Quick Start Guide... PL1000E Communication


ECM Caterpillar

Modbus Parameter Translation and ECM Configuration Quick


Start Guide
The checklist that is in this section provides information for implementing and for configuring
Modbus parameter translations with the use of the PL1000E ECM. Each step or procedure in the
checklist references the appropriate section(s) of this System Operation Troubleshooting Testing
and Adjusting, RENR8091, "PL1000E Communication ECM" that explains the detail of the
respective procedure.

Gathering Information for PL1000E Commissioning


Preparation for Commissioning PL1000E
1. Identify the type of "Programmable Logic Controller" (PLC) that is being used.
2. Verify that the PLC supports the native Modbus, NOTModbus+.
3. Verify that the PLC is a Modbus Master that is capable of requesting
registers 40,001 through 42,000.
4. Identify the protocol that is required for the Modbus. (TCP, RS-232, RS-485 (4 wire), RS-485
(2 wire), and RS-422).
5. Verify the baud rate for the serial port.
6. Identify the Modbus slave address in the PL1000E that the "Master" will request the
information from.
7. If applicable, locate the unused Modbus slave address for the internal housekeeping.
8. Verify that the PL1000E is connected to a network.
9. Identify the type of network addressing that is currently being used.
Note: The address type will be either "Dynamic Host Configuration Protocol" (DHCP) or
"Static" addressing.
i. Locate the "Static" address information.
ii. Verify the "Internet Protocol" IP Address.
iii. Verify the Subnet Address.
iv. If applicable, depending on the network, verify the Gateway Address.

Caterpillar Dealer Questions


1. Verify all of the Cat Data Link ECM addresses.
Note: The ECM address depends on the type of engine that is being used. To locate the
ECM address, log onto Cat ET. Initially, ECM addresses may be in hexadecimal format, and
will need to be converted into decimal format for the Parameter Translation Editor.
https://avspare.com/catalog/cat/content/i02428891/ 1/5
8/8/2017 Quick Start Guide... PL1000E Communication ECM Caterpillar | Spare parts

2. Locate the data link that the information is on from each ECM and the starting registers.

System Block Diagram


Refer to Illustration 1 for the system block diagram.

Transferring System Block Diagram to PCL Editor


1. Ensure that each Caterpillar ECM is defined. Ensure that each ECM has the correct address.
2. Verify all Modbus ECMs, and that each Modbus ECM has the correct Modbus slave ID.
Note: The PL1000E has two Modbus slave addresses. The Modbus slave address that is
configured in the PCL file is the address the Modbus Master uses in order to retrieve engine
information. The Modbus slave address that is configured in Cat ET, Caterpillar
Communication Tool Kit, or through the web server, is for the PL1000E's internal statistics.
3. Define all of the translation lines from the Caterpillar ECMs to the Modbus ECMs.
4. Select the NEEDED parameters on each translation line.
Note: The Modbus registers that are associated with each parameter are shown in the right
hand column.
Note: All of the parameters that are in the General Parameter Translation Editor (PTE) files
may not be supported.
5. Ensure that each defined ECM has a unique "ECM ID".
Note: Please review the parameter list report for scaling.
6. Save a ".CSV" file from each translation line. This will be given to the PLC integrator.
7. Save the PCL file to a computer.

Items During Commissioning


1. Wire the PL1000E for use with the PLC. Refer to "Caterpillar Dealer Questions" for
instructions about the required connections for the PLC.
2. Upload the PCL file into the PL1000E via FTP. Use the "IP" address or "Internet Host Name".
The "IP" address or "Internet Host Name" are both defined in the "Configuration" screen in
Cat ET. The default username and the password are both "admin". Check the ECM mapping
screen for correct addresses and for correct Modbus slave addresses.
3. Verify that the PL1000E is communicating the correct data.
4. Locate a parameter that is in a Cat ET status screen. Check for accuracy between the PCL
file and Cat ET.
5. Verify that there are no problems with the communications. Modify the PCL file in order to
send the data to a RS-232 port. Check to make sure the data is being sent by the PL1000E.

Develop A System Block Diagram


Show/hide table

Begin by making a sketch of the system diagram. The system diagram should identify each ECM
that is in the system. The system diagram should identify each ECM communication type.
Refer to the sample of a system diagram that is shown in Illustration 1. Illustration 1 provides an
explanation and a description of each electronic control that is used. There is certain information
that is needed about each device in order to perform the integration successfully.

https://avspare.com/catalog/cat/content/i02428891/ 2/5
8/8/2017 Quick Start Guide... PL1000E Communication ECM Caterpillar | Spare parts

The system diagram that is shown in Illustration 1 is a generic example that could be used for an
application. Each system may vary depending on the components and on the interfaces that the
system contains.

Caterpillar Electronic Control Numbers 1, 2, and 3


The control numbers can represent an engine control, a combustion module, or other electronic
devices that exist in the Caterpillar application.
Required Information and Tools:
Package or Engine Serial Number
Parameter Translation Editor PTE file
Data Link Addresses
Note: The PTE file should be located on same Compact Disc (CD) with the PL1000E information.
If the PTE file is not included, then contact local Caterpillar dealer.
Note: For "Data Link Addresses" information, refer to the System Operation Troubleshooting,
Testing and Adjusting, RENR8091, "Data Link Address of Caterpillar Electronic Control".

PL1000E Communication ECM


The PL1000E Communication ECM is designed specifically for communication translations from
Caterpillar electronic controls.
Required Information and Tools:
Modbus Port Configuration
Caterpillar Communication Tool Kit or Caterpillar ET 2007B or later
List of Requested Parameters
Modbus and PL1000E Modbus Slave Address

Modbus Master Device


This device may be any industry available Modbus communications device so long as it meets the
following criteria:
Capable of Modbus communications over RS-232, RS-422, RS-485 (4 wire) and RS-485 (2
wire) or Ethernet
Modbus Protocol communications designed in accordance with Modbus Application
Protocol Specification V1.1a
Capable of requesting single and multiple Modbus registers in the range
of 40,001 through 42,000

Prepare the PCL File


Use the Caterpillar Communications Tool Kit or Caterpillar Electronic Technician (Cat ET) in order
to prepare the PCL file as described in this document.
Refer to the System Operation Troubleshooting Testing and Adjusting, RENR8091, "PL1000E
Communication ECM", "Parameter Translation Configuration" section.
Refer also to the System Operation Troubleshooting Testing and Adjusting, RENR8091, "PL1000E
Communication ECM", "Create Parameter Translation Design" section.
https://avspare.com/catalog/cat/content/i02428891/ 3/5
8/8/2017 Quick Start Guide... PL1000E Communication ECM Caterpillar | Spare parts

In the PCL design window, each Caterpillar electronic control from the system block diagram would
be represented by a CDL or a J1939 ECM Object. Each Caterpillar electronic control from the
system block diagram will require a PTE file association. The PL1000E Modbus interface would be
represented by a Modbus ECM. The translations are defined by the "Translation Lines". The
"Translation Lines" are defined by the CDL or J1939 ECM, and by the Modbus ECM.

Contact Network Administrator


Each network is different. Each network requires slightly different configurations. The configuration
is dependent upon the hardware and the software that is used in order to configure, manage, and
maintain the system's servers.
If the embedded web server of the PL1000E Communication ECM's is to be accessible over a
local network, then the local network administrator should be contacted in order to obtain the
appropriate configurations. The factory default setting for the PL1000E is "Dynamic Host
Configuration Protocol" (DHCP).
In order to change from the DHCP setting, refer to the System Operation Troubleshooting Testing
and Adjusting, RENR8091, "PL1000E Communication ECM", "Internet Protocol Configuration"
section.

Configure the PL1000E


The Modbus communications must be configured in the PCL file. The Modbus communications
must also be configured separately in the configuration screen of Cat ET.
Refer to the "Modbus Configuration" section of this document in order to determine the appropriate
configurations for the system. The ethernet port is used to transfer the PCL file to the PL1000E.
The ethernet port can be configured with Cat ET or Caterpillar Communication Toolkit.
If the embedded web server is to be used, then the embedded web server must also be initially
configured using Cat ET. Refer to System Operation Troubleshooting Testing and Adjusting,
RENR8091, "PL1000E Communication ECM", "Internet Protocol Configuration" for the appropriate
configurations for the system.
Note: Configuration of the PL1000E Communication ECM and preparation of the PCL file may be
completed prior to the actual installation at the system site. The PL1000E Communication ECM
does not need to be connected to the Caterpillar electronic controls in the system in order to allow
proper configurations, PCL file creation, or PCL file installation.

Install the PCL File onto the PL1000E


Note: The PL1000E must be configured before installation of the PCL file.
There are several different methods that can be used in order to install the PCL file, however, all of
the methods must be executed using "File Transfer Protocol" FTP over the ECM's ethernet
connection. After the PCL file has been successfully installed on the ECM, the module is ready for
installation. Also, the module is ready for integration with the other Caterpillar electronic controls
and the Modbus master.
Refer to the "LAN Network Ethernet Connection" section and to the "PL1000E Communication
ECM" section of this document for information about connection methods.
Also, refer to System Operation Troubleshooting Testing and Adjusting, RENR8091, "PL1000E
Communication ECM", "Direct Crossover Ethernet Connection" section.

https://avspare.com/catalog/cat/content/i02428891/ 4/5
8/8/2017 Quick Start Guide... PL1000E Communication ECM Caterpillar | Spare parts

Install the Necessary Infrastructure to Integrate the


PL1000E Into A System
Refer to Special Instruction, REHS2362 for installation and wiring requirements of the PL1000E
Communication ECM.

Validate Successful Communications of the


PL1000E to Caterpillar Electronic Controls
Using either the embedded communication adapter of the ECM or other external communication
adapters, verify that the service tool can successfully detect all Caterpillar electronic controls in the
system.

Validate Successful Modbus Communications of the


PL1000E to the Modbus Master
Configure or program the Modbus master to request any or all of the status and statistics Modbus
registers from the ECM. In order to retrieve the standard and statistics Modbus register data, the
ECM Modbus slave address that is defined in the Modbus configuration through the Cat ET,
Caterpillar Communication Toolkit (the ECM configuration), or embedded web pages must be
used.
Alternately, configure or program the Modbus master in order to request any of the Modbus
registers that are defined in the PCL file for one of the Caterpillar electronic controls in the system.
In order to retrieve the Modbus registers from the other Caterpillar electronic controls in the
system, the ECM Modbus slave address that is defined in the PCL file must be used.
This is the end of "Quick Start Guide".