OV PRI 120124OV SEC 1201208V SEC
12124V SEC
I -
***** ***** ***** *****
18
***** ***** ***** ***** *****
14 -
***** 16 I 24 I ***** 16 21
***** ***** ***** ***** *****
18
***** ***** *****
112.5 18
I I
I
24 24
***** ***** *****
30
***** ***** ***** ***** *****
24
***** ***** ***** ***** *****
26 -
***** 24 ***** *****
32 36
***** ***** ***** ***** *****
32 -
***** ***** *****
28 35 40
***** ***** ***** *****
42 46
***** ***** ***** *****
56 54

1,000 ***** ***** ***** ***** ***** 70

NOTES:
Primary, secondary, and ground connections labor are included.
Allow for grounding, bonding as required.
Labor hours are based upon floor or wall mounting. Allow for rigging, lifting if required.
Allow for special supports, trapeze hangers, framing, etc.

Figure 3-47
128 How to Estimate Electrical Construction Projects

MAIN LABOR HRS TO INSTALL EACH


SERVICE W1 CT SECT' WI CT SECT W/CT SECT W l CT SECT DIST SECTION DIST SECTION
SECTION 1201208V 277140ov 1201208V 27714aov 120/200v 277148OV
AMPS 3 0 4W MLO 3 0 4W MLO 3 0 4W 3 0 4W 3 0 4W 3 0 4W
6 CB SPACES 6 CB SPACES MAIN FU SW MAIN CB CBISW NOT INC CBISW NOT INC

400 16 16 18 20 16 16

600 20 20 22 24 20 20

800 24 24 28 30 24 24

1,000 26 26 30 32 26 26

1,200 30 30 34 38 30 30

1,600 48 48 56 60 48 48

2,000 52 52 62 65 52 52

3,000 64 64 76 80 64 64

4,000 80 80 96 100 80 80

Figure 3-48
Labor Rate Schedules and Forms, Charts, and Diagrams 129

METER SOCKETS LABOR NOTES

SINGLE-METER SOCKET 1 0 PHASE 100 AMPS 2 HRS EA


Labor is included to connect the bonds
SINGLE-METER SOCKET 1 0 PHASE 150 AMPS 3 HRS EA
and grounding.
SINGLE-METER SOCKET 1 0 PHASE 200 AMPS 4 HRS EA

TWIN-METER SOCKET 1 0 PHASE 100 AMPS 4 HRS EA

TWIN-METER SOCKET 1 0 PHASE 150 AMPS 6 HRS EA

TWIN-METER SOCKET 1 0 PHASE 200 AMPS 8 HRS EA

Labor is included to connect

the bonds and grounding.

Allow for special lifting if


II II II II
1,000 22 22
required.
,I II II I1
1,200 24 24
II II ,I I1
1,600 28 28

NOTES:
Connections of service conductors are included.
Allow for housekeeping pads as required.

Figure 3-49
130 How to Estimate Electrical Construction Projects

FIELD INSTALLATION OF METER STACKS

AMP MAIN MAINSW 3METER 4METER 5METER 6METER ------NOTES------


RATING CB FUSED STACK STACK STACK STACK

400 13 13 16 18 22 24 Labor is included to connect

600 17 17
\I ll ,, I' the bonds and grounding.

800 20 20 ,I I, I,
" Allow for special lifting if

1,000 26 26
!I 11 11
required.

I, ,I ,! $1
1,200 28 28
,I I, 0 I1
1,600 32 32

Figure 3-50
Labor Rate Schedules and Forms, Charts, and Diagrams 131

FIELD INSTALLATION OF INDOOR SURFACE PANEL BOARDS

3 0 LABOR HRS TO INSTALL EACH


3 WIRE 30 42
240V CIR BRK CIR BRK
MLO SPACES SPACES

100 AMP 5 5.5

125 AMP 5 5.5

250 AMP 6 6.5

400 AMP 7 7.5

4 WIRE
2771480V CIR BRK CIR BRK

125 AMP 5.5 6

400AMP

NOTES:
Above labor includes installing the back box and cover, and connecting the main lugs.
Installing and connecting the branch breakers is not included.
Add .5 hrs to install a ground bar kit.
Add 1.0 hrs to each panel for flush mounting.
Manufacturers specifications may vary slightly from those listed above.

Figure 3-51
132 How to Estimate Electrical Construction Projects

FIELD INSTALLATION OF INDOOR SURFACE-MOUNTED PANELS

10 LABOR HRS TO INSTALL EACH


3 WIRE 6 8 16 24 30 42
120l240V CIR' BRK'R CIR' BRK'R CIR' BRK'R CIR' BRK'R CIR' BRK'R CIR' BRK'R
MLO SPACES SPACES SPACES SPACES SPACES SPACES

100 AMP 2 2 ***** ***** ***** *****

125 AMP ***+* *****


2 2.5 3 3.5

150 AMP ***** ***** ***** 4 4 *****

200 AMP ***** **tt* *


4 4 4.5

225 AMP ***** I**** ***** ***** ***** 5

Figure 3-52
Labor Rate Schedules and Forms, Charts, and Diagrams 133

FIELD INSTALLATION OF CIRCUIT BREAKERS

INSTALLEDAND CONNECTED
CIR' BRK'R LABOR HRS TO INSTALL EACH
AMPERES ONE POLE TWO POLE
CIR' BRKR CIR' BRK'R

15 0.3 0.5

20 0.3 0.5

25 0.3 0.5

30 0.4 0.5

35 ***** 0.5

40 0.45 0.6
***** 0.6
45

50 0.45 0.8
***** 0.8
60
***** 0.8
70
***** 0.9
80
***** 0.9
90
***** 1
100
***** 1.05
110
***** 1.15
125

Figure 3-53
134 How to Estimate Electrical Construction Projects

FIELD CONNECTlON OF PRElNSTALLED CIRCUIT BREAKERS/PRESSURE


SWITCHES AN D S INGLE-W IRE TERMINATIONS
CIRCUIT LABOR HF i TO CONNE( EACH
BREAKER 3 POLE AWG SIZE SHAPE CUT
AMPERE CIRCUIT CIRCUIT CIRCUIT COPPER STRIP
RATINGS BREAKEW WIRE TERMINATE
PRESS SW' CABLE

15 0.3 0.5 0.75 #I 4 0.1

20 0.3 0.5 0.75 #I 2 0.1


*****
25 0.3 0.5 #10 0.1

30 0.4 0.5 0.75 #8 0.15

35 ***** ***** ***** #6 0.15

40 0.45 0.6 0.85 #4 0.15

45 ***** ***** #3 0.2


0.95

50 0.45 0.8 1.25 #2 0.2

60 ***** 0.8 1.25 #1 0.25

70

80

90
--e- *****

*t*t*

*****
1.25

1.35

1.35
#1 /o

#2/0

#3/0
0.25

0.3

0.3

100 *****
1.5 #4/0 0.35

110 *****
~

1.6 #250 0.35


*****
125

200 *****
I 1.15

1.2
1.7

1.8
#300

#350
0.4

0.4
*****
225

250 **+**
I 1.35

1.35
1.9

I .9
#400

#500
0.45

0.5
*****
275 2 #600 0.6

300 ***** 2 #750 0.75


*****
4 325 1.6 2.25 #loo0 1

Figure 3-54
Labor Rate Schedules and Forms, Charts, and Diagrams 135

CIRCUIT LABOR HRS TO CONNE.CT


BREAKER 1 POLE 2 POLE 3 POLE
AMPERE CIRCUIT CIRCUIT CIRCUIT
RATINGS BREAKER BREAKER BREAKER

350 *****
1.6 2.25

375 *****
1.7 2.5

400 *****
1.7 2.5

450 ***** 1.9 2.6

500 ***** 2 2.8

600 ***** 2.1 3.15

800 ***** 3 4.5

1,000 *****
4.2 5.25
*****
1,200 5.6 7.1

1,600 ***** ***** 8.25

2,000 ***** ***** 9.5

2.500 ***** ***** 11

3,000 ***** *+*** 16

4,000 ***** ***** 24

Figure 3-55
136 How to Estimate Electrical Construction Projects

FIELD INSTALLATION OF CIRCUIT BREAKER ENCLOSURES AND CIRCUIT BREAKERS


ENCLOSURES

CIRCUIT BREAKERS

AMPERE SIMILAR LABOR HRS TO INSTALL EACH


RANGES TO 1 POLE CIR. BRK. 1 2 POLE CIR. BRK. 1 3 POLE CIR. BRK.
1 I
15 TO 30 AMP FAL,FHL 0.5 0.75 1

35 TO 60 AMP FAL,FHL 0.75 1.05 1.5


.*.I*
60 TO 100 AMP FAL,FHL 1.25 2
*****
100 TO 150 AMP Q2L,Q2LH 1.4 2.3
***+*
150 TO 200 AMP Q2L,Q2LH 1.45 2.3
***e*
200 TO 300 AMP LAL,KAL 1.75 2.5

300 TO 400 AMP "**.*


LAL,KAL 1.95 3

400 TO 600 AMP MEL


....t
2.35 3.65

600 TO 800 AMP MEL I****


3.25 5

800 TO 1,000 AMP MAL,LAL .I****


4.5 5.75

1,000 TO 1,200 AMP NAL,NCL **Iff


6 7.6

Figure 3-56
Labor Rate Schedules and Forms, Charts, and Diagrams 137

Section 8: Fire Alarm and Miscellaneous Systems

FIELD INSTALLATION OF FIRE ALARM SYSTEM EQUIPMENT

FIRE LABOR HRS TO INSTALL EACH


ALARM FAPNL MANUAL ALARM BELL& F/T&WR SMOKE DUCT ELR
PANEL W/BATT STATION BELL LIGHT DETECT' DETECT' DETECT'
# ZONES BACKUP W/TUBE

1 TO6 8 0.8 0.8 1 0.75 1 2 0.25

7 T 0 12 12 0.8 0.8 1 0.75 1 2 0.25

13 TO 16 18 0.8 0.8 1 0.75 1 2 0.25

17TO24 24 0.8 0.8 1 0.75 1 2 0.25

FA LABOR.HRS TO INSTALL EACH ,

REMOTE BACK ANNUN' ELECT' MAG'NT SPRNK'R SPRNKR


ANNUN' BOX PANEL DOOR FOR *FLOW *ALARM
PNL' HOLD'R HOLD'R sw SIGNAL

1 TO 6 2 6 1.5 0.5 1.5 1

7 T 0 12 3 9 1.5 0.5 1.5 1

1 3 T 0 16 4 12 1.5 0.5 1.5 1

17TO24 4 20 1.5 0.5 1.5 1

FA CABLE LABOR HRS TO INSTALL PER "M"


PLENUM-
RATED 2/c 4/c 6/C 8lC 1o/c 12/c
150 VOLT

#I 6 11 13 15 17 19 21

#18 10 12 14 16 18 20

#20 8 10 12 14 16 18

NOTES:
*These items are installed by others.
Plenum-cable labor is installed open above ceilings.
Cable hangers up to 36" long included in labor (add additional labor for longer hangers).
Add for wall penetrations and sleeves as required.
Cable terminations are not included in cable labor.

Figure 3-57
138 How to Estimate Electrical Construction Projects

FIELD INSTALLATION OF MISCELLANEOUS SYSTEMS

I MASTER CLOCK SYSTEM EQUIPMENT LABOR HRS TO INSTALL EACH

I
I MASTER
CLOCK
I
I
CLOCK
BOX
1
I
CLOCK I
I
CLOCK&
SPEAKER
1
I
PROG
SIGNAL
I
WALL
PHONE
1 BOX
8 0.5 1 1 0.75 1.25

MAIN REMOTE SPEAKER SPEAKER MIC PROJ


COUNSEL I AMP BOX I OUTLET I OUTLET
40 8 0.5 0.8 1 1

I DOORBELL SYSTEM EQUIPMENT LABOR HRS TO INSTALL EACH ~ ~~~


I
BELL BUZZER CHIME TRANS F' PUSH WP
& BOX & BOX BUTTON P/B
1 1 2 1 1 1.5

NURSE CALL SYSTEM EQUIPMENT LABOR HRS TO INSTALL EACH

40 STATION DOME DUTY EM PULL SINGLE DUAL


MASTER LIGHT STATION CORD BED STA BED STA
CONTROL
40 1 2.5 1.5 1.5 2.5 A

PUBLIC TV & CCTV SYSTEM EQUIPMENT LABOR HRS TO INSTALL EACH


I I I I I I I I
MAIN HEAD ANTENNA TV TV TV CAM' TV TV TV
END AND MONITOR CAMERA WP ENCLO OUTLET SPLITTER PREAMP
EQUIPMENT SUPPORT
16 8 1 4 4 1 1 4

Figure 3-58
Labor Rate Schedules and Forms, Charts, and Diagrams 139

Section 9: Electric Heating

FIELD INSTALLATION OF ELECTRIC HEATING

WALL HEATER HRS TO


WITH FAN INSTALL
12Ol208I24OV EACH
TOTAL WATTS

500 1.25

750 1.25

1,000 1.5

1,250 1.75

1,500 1.75

2,000 2

2,500 2.25

3,000 2.75

4,000 3

UNIT HEATER HRS TO RADIANT PNL'S HRS TO


3 0 INSTALL 12Ol2081277V INSTALL
20812401480V EACH TOTAL WATTS EACH
TOTAL WATTS LENGTH

5,000 3.25 24 " 310 W 1

7,500 5 36" 470 W 1.25

10,000 6.5 48" 625 W 1.5

15,000 8 60" 785 W 2

20,000 8.75 72" 940 W 2.5

30,000 10 84" 1,095 W 3

40,000 12 96" 1,250 W 3.5

50,000 14

NOTES:
Allow 1.25 hrs each for trapeze hangers (add 15% each foot if longer than 3').
Add additional labor if installed above 15'.

Figure 3-59
140 How to Estimate Electrical Construction Projects

EXPLOSION PRF' HRS TO UNIT HEATER HRS TO


UNIT HEATER INSTALL 1 0 PHASE INSTALL
200/240/400v EACH 120/200/240v EACH
3 0 PHASE TOTAL W A T S
WATS
3,000 2.5
3,000 4
5,000 3
5,000 6
7,500 4.5
7,500 10
10,000 6
10,000 12
15,000 9
15,000 16
20,000 *****
20,000 18
25,000 *****
25,000 19
30,000 *****
30,000 20
40,000 *****

EXPLOSION PRF'
UNIT HEATER
HRS TO
INSTALL
1 50,000 *****

120/200/277v
SINGLE PHASE
WATTS

3,000 5

5,000 6

7,500 9

10,000 12

15,000 10

20,000 ttttt

25,000 t**t*

30,000 *****

Figure 3-60
Labor Rate Schedules and Forms, Charts, and Diagrams 141

FIELD INSTALLATION OF SNOW MELTING MATS,


SNOW MELTING CABLE, AND HEAT TRACING CABLE

SNOW MATS LABOR NOTES


Add .15 hrs for each additional 5' in length
8" WIDE X 5'LONG .50HRS EACH
on all mats. Connection of power leads to mat
12" WIDE X 5' LONG 5 0 HRS EACH
leads are included. Installation of power source,
18" WIDE X 5' LONG .60HRS EACH
automatic controllers, or sensors not included.
24" WIDE X 5' LONG .70HRS EACH
Allow for extra labor to witness the installation
30" WIDE X 5' LONG 3 0 HRS EACH
of permanent cover material. Sub-base material
36" WIDE X 5' LONG .90HRS EACH
leveling not included.
48" WIDE X 5' LONG 1.OO HRS EACH

60" WIDE X 5' LONG 1.10 HRS EACH

72" WIDE X 5' LONG 1.20 HRS EACH

HEAT TRACE CABLE LABOR NOTES

120/240/48OV AWG#12 8 HRS PER "C" Labor includes tape, pipe straps, labels, etc.
I, I,
" #10 10 HRS PER "C" . Add 25% if installing from 15' to 25'.
CABLE / PWR CON" 1 HREA Allow for scaffold or lift as required.

SPLICE &TEE 1.5 HRS EA

END SEAL 1 HREA

THERMOST T 1.5 HRS EA

NOTES:
Manufacturer's equipment may vary from each other.
Estimator may need to adjust the labor rates to fit the designed project.

Figure 3-61
142 How to Estimate Electrical Construction Projects

FIELD INSTALLATION OF SNOW MELTING MATS,


SNOW MELTING CABLE, AND HEAT TRACING CABLE

120V CABLE 12 HRS PER "C"

PWR CONN KIT

END SEAL KIT

DOWNSPOUT HNGR

NOTES:
*Included with cable installation.
Manufacturer's equipment may vary from each other.
Estimator may need to adjust the labor rates to fit the
designed project.

Figure 3-62
Labor Rate Schedules and Forms, Charts, and Diagrams 143

Section I O : High- and Low-Voltage Cables

5&15KV HRS TO INSTALL PER "M" FEET HRS TO INSTALL EACH


CABLE COPPER COPPER ALUM' ALUM' INDOOR OUTDOOR
SIZES 5KV SHLD' 15KV SHLD' 5KV SHLD' 15KV SHLD' CABLE CABLE
CABLE CABLE CABLE CABLE TERM' TERM'

#4 36.4 ***** ***** *****


1 1.25

#2 40 ***** 32 ***** 1 1.25

#1 40 40 36.4 36.4 1 1.25

#1/0 42.1 42.1 40 40 1.5 1.75

#2/0 44.4 44.4 42.1 42.1 1.5 1.75

#4/0 50 50 44.4 44.4 1.5 1.75

#250 53.3 53.3 50 50 1.75 2

#350 61.5 61 -5 53.3 53.3 1.75 2

#500 66.7 66.7 61.5 61.5 2 2.5


***** ***** 66.7 66.7 2 2.5
#750

Figure 3-63
144 How to Estimate Electrical Construction Projects

FIELD INSTALLATION OF "COPPER" WIRE AND CABLE


AWG WIRE LABOR HRS TO INSTALLPER i i ~ f i p ~ LA%R HOURS
CABLE CABLE CABLE INSTALLED TO ADD
SIZES INSTALLED (SHORT RUNS) FOR SETUP
IN CONDUIT IN CONDUIT OF REELS

#14 & (drag line) 6 BR .**** *****

*****
#12 8 BR .I***

$6 14 BR *tit* *****

#4 10 FDR 17 FDR 1

#3 11 FDR 18 FDR 1

#2 12 FDR 20 FDR 1.5

#1 14 FDR 22 FDR 1.5

#1/0 16 FDR 25 FDR 1.5

#2/0 20 FDR 30 FDR 2

#3/0 21 FDR 33 FDR 2

#4/0 24 FDR 35 FDR 3

Figure 3-64
Labor Rate Schedules and Forms, Charts, and Diagrams 145

FIELD INSTALLATION OF "COPPER" WIRE AND CABLE


AWG WIRE , LABOR HRS TO INSTALL PER "M" LABOR TO ADD
CABLE CABLE CABLE INSTALLED FOR SETUP
SIZES INSTALLED (SHORT RUNS) OF REELS
IN CONDUIT IN CONDUIT

#250 27 FDR 37 FDR 3

#300 31 FDR 40 FDR 3.5

#350 33 FDR 48 FDR 4

#400 36 FDR 54 FDR 5

#500 40 FDR 64 FDR 6

#600 50 FDR 74 FDR 7

#750 70 FDR 100 FDR 8

NOTES:
Direct burial cable x 50% of above hours (warning tape labor at 2 - 4 hrs per "M").
FDR = feeder.
Duplicate pulls #14 through #1 deduct 10%.
Duplicate pulls #1/0 through #750 mcm deduct 12%.
Aluminum cable x 80% of above hours.

Figure 3-65
146 How to Estimate Electrical Construction Projects

MULTI- LABOR TO INSTALL PER "M"


COND' 600V TIC 600V TIC 5KV TIC 5KV TIC 15KV TIC 15KV TIC
CABLE 3 I COND' 4 I COND' 3 I COND' 3 I COND' 3 I COND' 3 I COND'
SIZES PVC JCKT' PVC JCKT' UNGND' NEUT' GND' NEUT' UNGND' NEUT' GND' NEUT'
PVC JCKT PVC JCKT' PVC JCKT' PVC JCKT'
t**t* ttttt ***** t**Ct
#6 24 28

#4 28 32 44 t*tt* *+*** ****I

#2 32 37 50 56 52 64

#I 36 40 54 60 56 68

#I10 40 44 58 65 62 76

#2/0 44 48 65 68 70 82

#310 40 53 68 72 76 90

#4/0 53 65 71 76 82 96

#250 65 70 75 80 80 104

#350 70 80 82 98 98 112

#500 80 90 96 108 117 134

Figure 3-66
Labor Rate Schedules and Forms, Charts, and Diagrams 147

FIELD INSTALLATION OF MULTICONDUCTOR COPPER CABLES

MULTI- LABOR HRS TO INSTALL PER "Mi'


COND' "AC I "MC" "AC I MC" "AC I MC" "NM" "NM" "NM"
CABLE CABLE CABLE CABLE CABLE CABLE CABLE
SIZES 2 3 4 2 3 4
COND' COND' COND' COND' COND' COND'

#I 4 25 30 35 30 35 40

#I 2 30 35 40 32 37 43

#I 0 36 50 55 42 55 70
*****
#8 50 65 75 55 65
ttttt
#6 70 80 90 65 75

#4 80 96 102 75 90 *****

t*t**
100 108 ***** ***** t*tt*
#3
***** 110 120 ttttt ***** ttttt
#2

NOTES:
Above labor does not include drilling wood beams (add 25% for drilling if required).
Cable connectors are included in above labor.
Cable hangers up to 36" are included in above labor.
Wall penetrations and sleeves are not included in above labor.

Figure 3-67
148 How to Estimate Electrical Construction Projects

FIELD INSTALLATION OF MULTICONDUCTOR COPPER CABLES

+
MULTI- LABOR HR TO INSTALL PER "M"
COND' "UF" "UF" "UF" I "SE.RH I "SE-U"
CABLE CABLE CABLE CABLE CABLE CABLE
SIZES 2 3 4 3 3
COND' COND' COND' COND' COND'

#14 22 24 t*t*t ***** ++***

#12 25 28 *.t*f ***** ttt**

*
#10 28 35 *
.
I **tt* *.***

.**** 65
#8 32 40 50

#6 40 48

#4 t*ttt *.***

*****

*
(it***

t*t** ttttt ti,***


118 104
***** ttlltt *it.*
130 118
ttttt .***. ***** 145 132
***** .*.** I
t
."
.
160 148

SERVICE HEAD FOR SEU CABLE 100 AMP 1.00 HR

NOTES:
Above labor does not include drilling wood beams (add 25% for drilling if required).
Cable connectors are included in above labor.
Cable hangers up to 36" are included in above labor.
Wall penetrations and sleeves are not included in above labor.

Figure 3-68
Labor Rate Schedules and Forms, Charts, and Diagrams 149

FIELD INSTALLATION OF LOW-VOLTAGEAND MULTICONDUCTOR CABLES


MULTI- LABOR HRS TO INSTALL PER "M"
COND' 2lC 2lC 4lC 41C 6lC 6lC 8lC 8lC 12lC 12lC
CABLE UN SHL'D UN SHL'D UN SHL'D UN SHL'D UN SHL'D
PLENUM SHL'D SHL'D SHLD SHL'D SHL'D
300V

#16 CU 15 15 16 16 18 18 19 19 22 22

#18 cu 10 10 11 11 15 15 16 16 70 70

#22 cu 8 8 9 9 12 12 13 13 18 18

#24 CU 1 8 8 9 9 10 10 11 11 16 16

THERMOSTAT LABOR HRS TO INSTALL PER "M"


CABLE
UNJACKETED 2lC 3lC 4lC 5IC 6lC 7lC 8lC
. TWISTED

#18 10 11 11 12 14 14 16

NOTES:
Plenum cable labor is installed open above ceilings.
Cable hangers up to 36" long are included in above labor (add additional labor for longer hangers).
Add for wall penetrations, sleeves, and patching as required.
Cable terminations are not included in cable labor.

Figure 3-69
150 How to Estimate Electrical Construction Projects

Section 11: Voice and Data Wiring

CATEGORY PATCH 32 PORT 64 PORT 6' LONG SURFACE COMMUNI COMBO DATA
5 PLENUM PANEL DATA DATA PATCH COMMUNI BOX PLATE CONN'S
DATA FLOOR PATCH PATCH CORD BOX PLATE VOICE &
CABLE STAND PANEL PANEL DATA

5 HOURS 2 HOURS 5 0 HOURS .50 HOURS ,151 HOURS .25 HOURS .10 HOURS .10 HOURS .25 HOURS
PER "M" EACH EACH EACH EACH EACH EACH EACH EACH

SHELF GROUND WIRE CABLE & J-HOOK CABLES


FOR PATCH CLAMP MANAGER PLATE SUPPORTS TO
~ PANEL FORSTAND LABELS TEST

1 HOUR .25 HOURS .50 HOURS .04 HOURS .25 HOURS .20 HOURS
EACH EACH EACH EACH EACH EACH

CATEGORY 100 PAIR 300 PAIR 2' TO 8' SURFACE NO BOX VOICE VOICE PUNCH
3 PLENUM 110 110 PATCH VOICE WALL BOX CONN'S DOWN
VOICE TERM TERM CABLES BOX RING PLATE 110 TERM
I CABLE BLOCK BLOCK BLOCK

5 HOURS 5 0 HOURS .75 HOURS .05 HOURS .25 HOURS .15 HOURS .10 HOURS .15HOURS .03 HOURS
PER "M" EACH EACH EACH EACH EACH EACH EACH PER PAIR
Labor Rate Schedules and Forms, Charts, and Diagrams 151

Section 12: Miscellaneous HVAC Devices

DESCRIPTION OF DEVICES LABOR HRS EACH

EP SWITCH TO CONNECT 0.5

PE SWITCH TO CONNECT 0.5

MOTORIZED DAMPERS TO CONNECT 0.5

MOTORIZED ZONE VALVE TO CONNECT 0.5

FREEZESTATTO CONNECT 0.5

FIRESTAT TO CONNECT 0.5

WALL HUMIDISTAT TO CONNECT 0.75

WALL THERMOSTATS TO CONNECT 0.75

PROVIDE POWER CONNECTIONS TO ATC PANEL (120V) 0.75

ELECTRIC DUCT HEATER 3 0 , l KW TO CONNECT 1


I1 IIII I,
I, I,
5KW 'I 1.5
I,
I, I, 4, I,,,
10KW 'I 2
,I
I, I, I, Ill,
15KW " 2.5
I1 I l l 1 I1
I, 11
20KW " 3
,I
I, I, I, ,I,,
40KW " 4

FAN COIL UNIT 10,TO CONNECT 1

CABINET HEATER 1 0 TO CONNECT 1

UNIT VENTILATOR 1 0 TO CONNECT 1

NOTES:
Labor does not include installation but does include connections.
Estimator to review HVAC specifications on installation responsibilities.

Figure 3-71
152 How to Estimate Electrical Construction Projects

Section 13: Light Bases

FIELD INSTALLATION OF CONCRETE BASES

SIZE OF BASES FLUSH W/GRADE BASES 36" ABOVE GRADE


CONCRETE CUBIC HOURS CUBIC HOURS
BASES YARDS TO INSTALL YARDS TO INSTALL

0.044 1 ***** *****


BOLLARDS

8' TO 12' POLE 0.196 2.75 0.392 3.5

14' TO 20' POLE 0.465 3.5 0.816 4.5


4
22' TO 30' POLE 0.582 4 0.932 5.15

32' TO 40' POLE 1.092 4.75 1.638 6

42' TO 60' POLE 1.454 5.5 2 6.75

Figure 3-72
Labor Rate Schedules and Forms, Charts, and Diagrams 153

Section 14: Voltage Drop Tables

VOLTAGE DROP TABLES FOR LOW-VOLTAGE CIRCUITS


TOTAL OF 6-VOLT SYSTEM 12-VOLT SYSTEM
WATTS ON WIRE GAUGE WIRE GAUGE
WIRE RUN LENGTH OF WIRE RUN IN FEET LENGTH OF WIRE RUN IN FEET
#12 #lo #8 #6 #12 #lo #8 #6

10 56 90 143 227 226 360 570 910

14 40 64 102 162 162 257 409 650

18 30 47 75 119 119 189 300 477

21 27 43 68 108 108 171 273 434

25 21 34 54 86 86 136 216 344

30 19 30 48 76 75 120 190 303

35 15 25 39 63 65 103 164 260

40 13 21 33 53 53 85 135 214

50 11 17 27 43 43 68 108 172

75 7 11 18 29 28 45 72 115

100 5 8 14 21 21 34 54 86

125 4 7 11 17 17 27 43 69

150 3 5 9 14 14 23 36 57

175 3 5 8 12 12 19 31 49

200 2 4 6 10 10 16 27 42

225 2 4 6 10 10 16 25 40

250 2 3 5 9 9 14 22 36

NOTE:
These values are used for sizing the wire based on the loads on the run.

Figure 3-73
154 How to Estimate Electrical Construction Projects

Section 15: Miscellaneous

MISCELLANEOUS INFORMATION, FORMULAS

A yard of sand weighs approximately 2,700 pounds, which is 1.35 times one ton (2,000 Ibs).

Conversion Factors: B.T .U./HOUR x .000393022 = HP

B.T.U./HOUR x .000293018 = KW

HP x 2544.39 = B.T.U./HOUR

HP x ,745702 = KW

KW x 3412.08 = B.T.U./HOUR

KW x 1.34102 = HP

WATTS x 3.413 = B.T.U./HOUR

WATTS x .0001341 = HP

AMPS = KW x 1,000 + 1.732 x VOLTS x POWER FACTOR (80%).

AMPS = KV x 1,000 + 1.732 x VOLTS x POWER FACTOR (100%).

Rule of thumb is that electrical demolition labor = 1/2 of the installation labor.

Basic rule of thumb is 1 square inch of copper bus (1/2" x 2") is = to 1,000 amps.

One horsepower = 746 watts

One kilowatt = 1,000 watts

Power factors = lighting at 100%; motors at 80 to 90%

Conversion formulas for illumination as follows:

Footcandles = LUX x .0929; LUX = Footcandles x 10.76 (e.g., 50 footcandles = 538 LUX).

Figure 3-74
Labor Rate Schedules and Forms, Charts, and Diagrams 155

AC Motor Connections Line 1 connects to motor lead #1


Most AC motors will come from the manufacturer with Line 2 connects to motor lead #2
the leads numbering 10, 11, and 1 2 , internally pre- Line 3 connects to motor lead #3
spliced together and not brought out into the connec- Motor leads #4 and #7 splice together and tuck in
tion box, or nosebag or pecker head as commonly nosebag
referred to in the field. Below are the common everyday
Motor leads #5 and #8 splice together and tuck in
connections you will see and need to follow when you
nosebag
are connecting the power feeds to the respective motor.
Motor leads #6 and #9 splice together and tuck in
AC 3-phase low-voltage motor connection at nose- nosebag
bag (208, 230, and 240 volts)
Line 1 connects to motor leads #1and #7 There may be times when the motor will have all 1 2
leads in the nosebag #1 to #12. If you see this condition,
Line 2 connects to motor leads #2 and #8
just connect the # l o , #11, and #12 together and fold
Line 3 connects to motor leads #3 and #9
into the nosebag.
Motor leads #4, #5, and #6 splice together and tuck Some larger motors will just have the #1, #2, and #3
in nosebag exposed for the power connections. The manufacturer
AC %phase high-voltage motor connection at nose- will have made the other connections inside the frame
bag (440, 460, and 480 volts) of the motor.
156 How to Estimate Electrical Construction Projects

Use Fig. 3-75 for squirrel-cage induction motors at all these factors with the motor manufacturer if in doubt.
1,800RF'M. Check the nameplate of the motor and see the To change the rotation direction of most standard
service factor, voltage, and class. Another consideration single-phase motors, interchange the lead connections
may be the temperature of the motor surroundings. Check of the starting winding.

MOTOR HP AND AMPERE RATINGS


SINGLE PHASE

HORSE- 115V 208V 230V 460V 575v


POWER AMPS AMPS AMPS AMPS AMPS

116 hp 4.4 2.4 2.2 1.1 0.9

114 hp 5.8 3.2 2.9 1.4 1.2

113 hp 7.2 4 3.6 1.8 1.4

112 hp 9.8 5.4 4.9 2.5 2

314 hp 13.8 7.6 6.9 3.5 2.8

1 16 8.8 8 4 3.2

1-112 20 11 10 5 4

2 24 13.2 12 6 4.8

3 34 18.7 17 8.5 6.8

5 56 30.8 28 14 11.2

7-112 80 44 40 21 16

10 100 55 50 26 20

Figure 3-75
Labor Rate Schedules and Forms, Charts, and Diagrams 157

Use Fig. 3-76 for squirrel-cage induction motors at ation may be the temperature of the motor surround-
1,800 RPM. Check the nameplate of the motor and see ings. Check all these factors with the motor manufac-
the service factor, voltage, and class. Another consider- turer if in doubt.

MOTOR HP AND AMPERE RATINGS

THREE PHASE

HORSE- 208V 230V 460V 575v


POWER AMPS AMPS AMPS AMPS

112 hp 2.4 2.2 1.1 0.9


314 hp 3.5 3.2 1.6 1.3
1 4.6 4.2 2.1 1.7
1-112 6.6 6 3 2.4
2 7.5 6.8 3.4 2.7

3 10.6 9.6 4.8 3.9

5 16.7 15.2 7.6 6.1


7-112 24.2 22 11 9

10 30.8 28 14 11
15 46.2 42 21 17

20 59.4 54 27 22

25 74.8 68 34 27

30 88 80 40 32

40 114 104 52 41

50 143 130 65 52

60 169 154 77 62

75 211 192 96 77

100 273 248 124 99

125 343 312 156 125

150 396 360 180 144

200 528 480 240 192

250 **I** ***** 302 24 1

300 ***** ***** 361 289


350 ***** .I****
414 336
***** ***** 477 382
400
***** ***** 514 411
450
500 **Ct* ***** 592 474

Figure 3-76
158 How to Estimate Electrical Construction Projects

TYPICAL MOTOR CONTROL CIRCUIT

EXAMPLE:
2-Wire ControCMaintained Contact

switch, pressure switch,

L1 5 + L2

Low-voltage release is a two-wire control scheme using a maintained contact pilot device in series with the starter coil.
This scheme is used when a starter is required to function automatically without the attention of an operator. If a power
failure occurs while the contacts of the pilot device are closed, the starter will drop out. When the power is restored, the
starter will pickup automatically through the closed contacts of the pilot device. The term two-wire control arises from
the fact that in the basic circuit only two wires are required to connect the pilot device to the starter.

Figure 3-77

TYPICAL MOTOR CONTROL CIRCUIT

EXAMPLE:

2-Wire ControCMaintained Contact


with Hand-Off-Auto Selector Switch

b-*J &kGz-j
A hand-off-autoselector switch is used on two-wire control applications where it is desirable to operate the starter
manually as well as automatically. The starter coil is energized manually when the switch is turned to the hand posi-
tion, and is energized automatically by the pilot device when the switch is in the auto position.

Figure 3-78
Labor Rate Schedules and Forms, Charts, and Diagrams 159

TYPICAL MOTOR CONTROL CIRCUIT

EXAMPLE:

3-Wire Control-Momentary Contact

4 r-+cl Aux holdins circuit

interlmk J
Using the wiring scheme above we use momentary hold devices such as push buttons for the control of the starter. The
starter is energized by pressing the start button. An auxiliary holding circuit interlock on the starter forms a parallel cir-
cuit around the start buttons contacts holding the starter in after the button is released. If a power failure does occur, the
starter will drop out and will open the holding circuit interlock. Upon the return of power, the start button must be oper-
ated again before the motor will restart. The term 3-wire control arises from the fact that in the basic circuit at least
three wires are required to connect the pilot devices to the starter.

Figure 3-79

TYPICAL MOTOR CONTROL CIRCUIT

4B
STOP
alo
STOP
9 I P
-- I
START

0 0 :: Ix
XI
1

M
I I

When a motor needs to be controlled from various places, any number of the start and stop push buttons may be
wired together as needed. It is also possible to use only one start-stop station and have several stop buttons at differ-
ent locations to serve as emergency stop locations.

Figure 3-80
160 How to Estimate Electrical Construction Projects

CONVERSION FACTORS: METRIC EQUIVALENTS

W T MULTIPLY BY TO GET

LINEAR: centimeter 0.3937 inches

inch 2.54 centimeters

foot 30.48 centimeters

meter 39.37 inches

yard 0.9144 meters

meter 1.0936 yards

kilometer 0.62137 miles

mile 1.6093 kilometers

AREA: square centimeter 0.155 square inches

square inch 6.452 square centimeters

square meter 1.196 square yards

square yard 0.8361 square meters

acre 160 square rods

acre 0.4047 hectares

square kilometer 0.386 square miles

square mile 2.59 square kilometers

VOLUME: cubic centimeter 0.061 cubic inches

cubic inch 16.39 cubic centimeters

cubic meter 1.308 cubic yards

cubic yard 0.7646 cubic meters

liter 1.0567 quarts-liquid

quart-liquid 0.9453 liters

WEIGHT gram 0.03527 ounces

ounce 28.35 grams

kilogram 2.2046 pounds

pound 0.4536 kilograms


(contin ues)
Figure 3-81
Labor Rate Schedules and Forms, Charts, and Diagrams 161

CONVERSION FACTORS
UNlT MULTIPLY BY TO GET

Ampere-hours 3,600 Coulombs

Ampere-hours 0.037307 Faradays

Atmospheres 76 Cm. of Hg (0' C)

Atmospheres 14.696 Pounds/square inch

B.T.U. 252 Calories, gram

B.T.U. 1.05508 x 1010 Ergs

B.T.U. 778.184 Foot-pounds

B.T.U. 1,055 Joules

B.T.U./hour 0.000393022 Horsepower

B.T.U./hour 0.000293018 Kilowatts (int.)

Calories, gram 0.00396832 B.T.U.

Calories, gram 4.18689 x 107 Ergs

Calories, gram 3.08808 Foot-pounds

Calories, gram 4.18689 Joules

Calories, gram/hour 155964 x 10-6 Horsepower

Calories, gram/hour 1.16279 x 10-6 Kilowatts

Cm. of Hg (0' C) 0.0131579 Atmospheres

Coulombs 0.000277778 Ampere-hours

Coulombs 1.0365 x 10-5 Faradays

Dynes 2.248089 x 10-6 Pounds

Dynedsquare cm. 1 x 10-6 Bars

Ergs 9.47798 x 1011 B.T.U.

Ergs 2.38841 x 10-8 Calories, gram

Ergs 7.3756 x 10-8 Foot-pounds

Ergs 1x107 Joules


(continues)
Figure 3-81 continued
162 How to Estimate Electrical Construction Projects

CONVERSION FACTORS
W T MULTIPLY BY TO GET

Ergslsec. 1.34102 x 10-10 Horsepower

Faradays 26.8 Ampere-hours

Faradays 96.48 Coulombs

Feet of H20 (60' F) 0.029469 Atmospheres

Feet of H20 (60"F) 62.364 Poundslsquare foot

FeetJhour 1.64468x 10-5 Knots

Feet/second 0.681818 Miledhour

Foot-pounds 0.00128504 B.T.U.

Foot-pounds 0.323826 Calories, gram

Foot-pounds 1.35582x 107 Ergs

Foot-pounds 1.35582 Joules

Foot-pounds 3.76617x 10-7 Kilowatt-hour

Foot-pounds/minute 3.0303x 10-5 Horsepower

Gram-cm. 9.29472x 10-8 B.T.U.

Gram-cm. 2.34223x 10-5 Calories, gram

Gram-cm. 980.665 Ergs

Gram-cm. 7.2330x 10-5 Foot-pounds

Horsepower 2544.39 B.T.U./hour

Horsepower 10686.3 Calories, gramlmin.

Horsepower 7.45702x lo9 Ergslsec.

Horsepower 550 Foot-pounds/sec.

Horsepower 0.745702 Kilowatts

Inches of Hg (32"F) 0.033421 Atmospheres

Inches of Hg (32' F) 33864 Dynedsquare cm.

Inches of Hg (32"F) 70.726 Poundslsquare foot


(continues)
Figure 3-81continued
Labor Rate Schedules and Forms, Charts, and Diagrams 163

CONVERSION FACTORS
W T MULTIPLY BY TO GET

Joules 0.000947798 B.T.U.

Joules 0.238841 Calories, gram

Joules 1 x107 Dynes-cm.

Joules Ix io7 Ergs

Joules 0.073756 Foot-pounds

Joules 10197.16 Gram-cm.

Kilowatts 3412.08 B.T.U./hour

Kilowatts 859,828 Calories, gram/hour

Kilowatts 1 x IOi0 Ergshecond

Kilowatts 2.65522 x 1O6 Foot-pounds/hour

Kilowatts 1.34102 Horsepower

Kilowatts 3.67098 x 1O5 Kg.-meterdhour

Kilowatts-hours 3.6 x IO6 Joules

Knots 1.8532486 Kilometers/hour

Knots 1 Miles (Naut.)/hour

Knots 1.15155 Miledhour

Lamberts 295.71 9 Candles/square foot

Lambeds 929.034 Lumendsquare foot

Light years 9.45994 x 10'2 Kilometers

Light years 5.8781 2 x 1012 Miles

Meters of Hg (0' C) 1.31579 Atmospheres

Meters of Hg (0' C) 44.65 Feet of H20 (60' F)

Meters of Hg (0' C) 19.3368 Pounds/square inch

Miles/ hours 1.46667 FeetJsec.

Million gal./day 1.54723 Cu. feet/sec.


(continues)
Figure 3-81 continued
164 How to Estimate Electrical Construction Projects

CONVERSION FACTORS
W T MULTIPLY TO GET

Ounces/square inch 0.0106042 Feet of Hg (32' F)

Ounces/square inch 0.144314 Feet of H20 (60" F)

Pounds/square foot 0.000472543 Atmospheres

Pounddsquare foot 0.000478803 Bars

Pounds/square foot 0.0359131 Cm. of Hg (0' C)

Poundslsquare foot 478.803 Dynes/sq. cm.

Pounds/square foot 0.00117825 Ft. of Hg (32' F)

Pounds/square foot 0.016035 Ft. Of H20 (60"F)

Pounds/square foot 0.488241 Gramkquare inch

Pounds/square foot 0.0359131 Cm. of Hg (0' C)

Watts 3.413 B.T.U./hour

Watts 860 Calories, gram/hour

Watts 1 x107 Ergsisecond

Watts 44.25 Foot-pounds/minute

Watts 0.0001341 Horsepower

Watt-hours 2655.75 Foot-pounds


(continues)
Figure 3-81 continued
Labor Rate Schedules and Forms, Charts, and Diagrams 165

CONVERSION FACTORS
WEIGHTS AND MEASURES
LENGTH

1 Nautical Mile = 1.115151 miles

1 Mile = 1,760 yards = 5,280 feet

1 Yard = 3 feet = 36 inches

1 Foot = 12 inches

AREA

1 Square Mile = 640 acres

1 Acre = 4,840 sq. yards = 43,560 sq. feet

1 Square Yard = 9 sq. feet

1 Square Foot = 144 sq. inches

VOLUME

1 Cubic Yard = 27 cubic feet

1 Cubic Foot = 1,728 cubic inches

1 Quart = 2 pints

1 U S . Gallon = 8 U S . pints

1 U S . Bushel = 64 U S . pints

WEIGHT

1 LongTon = 2,240 pounds

1 ShortTon = 2,000 pounds

1 Pound = 16 ounces

1 Ounce = 437.5 grams

Figure 3-81 continued


166 How to Estimate Electrical Construction Projects

AMPERE RATINGS OF RESISTANCE LOADS


SINGLE PHASE

KW 120v 208V 240V 277V

0.5 4.2 2.5 2.1 1.9

0.75 6.3 3.7 3.2 2.8

1 8.4 4.9 4.2 3.7

2 16.7 9.7 8.4 7.3

3 25 14.5 12.5 10.9

4 33.4 19.3 16.7 14.5

5 41.7 24.1 21 18.1

6 50 28.9 25.2 21.7

7.5 62.5 36.1 31.3 27.1

10 83.4 48.1 41.7 36.2

12 100 57.7 50 43.4

15 125 72.2 62.5 54.2

20 166.7 96.2 83.4 72.3

25 208.4 120.2 104.2 90.3

30 250 144.3 125 108.4

50 416.7 240.4 208.4 180.6

75 625 360.6 312.5 270.8

100 833.4 480.8 416.7 361.1


NOTE:
To find kw for loads not listed, just combine the total of kw needed. For example, to find amps for 18 kw at 277V,
find amps for 15 kw = 54.2 amps. Next find amps for 3 kw = 10.9 amps and add this to 54.2 amps = 65.1 amps total.

Figure 3-82
Labor Rate Schedules and Forms, Charts, and Diagrams 167

AMPERE RATINGS ON RESISTANCE LOADS

THREE PHASE

KW 208V 240V 480V

1 2.8 2.5 1.3

2 5.6 4.9 2.5

3 8.4 7.3 3.7

4 11.2 9.7 4.9

5 13.9 12.1 6.1

6 16.8 14.5 7.3

8 22.4 19.4 9.8

10 27.8 24.1 12.1

12 33.4 29 14.5

15 41.7 36.2 18.1

20 55.6 48.2 24.1

30.2

36.2

50 139 120.5 60.3

75 208.5 180.7 90.4

100 278 240.9 120.5


NOTE:
To find kw for loads not listed, just combine the total of kw needed. For example, to find amps
for 18 kw at 480V, find amps for 15 kw = 18.1 amps. Next find amps for 3 kw = 3.7 amps and
add this to 18.1 amps = 21.8 amps total.

Figure 3-83
168 How to Estimate Electrical Construction Projects

TRANSFORMER CONNECTIONS

DELTA TO WYE

HIGH-VOLTAGE PRIMARY CONNECTION


3-PHASE 3-WIRE INPUTVOLTAGE
Also referred to as a DELTA connection

7
2

T T T
I

Y 7
d d

LOW-VOLTAGE SECONDARY CONNECTION


3-PHASE 4-WIRE OUTPUTVOLTAGE
Also referred to as a WYE connection
NOTE:
This is a typical transformer connection that we see all the time with three single-phase transformers connected together
to provide 3-phase service.

Figure 3-84
Labor Rate Schedules and Forms, Charts, and Diagrams 169

TRANSFORMER CONNECTIONS

DELTA TO DELTA

HIGH-VOLTAGE PRIMARY CONNECTION


3-PHASE 3-WIRE INPUTVOLTAGE
Also referred to as a DELTA connection

Phase Phase Phase

f F ?

t t t
Phase Phase Phase

LOW-VOLTAGE SECONDARY CONNECTION


3-PHASE 3-WIRE OUTPUT VOLTAGE
Also referred to as a DELTA connection
NOTES:
This transformer connection that we see sometimes is not as common as the typical %phase primary to 3-phase 4-wire
secondary transformer setup using the three single-phase transformers.
This configuration allows the enduser to determine whether to ground one phase of the three phases. This must be coor-
dinated with the utility company that supplies the electricity. The purpose of grounding one phase is for safety.

Figure 3-85
170 How to Estimate Electrical Construction Projects

TRANSFORMER KVA AND AMPERE RATINGS

SINGLE PHASE

KVA 120v 208V 240V 277V 480V


RATINGS AMPS AMPS AMPS AMPS AMPS

0.25 2.1 1.2 1 0.9 0.52

0.5 4.2 2.4 2.1 1.8 1.4

0.75 6.3 3.6 3.1 2.7 1.6

1 8.3 4.8 4.2 3.6 2.1

1.5 12.5 7.2 6.3 5.4 3.1

2 16.7 9.6 8.3 7.2 4.2

3 25 14.4 12.5 10.8 6.3

5 41.7 24 20.8 18.1 10.4

7.5 62.5 36.1 31.3 27.1 15.6

10 83.3 48.1 41.7 36.1 20.8

15 125 72.1 62.5 54.2 31.3

25 208.3 120.2 104.2 90.3 52.1

37.5 312.5 180.3 156.3 135.4 78.1

50 416.7 240.4 208.3 180.5 104.2

75 625 36 1 313 271 156

100 833 48 1 417 36 1 208

167 1392 803 696 603 348

200 1667 962 833 722 41 7

250 2083 1202 1042 903 52 1

AMPS = KVA x 1OOONOLTAGE (e.g., 50 x 1000 = 50,000/277V= 180.51 AMPS)

NOTES:
To choose the correct size of a transformer, the load amperes must be known. When the amperes are known, select the
next higher KVA size transformer (e.g., load amperes are 28 at 277V,so select 10 KVA [ 7 . 5 KVA is too small]).
All calculations are rounded off to the nearest tenth or whole number.
Check with the transformer manufacturer for recommendations based on the application. Location, distribution equip-
ment, and loads to be serviced may have a direct impact on the type and size of transformer needed.

Figure 3-86
Labor Rate Schedules and Forms, Charts, and Diagrams 171

TRANSFORMER KVA AND AMPERE RATING

THREE PHASE
KVA 208V 240V 460V 480V
RATING AMPS AMPS AMPS AMPS

3 8.3 7.2 3.8 3.6

6 16.7 14.4 7.5 7.2

9 25 21.7 11.3 10.8

15 41.6 36.1 18.8 18

30 83.3 72.2 37.7 36.1

45 125 108.3 56.5 54.1

75 208.2 180.4 94.1 90.2

112.5 312 271 141.2 135

150 416 361 188.3 180

225 625 541 282.4 271

300 833 722 376.6 361

500 1,388 1,203 627.6 60 1

NOTES:
To choose the correct size of a transformer, the load amperes must be known. When the amperes are known, select the
next higher KVA size transformer from the chart (e.g., load amperes are 40 at 460V, so select 45 KVA [30 KVA is too
smalll).
AMPS = KVA x 1,000 I VOLTAGE x 1.732 (e.g., 75 x 1,000 = 75,000/460 x 1.732 (796.7) = 94.14 AMPS).
All calculations are rounded off to the nearest tenth or whole number.
Check with the transformer manufacturer for recommendations based on the application. Location, distribution equip-
ment, and loads to be serviced may have a direct impact on the type and size of transformer.

Figure 3-87
172 How to Estimate Electrical Construction Projects

LIGHTING DESIGN / FOOTCANDLE RECOMMENDATIONS

THIS TABLE REPRESENTS THE "IES" ILLUMINANCE CATEGORIES AND VALUES FOR GENERIC

TYPE OF INDOOR ACTIVITIES. ALLTASKS FALL INTO 1 OF 9 ILLUMINANCE CATEGORIES, COVERING

FROM 20 TO 20,000 LUX (2 TO 2,000 FOOTCANDLES). THE CATEGORIES ARE KNOWN AS " A T 0 I"

AND EACH PROVIDE A RANGE OF 3 ILLUMINANCES VALUES (LOW-MEDIUM-HIGH),

ACTIVITY CATEGORY LUX FOOTCANDLES


LOW-MEDIUM-HIGH LOW-MEDIUM-HIGH

PUBLIC SPACES WITH


DARK SURROUNDINGS A 20-30-50 2-3-5

SIMPLE ORIENTATION FOR


SHORT TEMPORARY VISITS B 50-75-100 5-7.5-10

WORKING SPACES WHERE


VISUAL TASKS ARE ONLY
OCCASIONALLY PERFORMED C 100-150-200 10-15-20

PERFORMANCE OF VISUAL
TASKS OF HIGH CONTRAST
OR LARGE SIZE D 200-300-500 20-30-50

PERFORMANCE OF VISUAL
TASKS OF MEDIUM CONTRAST
OR SMALL SIZE E 500-750-1,000 50-75-100

PERFORMANCE OF VISUAL
TASKS OF LOW CONTRAST
OR VERY SMALL SIZE F 1,000-1,500-2,000 100-150-200

PERFORMANCE OF VISUAL
TASKS OF LOW CONTRAST
AND VERY SMALL SIZE OVER
A PROLONGED PERIOD G 2,000-3,000-5,000 200-300-500

PERFORMANCE OF VERY
PROLONGED AND EXACTING
VISUAL TASKS H 5,000-7,500-10,000 500-750-1,000

PERFORMANCE OF VERY
SPECIAL VISUAL TASKS OF
EXTREMELY LOW CONTRAST
AND SMALL SIZE I 10,000-15,000-20,000 1,000-1,500-2,000
(contin ues)
Figure 3-88
labor Rate Schedules and Forms, Charts, and Diagrams 173

COMMERCIAL, INDUSTRIAL, AND RESIDENTIAL LIGHTING LEVELS

AREA OF THE ILLUMINANCE


ACTIVITY CATEGORY

AUDITORIUMS:
ASS EMBLY C
SOCIAL ACTIVITIES B

BANKS:
GENERAL C
WRITING AREA D
TELLER STATIONS E

CONFERENCE ROOMS D

EDUCATIONAL FACILITIES:
CLASSROOMS GENERAL
DRAFTING
SCIENCE
LECTURE HALLS
SHOP ROUGH WORK
SHOP MEDIUM BENCH WORK
SHOP FINE BENCH WORK
SHOP EXTRA-FINE BENCH WORK

EXHIBITION HALLS C

FOOD SERVICES:
DINING B
KITCHEN E
FOOD DISPLAYS E

GASOLINE STATIONS:
*****
W/ DARK SURROUNDINGS
APPROACH A
DRIVEWAY A
PUMP ISLAND AREA D
SERVICE AREA A
LANDSCAPE HIGHLIGHTS A
****e
W/ LIGHT SURROUNDINGS
APPROACH A
DRIVEWAY B
PUMP ISLAND AREA D
SERVICE AREAS B
LANDSCAPE HIGHLIGHTS B

HEALTH CARE FACILITIES:


CORRIDORS C
NURSING AREAS-DAY C
NURSING AREAS-NIGHT B
OPERATING AREAS E
DELIVERY E
RECOVERY E
LAB SUITES/SERVICES E
LOBBY AREA C
MEDICAL RECORDS E
PATIENTS ROOMS GENERAL B
SOLARIUM GENERAL C
STA IRWAY S C
WAITING AREAS GENERAL C
(continues)
Figure 3-88 continued
174 How to Estimate Electrical Construction Projects

COMMERCIAL, INDUSTRIAL, AND RESIDENTIAL LIGHTING LEVELS (continued)

AREA OF THE ILLUMINANCE


ACTIVITY CATEGORY

LIBRARIES:
READING AREAS GENERAL E

MUNICIPAL BUILDINGS:
FIRE AND POLICE RECORDS F
INTERROGATION-CELLS D
FIRE HALL D

0FFIC ES :
GENERAL LEVELS C
MAIL SORTING E
PRINTING AND COPING D

STORAGE YARDS:
ACTIVE D
INACTIVE A

TRANSPORTATION TERMINALS:
WAITING ROOM AND LOUNGE C
TICKET COUNTERS E
BAGGAGE CHECKING D
RESTROOMS C
CONCOURSE B
BOARDING AREA C

INDUSTRIAL ASSEMBLY:
SIMPLE D
MODERATELY DIFFICULT E
DIFFICULT F
VERY DIFFlCULT G
EXACTING H

GARAGES-SERVICE:
REPA IRS E
ACTIVE TRAFFIC AREAS C
WRITE-UP D

GENERAL PARKING AREAS:


MAIN LOTS A
SECONDARY LOTS A

Figure 3-88 continued


CHAPTER 4

Sample Estimate and Forms

forward to the Recapitulation Sheet of the estimate.


T he following sample estimate (Figs. 4-1A-S) shows
the contractor andlor estimator how a professional
estimate is formatted and assembled into a logical easy-
(The quotations entered on the PN-1 sheet will not be
included on the RE-1 sheet.)
to-read estimate. The remaining 16 pages of the sample estimate (Figs.
The first sheet of the estimate is referred to as the Re- 4-1D-S) list the materials, labor hours, and subcontrac-
capitulation Sheet (Fig. 4-1A). On this sheet the front is tor requirements.
designed to enter all costs associated with the particular As shown, the material pricing is left out purposely
project. The back of the sheet alerts the contractor and/or due to their fluctuations and each contractors buying
estimator to various cost items not shown on the plans but power with their respective suppliers. The labor hours,
that may be required in the project bid documents. however, are included and are based on years of esti-
The second sheet of the estimate, referred to as PN-1 mating experience and applications. Some items of the
(prices needed) (Fig. 4-1B), is the recapitulation of all the estimate need allowances in dollars and/or hours as a
costs sometimes referred to as major materials, equip- project requires. Therefore, each contractor must use
ment, or subcontractors required for the project that are their experience and know-how as to the allowance of
listed in detail on the estimate sheets. The estimated dollars and hours that need to be addressed.
material should be listed along with quotations of costs This sample estimate was prepared using a method
for these materials. When all of the quotations are to- developed over 30 years ago and used very success-
taled, transfer this total to the first sheet of the estimate fully. Follow these few simple rules when preparing
as shown on the sample estimate. your estimates:
The third sheet of the estimate, referred to as RE-1
(recapitulation of the estimate) (Fig. 4-1C), is a list of all 1. Review the scope of your work completely and
of the estimate sheets for the project. Each estimate highlight all items of possible cost.
sheet will have a total of labor hours and the materials 2. Read all the specifications for the project. Not
listed. (NOTE: This sample does not include material only the electrical but all of the other trades
prices due to their fluctuation.) These totals are placed involved in the project. There may be a hint of
accordingly on the RE-1 sheet to be totaled and brought cost that may affect your estimate.

175
176 How to Estimate Electrical Construction Projects

3. Open the plans and confirm that they include all tractor or the estimators immediate superior. This final-
the electrical layouts, a site plan, a utility plan, ization of the estimate will produce the bid amount in-
mechanical plans, architectural plans, riser dia- cluding all of the items on the main cover recapitulation
grams, and all addendums and other bulletins that sheet. This final tally may be adjusted up or down at the
may have been issued. discretion of the contractor.
4. There will be certain projects that will not have a
complete set of plans, specifications, or a scope of Estimators Check Sheet
work. In these cases the contractor should include The following check list will help an estimator in prepar-
in the bid a complete scope of the work that lists ing an estimate and avoid leaving some of the important
all of the work included and excluded prior to items out of the estimate.
contract acceptance.
5 . In seeking answers from a builder, engineer, archi-
0 Review the bidding documents and confirm that
tect, or owner always document the question and all were received.
answer. Follow up with a speedy message con- 0 Forward the insurance and bonding requirements
firming the conversation and keep a copy for the to the proper department in the company.
job file. 0 Notify all suppliers that you have a set of bid doc-
uments and are requesting their quotations.
These simple rules may help a contractor avoid 0 Contact outside subcontractors for their estimates
common pitfalls such as being held responsible for on the project as needed.
work specified in the contract documents that other-
0 Organize the estimate takeoff and in-house pricing
wise may be missed in the estimate. NOTE: In rule #2 it
with the material purchasing department.
is recommended that all specifications be read to deter-
mine if there may be costs that reflect on the estimate. 0 Meet with the shop foreman in regards to the tools
A seasoned estimator will know exactly what sections that may need to be rented or purchased.
of the specifications may have a direct impact on the 0 Estimators will generally begin the takeoff by list-
estimated cost of the project. An example of what can ing all of the materials as shown on the electrical
be skimmed over may be fabrication of the stairs, doors, plans including items such as lighting fixtures,
windows, bricks, etc. You may uncover a cost-saving lamps, switches, receptacles, electrical panels, site
item such as cutting, patching, and painting that may lighting poles and fixtures, life-safety systems,
be included in the general contractors specifications, communications systems, feeders, branch wiring
reinforcement of the suspended ceiling to support the racewaysfcablesfwire, power distribution ducts,
superimposed load of the lighting fixtures, roof open- under floor ducts, and many other visible items.
ings and placement of portals and/or pitch pockets for
the mechanical trades, automatic temperature control A lot of the mistakes that are made in the materials
wiring, and more. So until you read over all of the spec- takeoff are materials that are not shown on the plans
ifications for a project for bid, the estimator is the only and oftentimes overlooked. And if material is over-
one who can effectively ensure that all hidden costs are looked, the associated labor hours that are necessary
included in the estimate. are not entered into the estimate.
Take the time to review the following sample estimate Listed below are some of the job-expense items that
-each estimate sheet, the recapitulation of the estimate are often overlooked.
sheets, the price quotations needed sheet, and finally
the main cover recapitulation sheet. Permit and inspection fees
The estimator should complete the main cover reca- Utility company charges for their services
pitulation sheet with the assistance of either the con- Insurance and bonding charges
Sample Estimate and Forms 177

Temporary electric meter charges Site lighting poles and fixtures


Cleanup Receiving, handling, and storing until installa-
As-built drawings tion (allow for lift to unload)
Rentals Moving poles to place of installation (allow for
Job site drinking water and sanitation facilities boom truck)
Preassemble fixtures on poles on ground and
Storage
test for illumination
Freight and shipping charges
Allow for boom truck to set poles
Travel and room-and-board allowances Allow shims for leveling
Inline fuse holders and fuses
Listed below are some of the materials needed that Building light fixtures
are often overlooked. Receiving, handling, and storing until installa-
tion (if on pallets, allow forklift)
Grounding
Check documents for spare lamp requirements
Transformers
Fixture hangers, supports, and hold-down
Manholes
clips on lay-ins
Site light poles and bases
Inspect for lamps installed at the factory
Distribution panels
Devices, boxes, and plates
Wood-pole installations
Check architects plans for special colors of
Communications stands and racks
devices and plates
Excavation and backfill Include box supports in stud walls (metal and
Machine excavation for trenches wood studs)
Machine backfill
Mechanical equipment
Removal andlor spreading of excess earth
Flexible connections
Hand excavation as needed
Safety disconnect devices and fuses
Sand fill if necessary
Overload heaters for motor protection
Stone base for precast items
Roof-mounted equipment conduit supports
Raceways under ground and portal responsibility
Chairs and spacers Allow testing for and adjusting motor direction
Tie-downs to prevent floating in encased con- if required
crete (PVC conduits) Expendable material allowances
Warning tape-buried utilities Wood-cutting blades
Raceways above ground Metal-cutting blades
Clamps, straps, anchors, fasteners, and hangers Threading oil
Cutting and patching for floor and wall Duct sealant
penetrations Bits for drilling concrete
Wire and cable Drill bits for metal
Wire splicing materials Metal files
Wire labeling Jet line or similar conduit snaking cords and
Cable wedges and insulators air cartridges
Wirelcable testing (high and low voltage) Wire-pulling compound
Allow stud sleeves for multiconductor cables Rags
(armored and plastic covered) Hydraulic fluid
Allow for cable supports and fasteners Silicone sealant for outdoor use
178 How to Estimate Electrical Construction Projects

Although this is not 100% of all unseen items of For the estimator: It is your responsibility to provide
material and labor, it will give an estimator a relatively the best interpretation of all of the project bidding doc-
good idea of the materials that will be required but are uments to the contractor in the form of an estimate.
unseen. The other bidding documents besides the plans Following the sample estimate, blank forms are pro-
will also specify certain materials and labor required vided in duplicate so that you may tear one each from
for the project. the book for use.
Sample Estimate and Forms 179

AS-BUILT DRAWINGS $2,500.00 TOTAL NET COST $549,730.00


INSURANCE FBO 8% PROFIT $43,978.00
WATCHMAN FBO SELLING PRICE (NO BOND) $593,708.00
PRO RATA CHARGES $0.00 BOND COST NIA
TRANSPORTATION, TOLLS, ETC. $450.00 SELLING PRICE (W / BOND) $593,708.00
TELEPHONE AND OFFICE COSTS $1,500.00 FINAL QUOTED PRICE $593,500.00
TOTAL (E) $9,850.00
180 How t o Estimate Electrical Construction Projects

RECAPITULATION 5 HEET (BACK)


1. THE CONTRACTOR MUST INVESTIGATE THE REQUIREMENTS OF EACH GOVERNMENT AGENCY AS IT RELATES TO
SALES TAXES ON BOTH MATERIALS AND LABOR, AND INCLUDE ALL OF THESE COSTS IN EACH PROPOSAL!
2 . Nonproductive labor section contains various areas of costs that are affected by noninstallation labor factors. These
items may or may not apply t o all proposals, but remind the contractor that there may be labor costs beyond the
actual labor cost associated with the project. This may also remind the contractor that there may be other items of
nonproductive labor cost that should be addressed in the proposal.
3. Job expense section contains important direct project-related costs. These dollar costs may or may not be applicable
t o each proposal submitted by the contractor. This may also remind the contractor that there may be additional job-
related expenses to be considered.
4. Labor hour section allows the contractor t o apply different labor rates as they may apply t o the level of grade of the
workers who physically install or direct the installations.
5. Taxes section allows the contractor t o include such taxable items of labor as they may apply t o the project.
6. Overhead section is a cost of doing business for the contractor. This cost may include insurances, office supplies,
postage, contractors building facility, utilities, office personnel payroll, telephone, association fees, periodicals, facil-
ity maintenance, rolling stock upkeep and fuel, rental of office equipment, support programs costs, etc. Include any
other costs that are fixed as they relate to the business inside the contractors facilities.
7. Profit is relative to the size of the proposal and the amount the contractor anticipates.
8. Bond section gives the contractor the ability to include the cost of a bid bond, performance bond, and/or payment
bonds.

Figure 4-1A continued


Sample Estimate and Forms 181

ESTIMATE NO: 234-11/02

JOB: XYZ TECH OFFICE AND WAREHOUSE #J-16 PAGENO: PN-1 OF 1


COMPTON COMPLEX OFFICES AND WAREHOUSING, INC. WARETOWN, MASS 12345-0006
PRICE QUOTATIONS NEEDED
ESTIMATED BY: DENIS SMITH CHCKDBY: MKR DATE: 11-29-02

1
2

3
4
5
6
7
8
9

10
11
12
13
14

15

16
17

18
19

20
21

22
23
24

25
26
27

28

29
30
31
32
"EST ONLY"
TOTAL TOTAL 0
$50,450.00

Figure 4-1B
182 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 234-11/02

JOB: XYZ TECH OFFICE AND WAREHOUSE #J-16 PAGENO: RE-1 OF 1


COMPTON COMPLEX OFFICES AND WAREHOUSING, INC. WARETOWN, MASS 12345-0006
RECAP OF ESTIMATE SHEETS
ESTIMATED BY: DENIS SMITH CHCK'D BY: MKR DATE: 11-29-02

1
2
3
4
5
6
7
8
9
1(
1'
1:
1:
1t

I!
1(

1'
11

l!
21
2
2:
2:
2s
2!
21
2'
21
2!
31 I I 30
3 I Ir 31
3: 32
"EST ONLY"
TOTAL $1 75,000.00 TOTAL 5,309.20

Figure 4-1C
Sample Estimate and Forms 183

30 I I 30
31 I I1 31
32 32

Figure 4-1 D
184 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 234-11/02

JOB: XYZ TECH OFFICE AND WAREHOUSE #J-l6 PAGE NO: 2 OF 16


COMPTON COMPLEX OFFICES AND WAREHOUSING, INC. WARETOWN, MASS 12345-0006
INCOMING SERVICE REQUIREMENTS: DRWG # E-1 RISER & SPEC. SECT. 16
ESTIMATED BY: DENIS SMITH CHCK'D BY: MKR DATE: 11-29-02

1
2

4
5
6
7
8
9

10
11

12

13
14

15

16
17

18
19
20
21

22
23
24
25

26
27

28
29

30
31
32

TOTAL TOTAL 83.4

Figure 4-1E
Sample Estimate and Forms 185

ESTIMATE SHEET ESTIMATE NO: 234-11/02

JOB: XYZ TECH OFFICE AND WAREHOUSE #J-16 PAGE NO: 3 OF 16


COMPTON COMPLEX OFFICES AND WAREHOUSING, INC. WARETOWN, MASS 12345-0006
MDPAND DISTRIBUTION EQUIPMENT, PANELS, TRANSFORMERS: DRWG # E-1 RISER & SPEC SECT.16
ESTIMATED BY. DENIS SMITH CHCKDBY: MKR DATE: 11-29-02

1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32

Figure 4-1F
186 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 234-11/02

JOB: XYZ TECH OFFICE AND WAREHOUSE #J-16 PAGENO: 4 OF 16


COMPTON COMPLEX OFFICES AND WAREHOUSING, INC. WARETOWN, MASS 12345-0006
a E-2 a SPEC SECT. 16
PANELS 8 TRANSFORMERS: DRWG.# E-i
ESTIMATED B Y DENIS SMITH CHCKDBY MKR DATE: 11-29-02

2
3
4
5
6
7

8
9

10
11

12
13
14

15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

Figure 4-1G
Sample Estimate and Forms 187

ESTIMATE SHEET ESTIMATE NO: 234-11/02

JOB: XYZ TECH OFFICE AND WAREHOUSE #J-16 PAGE NO: 5 OF 16


COMPTON COMPLEX OFFICES AND WAREHOUSING, INC. WARETOWN, MASS 12345-0006
FEEDERS PER ONE LINE DIAGRAM ON DRWG # E-1 8. E-2 & SPEC SECT.16
ESTIMATED BY: DENIS SMITH CHCK'DBY MKR DATE: 11-29-02

1
2
3
4

5
6

7
8

9
10
11
12

13
14

15

16
17
18
19
20
21

22
23

24

25
26
27

28
29
30 / 30
31 31
/ 32
32

Figure 4-1H
188 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 234-11/02

JOB: XYZ TECH OFFICE AND WAREHOUSE #J-16 PAGENO: 6 OF 16


COMPTON COMPLEX OFFICES AND WAREHOUSING, INC. WARETOWN, MASS 12345-0006
FEEDERS PER ONE LINE DIAGRAM ON DRWG # E-1 & E-2 & SPEC SECT.16
ESTIMATED BY: DENIS SMITH CHCKDBY MKR DATE: 11-29-02

DESCRIPTION OF MATERIALS MATERIALS LABOR HOURS


QUANTITY UNITCOST PER AMOUNT UNIT PER AMOUNT
1 8" X 8" X 4EWWIREWAY NEMA 1 SCREW COVER 2 EA 1.6 EA 3.2 1

2 8" X 8" BLANK END FllTlNG 4 EA 0.1 EA 0.4 2

3 4' X 4' X lip" INDOOR PLYWOOD 8 SUPPORTS 2 EA 1 EA 2 3

4 4

5 5
6 6
7 7
8 8
9 9
1( 10
1' 11
1: 12

1: 13

1 d 14
l! 15

11 16
1' 17
11 18
l! 19
21 20
2 21
2:
2:
2,
2!
21
2
21

2!
31
3
3
~~ ~ ~-

TOTAL ~ ~~
TOTAL 351.2

Figure 4-1I
Sample Estimate and Forms 189

ESTIMATE SHEET ESTIMATE NO: 234-11/02

JOB: XYZ TECH OFFICE AND WAREHOUSE #J-16 PAGENO: 7 OF 16


COMPTON COMPLEX OFFICES AND WAREHOUSING, INC. WARETOWN, MASS 12345-0006
TELEPHONE SERVICE CONDUITTO BUILDING PER DRWG # E-1 AND SPEC SECT. 16

1
2

5
6
7
8
9
1

1
1
1
1
1

1
2

2
2
2
2
2
2

2
2 I I 29
3 I I 30
3 I I 31
3 32

TOTAL TOTAL 17.55 ~

Figure 4-1J
190 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 234-11/02

JOB: XYZ TECH OFFICE AND WAREHOUSE #J-16 PAGE NO: 8 OF 16


COMPTON COMPLEX OFFICES AND WAREHOUSING, INC. WARETOWN, MASS 12345-0006
PLUG-IN COPPER BUS DUCT 8 PLUG-IN CIRCUIT BREAKERS PER DRWG # E-3AND SPEC SECT. 16
ESTIMATED B Y DENlS SMITH CHCK'D BY: MKR DATE: 11-29-02

DESCRIPTIONOF MATERIALS MATERIALS I 1


QUANTITY 1 I
UNITCOST PER1 AMOUNT I UNIT
1 225 AMP 3 0 3W CU 480V PLUG-IN DUCT WlGND BUS loo'
2 ( INSTALL DUCT AT 18' HGT. AFF)
3 END CABLE TAP BOX FOR FEED IN TO DUCT 1
4 60 AMP 3 POLE 3W 48OV 8 GND PLUG-IN CB 1
5 40 AMP 3 POLE 1
6 30 AMP 3 POLE 2
7 20 AMP 3 POLE v 2
8 DUCT HANGER CLAMPS 0 5' INTERVALS 21 10.5
9 DUCT SPRING SUPPORTS 21 28.35
1 SINGLE ROD AND FASTNER FOR DUCT HANGERS 21 AL 1.55 32.55
1

1
1

1
1
1

1
1

2
2
2
2
2
2
2

2
2

2
3
3
3

Figure 4-1K
Sample Estimate and Forms 191

ESTIMATE SHEET ESTIMATE NO: 234-11/02

JOB: XYZ TECH OFFICE AND WAREHOUSE #J-16 PAGE NO: 9 OF 16


COMPTON COMPLEX OFFICES AND WAREHOUSING, INC. WARETOWN, MASS 12345-0006
BRANCH CIRCUIT WIRING PER DRWG # E-2 THRU E-6AND SPEC SECT. 16
ESTIMATED BY: DENIS SMITH CHCK'D BY: MKR DATE: 11-29-02

I TOTAL I 962.95 I
Figure 4-1L
192 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 234-11/02

JOB: XYZ TECH OFFICE AND WAREHOUSE #J-l6 PAGENO: 10 OF 16


COMPTON COMPLEX OFFICES AND WAREHOUSING, INC. WARETOWN, MASS 12345-0006
BRANCH CIRCUIT WIRING PER DRWG # E-2 THRU E-6 AND SPEC SECT. 16
ESTIMATED BY: DENlS SMITH CHCK'D BY: MKR DATE: 11-29-02

29 I
30 I I
31 I I
I
32

I TOTAL
I TOTAL 872.5

Figure 4-1 M
Sample Estimate and Forms 193

ESTIMATE SHEET ESTIMATE NO: 234-11/02

JOB: XYZ TECH OFFICE AND WAREHOUSE #J-l6 PAGE NO: 11 OF 16


COMPTON COMPLEX OFFICES AND WAREHOUSING, INC. WARETOWN, MASS 12345-0006
SITE LIGHTING REQ'S PER DRWG # PHE-1, E-1 AND SPEC SECT. 16
ESTIMATED BY: DENIS SMITH CHCKDBY MKR DATE: 11-29-02

7 7' X 30" RND CONCRETE BASES (3'AFG) (PRECAST) 24 3 EA 72 1


8 8
9 9
10 10

11 11

12 12
13 I?
1
1
114
1 15

1 16

1 17

1 18

1 19

2 20

2 21

2 22

2 23

2 24

2 25

2 26

2 27

2 28

31 31
/ c 32
32

TOTAL TOTAL 465.8


194 How to Estimate Electrical ConstructionProjects

ESTIMATE SHEET ESTIMATE NO: 234-11/02

JOB: XYZ TECH OFFICE AND WAREHOUSE #J-16 PAGE NO: 12 OF 16


COMPTON COMPLEX OFFICES AND WAREHOUSING, INC. WARETOWN, MASS 12345-0006
LIGHTING FIXTURES PER DRWG # E-3 THRU E-6 AND SPEC SECT. 16
ESTIMATED BY DENIS SMITH CHCKDBY: MKR DATE: 11-29-02

1
2

3
4

6
7

8
9

10
11

12
13
14

15
16
17

18
19
20
21

22

23

24
25
26
27

28
29
30
31
32

Figure 4-10
Sample Estimate and Forms 195

ESTIMATE SHEET ESTIMATE NO: 234-11/02

JOB: XYZ TECH OFFICE AND WAREHOUSE #J-16 PAGENO: 13 OF 16


COMPTON COMPLEX OFFICES AND WAREHOUSING, INC. WARETOWN, MASS 12345-0006
DEVICES, BOXES, & PLATES PER DRWG # E-2 THRU E-6 AND SPEC SECT. 16
ESTIMATED BY: DENlS SMITH CHCK'D BY: MKR DATE: 11-29-02

1
2

6
7
8
9
10
11

12
13
14

15
16
I?
18
19

20

21

22
23

24
25
26
27

28

29
30

31 I I I I/ I / 31
32 32

Figure 4-1P
196 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 234-11/02

JOB: XYZ TECH OFFICE AND WAREHOUSE #J-16 PAGENO: 14 OF 16


COMPTON COMPLEX OFFICES AND WAREHOUSING, INC. WARETOWN, MASS 12345-0006
VOICE & DATA COMMUNICATIONS WIRING REQUIREMENTS PER DRWG # E-3 & E-4 PER SPEC SECT 16
ESTIMATED BY: DENIS SMITH CHCK'D BY: MKR DATE: 11-29-02

1
2
3
4
5

6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

Figure 4-14
Sample Estimate and Forms 197

ESTIMATE SHEET ESTIMATE NO: 234-11/02

JOB: XYZ TECH OFFICE AND WAREHOUSE #J-16 PAGE NO: 15 OF 16


COMPTON COMPLEX OFFICES AND WAREHOUSING, INC. WARETOWN, MASS 12345-0006
FIRE ALARM SYSTEM REQUIREMENTS PER DRWG # E-2 THRU E-5 AND SPEC SECT. 16
ESTIMATED BY: DENIS SMITH CHCKDBY: MKR DATE: 11-29-02

3
4

5
6
7

8
9

10
11

12
13
14

15
16
17
- 18
19

20

21
22

23
24

25
26

27
28
29

30 I I 30

31
32
I I
I
31
32

Figure 4-1R
198 How to Estimate Electrical Construction Projects

ESTIMATE SHEET ESTIMATE NO: 234-11/02

JOB: XYZ TECH OFFICE AND WAREHOUSE #J-16 PAGENO: 16 OF 16


COMPTON COMPLEX OFFICES AND WAREHOUSING, INC. WARETOWN, MASS 12345-0006
MECHANICAL EQUIPMENT REQUIREMENTS PER DRWG # E-2 THRU E-5 PER SPEC SECT. 16
ESTIMATED BY: DENIS SMITH CHCK'D BY: MKR DATE: 11-29-02

1
2
3
4

6
7
8
9
10
11

12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

Figure 4-15
RECAPITULATION SHEET ESTIMATE NO:

JOB SHEETNO: OF

ESTIMATED BY CHECKED BY DATE:

SHEETNO I ESTIMATE SHEETS DESCRIPTION $ MATERIAL I HOURS


I I I

I I I

AS-BUILT DRAWINGS TOTAL NET COST


INSURANCE % PROFIT
WATCHMAN SELLING PRICE (NO BOND)
PRO RATA CHARGES BOND COST
TRANSPORTATION, TOLLS, ETC. SELLING PRICE (W I BOND)
TELEPHONE AND OFFICE COSTS FINAL QUOTED PRICE
TOTAL (B)
I
RECAPITULATION SHEET (BACK)
1. THE CONTRACTOR MUST INVESTIGATE THE REQUIREMENTS OF EACH GOVERNMENT AGENCY AS IT RELATES TO
SALES TAXES ON BOTH MATERIALS AND LABOR, AND INCLUDE ALL OF THESE COSTS IN EACH PROPOSAL!
2 . Nonproductive labor section contains various areas of costs that are affected by noninstallation labor factors. These
items may or may not apply to all proposals, but remind the contractor that there may be labor costs beyond the
actual labor cost associated with the project. This may also remind the contractor that there may be other items of
nonproductive labor cost that should be addressed in the proposal.
3. Job expense section contains important direct project-related costs. These dollar costs may or may not be applicable
to each proposal submitted by the contractor. This may also remind the contractor that there may be additional job-
related expenses t o be considered.
4. Labor hour section allows the contractor t o apply different labor rates as they may apply t o the level of grade of the
workers who physically install or direct the installations.
5. Taxes section allows the contractor t o include such taxable items of labor as they may apply to the project.
6. Overhead section is a cost of doing business for the contractor. This cost may include insurances, office supplies,
postage, contractor's building facility, utilities, office personnel payroll, telephone, association fees, periodicals, facil-
ity maintenance, rolling stock upkeep and fuel, rental of office equipment, support programs costs, etc. Include any
other costs that are fixed as they relate t o the business inside the contractor's facilities.
7. Profit is relative to the size of the proposal and the amount the contractor anticipates.
8. Bond section gives the contractor the ability t o include the cost of a bid bond, performance bond, and/or payment
bonds.
RECAPITULATION SHEET ESTIMATE NO:
JOB SHEETNO: OF

ESTIMATED BY CHECKED BY DATE:


RECAPITULATION SHEET (BACK)
1. THE CONTRACTOR MUST INVESTIGATE THE REQUIREMENTS OF EACH GOVERNMENT AGENCY AS IT RELATES TO
SALES TAXES ON BOTH MATERIALS AND LABOR, AND INCLUDE ALL OF THESE COSTS IN EACH PROPOSAL!
2 . Nonproductive labor section contains various areas of costs that are affected by noninstallation labor factors. These
items may or may not apply to all proposals, but remind the contractor that there may be labor costs beyond the
actual labor cost associated with the project. This may also remind the contractor that there may be other items of
nonproductive labor cost that should be addressed in the proposal.
3. Job expense section contains important direct project-related costs. These dollar costs may or may not be applicable
t o each proposal submitted by the contractor. This may also remind the contractor that there may be additional job-
related expenses to be considered.
4. Labor hour section allows the contractor to apply different labor rates as they may apply t o the level of grade of the
workers who physically install or direct the installations.
5. Taxes section allows the contractor to include such taxable items of labor as they may apply t o the project.
6. Overhead section i s a cost of doing business for the contractor. This cost may include insurances, office supplies,
postage, contractor's building facility, utilities, off ice personnel payroll, telephone, association fees, periodicals, facil-
ity maintenance, rolling stock upkeep and fuel, rental of office equipment, support programs costs, etc. Include any
other costs that are fixed as they relate to the business inside the contractor's facilities.
7. Profit is relative to the size of the proposal and the amount the contractor anticipates.
8. Bond section gives the contractor the ability to include the cost of a bid bond, performance bond, and/or payment
bonds.
ESTIMATE SHEET ESTIMATE NO:

JOB: PAGE NO: OF

31 31

32 32

TOTAL TOTAL
ESTIMATE SHEET ESTIMATE NO:

JOB: PAGE NO: OF

ESTIMATED BY: CHCKD BY: DATE:

DESCRIPTION OF MATERIALS MATERIALS LABOR HOURS


QUANTITY I UNIT COST IPERI
AMOUNT UNIT I PERI AMOUNT
1 I I 1 I I
CHANGE ORDER RECAPITULATION SHEET

CUSTOMER PROJECT
DATE JOB NO. C.O. NO.

8- TEMPORARY LIGHT & POWER


9- ACCEPTANCE TESTING
10- ESTIMATING & BREAKDOWN

15- TRUCKING ON SITE


16- STORAGE
17- TOOL FACTOR (1Yo OF LINE 3)
18- CLEAN UP (lo% OF LINE 6)
19- HOISTING / LIFTING
20- RENTAL EQUIPMENT
21- PERMIT Yo INSPECTION FEES
TOTAL COST--------
Total Jrnyrnn hrs @----- % OVERHEAD-----
" Forrnan hrs @---- SUBTOTAL-----------
" Super'nt hrs @--- % PROFIT ____________
TOTAL LABOR-------------- C.O. PRICE----------
(ENTER ON LINE 6 ABOVE)

I
CHANGE ORDER RECAPITULATION SHEET

CUSTOMER PROJECT
DATE JOB NO. C.O.NO.

~~

1- RIGGING CHARGES
2-EQUIPMENT
3- MATERIALS
4-SUNDRIES (5%OF LINE 3)
5- SALES TAXES I
6- LABOR (SEE BELOW)
7-SUPERVISION (IOYo OF LINE 6)
8- TEMPORARY LIGHT & POWER
9- ACCEPTANCE TESTING
10- ESTIMATING & BREAKDOWN
1 1 - BLUEPRINT CHARGES
12-ENGINEERING & COORDINATION (3%OF LINE 6)
13- INSURANCE COVERAGE
14-DELAY IMPACT
15- TRUCKING ON SITE
16- STORAGE
17-TOOL FACTOR (I Yo OF LINE 3)
18- CLEAN UP (lo/o OF LINE 6)
19- HOISTING / LIFTING
20- RENTAL EQUIPMENT
21 - PERMIT Yo INSPECTION FEES
TOTAL COST--------
Total Jrnymn hrs @----- o
/'OVERHEAD-----
" Forman hrs Q---- SUBTOTAL-----------
" Super'nt hrs Q--- Oo
/ ____________
PROFIT
TOTAL LABOR-------------- C.O. PRICE----------
(ENTER ON LINE 6 ABOVE)
EST. NO: ROUGH TAKEOFF SHEET SHEET NO: OF:
T
EST. NO: FEEDER SCHEDULE SHEET NO: -OF-
JOB: DATE:
EST. NO: FEEDER SCHEDULE SHEET NO: -OF-
JOB: DATE:
CONTRACTOR NAME: DATE:

PROJECT NAME:

PROJECT LOCATION:

REQUEST FOR INFORMATION (RFI)


TO:

SENDER: TEL#:

SIGNATURE: DATE:

REQUEST FOR INFORMATION (RFI)


1. The RFI is an important tool for both the contractor and others who are involved in the project. Too many times
phone calls and undocumentedconversations lead to major disagreements that may involve large sums of money.
2. The RFI is used to document all questions and/or clarifications sought by the party issuing the RFI, thus avoiding the
possibility of serious consequences.
3. The RFI can be used during the bidding phase as well as the construction phase of the project.
4. The recipient of the RFI is requested to respond to the information sought by the sender.
CONTRACTOR NAME: DATE:

PROJECT NAME:

PROJECT LOCATION:

REQUEST FOR INFORMATION (RFI)


TO:

SUBJECT

INFORMATION REQUESTED:

SIG NATU RE: DATE:

REQUEST FOR INFORMATION (RFI)


1. The RFI is an important tool for both the contractor and others who are involved in the project. Too many times
phone calls and undocumented conversations lead t o major disagreements that may involve large sums of money.
2 . The RFI is used t o document all questions and/or clarifications sought by the party issuing the RFI, thus avoiding the
possibility of serious consequences.
3. The RFI can be used during the bidding phase as well as the construction phase of the project.
4. The recipient of the RFI is requested t o respond t o the information sought by the sender.
CONTRACTOR NAME:
STREET ADDRESS:
CITY: STATE: ZIP CODE:
LICENSE #: STATE PERMIT #: LOCAL PERMIT #:
PHONE #: FAX #: EMAIL:

WORK AUTHORIZATION FORM


This authorization is accompanied by the Time and Material Sheet(s) that will be filled out
at the completion of each day that work is performed. The accompanying Time and Material
Sheet(s) are to be approved on a daily basis by the authorizing party. At the completion of
the authorized work, the contractor will issue an invoice for the work at the authorized hourly
rate of charge and the material cost plus the authorized percentages for overhead and profit.

This is your authorization to perform the following work:

Work to be performed:

Hourly Rate per Worker: Superintendent $ Foreman $ Journeyman $


Other worker as applicable $

Percentages for overhead: % Profit: % (plus applicable taxes)

Authorized By:
Address:
Phone #:

Signature: Date:
SEE BACK FOR ADDITIONAL CONDITIONS
WORK AUTHORIZATION FORM (BACK)
1. This form is required to be filled out completely by the contractor's foreman prior t o any work being performed.
2 . This work authorization form will be accompanied by daily time and material sheets.
3. By authorizing the work to be performed, which is described on the front of this sheet, the authorizing authority
agrees to all the conditions set forth herein.
4. The hourly rate of charge is "portal to portal," per worker, per hour for performing the work described on the front
of this sheet.
5 . The percentages as shown on the front of this sheet will apply for all of the materials necessary to perform the work
as indicated and authorized on the front of this sheet. (Applicable taxes will be added as required.)
6. The percentages as shown on the front of this sheet will also apply for materials that need t o be ordered from a sup-
ply company in order to complete the work as described on the front of this sheet.
7. The percentages as shown on the front of this sheet do not apply t o the hourly rate of charge for workers.
8. A copy of this authorization will accompany the contractor's invoice for payment a t the completion of the work.
NOTE: If the work extends beyond 30 days from the time the authorization t o begin the work is received, the con-
tractor may issue a partial invoice for the work completed within those 30 days.
9. This form should be filled out in triplicate: original and one copy for the contractor, and a third copy for the customer.
CONTRACTOR NAME:
STREET ADDRESS:
CITY: STATE: ZIP CODE:
LICENSE #: STATE PERMIT #: LOCAL PERMIT #:
PHONE #: FAX #: EMAIL:

WORK AUTHORIZATION FORM


This authorization is accompanied by the Time and Material Sheet(s) that will be filled out
at the completion of each day that work is performed. The accompanying Time and Material
Sheet(s) are to be approved on a daily basis by the authorizing party. At the completion of
the authorized work, the contractor will issue an invoice for the work at the authorized hourly
rate of charge and the material cost plus the authorized percentages for overhead and profit.

This is your authorization to perform the following work:

Work to be performed:

Hourly Rate per Worker: Superintendent $ Foreman $ Journeyman $


Other worker as applicable $

Percentages for overhead: % Profit: % (plus applicable taxes)

Authorized By:
Address:
Phone #:

Signature: Date:
SEE BACK FOR ADDITIONAL CONDITIONS
WORK AUTHORIZATION FORM (BACK)
1. This form is required to be filled out completely by the contractor's foreman prior to any work being performed.
2 . This work authorization form will be accompanied by daily time and material sheets.
3. By authorizing the work to be performed, which is described on the front of this sheet, the authorizing authority
agrees to all the conditions set forth herein.
4. The hourly rate of charge is "portal to portal," per worker, per hour for performing the work described on the front
of this sheet.
5 . The percentages as shown on the front of this sheet will apply for all of the materials necessary t o perform the work
as indicated and authorized on the front of this sheet. (Applicable taxes will be added as required.)
6. The percentages as shown on the front of this sheet will also apply for materials that need to be ordered from a sup-
ply company in order to complete the work as described on the front of this sheet.
7. The percentages as shown on the front of this sheet do not apply to the hourly rate of charge for workers.
8. A copy of this authorization will accompany the contractor's invoice for payment a t the completion of the work.
NOTE: If the work extends beyond 30 days from the time the authorization to begin the work is received, the con-
tractor may issue a partial invoice for the work completed within those 30 days.
9. This form should be filled out in triplicate: original and one copy for the contractor, and a third copy for the customer.
TIME AND MATERIAL WORK ORDER

CONTRACTOR----. LIC# PERMIT#: CUSTOMER


NAME: VAME:
ADDRESS: ADDRESS:

PHONE#: FAX#: PHONE#: FAX#:

I I I I

MATERIAL USED QUANTITY $ PRICE EACH $TOTAL PRICE


I I

I $
TOTAL JOURNEYMAN HOURS Q------ $ PER HR=$ MATERIAL COST $
TOTAL FORMAN HOURS @------------. $ PER HR=$ LABOR COST $
TOTAL SUPERINTENDENT HRS 0------- $ PER HR=$ RENTAL COST $
OTHER HRS 0- $ PER HR=$ TAX $
TOTAL LABOR COST $ TOTAL COST $

WORKER CLASS: S/SUPERINTENDENT F/FORMAN J/JOURNEYMAN


APPROVED BY: DATF, ""'SEE BACK FOR ADDITIONAL CONDITIONS""'
TIME AND MATERIAL WORK ORDER (BACK)
1. The work will not commence until the work authorization form is completed by the party requesting the work t o be
performed. (Refer to the Work Authorization Form.)
2 . This Time and Material Sheet will be filled out on a daily basis by the contractor's workers and approved by the
recipient of these services on a daily basis.
3. This sheet details the labor and materials charges as agreed to in the Work Authorization Form.
4. The contractor will include copies of the Time and Material Sheet and the Work Authorization Form with each
invoice.
5. This form should be filled out in triplicate: original and one copy for the contractor, and a third copy for the customer.
TIME AND MATERIAL WORK ORDER

CONTRACTOR----- LIC#: PERMITI: CUSTOMER


NAME: VAME:
ADDRESS: ADDRESS:

I -r- I I I

MATERIAL USED QUANTIlY $ PRICE EACH $TOTAL PRICE

$ $

$ $

TOTAL JOURNEYMAN HOURS 0------- $ PER HR=$ MATERIAL COST $

TOTAL FORMAN HOURS O-i---------- -$ PER HR=$ LABOR COST $


TOTAL SUPERINTENDENT HRS @I-------
$ PER HR=$ RENTAL COST $
OTHER HRS 0- $ PER HR=$ TAX $
TOTAL LABOR COST $ TOTAL COST $
WORKER CLASS': S/SUPERINTENDENT F/FORMAN J/JOURNEYMAN
APPROVED BY DATF, ""'SEE BACK FOR ADDITIONAL C O N D I T I O N S
TIME AND MATERIAL WORK ORDER (BACK)
1. The work will not commence until the work authorization form is completed by the party requesting the work to be
performed. (Refer to the Work Authorization Form.)
2. This Time and Material Sheet will be filled out on a daily basis by the contractor's workers and approved by the
recipient of these services on a daily basis.
3. This sheet details the labor and materials charges as agreed to in the Work Authorization Form.
4. The contractor will include copies of the Time and Material Sheet and the Work Authorization Form with each
invoice.
5. This form should be filled out in triplicate: original and one copy for the contractor, and a third copy for the customer.