xii) Minimum creepage distance 31mm/kV

xiii) Degree of protection IP-55

3.2.15.3 Surge Monitor


i). Surge monitor connected in series between the lightning arrestors and ground shall be
provided to determine the service performance and on-line condition of the lightning
arrestors.
ii). Surge monitor shall include counter with ammeter to record the number of operation
and healthiness performed by the arrestor.
iii). To monitor health of arrestor, diagnostics and alarms.

3.2.15.4 Fittings & Accessories


i). Surge monitors shall be fitted with pressure relief device
ii). Surge monitors shall be supplied complete with supporting insulators, terminal
connectors, standard fittings and accessories.

3.2.16 11 kV OUTDOOR CIRCUIT BREAKER


The 11kV circuit breaker shall be suitable for installation in open yard in heavily
polluted environment. Circuit breakers shall be capable of interrupting induction
currents caused by switching operations of unloaded transformers and low capacitive
currents without causing undue over voltage. The 11 kV CB shall conform to IEC
62271-100.

3.2.16.1 Technical Particulars of 33 kV Circuit Breaker:


31) Nominal system voltage 11 kV
32) Highest system voltage 12 kV
33) Rated frequency 50 + 5%Hz
34) Rated continuous current 1250 A
35) Design short circuit level 26.3 kA for 3 Seconds
36) Type Vacuum circuit breaker
37) Closing mechanism Motorised spring charged
stored energy.
38) Operating voltage for Spring 240 AC
charging
39) Operating voltage for Closing coil 110 V DC
Tripping coil

RMD, BARSUA CET/14/RN/3888/TS/EE/01/R=2


Installation of 33kV substation for enhancement PAGE 3.25
of contract demand from 4 MVA to 5 MVA for BIM
40) Number of poles 3 (three)
41) Total break time for any current upto Less than 2.5 cycles
the rated breaking current measured
from the instant of trip coil
energisation.
42) First pole to clear factor 1.5
43) Temp. rise As per IEC
44) Whether the circuit breaker is Yes
intended for rapid re-closing
45) Operating duty 0-0.3 sec CO 3 min CO
46) Dead time of the breaker Adjustable between 0.3 sec. to
15 sec.
47) Latching requirement Trip free
48) Insulation level
c) Rated one min. power frequency 28 kV rms
withstand voltage.
d) Rated impulse withstand voltage 75 kV peak
49) Min. creepage distance 31 mm/kV
50) Control supply voltage 110 V DC
51) Aux. contacts with each circuit 6 NO + 6 NC, with provision
breaker interchangeable at site to extend no. of contacts
additional contacts will be
given if add on is possible
52) Type tests for performance As per IEC
verification.
53) ON/OFF indicator Mechanical as well as
electrical
54) Emergency tripping & closing Mechanical
mechanism
55) Termination suitability with ACSR conductor
connectors
56) Anti-pumping relay operation, Shall be provided
counter, local control panel, local /
remote selector switch.

RMD, BARSUA CET/14/RN/3888/TS/EE/01/R=2


Installation of 33kV substation for enhancement PAGE 3.26
of contract demand from 4 MVA to 5 MVA for BIM
57) Space heater with thermostat panel Shall be provided
illumination lamp, 240 V switch
socket in local control panel, gland
plate with double compression
glands.
58) Degree of Protection IP-55

3.2.16.2 Bushings
Equalised electrical stress internally and over the bushing surface

Free from radio interference

Provision for expansion over normal operating temperature range

Bushings with combination potential and power factor test cap.


3.2.16.3 Operating Mechanism
Circuit breakers shall be suitable for remote control from the electrical control room.
A local control switch with locking arrangement shall be provided for each circuit
breaker for local operations i.e. tripping and closing during maintenance, test etc.
Local/remote selector switch shall be provided in the mechanism cabinet.

Each circuit breaker shall have ON/OFF indication lamp along with a mechanical
`open/closed' position indicator visible with the mechanism cabinet closed.
One close coil and two trip coils.
Cabinet for operating mechanism and its accessories shall be of IP55 protection with
pad locking facility. Cabinet shall be simplex type all equipment mounted on front
side and wiring on back in proper wire ways.
Anti condensation heater shall be provided in the local cabinet with load break fuse
switch. It shall house relays for control and interlocking as per scheme requirement.
Wire-ways/cable ways shall be provided in operating mechanism cabinet so that
wiring is neat. All the connection shall be at back and equipment in front.
Closing circuit to operate satisfactorily from 80% to 110% of the rated control
voltage and tripping from 50% to 110% of the rated control voltage.
3.2.16.4 Terminal Connections
The terminal connector shall be suitable for ACSR conductor
Suitable terminal earth connector for earthing connections shall also be supplied.

RMD, BARSUA CET/14/RN/3888/TS/EE/01/R=2


Installation of 33kV substation for enhancement PAGE 3.27
of contract demand from 4 MVA to 5 MVA for BIM