Solution:

Refer to the Figure 1 for the substation system.

Section B power rating is, Sb 75 MVA


Substation operating voltage is, Vb 33 kV
Short circuit capacity (SCC) or short circuit level (SCL) in per unit (p.u.) quantity is,
750 MVA
SCL 10 pu
75 MVA
Generators reactance in per unit at the section A is,
75 MVA
X G 15%
15 MVA
0.15 5
0.75 pu
The impedance diagram is shown in the Figure 2 below.

Short circuit level (SCL) in per unit (p.u.) quantity is,


1 1 1 1 1
SCL
X th X 0.08 0.75 0.75 0.75
1
10 pu 1.333 3
X 0.08
1
10 pu 4
X 0.08
1
10 4 6 pu
X 0.08
1
X 0.08 0.167
6
X 0.167 0.08 0.087 pu
V 2 33 kV
2
332
Base impedance is, Zb b
Sb 75 MVA 75
The reactance of the reactor is,
332 1089
X 0.087 pu 0.087 pu 0.087 pu 14.52
75 75
X 1.263 pu