Substation operating voltage is, Vb 33 kV Short circuit capacity (SCC) or short circuit level (SCL) in per unit (p.u.) quantity is, 750 MVA SCL 10 pu 75 MVA Generators reactance in per unit at the section A is, 75 MVA X G 15% 15 MVA 0.15 5 0.75 pu The impedance diagram is shown in the Figure 2 below.
Short circuit level (SCL) in per unit (p.u.) quantity is,
1 1 1 1 1 SCL X th X 0.08 0.75 0.75 0.75 1 10 pu 1.333 3 X 0.08 1 10 pu 4 X 0.08 1 10 4 6 pu X 0.08 1 X 0.08 0.167 6 X 0.167 0.08 0.087 pu V 2 33 kV 2 332 Base impedance is, Zb b Sb 75 MVA 75 The reactance of the reactor is, 332 1089 X 0.087 pu 0.087 pu 0.087 pu 14.52 75 75 X 1.263 pu