Anda di halaman 1dari 94

MS ISO/IEC TR 10037 : 1995

MALAYSIAN
STANDARD
MS 761 : 1982
ICS : 75.080

CODE OF PRACTICE
FOR THE STORAGE AND
HANDLING OF FLAMMABLE
AND COMBUSTIBLE LIQUIDS

STANDARDS & INDUSTRIAL RESEARCH INSTITUTE OF MALAYSIA


Copyright
MS 761:1982

This Malaysian Standard, which had been approved by the Chemical and

Pharmaceutical Industry Standards Committee and endorsed by the Council of the


Standards and Industrial Research Institute of Malaysia (SIRIM) was published under

the .authority of the SIRIM Council in July, 1982.

SIRIM wishes to draw attention to the fact that this Malaysian Standard does not
purport to include all the necessary provisions of a contract.

The Malaysian Standards are subject to periodical review to keep abreast of progress
in the industries concerned. Suggestions for improvements will be recorded and in

due course brought to the notice of the Committees charged with the revision of the

standards to which they refer.

Committee reference: SIRIM 402/2/8


Draft for comment: D39 (ISC B)

1
MS761 :1982

CONTENTS
Page
Committee representation 5
Foreword 6

Section One: Scope and general 7


1.1 Scope 7
1.2 Classification 7
1.3 Definitions 8
1.4 Storage 12
1.5 Pressurevessels 12
1.6 Exits 12

Section Two: Tank storage 12


2. 1 Design and construction of tanks 12
2.2 Installation of outdoor aboveground tanks 14
2.3 Installation of underground/mounded tanks 27
2.4 Installation of tanks inside of buildings 29
2.5 Supports, foundations and anchorage for all tank locations 31
2.6 Sources of ignition 31
2.7 Testing 31
2.8 Fire protection and identification 32
2.9 Prevention of overfilling of tanks 32

Section Three: Piping, valves and fittings 33


3.1 General 33
3.2 Materials for piping, valves and fittings 33
3.3 Pipe joints
3.4 Supports
3.5 Protection against corrosion 34
3.6 Valves
3.7 Testing

Section Four: Container and portable tank storage 35


4.1 Application 35
4.2 Design. construction and capacity of containers 35
4.3 Design, construction and capacity of storage cabinets 36
4.4 Design, construction and operation of separate inside storage areas 37
4.5 Indoor storage 40
4.6 Protection requirements for protected storage of liquids 43
4.7 Fire control 45
4.8 Outdoor storage 45

Section Five: Industrial plants 47


5.1 Application 47
5.2 Incidental storage or use of liquids 47
5.3 Unit physical operations 48
5.4 Tank vehicle and tank car loading and unloading 49
5.5 Fire control 49
5.6 Sources of ignition 50
5.7 Electrical equipment 50
5.8 Repairs to equipment 53
5.9 Housekeeping 53

2
MS761 :1982

CONTENTS (CONTD.)
Page

Section Six: Bulk plants 53


6.1 Storage 53
6.2 Buildings 53
6.3 Loading and unloading facilities 54
6.4 Wharves 55
6.5 Electrical equipment 57
~.6 Sources of ignition 61
6.7 Drainage and waste disposal 61
6.8 Fire control 61

Section Seven: Service stations 61


7.1 Application 61
7.2 Storage 61
7.3 Piping, valves and fittings 63
7.4 Fuel dispensing system 64
7.5 Electrical equipment 65
7.6 Operational requirements 70
7.7 Sources of ignition 72
7.8 Fire control 72

Section Eight: Processing plants 72


8.1 Application 72
8.2 Location 72
8.3 Processing building 73
8.4 Liquid handling 74
8.5 Tank vehicle and tank car loading and unloading 75
8.6 Fire control 75
8.7 Sources of ignition 75
8.8 Electrical equipment 76
8.9 Housekeeping 76

Section Nine: Refineries, chemical plants and distilleries 76


9.1 Storage 76
9.2 Wharves
9.3 Location of process units
9.4 Fire control

Section Ten: Storage on farms and isolated construction projects 77


10.1 Application 77
10.2 Types of approved storage 77
10.3 Individual containers of 225 litres or less capacity each 78
10.4 Tanks of 226 to 4,1 60 litres capacity each 78
10.5 Marking of tanks and containers 79

3
MS761 :1982

CONTENTS (CONTD.)
Page
Tables

1 Stable liquids (Operating pressure 1 7 kPa (gauge) or less) 16


2 Stable liquids (Operating pressure greater than 1 7 kPa (gauge)) 17
3 Boil-over liquids 17
4 Unstable liquids 18
5 Class IIIB liquids 19
6 Reference table for use in tables 1 to 4 19
7 Minimum tank spacing (shell-to-shell) 20
8 Wetted area versus cubic metres free air per hour
(venting capacity) at 101.5 kPa (absolute) and 15C 24
9 Wetted area over 260 rn2 and pressures over 7 kPa (gauge) 24
10 Vent line diameters 28
11 Maximum allowable size of containers and portable tanks 36
12 Storage in inside rooms 37
13 Indoor unprotected storage of liquids in containers
and portable tanks 39
14 Storage arrangements for protected palletized or solid pile storage
of liquids in containers and portable tanks 44
1 5 Storage arrangements for protected rack storage of liquids in
containers 44
16 Outdoor liquid storage in containers and portable tanks 46
17 Electrical equipment classified area Industrial plants
- 51
18 Electrical equipment classified areas Bulk plants
- 58
19 Electrical equipment classified areas Service stations
- 66
20 Locations of processing vessels from property lines 72

Appendices

A Abandonment or removal of underground tanks 80


B Protection of tanks containing flammable or combustible liquids in
locations that may be flooded 82
C Classification of hazardous areas 85
D List of reference standards 87

4
MS761 :1982

Committee representation

This Malaysian Standard was prepared by the Task Force on storage and Utilization of Petroleum and Petroleum Products
which consists of the following:

Tuan Haji Abdul Jalil Mahmud lChairman) Factories and Machinery Department

Encik Ooi Cheng Lee Standards and Industrial Research Institute of Malaysia
Encik Lee Yuke Chin Standards and Industrial Research Institute of Malaysia

Encik Abdul Rahim Kechot Civil Aviation Department

Encik M. Chelliah Fire Department

Encik Zachariah Ali Petronas


Encik Lim Khim Nik Petronas
Encik Lee Heng Kong Ministry of Science. Technology and the Environment (Environment
Division)

Encik Manmohan Singh Town and Country Planning Department


Cik Yip Slew Kuan Town and Country Planning Department
Cik Latifah Yatim Town and Country Planning Department
Encik Lum Kon Woon Chemistry Department
Encik Mohd. Hazis Ngah Ministry of Trade and Industry
Encik Mohd. Said Md. Zain Ministry of Trade and Industry
Encik Leong Chew Kum Factories and Machinery Department

Encik Zulkarnain b. Ibrahim Prime Ministers Department (Petroleum Development Unit)


Cik Yap Siew Ying Prime Ministers Department (Petroleum Development Unit)
Cik Sabarish Mohd. Noor Ministry of Transport

5
MS761 :1982

FOREWORD

This Code of Practice was prepares by the Task Force on Storage and Utilization of
Petroleum and Petroleum Products. This Task Force is responsible to the Sub-
Committee on Storage and Sub-Committee on Utilization which were established by
the Committee on the Review of Petroleum Safety Laws and Regulations. It was
initiated as a result of steps taken to review the Petroleum Ordinance 1 949.

This code is based on the following standards of the United States National Fire
Protection Association (NFPA):

(a) NFPA 30:1 978, Flammable and combustibe liquids code.


(b) NFPA 395:1 978, Flammable and combustible liquids on farms and isolated
construction projects.

Acknowledgment is made for permission to use the aove standards.

This code represents a standard of good practice and provides safety principles for the
design, construction and operation of installations for the storage and handling of
flammable and combustible liquids. Petroleum and petroleum products are in this
range of flammable and combustible liquids.

This code does not set out the whole field of requirements relating to wiring and
electrical equipment. However familiarity and compliance with good electrical safe
practice and with the relevant codes, standards and regulations are therefore
assumed. In this aspect attention is drawn to the requirements of the Electricity
Regulations 1951 (Revised 1977).

This code requires reference to a number of other standards, a listing of which is given
in appendix D.

6
MS761 :1982

CODE OF PRACTICE FOR THE STORAGE AND HANDUNG OF


FLAMMABLE AND COMBUSTIBLE LIQUIDS

SECT~ONONE: SCOPE AND GENERAL property and character of construction of such


buildings. capacity and construction of
proposed tanks and character of liquids to
1.1 SCOPE be stored, nature of process, degree of
private fire protection to be provided and the
1.1.1 This Code of Practice covers the adequacy of facilities of the fire department to
design, construction and operation of in- cope with flammable or combustible liquid fires.
stallations for the storage and handling of
flammable and combustible liquids including 1.1,4 This code shall not apply to the following:
petroleum and petroleum products.
1.1.4.1 The transportation of flammable and
1.1.2 Requirements for the safe storage and combustible liquids.
use of the great variety of flammable and
combustible liquids commonly available -1.1.4.2 Storage, handling and use of fuel oil
depend primarily on their fire characteristics, tanks and containers connected with oil burning
particularly the flash point, which is the basic equipment.
for the several classifications of liquids as defined
in 1.2. It should be noted thatthe classification of 1.1.4.3 Storage and handling of liquefied
a liquid can be changed by contamination. For petroleum gases and liquefied natural gases.
example, filling a Class II liquid into atankwhich
last contained a Class I liquid can alter its 1.1.4.4. Liquids without f!ash points that can
classification, as can exposing a Class II liquid be flammable under some conditions, such as
to the vapours of a Class I liquid via an inter- certain halogenated hydrocarbons and mixtures
connecting vapour line (see 2.2,6.4 and 2.3.5.6), containing halogenated hydrocarbons.
Care shall be exercised in such cases to apply
the requirements appropriate to the actual 1.1.4.5 Mists, sprays or foams. (Except
flammable aerosols in containers are included in
classification.
section 4).
1.1.3 In particular installations the provisions
of this code may be altered at the
discretion of the authority having jurisdiction 1.2 CLASSIFICATION
after consideration of the special features such
as topographical conditions, barricades, walls, 1.2.1 Flammable and combustible liquids
adequacy of building exits, nature of including petroleum and petroleum products,
occupancies, proximity to buildings or adjoining shall be classified into the following classes:

7
MS761 :1982

1.2.1.1 C/ass I.Class I liquids shall be jurisdiction may base acceptance on compliance
subdivided as follows: Flammable liquids having with appropriate standards.
flash points below 37.8C (100F).
In the absence of such standards, said authority
C/ass IA shall include those having flash points may require evidence of proper installation,
below 22.8C (73F) and having a boiling point procedure or use. The authority having
below 37.8C (100F). jurisdiction may also refer to the listings or
labelling practices of nationally recognized
C/ass lB shall include those having flash points testing laboratories, inspection agencies, or
below 22.8C (73F) and having a boiling point at other organizations concerned with product
or above 37.8C (100F). evaluations which are in a position to
determine compliance with app ropr iate
C/ass/C shall include those having flash points at standards for the current production of listed
or above 22.8C (73F) and below 37.8C items, and the satisfactory performance of such
(100F). equipment or materials in actual usage.

1.2.1.2 C/ass II: Combustible liquids having 1.3.3 Assemby occupancy shall mean the
~lash points at or above 37.8C (100F) and occupancy or use of a building or structure or any
below 60C (140F). portion thereof by a gathering of persons for
civic, political, travel, religious or recreation
1.2.1.3 C/ass ///. Combustible liquids having
purposes.
flash points at or above 60C (140F). Class Ill
liquids shall be subdivided as follows:
1.3.4 Atmospheric tank shall mean a storage
C/ass I//A shall include those having flash points tank which has been designed to operate at
at or above 60C (140F) and below 93.4C pressures from atmospheric to 3.5 kPa (gauge).
(200F).
1.3.5 Authority having jurisdiction shall mean
C/ass f//B shall include those having flash points the organization, office or individual responsible
at or above 93.4C (200F). for approving equipment, an installation, or a
procedure.

1.3 DEFINITIONS .1.3.0 8arr& shall mean a volume of 1 58.987


litres,
For the purpose of this code, the following
definitions shall apply: 1.3.7 Basement shall mean any storey or
storeys of a building which is or are at a level
1.3.1 Aerosol shall mean a material which is lowers than the ground storey.
dispensed from its container as a mist, spray or
foam by a propellent under pressure. 1.3.8 Boiling point shall mean the boiling point
of a liquid at a pressure of 101 .5 kPa (absolute)
1.3.2 Approved shall mean acceptable to the (760 mmHg). Where an accurate boiling point is
authority having jurisdiction. In determining the unavailable for the material in question, or for
acceptability of installations or procedures, mixtures which do not have a constant boiling
equipment or materials, the authority having point, for purposes of this code the 1 0% point of a

8
MS761 :1982

distillation performed in accordance with 1.3.16 Distillery shall mean a plant or that
MS 563 Method of test for distillation of portion of a plant where liquids produced by
petroleum products. may be used as the boiling fermentation are concentrated, and where the
point of the liquid. concentrated products may also be mixed,
stored, or packaged.
1.3.9 Boil-over shall mean the expulsion of
crude oil (or certain other liquids) from a burning 1.3.17 Educational occupancy shall mean the
tank. The light fractions of the crude oil burn off occupancy or use of a building or structure or any
producing a heat wave in the residue, which on portion thereof by persons assembled for the
reaching a water strata may result in the purpose of learning or of receiving educational
expulsion of a portion of the contents of the tank instruction.
in the form of froth.
1.3.18 Fire compartment shall mean an area of
1.3.10 Bulk plant shall mean that portion of a a building separated from the remainder of the
property where liquids are received by tank building by construction having a fire resistance
vessel, pipe lines, tank car, or tank vehicle, and of at least one hour and having all communicating
are stored or blended in bulk for the purpose of openings properly protected by an assembly
distributing such liquids bytankvessel. pipe line, having a fire resistance rating of at least one hour.
tank car, tank vehicle, or container.
1.3.19 Flammable aerosol shall mean an
1.3.11 Chemical plant shall mean a large aerosol which is required to be labelled
integrated plant or that portion of such a plant Flammable by the appropriate authority.
other than a refinery or distillerywhere liquids are
produced by chemical reactions or used in 1.3.20. Flammabe liquid shall mean a liquid
chemical reactions. having a flash point below 37.8C (100F) and
having a vapour pressure not exceeding 276 kPa
1.3.12 Closed containers shall mean a con- (absolute) at 37.8C (100F).
tainer as herein defined, so sealed by means of a
lid or other device that neither liquid nor vapour 1.3.21 Flash point of a liquid shall mean the
will escape from it at ordinary temperatures. lowest temperature at which it gives off vapour in
sufficient concentration to ignite momentarily or
1.3.13 Combustible liquid shall mean a liquid flash on application of a flame as specified by
having a flash point at or above 37.8C (100F). appropriate test procedure and apparatus as
follows:
1.3.14 Container shall mean any vessel of 225
litres or less capacity used for transporting or (a) The flash point of Class I and Class II liquids
storing liquids. shall be determined in accordance with MS 648,
Method of test for flash point by the Abel
1.3.15 Crude petroleum shall mean raw Apparatus.
petroleum as it comes from the earth in its natural
unprocessed, unrefined state. It is composed (b) The flash point of a Class III liquid shall be
principally of hydrocarbons with traces of determined in accordance with MS 686, Method
sulphur, nitrogen or oxygen compounds and can of test for flash and fire points by Pensky-Martens
be removed from the earth in a liquid state. Closed Tester.

9
MS 761 :1982

As an alternate, ASTM D3243, Standard 1.3.26 Liquid shall mean, any material which
methods of testsforflash point of aviationturbine has a fluidity greater than that of 300 penetration
fuels by Setaflash Closed Tester, may be used for asphaltwhen tested in accordancewith MS 541,
testing aviation turbine fuels within the scope of Method for determining of penetration of
this procedure. (See note 1). bituminous materials. When not otherwise
identified, tlie term liquid shall mean both
As an alternate, ASTM D3278, Standard method flammable and combustible liquids.
of tests for flash point of liquids by Setaflash
Closed Tester, may be used for paints, enamels, 1.3.27 Low pressute t~ok,Low pressure tank
lacquers, varnishes and related products and shall mean a storage tank designed to withstand
their components having flash points between an internal pressure above 3.5 kPa (gauge) but
0C (32F) and 1 10C (230F) and having not more than 103 kPa (gauge).
viscosity lower than 1 50 stokes at 25C (7 7F)
(see note 1). - 1.3.28 Mercantile occupancy shall mean the
occupancy or use of a building or structure or any
NOTE 1. in the case of arty dispute the methods specified in (a) and (b) portion thereof for the displaying, selling or
shall be the referee method.
buying of goods, wares, or merchandise.

1.3.22 Flat shall mean a building or that 1.3.29 Office occupancy shall mean the
portion of a building containing more than two occupancy or use of-a building or structure or any
dwelling units. portion thereof for the transaction of business, or
the rendering or receiving of professional
1.3.23 -Hotel shall mean any building
services.
specifically designed and constructed or sub-
stantially adapted to be used to accomodate
1.3.30 Petroleum shall mean a naturally
persons for the purpose of gains or profit, with or
occurring mixture, consisting predominantly of
without arrangements for communal feeling, and
many different hydrocarbons, and can be
includes a boarding house, lodging-house or
gaseous (natural gas), liquid (crude petroleum),
guest-house.
solid (asphalt, tar, bitumen) or a combination of
1 .3,24 ~nstitutionaloccupancy shall mean the states. It is the raw material from which gasoline.
occupancy or use of a building or structure or any kerosene, diesel fuel, fuel oil, lubricating oil,
portion thereof by persons harboured or detained paraffin wax, bitumen and other products are
to receive medical, charitable or other care or obtained.
treatment, or by persons involuntarily detained.
1.3.31 Petroleum products shall mean
1.3.25 Labelled shall mean equipment or materials derived from petroleum, natural gas, or
materials to which has been attached a label, asphalt deposits; includes gasoline, kerosene,
symbol or other identifying mark of a nationally diesel fuel, fuel oil, lubricating oil, liquefied
recognized testing laboratory, inspection agency, petroleum gases, waxes, greases, toluene,
or other organization concerned with product benzene and any like flammable and combustible
evaluation that maintains periodic inspection of liquids. -
production of labelled equipment or materials,
and by whose labelling is indicated compliance 1.3.32 Portable tank shall mean any closed
with nationally recognized standards or tests to vessel having a liquid capacity over 225 litres and
determine suitable usage in a specified manner. not intended for fixed installation.

10
MS 761 :1982

1.3.33 Pressure vessel shall mean any fired or (c) Attached building. A building having only
unfired vessel within the scope of the applicable one common wall with a building having other
section of the ASME Boiler and pressure vessel type occupancies.
code or equivalent standard acceptable to the
appropriate approving authority. -
1.3.40 Service stations

1.3.34 Protected shall mean protected with (a) Automotive service station shall mean that
approved automatic sprinklers. portion of property where liquids used as motor
fuels are stored and dispensed from fixed
1.3.35 Protection for exposures shall mean equipment into the fuel tanks of-motor vehicles
.fire protection for strudtures on property adjacent and may include any facilities available for the
to liquid storage. Fire protection for such sale and service of tyres, batteries and acces-
structures shall be acceptable when located (1) sories, and for minor automotive maintenance
within the jurisdiction of any public fire work. Major automotive repairs, hot-work, paint-
department, or (2) adjacent to plants having ing, body and fender work are excluded.
private fire brigades capable of providing cooling
water streams on structures on property adjacent (b) Marine service station shall mean that
to liquid storage. portion of a property where liquids used as fuels
are stored and dispensed from fixed equipment
- 1.3.36 Refinery shall mean a plant in which on shore, piers, wharves, or floating docks into
flammable or combustible liquids are produced the fuel tanks of self-propelled craft, and shall
on a commercial scale from crude petroleum. include all facilities used in connection therewith.
natural gasoline, or other hydrocarbon sources.
1.3.41 Unstable (reactive) liquid shall mean a
1.3.37 Residential building shall mean a liquid which in the pure state or as commercially
building or part thereof designed, adapted or produced or transported will vigorously poly-
used for human habitation. merize, decompose, condense, or will become
self-reactive under conditions of shock, pressure,
1.3.38 Safety can shall mean an approved or temperature.
container of not more than 20 litres capacity,
having a spring-closing lid and spout cover and 1.3.42 Vapour pressure shall mean the
so designed that it will safely relieve internal pressure, measured in kPa (absolute). exerted by
pressure when subjected to fire exposure. a volatile liquid as determined by MS 538
Methods of test of vapour pressure of petroleum
1.3.39 Separate inside storage area shall mean products (Reid method).
a room or building used for the storage of liquids
in containers or portable tanks, separated from 1.3.43 Vapour processing equipment shall
other types of occupancies. Such areas may mean those components of a vapour processing
include: system which are designed to processvapoursor
liquids captured during filling of tanks or
(a) /nsideroom.Aroomtotallyenclosedwithina containers or during fueling of vehicles.
building and having no exterior walls;
1.3.44 Vapour processing system shall mean a
(b) Cut-off room. A-room within a building and system designed to capture and process vapours
having at least one exterior wall; displaced during filling of tanks or containers or

11
MS761 :1982

during fueling of vehicles by use of mechanical 1.5 PRESSURE VESSEL - -

and/or chemical means. Examples are systems


using blower-assist for capturing vapours. and 1.5.1 All pressure vessels containing liquids
refrigeration, absorption and combustion shall comply with 1.5.1.1 or 1.5.1.2 as
systems for processing vapours. applicable.

1.3.45 Vapour recovery system shall mean a 1.5.1.1 Fired pressure vessels shall be de-
system designed to capture and retain, without signed and constructed in accordance with the
processing. vapours displaced during filling of applicable sections of the ASME Boiler and
tanks or containers or during fueling of vehicles. pressure vessels code or equivalent standard
An example is a balanced-pressure vapaur acceptable to the appropriate approving
displacement system. authority.

1.3.46 Ventilation as specified in this code is 1.5.1.2 Unfired pressure vessels shall be
for the prevention of fire and explosion. It is designed and constructed in accordance with the
-considered adequate if it is sufficient to prevent applicable sections of the ASME Boiler and
accumulation of significant quantities of vapour- pressure vessels code~BS 5500, Unfired fusion
air mixtures in concentration over one-fourth of welded pressure vessels or equivalent standard
the lower flammable limit. acceptable to the appropriate approving
authority.
1.3.47 Warehouses

(a) General purpose warehouse shall mean a 1.6 EXITS


separate, detached building or portion of a
building used only for warehousing type opera- 1.6.1 Engress from buildings and areas
tions (see note 2). covered by this Code shall be in accordance with
the requirements of the Uniform Building By-
NOTE 2. Warehousing operations referred to above are those Laws.
operations not accessible to the public-and include general purpose.
merchandise, distribution and industrial warehouse type operations.

(b) Liquid warehouse shall mean a separate.


detached building or attached building used for
warehousing type operations for liquids.
SECTION TWO: TANK STORAGE
1.3.48 Wharf superintendent or representa-
tive shall mean an officer appointed by a terminal
operator which could be a private operator or a 2.1 DESIGN AND CONSTRUCTION OF TANKS
duly constituted authority established by law
operating the terminal. 2.1.1 Materials. Tanks shall de designed and -

built in accordance with recognized good


engineering standards for the material of
1.4 STORAGE - construction being used, and shall be of steel
with the following limitations and exceptions:
1.4.1 Liquids shall be stored in tanks or in
containers in accordance with section 2 or (a) The material of tank construction shall be
section 4. compatible with the liquid to be stored. In case of

12
MS761 :1982

doubt about the properties of the liquid to be 2.1.3 Atmospheric tanks


stored, the supplier, producer of the liquid, or
other competent authority shall be consulted. 2.1.3.1 Atmospheric tanks shall be built in
accordance with recognised standards of design.
(b) Tanks constructed of combustible materials Atmospheric tanks may be built in accordance
shall be subject to the approval of the authority with:
having jurisdiction and limited to:
(a) Underwriters laboratories Inc., UL142,
(i) installation underground; or Standard for steel aboveground tanks for
flammable and combustible liquids, ULB8,
(ii) use where required by the properties of the
Standard for steel underground tanks for
liquid stored; or
flammable and combustible liquids, or UL8O.
Standard for steel inside tanks for oil burner fuel.
(iii) storage of Class lllB liquids aboveground in
- areas not exposed to a spill or leak or Class I or
(b) American Petroleum Institute Standard
Class II liquids; or
No. 650, Welded steel tanks for oil storage.

(iv) storage of Class IlIB liquids inside a building


(c) American Petroleum Institute Standard
protected by an, approved automatic fire ex-
No. 1 2B. Specification for bolted production
tinguishing system.
tanks, No. 1 2D, Specification for large welded
production tanks, or No. 1 2F. Specification for
(c) Unlined concrete tanks may be use for
small welded production tanks. Tanks built in
storing liquids having a gravity of 40 degrees API
accordance with these standards shall be -used
or heavier. Concrete tanks with special linings
only as production tanks for storage of crude
may be used for other services provided the
petroleum in oil-producing areas.
design is in accordance with sound engineering
practice.
(d) Any equivalent standards acceptable to the
appropriate approving authority.
(d) Tanks may have combustible or non-
combustible linings.
2.1.3.2 Low pressure tanks and pressure
(e) Special engineering consideration shall be vessels may be used as atmospheric tanks.
required if the specific gravity of the liquid to be
stored exceeds that of water or if the tank is 2.1.3.3 Atmospheric tanks shall not be used for
designed to contain liquids at a liquid tempe- the storage of a liquid at a temperature at or above
rature below -17.8C (0F). its boiling point.

2.1.4 Low pressure tanks -


2.1.2 Fabrication

2.1.2.1 Tanks may be of any shape or type 2.1.4.1 The normal operating pressure of the
consistent with sound engineering design. tank shall not exceed the design pressure of the
tank.
2.1.2.2 Metal tanks shall be welded. riveted
and caulked. or bolted, oLcon~ructedby useofa 2.1.4.2 Low pressure tanks shall be built in
combination o-fth~~ methods. accordance with recognized standards of design.

13
MS761 :1982

Low pressure tanks may be built in accordance 2.2 INSTALLATION OF OUTDOOR ABOVE-
with: GROUND TANKS

(a) American Petroleum Institute Standard 2.2.1 Location with respect to property lines,
No. 620, Recommended rules for the design and public ways and important buildings on the
construction of large, welded, low-pressure same property.
storage tanks. -
2.2.1.1 Every aboveground tanks for the
(b) The principles of the Code for unfired storage of Class I. Class II or Class lilA
pressure vessels of the ASME Boiler and liquids, except as provided in 2.2.1.2 and those
pressure vessels code. liquids with boil-over characteristics and un-
stable liquids, operating at pressures not ex-
(c) Any approved equivalent standards accept- ceeding 17 kPa (gauge) and designed with a weak
able to the appropriate approving authority. roof-to-shell seam or equipped with emergency
venting devices which will not permit pressures to
2.1.4.3 Tanks built according to Underwriters exceed 1 7 kPa (gauge)-, shall be located in
Laboratories Inc. requirements in 2.1.3.1 may be accordance with table 1.
used for operating pressures not exceeding 7 kPa
(gauge) and shall be limited to 1 7 kPa (gauge) (a) For the purpose of 2.2, a floating roof
under emergency venting conditions. tank is defined as one which incorporates either:

2.1.4.4 Pressure vessels may be used as low (1) A pontoon or double deck metal floating
pressure tanks. roof in an open top tank in accordance with
API Standard 650. or
2.1.5 Pressure vessels
(2) A fixed metal roof with ventilation at the
2.1.5.1 The normal operating pressure of the top and roof eaves in accordance with API
vessel shall not exceed the design pressure of Standard 650 and containing a metal floating
roof or cover meeting any one of the following
the vessel.
requirements:
2.1.5.2 Storage tanks designed to withstand
pressures above 103 kPa(gauge) shall meet the (i) A pontoon or double deck metal floating roof
requirements of 1 .5. -
meeting the requirements of API Standard 650.

(ii) A metal floating cover supported by liquid-


2.1.6 Provisions for internal corrosion. When tight metal pontoons or floats which provide
tanks are not designed in accordance with the sufficient l~uoyancyto prevent sinking of the
Americal Petroleum Institute, American Society cover when half of the pontoons or floats are
of Mechanical Engineers or the Underwriters punctured.
Laboratories Inc. Standards, or if corrosion is
anticipated beyond that provided for in the design (b) An internal metal floating pan, roof or cover
formulas used, additional metal thickness or which does not meet the requirements of (a) (2).
suitable protective coatings or linings or cathodic or one which uses plastic foam (except for seals)
protection shall be provided to compensate for for flotation even if encapsulated in metal or
the corrosion loss expected during the design life fiber glass shall be considered as being a fixed
of the tank.- roof tank.

14
MS761 :1982

2.2.1.2 Vertical tanks having a weak roof-to- authority having jurisdiction may, with the written
sKell seam and storing Class lIlA liquids may be consent of the owners of the two properties,
located at one-half the distances specified in substitute the distances provided in 2.2.2.1 to
table 1. provided the tanks are not within a 2.2.2.6 for the minimum distances set forth in
bunded area or drainage path for a tank 2.2.1.
storing a Class I or Class II liquid.
2.2.1.8 Where end failure of horizontal
2.2.1.3 Everyabovegroundtankforthestorage pressure tanks and vessels can expose property,
of Class I, Class II or Class lIlA liquids, except the tank shall be placed with the longitudinal
those liquids with boil-over characteristics and axis parallel to the nearest important exposure.
unstable liquids, operating at pressures ex-
ceeding 1 7kPa (gauge) or equipped with 2.2.2 Spacing (shell-to-shell) between any
emergency venting which will permit pressures to two adjacent aboveground tanks.
exceed 1 7 kPa (gauge) shall be located in
accordance with table 2. 2.2.2.1 Tanks storing Classes I. II or lIlA
stable liquids shall be separated in accordance
2.2.1.4 Every aboveground tank for storage of with table 7. except as provided in 2.2.2.2.
liquids with boil-over characteristics shall be
located in accordance with table 3. 2.2.2.2 Crude petroleum tanks having in-
dividual capacities not exceeding 477.000 litres
(a) Liquids with boil-over characteristics shall
(3.000 barrels), when located at production
not be stored in fixed roof tanks larger than 45 m facilities in isolated locations, need not be
diameter, unless an approved inerting system or separated by more than 1 m.
sub-surface foam injection system is provided on
the tank. -

2.2.2.3 Tanks used only for storing Class IIIB


liquids may be spaced no less than 2 m apart
2.2.1.5 Everyabovegroundtankforthestorage unless within a bunded area or drainage path for a
of unstable liquids shall be located in accordance tank storing a Class I or Class II liquid, in
with table 4. which case the provisions of table 7 apply.

2.2.1.6 Everyabovegroundtankforthestorage
2.2.2.4 For unstable liquids, the distance
of Class IlIB liquids, excluding unstable liquids.
between such tanks shall not be less than one-
shall be located in accordance with table 5 except
half the sum of their diameters.
when located within a bunded area or drainage
path for a tank or tanks storing a Class I or Class II
liquid. When a Class IIIB liquid storage tank is 2.2.2.5 When tanks are in a bunded area
within the bunded area oi drainage path for a containing Class I or Class II liquids, or in the
Class I or Class II liquid, 2.2.1.1 or 2.2.1.2 shall drainage path of Class I or Class II liquids, and are
apply. compacted in three or more rows or in an
irregular pattern, greater or other means may be
required by the authority having jurisdiction to
2.2.1.7 Where two tank properties of diverse make tanks in the interior of the pattern
ownership have a common boundary. the accessible for fire fighting purposes.

15
MS761 :1982

Table 1. Stable liquids [Operating pressure 17 kPa (gauge) or less]

Minimum distance in
Minimum distance in
metres from property
line which is or can metres from nearest side
Protection of any public way or from
Type of be built upon, includ- nearest permanent build-
tank ing the opposite side .
ung on the same property
of a public way and and shall be not less
shell be not less than
than 2.3 m
2.3 m

Protection times diameter of 1/6times diameter of


Floating for tank tank
roof [see exposures*
2.2.l.l(a)J
Diameter of tank but 1/6 times diameter of
None
need not exceed 53 m tank

Approved foam
or inerting
times diameter of 1/6 times diameter of
system on
tanks not ex- tank tank
ceeding 45 m
Vertical in diameter**
with weak Protection 1/3 times diameter of
roof to
for Diameter of tank tank
shell
exposures*
seam (see
2.2.1.1> . .
2 times diameter of 1/3 times diameter of
None tank but need not
tank
exceed 107 m

Approved
inerting
Horizontal system on
and vertical the tank or
with emer- approved times table 6 times table 6
gency relief foam system
venting to on vertical
limit pres- tanks
sures to Protection
17 kPa for Table 6 Table 6
(gauge) exposures*

None 2 times table 6 Table 6

~5eedefinition for Protection for exposures


For tanks over 45 m in diameter use Protection for exposures or None as applicable.

16
MS761 :1982

Table 2. Stable liquids [Operating pressure


greater than 17 kPa (gauge)]

Minimum distance in Minimum distance in


metres from property metres from nearest side
Type of line which is or can of any public way or
tank Protection
be built upon, includ- from nearest permanent
ing the opposite side building on the same
of a public way property

Protection 1 times table 6 but 1 times table 6 but


for shall not be less than shall not be less than
exposures* 7.5 .m 7.5 m
Any type
3 times table 6 but 1 times table 6 but
None shall not be less than shall not be less than
15m 7.5m

5ee definition for Protection for exposures.

Table 3. Boil-over liquids

Minimum distance in Minimum distance in


- - metres from property metres from nearest side
Type of line which is or can of any public way or
tank be built upon, includ- from nearest permanent
Protection ing the opposite side building on the same
of a public way and property and shall be
shall be not less than not less than 2.3 m
2.3m

. Protection
Floating times diameter of 1/6times diameter of
roof for
tank tank
exposures*
[see
2.2.1.1(a)] None Diameter of tank 1/6 times diameter of
tank

Approved
foam or
inerting Diameter of tank 1/3 times diameter of

tank
system
Fixed roof .

[see Protection
2.2.1.4(c)] 2 times diameter of 2/3times of diameter
for
tank tank
exposures*

4 times diameter of
None tank but need not 2/3 times diameter of
exceed 107 m. tank -

5ee definition for Protection for exposures.

17
MS 761:1982

Table 4. Unstable liquids

Minimum distance in Minimum distance in


metres from property metres from nearest side
Type of Protection line which is or can of any public way or
tank be built upon, includ- from nearest permanent
ing the opposite side building on the same
of a public way property

Tank
protected
with any one
of the
Horizontal
following:
and approved
vertical water spray,
tanks wi.th approved
emergency inerting, Tables 2 to 6 but not
relief Not less than 7.5 m
less than 7.5 m
venting to approved
insulation
permit and refri-
pressure
geration,
notin -
approved
excess of barricade
17 kPa
(gauge)
-
,
Protection 2 times table 6 but
for Not less than 15 m
exposures* not less than 15 m

None 5 times table 6 but


Not less than 30 m
not less than 30 m

Tank
protected
with any one
ofthe
Horizontal .
and following:
vertical approved
tanks with water spray, 2 times table 6 but Not less than 15 m
approved not less than 15 m
emergency
relief inerting,
venting approved
insulation
to permit and refri-
pressure
geration.
over 17 kPa
(gauge) approved
barricade

Protection 4 times table 6 but


for not less than Not less than 30 m
exposures* 30 m

None 8 times table 6 but Not less than 46 m


not less than 46 m

5ee definition for Protection for exposures.

18
MS761 :1982

Table 5. Class IIIB liquids

Minimum distance in Minimum distance in


metres from property metres from nearest
litres beline which
built is or
upon, can
includ- side of any public way
or from nearest perma-
ing the opposite side nerit building on the
of a public way same property

or less 2.3
to 110,000 3 2.3
to 190,000 3 3
to 380,000 4.5 3
or more 4.5 4.5

Table 6. Reference table for use in tables 1 to 4

Minimum distance in Minimum distance in


metres from property metres from nearest
Capacity tank, line which is or can side of any public way
litres be built upon, includ- or from nearest perma-
ing the opposite side nent building on the
of a public way same property

1,000 or less 2.3 2.3


1,001 to 3,000 3 2.3
3,001 to 45,000 4.5 2.3
45,001 to 110,000 6 2.3
110,001 to 190,000 9 3
190,001 to 380,000 15 4.5
380,001 to 1,900,000 25 7.5
1,900,001 to 3,800,000 30 11
3,800,001 to 7,600,000 41 14
7,600,001 to 11,400,000 50 17 -
11,400,001 or more 53 18

19
MS761 :1982

Table 7. Minimum tank spacing (shell-to-shell)

Fix&d roof tanks


Floating roof
Class I or II Class Ill A
tanks . . .
liquids liquids

All tanks not 1/6 sum of adja- 1/6 sum of adja- 1/6 sum of adja-
over 45 m dia- cent tank dia- cent tank dia- cent tank dia-
meter meters but not meters but not meters but not
less than 1 m less than 1 m less than 1 m

Tanks larger than


45 m diameter
If remote im- 1/6sum of adja- sum of adja-
1,4 1/6 sum of adja-
pounding is in cent tank dia- cent tank dia- cent tank dia-
accordance with metres meters meters
2.2.3.2
If impounding is. sum of adja-
1,4 1/3 sum of adja-
1%sum of adja- -

around tanks in cent tank dia- cent tank dia- cent tank dia-
accordance with meters meters meters
2.2.3.3

2.2.2.6 The minimum horizontal separation 2.2.3 Control of spillage from aboveground
between an LP Gas container and a Class I, Class II tanks
or Class lIlA liquid storage tank shall be 6 m
except in the case of Class I, Class II or Class lIlA 2.2.3.1 Facilities shall be provided so that
liquid tanks operating at pressures exceeding any accidental discharge of any Class 1,11 or their
1 7 kPa (gauge) or equipped with emergency lIlA liquids will be prevented from endangering.
venting which will permit pressures to exceed important facilities, adjoining property, or reach-
1 7 kPa (gauge) in which case the provisions of ing waterways, as provided for in 2.2.3.2 or
2.2.2.1 and 2.2.2.2 shall apply. Suitable means 2.2.3.3. Tanks storing Class IlIB liquids do not
shall be taken to prevent the accumulation of require special drainage or bunding provisions
Class I. Class Ii or Class lIlA liquids under adjacent for fire protection purposes.
LP Gas containers such as by bunds, diversion
2.2.3.2 Remote impounding. Where protection
curbs or grading. When flammable or com-
of adjoining property or waterways is by means of
bustible liquid storage tanks arewithin a bunded
drainage to a remote impounding area, so that
area, the LP Gas containers shall be outside the
impounded liquid ~iIl not be held against tanks,
bunded area and at least 3 m away from the
such systems shall comply with the following:
centre line of the wall of the bunded area. The
foregoing provisions shall not apply when LPGas
(a) A slope of not less than 1% away from the
containers of 470 litres or less capacity are
tank shall be provided for at least 15 m toward the
installed adjacent to fuel oil supply tanks of 2500
impounding area.
litres or less capacity. No horizontal separation is
required between aboveground LP Gas con-
tainers and underground flammable and com- (b) The impounding area shall have a capacity
bustible liquid tanks installed in accordance not less than that of the Iargesttankthat can drain
with 2.3. into it,

20
MS761 :1982

(c) The route of the drainage system shall be so extremely porous soils may require special
located that, if the liquids in the drainage system treatment to prevent seepage of hazardous
are ignited. the firewill not seriously exposetanks quantities of liquids to low-lying areas or
or adjoining property. waterways in case of spills.

(d) The confines of the impounding area shall be (e) Except as provided in (f) below, the walls of
located so that when filled to capacity the liquid the bunded area shall be restricted to an average
level will not be closer than 1 5 m from any interior height of 2 m above interior ground.
property line that is or can be built upon, or from
any tank. (f) Bunds may. be higher than an average of 2 m
above interior ground where provisions are made
2.2.3.3. Impounding around tanks by. bunding. for normal access and necessary emergency
When protection of adjoining property or access to tanks, valves and other equipment,and
waterways is by means of impounding by bunding safe egress from the bunded enclosure.
around the tanks, such system shall comply with
the following: (i) Where the average height of the bund
containing Class I liquids is over 4 m high.
(a) A slope of not less than 1 % away from the measured from interior ground, or where the
tank shall be provided for at least 1 5 m or to the distance between any tank and the top inside
bund base, whichever is less. edge of the dile wall is less than the height of the
bund wall, provisions shall be made for normal
(b) The volumetric capacity of the bunded area operation of valves and for access to tank roof (s)
shall not be less than the greatest amount of without entering below the top of the bund. These
liquid that can be released from the largest tank provisions may be met through the use of remote
within the bunded area, assuming a full tank. To operated valves, elevated walkways or similar
allow for volume occupied by tanks, the capacity arrangements.
of the bunded area enclosing more than one tank
(ii) Piping passing through bund walls shall be
shall be calculated after deducting the volume of
designed to prevent excessive stresses as a result
the tanks, other than the largest tank, below the
of settlement of fire exposure.
height of the bund.
(iii) The minimum distance between tanks and
(c) To permit access, the outside base of the
toe of the interior bund walls shall be 1.5 m.
bund at ground level shall be no closer than 3 m
to any property line that is or can be built upon.
(g) Each bunded area containing two or more
tanks shall be subdivided preferably by drainage
(d) Walls of the bunded area shall be of earth. channels or at least by intermediate curbs in
steel, concrete or solid masonry designed to be order to prevent spills from endangering adjacent
liquidtight and to withstand a full hydrostatic tanks within the bunded area as follows:
head. Earthen walls 1 m or more in height shall
have a flat section atthe top not less than 600 mm (i) When storing normally stable liquids in
wide. The slope of an earthen wall shall be vertical cone roof tanks constructed with weak
consistent with the angle of repose of the material roof-to shell seam or approved floating roof
of which thewall is constructed. Bunded areas for tanks or when storing crude petroleum in
tanks containing Class I liquids located in producing areas in any type of tank, one

21
MS761 :1982

subdivision for each tank in excess of water sources. public sewers. or public drains, if
1,590,000 litres (10,000 barrels) and one sub- their presence would constitute a hazard. Control
division for each group of tanks [no tank of drainage shall be accessible under fire
exceeding 1.590,000 litres (10.000 barrels) conditions from outside the bund.
capacity] having an aggregate capacity not
exceeding 2,385,000 litres (1 5,000 barrels). (i) Storage of combustible materials, empty or
full drums or barrels, shall not be permitted within
(ii) When storing normally stable liquids in the bunded area.
tanks not covered in subsection (1), one
subdivision for each tank in excess of 397,000
2.2.4 Normal venting for aboveground tanks
litres (2,500 barrels) and one subdivision for
each group of tanks (no tank exceeding 397,000 2.2.4.1 Atmospheric storage tanks shall be
litres (2,500 barrels capacity) having an adequately vented to prevent the development of
aggregate capacity not exceeding 568,000 litres vacuum or pressure sufficient to distort the roof
(3,570 barrels). of a cone roof tank or exceeding the design
pressure in the case of other atmospheric tanks,
(iii) When storing unstable liquids in any type of
as a result of filling or emptying, and atmospheric
tank, one subdivision for each tank except that
temperature changes. -

tanks installed in accordance with the drainage


requirements of NFPA 1 5. Standard for water 2.2.4.2 Normal vents shall be sized either in
spray fixed systems for fire protection, shall accordance with: (1) the American Petroleum
require no additional subdivision. Since unstable Institute Standard No. 2000, Venting
liquids will react more rapidly when heated than
atmospheric and low-pressure storage tanks, or
when at ambient temperatures, subdivision by (2) other accepted standard, or (3) shall be at
drainage channels is the preferred method. least as large as the filling or withdrawal
connection, whichever is larger but in no case
(iv) Whenever two or more tanks storing Class I
less than 32 mm nominal inside diameter.
liquids, any one of which is over 45 m in diameter,
are located in a common bunded area, inter-
2.2.4.3 Low-pressure tanks and pressure
mediate bunds shall be provided between
vessels shall be adequately vented to prevent
adjacent tanks to hold at least 10% of the capacity
development of pressure orvacuum, as a result of
of the tank so enclosed, not including the volume
filling or emptying and atmospheric temperature
displaced by the tank,
changes. from exceeding the design pressure of
(v) The drainage channels or intermediate the tank or vessel. Protection shall also be
curbs shall be located between tanks so astotake provided to prevent overpressure from any pump
full advantage of the available sp~acewith due discharging into the tank or vessel when the
regard for the individual tank capacities. Inter- pump discharge pressure can exceed the design
mediate curbs, where used, shall be not less than pressure of the tank or vessel.
450 mm in height.
2.2.4.4 If any tank or pressure vessel has more
(h) Where provision is made for draining water than one fill or withdrawal connection and
from bunded areas, such drains shall be simultaneous filling or withdrawal can be made,
controlled in a manner so as to preventflammable the vent size shall be based on the maximum
or combustible liquids from entering natural anticipated simultaneous flow.

22
MS761 :1982

2.2.4.5 The outlet of all vents and vent drains 2.2.5.2 Tanks larger than 45,000 litres
on tanks equipped with venting to permit capacity storing Class IIIB liquids and not within
pressures exceeding 1 7 kPa (gauge) shall be the bunded area or the drainage path of Class I or
arranged to discharge in such a way as to prevent Class II liquids do not require emergency relief
localized over-heating of. or flame impingement venting.
on, any part of the tank, in the event vapours from
such vents are ignited. 2.2.5.3 In a vertical tank the construction
referred to in 2.2.5.1 may take the form of a
2.2.4.6 Tanks and pressure vessels storing floating roof, lifter roof, a weak roof-to-shell
Class IA liquids shall be equipped with venting seam, or other approved pressure relieving
devices which shall be normally closed except construction. The weak roof-to-shell seam shall
when venting to pressure or vacuum conditions. be constructed to fail preferential to any other
seam.
Tanks and pressure vessels storing class lB and IC
liquids shall be equipped with venting devices 2.2.5.4 Where entire dependence for
which shall be normally closed except when emergency relief is placed upon pressure
venting under pressure orvacuum conditions, or relieving devices, the total venting capacity of
with approved flame arresters. Tanks of 477,000 both normal and emergency vents shall be
litres (3,000 barrels) capacity or less containing enough to prevent rupture of the shell or bottom
crude petroleum in crude-producing areas, and of the tank if vertical, or of the shell or heads if
outside aboveground atmospheric tanks under horizontal. If unstable liquids are stored, the
3790 litres capacity containing other than Class effects of heat or gas resulting from polymeriza-
IA liquids may have open vents (see 2.2.6.2). tion, decomposition, condensation, or self-
reactivity shall bd taken into account. The total
2.2.4.7 Flame arresters or venting devices capacity of both normal and emergency venting
required in 2.2.4.6 may be omitted for lB and IC devices shall be not less than that derived from
liquids where conditions are such that their use table 8 and 9 except as provided in 2.2.5.6 or
may. in case of obstruction, result in tank
- 2.2.5.7. Such device may be a self-closing
damage. Liquid propertiesjustifying the omission manhole cover, or- one using long bolts that
of such devices include, but are not limited to, permit the cover to lift under internal pressure, or
condensation, corrosiveness, crystallization, an additional or larger relief valve or valves. The
polymerization, freezing or plugging. When any wetted area of the tank shall be calculated on the
of these conditions exist, consideration may be basis of 55% of the total exposed area of a sphere
given to heating,use of devices employing special or spheroid. 75% of the total exposed area of a
materials of construction, the use of liquid seals, horizontal tank and the first 9 m aboveground of
or inerting. the exposed shell area of a vertical tank. (When
more detailed information is required, the
2.2.5 Emergency relief venting for fire ex- American Petroleum Institute Standard No.
posure for aboveground tanks. 2000, Venting atmospheric and low-pressure
storage tanks should be consulted).
2.2.5.1 Except as provided in 2.2.5.2. every
aboveground storage tank shall have some form 2.2.5.5 -If the wetted area do not exceed 260 m2
of construction or device that will relieve and the tank is designed for pressures over 8 kPa
excessive internal pressure caused by exposure (gauge), the total rate of venting shall be
fires. determined in accordance with table 8. When the

23
MS 761:1982

Table 8. Wetted area versus cubic metres free


air per hour (venting capacity) at 101.5 kPa
(abso!ute) and 15C

Wetted Free air venting Wetted Free air Venting


area capacity* area capacity
2 3 2 3
m m /h m m /h

1 321 35 8510
2 6.43 40 9200
3 964 45 9875
4 1286 50 10450
5 1607 55 11010
6 1929 65 12110
7 2250 75 13130
8 2572 85 14100
9 2893 95 15000
10 3214 110 15680
12 3857 130 16600
14 4500 150 17400
16 5143 170 18170
18 5786 200 19200
20 - 6200 230 20170
25 7030 260 21000
30 7800 and over**

Interpolate venting capacity for intermediate values of wetted area.


2
If the wetted area exceeds 260 m but the tank is designed for pressures of
7 kPa (gauge) or lower. no increase in venting capacity is required.

Table 9. Wetted area over 260 m2 and pressures


over 7 kPa (gauge)

Wetted Free air venting Wetted Free air venting


area capacity area capacity
2 3 2 3
m m /h m m /h

260 21000 850 55500


280 22300 1000 63500
300 23600 1300 78700
350 26800 1600 93300
400 29900 2000 112000
450 33000 2500 134500
550 38900 3000 156200
650 44600 3500 177200
750 50100 4000 197700

24
MS761 :1982

exposed wetted area of the surface exceeds 3 for water spray in accordance with NEPA 1 5,
-260 m2 and the tank is designed for pressure over Standard for water spray fixed systems for fire
7 kPa (gauge), the total rate of venting shall be in protection. and drainage in accordance with
accordance with table 9 or calculated by the 2.2.3.2.
following formula:
3 for insulation in accordance with 2.2. 5.7(a).
C = 220A82
where, .1 5 for water spray with insulation in accordance
C is the venting requirement, in cubic.metres of with 2.2.5.7(a) and drainage in accordance with
free air per hour; 2.2.3.2.

A is the exposed wetted surface, in square metres. (a) Insulation systems for which credit is taken
shall meet the following performance criteria:
2.2.5.6 The total venting requirements deter-
mined from table 8 are based on the assumption (i) Remain in place under fire exposure
that the stored liquid will have the characteristics conditions.
of hexane, since this will provide results which are
(ii) Withstanding dislodgment when subjected
within an acceptable degree of accuracy for
almost all petroleum liquids encountered. How- to hose stream impingement during fire ex-
ever, if a greater degree of accuracy is desired, posure. This requirement may be waived where
the total emergency relief venting capacity for any use of solid hose st~eamis not contemplated or
would not be practical. -
specific stable liquid can be determined by the
following formula:
(iii) Maintain a maximum conductancevalue of
20 kcal/m2hC ~vhenthe outer insulation jacket
or cover is at a temperature of 904C (1,660F)
Emergency relief venting capacity (m3/h) =
~110v and when the mean temperature of the insulation
is 538C (1.000F). -

where, 2.2.5.8 The outlet of all vents and vent drains


V is the emergency relief venting capacity from on tanks equipped with emergency venting to
table 8. in cubic metres per hour; permit pressures exceeding 1 7 kPa (gauge) shall
be arranged to discharge in such a way as to
L is the specific latent heat ofvapourization of the
prevent localized overheating of or flame
liquid, in kilojoules per kilogramme;
impingement on any part of the tank. in the event
vapours from such vents are ignited.
M is the molecular weight of the liquid.

2.2.5.7 For tanks containing stable liquids, the 2.2.5.9 Each commercial tank venting device
required air-flow rate of 2.2.5.4 or 2.2.5.6 may be shall have stamped on it the opening pressure,
multiplied by the appropriate factor listed in the the pressure at which the valve reaches the full
following schedule when protection is provided open position and the flow capacity at the latter
as indicated. Only one factor can be used for any pressure. If the start to open pressure is less than
one tank. 1 7 kPa (gauge) and the pressure at full open
position ~sgreater than 1 7 kPa (gauge) the flow
.5 for drainage in accordance with 2.2.3.2 for capacity at 1 7 kPa (gauge) shall also be stamped
tanks over 1 8 m2 of wetted area. on the venting device. The flow capacity shall be~

25
MS761 :1982

expressed in cubic metres per hour of air at vapour conservation or air pollution control.
101.5 kPa (absolute) and 15C. When tank vent piping is manifolded, pipe sizes
shall be such as to discharge, within the pressure
(a) The flow capacity of tank venting devices limitations of the system, the vapours they may be
under 200 mm in nominal pipe size shall be
- required to handle when manifolded tanks are
determined by actual test of each type and size of subject to the same fire exposure.
vent. These flow test may be conducted by the
manufacturer if certified by a qualified impartial 2.2.6.4 Vent piping for tanks storing Class I
observer, or may be conducted by a qualified, liquids shall not be manifolded with vent piping
impartial outside agency. The flow capacity of for tanks storing Class II or Class Ill liquids unless
tank venting devices 200 mm nominal pipe size positive means are provided to prevent the
and larger. .including manhole covers with long vapours from Class I liquids from entering tanks
bolts or equivalent. may be calculated by the storing Class II or Class Ill liquids, to prevent
following formula: contamination (see 1.1.2) and possible change in
classification of the less volatile liquid.
Venting capacity (m3/h) = 0.0575 ~
2.2.7 Tank openings other than vents for
where, aboveground tanks

d is the diameter of orifice, in millimetres; 2.2.7.1 Each connection to an aboveground


tank through which liquid can normally flowshall
AP is the difference in pressure between the be provided with an internal or an external valve
inside and the outside of the tank, in kilopascals.
located as close as practical to the shell of the
tank.
2.2.6 Vent piping for aboveground tanks
2.2.7.2 Each connection below the liquid level
2.2.6.1 Vent piping shall be constructed in
through which liquid does not normallyflowshall.
accordance with section 3.
be provided with a liquid-tight closure. This may
be a valve, plug or blind, or a combination ,pf
2.2.6.2 Where vent pipe outlets for tanks
storing Class I liquids are adjacentto buildings or these.
public ways. they shall be located so that the
2.2.7.3 Openings for gauging on tanks storing
vapours are released at a safe point outside of
Class I liquids shall be provided with a
buildings and not less than 3.5 m above the
vapourtight cap or cover. Such covers shall be
adjacent ground level. In order to aid their
closed when not gauging.
dispersion. vapours shall be discharged upwards
or horizontally away from closely adjacent walls. 2.2.7.4 For Class lB and Class IC liquids other
Vent outlets shall be located so that flammable than crude oils, gasolines and asphalts. the fill
vapours will not be trapped by eaves or other pipe shall be so designed a~dinstalled as to
obstructions and shall be at least 1 .5 m from minimize the possibility of generating static
building openings. electricity.

2.2.6.3 The manifolding of tank vent piping A fill pipe entering the top of a tank shallterminate
shall be avoided except where required for within 150mm of the bottom of the tankand shall
special purposes such as vapour recovery, be installed to avoid excessive vibration.

26
MS761 :1982

2.2.7.5 Filling and emptying connections for 2.3.2.2 Steel underground tanks shall be
Class I, Class II and Class lIlA liquids which are covered with a minimum of 600 mm of earth, or
made and broken shall be located outside of shall be covered with not less than 300 mm of
buildings at a location free from any source of earth, on top of which shall be placed a slab of
ignition and not less than 1 .5 m away from any reinforced concrete not less than 1 00 mm thick.
building opening. Such connections for any When they are, or are likely to be, subjected to
liquid shall be closed and Iiquidtight when not in traffic, they shall be protected against damage
use and shall be properly identified. from vehicles passing over them by at least 1 m of
earth cover, or 450mm of well-tamped earth plus
1 50 mm of reinforced concrete or 200 mm of
asphaltic concrete. When asphaltic or reinforced
2.3 INSTALLATION OF UNDERGROUND/ concrete paving is used as part of the protection,
MOUNDED TANKS it shall extend at least 300 mm horizontally
beyond the outline of the tank in all directions.
2.3.1 Location. Excavation for underground
storage tanks shall be made with due care to 2.3.2.3 Nonmetallic underground tanks shall
avoid undermining of foundations of existing be installed in accordance with the manu-
structures. Underground tanks or tanks under facturers instructions. The minimum depth of
buildings shall be so located with respect to cover shall be as specified in 2.3.2.2 for steel
existing building foundations and supports that tanks.
the loads carried by the latter cannot be
transmitted to the tank. The distance from any 2.3.2.4 For tanks built in accordance with
part of a tank storing Class I liquids to the nearest 2.1.3.1(a), the burial depth shall be such that the
wall of any basement or pit shall be not less than static head imposed at the bottom of the tank
300 mm, and to any property line that can be built will not exceed 69 kPa (gauge) if the fill or vent
upon, not less than I m. The distance from any pipe are filled with liquid. If the depth of cover is
part of a tank storing Class II or Class Ill liquids to greater than the tank diameter, the tank
the nearest wall of any basement, pit or property manufacturer shall be consulted to determin.e if
line shall be not less than 300 mm. reinforcement is required.

2.3.2 burial depth and cover 2.3.3 Corrosion protection. Corrosion protec-
tion for the tank and its piping shall be provided
2.3.2.1 Steel underground tanks shall beseton by one or more of the following methods: (1) use
firm foundations and surrounded with at least of protective coatings or wrappings; (2) cathodic
1 50 mm of noncorrosive inert material such as protection; or (3) corrosion resistant materials of
clean sand or gravel well-tamped in place. The construction. Selection of the type of protection
tank shall be placed in the hole with care, since to be employed shall be based uponthe corrosion
dropping or rolling the tank into the hole can history of the area and the judgement of a
break a weld, puncture or damage the tank, or qualified engineer.
scrape off the protective coating of coated tanks.
Mounded tanks shall be treated as underground 2.3.4 Abandoned underground tanks. Under-
tanks and the appropriate requirements shall ground tanks taken out of service shall be safe-
apply. guarded or disposed of in a safe manner.

27
MS761 :1982

Compliance with the provisions contained within shall not be less than 32 mm nominal inside
appendix A shall be considered to meet this diameter. The required venting capacity depends
requirement. upon the filling or withdrawal rate, whichever is
greater. and the vent line length. Unrestricted
2.3.5 Vents for underground tanks vent piping sized in accordance with table 1 Owill
prevent back-pressure development in tanks from
2.3.5.1 Location and arrangement of vents for exceeding 1 7 kPa (gauge). Where tank venting
Class I liquids. Vent pipes from underground devices are installed in vent lines, their flow
storage tanks storing Class I liquids shall be so capacities shall be determined in accordance
located that the discharge point is outside of with 2.2.5.9.
buildings, higher than the fill pipe opening, and
not less than 4 m above the adjacent ground level.
Table 10. Vent line diameters
Vent pipes shall not be obstructed by devices
provided for vapour recovery or other purposes
Nominal pipe size, mm
unless the tank and associated piping and Maximum flow

equipment are otherwise protected to limit back- litres/mm .


Pipe length-
pressure development to less than the maximum
working pressure of the tank and equipment by 15m 3Dm 6Dm

the provision of pressure-vaccum vents, rupture 350 32 32 32


discs or other tank venting devices installed in the 750 32 32 32
tank vent lines. Vent outlets and devices shall be 1000 32 32 38
1500 32 38 50
protected to minimize the possibility of blockage 2000 38 38 50
from weather, dirt or insect nests, and shall be so 2250 38 50 50
located and directed that flammable vapours will 2500 50 50 50
3000 50 50 76
not accumulate or travel to an unsafe location, 3500 50 50 76
enter building openings or be trapped under 4000 50 50 76
eaves. Tanks containing -Class IA liquids shall be
equipped with pressure and vacuum venting vent lines of 15 m, 30 rn and 60 m of pipe plus 7 ells.
devices which shall be normally closed except
when venting under pressure or vacuum condi- 2.3,5.3 Location and arrangement of vents for
tions. Tanks storing Class lB or Class IC liquids Class I/or Class I/IA liquids. Vent pipes from tanks
shall be equipped with pressure-vacuum vents or storing Class II or Class lIlA liquids shall terminate
with approved flame arresters. Tanks storing outside of buildings and higher than the fill pipe
gasoline are exempt from the requirements for opening. They may be fitted with return bends,
pressure and vacuum venting devices, except as coarse screens or other devices to minimize
required to prevent excessive back-pressure, or ingress of foreign material.
flame arresters, provided the vent does not
exceed 76 mm nominal inside diameter (see also 2.3.5.4 Vent piping shall be constructed in
7.2.1.1) accordance with section 3. Vent pipe shall be so
laid as to drain toward the tank without sags or
2.3.5.2 Vent capacity. Tank venting systems traps in which liquid can collect. They shall be
shall be provided with sufficient capacity to located so that they will not be subjected to
prevent blowback of vapour or liquid at the fill physical damage. The tank end of the vent pipe
opening while the tank is being filled. Vent pipes shall enter the tank through the top.

28
MS 761 :1982

2.3.5.5 When tank vent piping is manifolded. 2.3.6.5 Filling and emptying and vapour re-
pipe sizes shall be such as to discharge. within the covery connections for Class I. Class II or Class
pressure limitations of the system, the vapours lIlA liquids which are made and broken shall be
they can be required to handle when manifolded located outside of buildings at a location free
tanks are filled simultaneously. from any source of ignition and not less than 1.5
m away from any building opening. Such
Exception: For service stations, the capacity of connections shall be closed and Iiquidtightwhen
manifoldd vent piping shall be sufficient to not in use and shall be properly identified.
discharge vapours generated when two mani-
folded tanks are simultaneously filled. 2.3.6.6 Tank openings provided for purposes
of vapour recovery shall be protected against
2.3.5.6 Vent piping for tanks storing Class I possible vapour release by means of a spring-
liquids shall not be manifolded with venf piping loaded check valve or dry-break connection, or
for tanks storing Class II or Class III liquids unless other approved device, unless the opening is
positive means are provided to prevent the pipe-connected to a vapour processing system.
vapours from Class I liquids from entering tanks Openings designed for combined fill and vapour
storing Class II or Class III liquids, to prevent recovery shall also be protected agaLnst vapour
contamination (see 1.1 .2) and possible change in release unless connection of the liquid delivery
classification of the less volatile liquid. line to the fill pipe simultaneously connects the
vapour recovery line: All connections shall be
2.3.6 Tank openings other than vents for va p0 u rti g ht.
underground tanks

2.3.6.1 Connections for all tank o~eningsshall


be !iquidtight.
2.4 INSTALLATION OF TANKS INSIDE OF
2.3.6.2 Openings for manual gauging, if BUILDINGS
independent of the fill pipe, shall be provided with
a liquidtight cap or cover. Covers shall be kept 2.4.1 Location. Tanks shall not be permitted
closed when not gauging. If inside a building. inside of buildings except as provided in sections
each such opening shall be protected against 5. 6, 7. 8 or 9.
liquid overflow and possible vapour release by
means of a spring loaded check valve or other 2.4.2.Vents. Vents for tanks inside of buildings
approved device. shall be as required in 2.2.4, 2.2.5, 2.2.6.2 and
2.3.5, except that emergency venting by the use
2.3.6.3 Fill and discharge lines shall enter of weak roof seams on tanks shall not be
tanks only through the top. Fill lines shall be permitted. Automatic sprinkler systems designed
sloped toward the tank. in accordance with the requirements of the
Uniform Building By-Laws, may he accepted by
2.3.6.4 For Class lB and Class IC liquids other the authority having jurisdiction as equivalent to
than crude oils, gasolines and asphalts. the fill water spray systems for purposes of calculating
pipe shall be so designed and installed as to the required air flow rates for emergency vents in
minimize the possibility of generating static 2.2.5.7. Except for tanks containing Class IIIB
electricity by terminating within 1 50 mm of the liquids, vents shall terminate outside the
bottom of the tank. buildings.

29
MS 761:1982

2.4.3 Vent piping. Vent piping shall be heavy-duty flat gauge glasses, magnetic,
constructed in accordance with section 3. hydraulic or hydrostatic remote reading devices
and sealed float gauges.
2.4.4. Tank openings other than vents for
tanks inside buildings 2.4.4.5 For Class lB and Class IC liquids other
than crude oils, gasolines and asphalts, the fill
2.4.4.1 Connections for all tanks openings pipe shall be so designed and installed as to
shall be liquidtight. minimize the possibility of generating static
electricity by terminating within 1 50 mm of the
2.4.4.2 Each connection to a tank inside of bottom of the tank.
buildings through which liquid can normally flow
shall be provided with an internal or an external 2.4.4.6 The fill pipe inside of the tank shall be
valve located as close as practical to the shell of installed to avoid excessive vibration of the pipe.
the tank.
2.4.4.7 The inlet of the fill pipe and the outlet of
2.4.4.3 Tanks for storage of Class I or Class II
a vapour recovery line for which connections are
liquids inside buildings shall be provided with
made and broken shall be located outside of
either:
buildings at a location free from any source of
ignition and not less than 1.5 m away from any
(a) a normally closed remotely activa.ted valve;
building opening. Such connetions shall be
(b) an automatic-closing heat-activated valve; closed and tight when not in use and shall be
or properly installed.

(c) another approved device on each liquid 2.4.4.8 Tanks storing Class I, Class II and Class
transfer connection below the liquid level, except lIlA liquids inside buildings shall be equipped
for connections used for emergency disposal, to with a device, or other means shall be provided, to
provide for quick cut-off of flow in the event of fire prevent overflow into the building Suitable
in the vicinity of the tank. devices include, but are not limited to, a float
valve, a preset meter on the fill line, a valve
This function can be incorporated in the valve actuated by the weight of the tank contents, a low
required in 2.4:4.2, and if a separate valve, shall head pump which is incapable of producing
be located adjacent to the valve required in overflow, or a Iiquidtight overflow pipe at least
2.4.4.2. one pipe size larger than the fill pipe discharging
by gravity back to the outside source of liquid or
2.4.4.4 Openings for manual gauging of Class I to an approved location.
or Class II liquids, if independent of the fill pipe,
shall be provided with a vapourtight cap orcover. 2.4.4.9 Tank openings provided for purposes
Openings shall be kept closed when notgauging. of vapour recovery shall be protected against
Each such opening for any liquid shall be possible vapour release by means of a spring-
protected against liquid overflow and possible loaded check valve or dry-break connections, or
vapour release by means of a spring loaded check other approved device, unless the opening is
valve or other approved device. Substitutes for pipe-connected to a vapour processing system.
manual gauging include. but are not limited to, Openings designed for combined fill and vapour

30
MS 761:1982

recovery shall also be protected against vapour engineering consideration. Appendix N of the API
release unless connection of the liquid delivery Standard No. 620, Recommended rules for the
line to the fill pipe simultaneously connects the design and construction of large, welded, low-
vapour recovery line. All connections shall be pressure storage tanks, contains information
yapo u rti g ht. regarding supporting structures.

2.5.5 Every tank shall be so supported as to


2.5 SUPPORTS, FOUNDATIONS AND prevent the excessive concentration of loads on
ANCHORAGE FOR ALL TANK LOCATIONS the supporting portion of the shell.

2.5.1 Tanks shall rest on the ground or on 2.5.6 Where a tank is located in an area that
foundations made of concrete, masonry, piling or may be subjected to flooding, the applicable
steel. Tank foundations shall be designed to precautions outlined in appendix B shall be
minimize the possibility of uneven settling of the observed.
tank and to minimize corrosion in any part of the
tank resting on the foundation. Appendix E of API
Standard No. 650, Specification for welded steel 2.6 SOURCES OF IGNITION
tanks for oil storage. and appendix B of API
Standard No. 620, Recommended rules for the 2.6.1 In locations where flammable vapours
design and construction of large, welded, low- may be present, precautions shall be taken to
pressure storage tanks, provided information on prevent ignition by eliminating or controlling
tank foundations. sources of ignition. Sources of ignition may
include open flames, lightning, smoking, cutting
2.5.2 When tanks are supported above the and welding, hot surfaces, frictional heat, sparks
foundations, tank supports shall be installed on (static, electrical and mechanical), spontaneous
firm foundations. Supports for tanks storing ignition, chemical and physic~I-chemicalreac-
Class I, Class Iron Class lIlA liquids shall be of tion and radiant heat. NFPA 77, Recommended
concrete, masonry or protected steel. Single practice on static electricity, and MS___________
wood timber supports (not cribbing) laid hori- Code of practice for the protection of structures
zontally may be used for outside aboveground against lightning provide information on suCh
tanks if not more than 300 mm high at their protection. -

lowest point.

2.5.3 Steel supports or exposed piling for tanks 2.7 TESTING -

storing Class I, Class II or Class lIlA liquids shall be


protected by materials having a fire resistance 2.7.1 All tanks, whether shop-built or field
rating of not less than two hours. exceptthat steel erected, shall be tested before they are placed in
saddles need not be protected if less than 300 service in accordance with the applicable
mm high at their lowest point. At the discretion of paragraphs of the Code under which they were
the authority having jurisdiction, water spray built.
protection in accordance with the Uniform
Building By-Laws may be used.

2.5.4 Thedesignofthesupportingstructurefor
tanks such as spheres shall require special Malaysian Standard in the course of preparation.

31
MS761 :1982

2.7.2 When the vertical length of the fill and available for vertical atmospheric fixed roof
vent pipes is such that when filled with liquid the storage tanks largerthan 1 90,000 litres, capacity
static head imposed upon the bottom of the tank storing Class I liquids if located in a congested
exceeds 69 kPa (gauge), the tank and related area where there is an unusual exposure hazard
piping shall be tested hydrostatically to a to the tank from adjacent property orto adjacent
pressure equal to the static head thus imposed. In property from the tank. Fixed roof tanks storing
special cases where the height of the vent above Class II or Ill liquids at temperatures below their
the top of the tank is excessive, the hydrostatic flash points and floating roof tanks storing any
test pressure shall be determined by using liquid generally do not require protection when
recognized engineering practice. installed in compliance with 2.2.

2.7.3 In addition to the test called for in 2.7.1 2.8.2 Signs and notices
and 2.7.2, all tanks and connections shall be
tested for tightness. Except for underground 2.8.2.1 The application of NFPA 704, ldenti~
tanks, this tightness shall be made at operating fication of the fire hazards of materials, to storage
pressure with air, inert gas or water prior to tank containing liquids shall not be required
placing the tank in service. In the case of field- except when the contents have a health or
erected tanks the test called for in 2.7.1 or 2.7.2 reactivity degree of hazard of 2 or more or a
may be considered to be the test for tank flammability rating of 4. The marking need not be
tightness. Underground tanks and piping, before applied directly to the tank but located where it
being covered, enclosed, or placed in use, shall c,an readily be seen, such as on the shoulder of an
be tested for tightness hydrostatically, or with air accessway or walkway to the tank or tanks or on
pressure at not less than 21 kPa (gauge) and not the piping outside of the bunded area. If more
more than 35 kPa (gauge) (see 3.7.1 for testing than one tank is involved, the markings shall be so
pressure piping). located that each tank can readily be identified.

2.7.4 Before the tank is initially placed in 2.8.2.2 Where flammable and combustible
service, all leaks or deformations shall be liquids are stored, a sign in accordance with
corrected in an acceptable manner. Mechanical MS 683, Class labels for dangerous goods,
caulking is not permitted for correcting leaks in appropriate to the class, shall be provided.
welded tanks.

2.7.5 Tanks to be operated at pressures below 2.9 PREVENTION OF OVERFILLING OF TANKS


their design pressure may be tested by the
applicable provisions of 2.7.1 or 2.7.2 based 2.9.1 Tanks receiving transfer of Class I liquids
upon the pressure developed under full from mainline pipelines or marine vessels and
emergency venting of the tank. located in an areawhere overfilling may endanger
a place of habitation or public assembly shall be
either:

2.8 FIRE PROTECTION AND IDENTIFICA- (a) Gauged at frequent intervals while receiving
TION transfer of product and communications main-
tained with mainline pipeline or marine personnel
2.8.1 Afire extinguishing system in accordance so that flow can be promptly shut down or
with an approved standard shall be provided or be diverted, or

32
MS 761:1982

(b) Equipped with an independent high level devices which serve such purposes as mixing,
alarm located where personnel are on duty during separating, snubbing, distributing, metering, or
the transfer and can promptly arrange for flow controlling flow.
stoppage or diversion, or

(c) Equipped with an independent high level 3.2 MATERIALS FOR PIPING, VALVES AND
alarm system that will automatically shut down or FIlliNGS
divert flow.
3.2.1 Pipe, valves, faucets, fittings and other
pressure containing parts as covered in 3.1.3
shall meet the material specifications and
pressure and temperature limitations of ANSI
B31.3 Petroleum refinery piping, or ANSI
B31.4. Liquid petroleum transportation piping
systems or equivalent except as provided by
SECTION THREE: PIPING, VALVES AND
3.2.2. 3.2.3, and 3.2.4. Plastic or similar
FITTINGS
materials, as permitted by 3.2.4, shall be
3.1 GENERAL designed to specifications embodying recogniz-
ed engineering principles and shall be com-
3.1.1 The design, fabrication, assembly. test patible with the fluid service.
and inspection of piping systems containing
liquids shall be suitable for the expected working 3.2.2 Nodular iron shall conform to ASTM
pressures and structural stresses. Conformity A395. Ferritic ductile iron pressure retaining
with the applicable sections of ANSI B31. Code castings for use at elevated temperatures.
for pressure piping or equivalent, and the
provisions of this section shall be considered 3.2.3 Valves at storage tanks, as required by
2.2.7.1 and 2.4.4.2. and their connections to the
prima facie evidence of compliance with the
tank shall be of steel or nodular iron except as
foregoing provisions.
provided in 3.2.3.1 or 3.2.3.2.
3.1.2 This section does not apply to any of the
3.2.3.1 Valves at storage tanks may be other
following:
than steel or nodular iron when the chemical
(a) Tubing or casing on any oil orgaswells and characteristics of the liquid stored are not
any piping connected directly thereto. compatible with steel or when installed internally
to the tank. When installed externallytothetank.
(b) Motor vehicle, aircraft. boat or portable or the material shall have a ductility and melting
stationary engine. point comparable to steel or nodular iron so asto
withstand reasonable stresses and temperatures
(c) Piping within the scope of any applicable involved in fire exposure. or otherwise be
boiler and pressure vessel code. protected such as by materials having a fire
resistance rating of not less than two hours.
3.1.3 Piping systems consist of pipe. tubing,
flanges, bolting. gaskets, valves, fittings. the 3.2.3.2 Cast iron, brass, copper. aluminium.
pressure containing parts of other components malleable iron, and similar materials maybe used
such as expansion joints and strainers, and on tanks described in 2.2.2.2 or for tanks storing

33
MS 761 :1982

Class lllB liquids when the tank is located above or below ground. If used aboveground
outdoors and not within a bunded area or outside of buildings, the piping shall either be
drainage path of a tank storing a Class I, Class II secured to prevent disengagement at the fitting,
or Class !IIA liquid. or the piping system shall be so designed that any
spill resulting from disengagement could not
3.2.4 Low melting point materials. such as unduly expose persons, permanent buildings or
aluminium, copper and brass; or materials which structures, and could be readily controlled by
soften on fire exposure, such as plastics; or remote valves.
nonductile material such as cast iron, may be
,

used underground for all liquids within the


pressure and temperature limits of ANSI B31,
3.4 SUPPORTS
Code for pressure piping or equivalent. If such
materials are used outdoors in. aboveground
3.4.1 Piping systems shall be substantially -
piping systems handling Class I. Class II or
supported and protected against physical
Class lIlA liquids or within buildings handling any
damage and excessive stresses arising from
liquid, they shall be either: (a) suitably protected
settlement, vibration, expansion or contraction.
against fire exposure, or (b) so located that any
The installation of nonmetallic piping shall be in
leakage resulting from the failure would not
accordance with the manufacturers instructions.
unduly expose persons, -permanent buildings or
structures, or (c) located where leakage can
readily be controlled by operation of an
accessible remotely located valve or valves. 3.5 PROTECTION AGAI NST CORROSION

3.2.5 Piping, valves and fittings may have 3.5.1 All piping for liquids, both aboveground
combustible or non-combustible linings. and underground, where subject to external
corrosion, shall be painted or otherwise
protected.

3.3. PIPE JOINTS


3.6 VALVES
3.3.1 Joints shall be made Iiquidtight and shall
be either welded, flanged or threaded. exceptthat 3.6.1 Piping systems shall contain a sufficient
approved flexible connectors may be used when number of valves to operate the system properly
installed in accordance with 3.3.2. Threaded and to protect the plant. Piping systems in
joints shall be made uptightwith a suitablethread connection with pumps shall contain a sufficient
sealant or lubricant. Joints in piping systems number of valves to control properly the flow of
handling Class I liquids shall be welded when liquid in normal operation and in the event of
located in concealed spaces within buildings. physical damage. Each connection to pipelines.
by which equipment such as tank cars or tank
3.3.2 Pipe joints dependent upon the friction vehicles discharge liquids by means of pumps
characteristics or resiliency of combustible into storage tanks, shall be provided with a check
materials for mechanical continuity or liquid- valve for automatic protection against back-flow
tightness of piping shall not be used inside if the piping arrangement is such that back-flow
buildings. They may be used outside of buildings from the system is possible. (See also 2.2.7.1).

34
MS 761 :1982

3.7 TESTING - (d) Medicines, foodstuffs, cosmetics and other


consumer products containing not more than
3.7.1 Unless tested in accordance with the 50% by volume of water miscible liquids and with
applicable sections of ANSI B31 Code. for the remainder of the solution not being
pressure piping or equivalent all piping before flammable when packaged in individual con-
being covered, enclosed or placed in use shall be tainers not exceeding 4 litres in size.
hydrostatically tested to 1 5% of the maximum
anticipated pressure of the system, or (e) The storage of liquids that have no fire point
pneumatically tested to 11 0% of the maximum when tested by ASTM D 92, Cleveland open cup
anticipated pressure of the system. but not less test method. up to the boiling point of the liquid,
than 35 kPa (gauge) at the highest point of the or up to a temperature at which the sample being
system. This test shall be maintained for a tested shows an obvious physical change.
sufficienttimetocompletevisual inspection of all
joints and connections. but for at least 10 (f) The storage of distilled spirits and wines in
minutes. wooden barrels or casks.

4.1.3 For the purpose of this section, unstable


liquids and flammable aerosols shall betreated as
Class IA liquids.

SECTION FOUR: CONTAINER AND


PORTABLE TANK STORAGE 4.2 DESIGN, CONSTRUCTION, AND CAPACITY
OF CONTAINERS.
4.1 APPLICATION

4.1.1 This section shall apply to the storage of 4.2.1 Only approved containers and portable
liquids, including flammable aerosols, in durms tanks shall be used. Metal containers and
or other containers not exceeding 225 litres portable tanks meeting the requirements of, and
individual capacity and portable tanks not containing products authorized by, Code of
exceeding 2500 litres individual capacity and Federal Regulations (United States Department
limited transfers incidental thereto. of Transportation (DOT) Regulations) or
NFPA 386, Standard for portable shipping tanks
or equivalent, shall be acceptable.
4.1.2 This section shall not apply to the
following: 4.2.2 Each portable tank shall be provided with
one or more devices installed in the top with
(a) Storage of containers in bulk plants. service
sufficient emergency venting capacity to limit
stations, refineries, chemical plants and
internal pressure under fire exposure conditions
distilleries.
to 69 kPa (gauge), or 30% of the bursting
(b) Liquids in the fuel tanks of motor vehicles pressure of the tank, whichever is greater. The
aircraft, boats or portable or stationary engines. total venting capacity shall be not less than that
specified in 2.2.5.4 or 2.2.5.6-. At least one
(c) Beverages when packaged in individual con- pressure-actuated vent having a minimum
tainers not exceeding a capacity of 4 litres. capacity of 170 m3 of free air per hour[101.5 kPa

35
MS761 :1982

(absolute) and 1 5C] shall be used. It shall be set 4.3 DESIGN, CONSTRUCTION AND CAPACITY
to open at not less than 35 kPa (gauge). If fusible OF STORAGE CABINETS
vents are used. they shall be actuated by elements
that operate at a temperature not exceeding 4.3.1 Not more than 450 litres of Class I, Class
1 50C. When used for paints, drying oils and II and Class lIlA liquids may be stored in a storage
similar materials where plugging of the pressure- cabinet. Of this total, not more than 225 litres
actuated vent can occur, fusible vents or vents of may be of Class I and ClassIl liquids and not more
the type that soften to failure at a maximum of than three (3) such cabinets may be located in a
1 50C under fire exposure. may be used for the single fire compartment, except that in an
entire emergency venting requirement. industrial occupancy, additional cabinets may be
located in the same fire compartments if the
4.2.3 Containers and portable tanks for liquids additional cabinet, or group of not more than
shall conform to table 11 except as provided in three (3) cabinets is separated from other
4.2.3.1 or 4.2.3.2. cabinets or group of cabinets by at least 30 m.

4.2.3.1 Medicines, beverages, foodstuffs,


cosmetics and other common consumer 4.3.2 Metal cabinets constructed in the follow-
products, when packaged according to com- ing manner are acceptable. The bottom, top, door
monly accepted practices for retail sales, shall be and sides of cabinet shall be of at least No. 1 8
exempted from the requirements of 4.2.1 and gauge sheet steel and double walled with 38 mm
4.2,3, air space Joints shall be riveted, welded or made
tight by some equally effective means. The door
4.2.3.2 Class IA and class lB liquids may be shall be provided with a three-point latch
stored in glass containers of not more than arrangement and the door sill shall be raised at
4 litres capacity if the required liquid puritywould least 50 mm above the bottom of the cabinet to
be affected by storage in metal containers or if the retain spilled liquid within the cabinet. Cabinets
liquid would cause excessive corrosion of the shall be labelled in conspicuous lettering,
metal container. FLAMMABLE KEEP FIRE AWAY.

Table 11. Maximum allowable size of containers and portable tanks

Flammable liquids, Combustible


litres liquids, litres
Container type

Class IA Class lB Class IC Class II Class Ill

Glass 0,5 1 4 4 20
Metal (other than
DOT drums) or -
approved plastic 4 20 20 20 20
Safety cans 7,5 20 20 20 20
Metal drum
(DOT Spec) 225 225 225 225 225
Approved portable
tanks 2500 2500 2500 250C) 2500

36
M5761 :1982

4.4 DESIGN, CONSTRUCTION AND OPERA- automatically in a fire emergency by provision of


TION OF SEPARATE INSIDE STORAGE AREAS. approved closure devices. Fire doors shall be
(See 1.3) installed in accordance with an approved
standard.
4.4.1 Inside rooms
(b) Noncombustible liquidtight raised sills or
4.4.1.1 Inside rooms shall be constructed to ramps at least 1 00 mm in height or otherwise
meet the selected fire resistance rating as designed to prevent the flow of liquids to the
specified in 4.4.1.4. Such construction shall adjoining areas. A permissibI~alternative to the
comply with the test specifications given in the sill or ramp is an open-grated trench, which
Uniform Building By-Laws. Except for drains, drains to a safe location, across the width of the
floors shall be liquidtight and the room shall be opening inside of room.
Iiquidtight where the walls join the floor. Where
an automatic fire protection system is provided, 4.4.1.3 Wood at least 25 mm nominal thick-
as indicated in 4.4.1.4. the system shall be ness may be used for shelving, racks, dunnage.
designed and installed in accordance with an scuffboards. floor overlay and similar installa-
approved standard for the type of system tions.
selected.

4.4.1.2 Openings in interior walls to adjacent 4.4.1.4 Storage in inside rooms shall comply
rooms or buildings shall be provided with: with table 12. -

(a) Normally - closed, approved 11/2 hour fire 4.4.1.5 Electrical equipment and wiring
doors for interior walls with fire resistance rating located in inside booms used for Class I liquids
of 2 hours or less. Where interior walls are shall meet the requirements for Zone 2 (see
required- to have greater than 2 hours fire appendix C). Electrical equipment and wiring
resistance rating, the approvedfiredoors shall be located in inside rooms used for Class II and Class
compatible with the wall rating. Doors may be Ill liquids shall meet the requirements of the
arranged to stay open during material handling Electricity Regulations 1951 (Revised 1977) for,
operations if doors are designed to close general use.

Table 12. Storage in inside rooms

Automatic Maximum Total allowable 2


fire protection* Fire 2 quantities Litres/m
resistance floor area, m
provided floor area

YES 2 hour 45 400


NO 2 hour 45 160
YES 1 hour 14
NO 1 hour 14 80
200

Fire protection system shall be sprinkler. water spray, carbon dioxiae. dry chemical. halon or
other approved system.

37
MS 761 :1982

4.4.1.6 Every inside room shall be provided shall provide ready accessibility for fire fighting
with either a gravity or a continuous mechanical operations through provision of access
exhaust ventilation system. Mechanical ventila- openings, windows or lightweight non-
tion shall be used if Class I liquids are dispensed combustible wall panels.
within the room.
Where Class IA or lB liquids are dispensed. or
(a) Exhaust air shall be taken from a point near a where Class IA liquids are stored in containers
wall on one side of the room and within 300 mm larger than 4 litres, the exterior wall or roof
of the floor with one or more make-up inlets construction shall be designed to include
located on tF~eopposite side of the room within explosion venting features, such as lightweight
300 mm fr~mthe floor. The location of both the wall assemblies, light-weight roof assemblies.
exhaust and inlet air openings shall be arranged roof hatches or windows of the explosion venting
to provide, as far as practicable. air movements type.
across all portions of the floor to prevent
acOumulation of flammable vapours. Exhaust 4.4.2.2 Where other portions of buildings or
from the room shall be directly to the exterior of other properties are exposed each opening in the
the building. If ducts are used, they shall not be exposing wall shall be protected with an
used for any other purpose and shall complywith approved 1 hour fire door installed in
the requirements of the Uniform Buildings By- accordance with an approved standard and the
Laws. If make-up air to a mechanical system is walls shall have a fire resistance rating of not less
taken from within the building, the opening shall than 2 hours.
be equipped with an approved fire door or
4.4.2.3 Except as noted in 4.4.2.6. interior
damper. For gravity systems. the make-up air
walls, ceiling and floors shall have a fire
shall be supplied from outside the building.
resistance rating of notlessthantwo hourswhere
floor area of the room or building exceeds 28 m2
(b) Mechanical ventilation systems shall
or a fire resistance rating of not less than one hour
provide at least 0.3 m3 per minute of exhaust per
for a floor area of 28 m2 or less. Such con-
squaremetre of floor area. but not less than
struction shall, comply with the test specifica-
4.3 m3/min.
tions given in the Uniform Building By-Laws.
Walls shall be liquidtight at the floor level.
4.4.1.7 In every inside room, an aisle at least
1 mwide shall be maintained sothat nocontainer 4.4.2.4 Openings in interior walls to adjacent
- is more than 4 m from the aisle. Containers over rooms or buildings shall be in accordance with
11 5 litres capacity storing Class I or Class II 4.4.1.2.
liquids shall not be stored more than one
container high. 4.4.2.5 Curbs. scuppers. special drains or
other suitable means shall be provided to prevent
4.4.1.8 Where dispensing is being done in the flow of liquids under emergency conditions
inside rooms, operations shall comply with the into adjacent building areas except where the
pro-visions of section 5. individual container capacity is 20 litres or less or
if the liquids stored are only Class Ill liquids. The
4.4.2 Cutoff rooms and attached buildings. drainage system, if used, shall have sufficient
capacity to carry off expected discharge of water
4.4.2.1 Construction design of exterior walls from fire protection systems and hose streams.

38
MS761 :1982

4.4.2.6 Roofs of attached buildings, one story class; the sum of proportional amounts shall not
in height, may be lightweight non-combustible exceed 1 00%. (See example).
construction if the separating interior wall as
specified in 4.4.2.3 has a minimum 1 m parapet. Example: It is desired to store Class 13. Class IC
and Class Il liquids in portable tanks according to
4.4.2.7 Unprotected storage in cutoff rooms the quantities permitted by table 1 3. If the
and attached buildings shall comply with table quantities of Class lB and Class IC liquids stored
1 3. (See 4.4.2.9 for mixed storage of liquids). are 1 900 litres (25% of maximum total permitted
for Class lB liquids) and 3800 litres (25% of
4.4.2.8 Protected storage in cuttoff rooms and maximum total permitted for Class IC liquids)
attached buildings shall comply with 4.6 as respectively, than the quantity of Class II liquids
applicable. (See 4.4.2.9 for mixed storage of that is permitted shall not exceed 20.800 litres
liquids). (50% of the maximum total permitted for Class II
liquids).
4.4.2.9 Where two or more classes of liquids
are stored in a single pile or rack section. the
maximum quantities and height of storage 4.4.2.10 Dispensing operations of Class I or
permitted in that pile or rack section shall be the Class II liquids are not permitted in cutoff rooms
smallest of the two or more separate quantities or attached buildings exceeding 93 m2floor area.
and heights. The maximum total quantities In rooms where dispensing is permitted.
permitted shall be limited to a sum of proportional electrical systems and ventilation shall be
amounts that each class of liquid present bears to provided per 4.4.1 .5 and 4.4.1 .6 and operations
the maximum total permitted for its respective shall comply with the provisions of section 6.

Table 13. Indoor unprotected storage of liquids in containers and portable tanks

Container storage Portable tank storage

Max. pile Max. quantity Max. total Max. pile Max. quantity Max. total
Class height per pile quantity height per pile quantity
(m) (litres) (litres) (m) (litres) (litres)

IA 1.5 2,500 2,500 Not permitted

lB 1.5 5,200 5,200 2 7,600 7,600

IC 1.5 10,400 10,400 2 15,200 15,200

II 3.0 15,600 31,200 2 20,800 41,600

11 1A 4.5 52,00 104,100 2 83,300 166,600

lii B 4.5 52,000 208,200 2 83,300 - 333,200

39
MS 761 :1982

4.4.2.11 Basement storage areas, Class I liquids shall be in containers stored in storage
liquids shall not be permitted in the basement cabinets, in safety cans. or in a separate inside
areas of cutoff rooms and attached buildings. storage area not having an opening com-
Class II and Class lIlA liquids may be stored in municating with that portion of the building used
basements provided that automatic sprinkler by the public.
protection and other fire protection facilities are
provided in accordance with 4.6. 4.5.4 Office, educational and institutional
occupancies. Storage shall be limited to that
required for operation of office equipment.
4.5 INDOOR STORAGE maintenance, demonstration and laboratory
work. This storage shall comply with the
4.5.1 Basic conditions provisions of 4.5.4.1 to 4.5.4.4 except that the
storage for industrial and educational laboratory
4.5.1.1 The storage of any liquids shall not work shall comply with the NFPA 45 Standard on
physically obstruct a means of egress. Class I fire protection for laboratories using chemicals.
liquids in other than separate inside storage areas
or warehouses shall be so placed that a fire in the 4.5.4.1 Containers for Class I liquids outside of
liquid storage would not preclude egress from the a separate inside storage area shall not exceed a
area. capacity of 4 litres exceptthat safety cans can be
of 7.5 litres capacity.
4.5.1.2 The storage of liquids in containers or
portable tanks shall comply with 4.5.2 to 4.5.7 as 4.5.4.2 Not more than 40 litres of Class I and
applicable. Where separate inside storage areas Class II liquids combined shall be stored outside
are required, they shall conform to 4.4. Where of a storage cabinet or a separate inside storage
other factors substantially increase or decrease area in a single fire compartment except in safety
the hazard, the authority having jurisdiction may cans.
modify the quantities specified.
4.5.4.3 Not more than 95 litres of Class I and
4.5.1.3 Liquids used for building maintenance Class II liquids combined shall be stored in a
painting or other similar infrequent maintenance single fire compartment in safety cans outside of
purposes may be stored temporarily in closed a separate inside storage area or storage cabinet.
containers outside of storage cabinets or
separate inside storage areas, if limited in 4.5.4.4 Not more than 225 litres of Class lIlA
amount, not to exceed a 10-day supply at Iiquids shall be stored outside of a separate inside
anticipated rates of consumption. storage area or storage cabinet.

4.5.2 Residential buildings and flats. Storage 4.5.5. Mercantile occupancies and retail
in excess of 40 litres per household of Class I and stores; and other related areas accessible to the
Class II liquids combined shall be prohibited. In public.
addition, storage in excess of 50 litres per
household of Class lIlA liquid shall be prohibited. 4.5.5.1 In rooms or areas accessible to the
public, storage of Class I, Class II and Class lIlA
4.5.3 Assembly occupancies and hotels. liquids shall be limited to quantities needed for
Storage in excess of 40 litres of Class I and Class display and normal merchandising purposes but
II liquids combined or 225 litres of Class lIlA shall not exceed 80 litres per m2 of gross floor

40
MS761 :1982

area. Storage of Class IA liquids shall be separate. detached buildings or shall be


prohibited in basement display areas and limited separated from other type occupancies by a
to 40 litres per m2 on other floors. In areas not standard 4 hour fire wall, orafire partition having
protected, storage of Class lB. IC, and II liquids on a fire resistance rating of not less than two (2)
other than the ground floor shall be limited to 40 hours. Each opening in a fire wall shall be
litres per m2 of gross floor area. The gross floor protected on each side of the wall with automatic
area used for computing the maximum quantity closing approved 3-hour fire doors. Each open-
permitted shall be considered as that portion of ing in a fire partition shall be protected with an
the floor actually being used for merchandising automatic-closing approved 11/2 hours fire doors.
liquids and immediately adjacent aisles. The doors shall be installed in accordance with an
approved standard.
4.5.5.2 The aggregate quantity of additional
stock in areas not accessible to the public shall 4.5.6.2 Warehousing operations that involve
not exceed the greater of that which would be storage of li~uidsshall be restricted to separate
permitted if the area were accessible to the public inside storage areas or to liquid warehouses in
or 225 litres of Class IA, 450 litres of Class lB. accordance with 4.4 or 4.5.7, as applicable
680 litres of Class IC. 900 litres of Class II, or except as provided in 4.5.6.3.
2500 litres of Class lIlA liquids, or 900 litres in
any combination of Class I and Class II liquids 4.5.6.3 Class lB and IC liquids in containers of
subject to the limitations of the individual class. 4 litres or less capacity. Class II liquids in
For water miscible liquids, or for protected areas containers of 20 litres or less capacity, Class Ill
these quantities may be doubled. liquids in containers of 225 litres or less capacity
may be stored in warehouses handling com-
4.5.5.3 Quantities in excess of those permitted
-
bustible commodities, provided that the storage
in 4.5.5:2 shall be stored in accordance with areas is protected and the quantities and height
other appropriate sections of this code. of liquid storage are limited to:

4.5.5.4 Containers shall not be stacked more (a) Class lB and IC 2500 1.5m
litres high
than 1 m or 2 containers high. whichever is the
greater. unless on fixed shelving or otherwise (b) Class II 5200 1,5.m
satisfactorily secured. litres high
(c) Class lIlA 10,400 3 m
4.5.5.5 Shelving shall be of stable construc- - litres, high
tion, of sufficient depth and arrangement such
(d) Class IIIB 52,000 4.5 m
that containers displayed thereon shall not easily litres high.
be displaced.
The liquid storage shall also conform to 4.5.6.4,
4.5.5.6 Leaking containers shall be removed 4.5.6.5, 4.5.6.6 and 4.5.6.7.
immediately to an adequatelyventilated area, and
the contents transferred to an undamaged 4.5.6.4 Basementstorageareas. Class I liquids
container. shall not be permitted in the basement areas of
buildings. Class II and Class lIlA liquids may be
4.5.6 General purpose warehouses. (See 1.3). stored in basements provided that automatic
sprinkler protection and other fire protection
4.5.6.1 General purpose warehouse shall be facilities are provided in accordance with 4.6.

41
MS 761 :1982

4.5.6.5 Palletized, solid pile or rack storage. other type occupancies by standard 4-hour fire
Liquids in containers may be stored on pallets, in walls, with communicating openings protected
solid piles or on racks subject to the quantities on each side of the wall with automatic-closing
and heights limits of 4.5.6.3 provided the approved 3-hour fire doors. Fire doors shall be
protection is in accordance with 4.6, as installed in accordance with an approved
applicable. standard.

4.5.6.6. Separation and aisles. Palletized or 4.5.7.2 If the warehouse building is located
solid pile storage shall be arranged so that .piles more than 3 m but less than 1 5 m from a
permitted in 4.5.6.3 are separated from each permanent building or line of adjoining property
other by at at least 1 .2 m aisles. Aisles shall be that can be built upon. the exposing wall shall
provided so that no container is more than 3.6 m have a fire resistance rating of at least 2 hours
from an aisle. Where the storage of liquids is on with each opening protected with an approved
racks, a minimum of 2 m wide aisle shall be 1 1/2-hour fire door.
provided between adjacent rows of racks and
adjacent storage of liquids. Main aisles shall be a 4.5.7.3 If the warehouse is located 3 m or less
minimum of 2.4 m wide. Where ordinary from a permanent building or line of adjoining
combustible cornmodities are stored in the same property that can be built up on. the exposing wall
area as liquids in containers, the minimum shall have a fire resistance rating of 4 hours with
distance between the types of storage shall be each opening protected with an approved
2.4 m. - 3-hour fire door.

4.5.6.7 Mixed storage. Liquids shall not be 4.5.7.4 An attached warehouse, having com-
stored in the same pile or in the same rack municating openings in the required 4-hour fire
sections as ordinary combustible commodities. wall separation from the adjacent building area
Where liquids are packaged together with shall have these openings protected by:
ordinary combustibles. as in kits, the storage shall
be considered on the basis of whichever (a) Normally closed approved 3-hour fire doors
commodity predominates. When two or more on each side of the wall. These doors may be
c-lasses of liquids are stored in a single pile or arranged to stay open during material handling
single rack section, the maximum quantities operations, only if the doors are designed to close
permitted in the pile or rack section shall be the automatically in a fire emergency by provision of
smallest of the two or more separate maximum approved closure devices.
quantities. and the height of storage permitted in
(b) Non-combustible Iiquidtight, raised sills or
that pile or rack section shall be the least of the
ramps, at least 100mm in height, or other design
two or more separate heights.The maximum total
features to preventflowofliquidstotheadjoining
quantities permitted shall be limited to the sum of
proportional amounts that each class of liquid area.
present bears to the maximum total permitted for
4.5.7.5 Fire doors shall be installed in
its respective class. The sum of proportional
accordance with an approved standard.
amounts shall not exceed 100 %.

4.5.7.6 The total quantity of liquids within a


4.5.7 Liquid warehouses. (See 1 .3).
liquid warehouse shall not be restricted. The
4.5.7.1 Liquid warehouses shall be separate, maximum pile heights and maximum quantity per
detached buildings or shall be separated from pile, arranged as palletized and/or solid pile

42
MS761 :1982

storage. shall comply with table 1 3. if un- 4.5.7.12 Mixed storage. When two or more
protected. or table 1 4 if protected with automatic classes of liquids are stored in a single pile, the
sprinklers in accordance with 4.6. The storage maximum quantity permitted in that pile shall be
heights of containers on protected racks shall the smallest of the two or more separate
comply with table i 5 as applicable. maximum quantities and the heights of storage
permitted in-that pile shall be the least of the two
4.5.7.7 Class I liquids shall not be permitted in or more separate heights as given in table 1 3 or
the basement areas of liquid warehouses. 14 as applicable. When two or more classes of
Class II and Class lIlA liquids may be stored in liquids are stored in the same racks as permitted
basements provided that automatic sprinkler in this code, the maximum height of storage
protection and other fire protection facilities are permitted shall be the least of the two or more
provided in accordance with 4.6. separate heights given in table 1 5.

4.5.7.8 Empty or idle combustible pallet


storage shall be limited to a maximum pile size
4.6 PROTECTION REQUIREMENTS FOR PRO
of 230 m2 and to a maximum storage height of

TECTED STORAGE OF LIQUIDS.


2 m. Idle pallet storage shall be separated from
liquids by at least 2.4 m wide aisleways. -
4.6.1 Containers and portable tanks storing
flammable and combustible liquidis may be
4.5.7.9 Containers in piles shall be separated
stored in the quantities and arrangements
by pallets or dunnage to provide stability and to
specified in tables 14 and 1 5 provided the
prevent excessive stress on container walls.
storage is protected in accordance with 4.6.2 and
Portable tanks stored over one tier high shall be
4.6.5, as applicable.
designed to nest securely, without dunnage.
Materials handling equipment shall be suitable to
4.6.1 .1 Other quantities and arrangements
handle containers and tanks safely at the upper may be used where suitably protected and
tier level.
approved by the authority having jurisdiction.

4.5.7.10 No container or portable tank shall be 4.6.2 Where automatic sprinklers are used,
stored closer than 1 m to the nearest beam,
they shall be installed in accordance with the
chord, girder or other roof member in an
requirements of the Uniform Building By-Laws
unprotected warehouse.
and approved by the authority having jurisdiction.

4.5.7.11 Solid pile and palletized storage shall 4.6.2.1 Other systems such as automatic foam-
be arranged so that piles are separated from each water systems, automatic water-spray systems, or
other by at least 1 .2 m. Aisles shall be provided so other combinations of systems may be con-
that no container or tank is more than 3.6 m from sidered acceptable if approved by the authority
an aisle. Where storage on racks exists as having jurisdiction.
permitted in thiscode,a minimuml.2mwide aisle
shall be provided between adjacent rows of racks 4.6.3 Racks storing Class I or Cl.ass II liquids
and any adjacent storage of liquids. Main aisles shall be either single-row or double-row.
shall be a minimum of 2.4 m wide. and access
shall be maintained to all doors required for 4.6.4 Ordinary combustibles other than those
egress. used for packaging the liquids shall not be stored

43
MS761 :1982

Table 14. Storage arrangements for protected palletized or solid pile storage of
liquids in containers and portable tanks

Max. storage height (m) Max. quentity per pile (litres) Max. quantity (litres)
Class Storege level .~ -_

Containers Portable tanks Containers Portehie tanks Containers Portable tanks

IA Ground floor 1.5 11,400 45,000


Upper floors 1.5 7,600 30,300

Basements Not permitted Not permitted -

lB Ground floor 2 2.1 19,000 75,700 56,800 151,400


Upper floors 2 2.1 11,400 37,800 45,000 75,700
Basements Not permitted Not permitted

IC Ground floor 2* - 2,1 19,000 75,700 56,800 151,400


Upper floors 2* 2.1 11,400 37,800 45,000 75,700
Basements Not permitted Not permitted -

II Ground floor 3 4.2 37,800 151,400 94,600 302,800


Upper floors 3 4.2 37,800 94,600 302,800
Basements 1.5 2.1 28,400 75,700 28,400 75J00

Ill Ground floor 6 4.2 56,800 227,100 190,000 380,000


Upper floors 6 4.2 56,800 227,100 190,000 380,000
Basements 3 2.1 37,800 75,700 94,600 151,400

Those height limitations may be increased to 3 m for containers of 20 litres or less in capacity.
NOTE 3. See 4.6 for protection requirements as applicable to this type of storage.

Table 15. Storage arrangements for protected rack storage of


liquids in containers

Max. storage height (m) Max. quantity (litres)


Class Type rack Storage level
Containers Containers

IA Double row Ground floor 7.5 28,400


or Upper floor 4.5 17,000
Single row Basements Not permitted

lB Double row Ground floor 7.5 56,800


or Upper floor 4.5 34.000
IC Single row Basements Not permitted

II Double row Ground floor 7.5 90,800


or Upper floor 75 90,800
Single row Basements 4.5 34.000

Ill Multi-row Ground floor 12 181,700


Double row Upper floor 6 181,700
or Single row Basements 6 90,800

NOTE 4. See 4.6 for protection requirements as applicable to this type of storage.

44
MS761 :1982

in the same rack section as liquids, and shall be 4.7.2 Control of ignition sources.
separated a minimum of 2.4 m horizontally, by
aisles or open racks, from liquids stored in racks. Precautions shall be taken to prevent the ignition
of flammable vapours. Sources of ignition
include but are not limited to open flames;
4.6.5 In-rack sprinklers shall be installed in
lightning; smoking; cutting and welding; hot
accordance with the provisions of NFPA 231C.
surfaces; frictional heat; static, electrical and
Rack storage of materials, except as modified by
mechanical sparks; spontaneous ignition. in-
4.6.2. Alternate lines of in-rack sprinklers
cluding heat-producing chemical reactions; and
shall be st~ggered.Multiple levels of in-rack
radiant heat.
sprinkler heads shall be provided with water
shields unless otherwise separated by horizontal 4.7.3 Dispensing of Class I and Class II liquids
barriers, or unless the sprinkler heads are in general purpose orliquid warehouses shall not
approved for such installations. be permitte-d unless the dispensing area is
suitably cut off from other ordinary combustible
or liquid storage areas, as specified in 4.4, and
4.7 FIRE CONTROL
otherwise conforms with the applicable
4.7.1 Suitable fire extinguishers or precon- provisions of 4.4.
nected hose lines. either 38 mm line or 25 mm
4.7.4 Materials with a water reactivity degree of
hard rubber, shall be provided where liquids are
2 or higher as outlined in NFPA 704, Standard
stored. Where 38 mm fire hose is used, it shall be
System for the identification of the fire hazards of.
installed in accordance with the requirements of
materials, shall not be stored in the same area
the Uniform Building By-Laws.
with other liquids.
4.7.1.1 At least one 9 kg BC dry chemical type
portable fire extinguisher shall be located outside
4.8 OUTDOOR STORAGE
of, but not more than 3 m from, the door opening
into any separate inside storage area.
4.8.1 Ouidoor storage of liquids in containers
and portable tanks shall be in accordance with
4.7.1.2 At least one 9 kg BC dry chemical type
table 1 6,.as qualified by 4.8.1.1 to 4.8.1.4 and
portable fire extinguisher shall be located not less
4.8.2. 4.8.3 and 4.8.4.
than 3 m nor more than 1 5 m. from any Class I or
Class II liquid storage area located outside of a 4.8.1 .1. When two or more classes of materials
separate inside storage area. are stored in a single pile, the maximum quantity
in that pile shall be the smallest of the two or more
4.7.1.3 In protected general purpose and liquid separate quantities.
warehouses. hand hose lines shall be provided in
sufficient number to reach all liquid storage 4.8.1.2 No container or portable tank in a pile
areas. shall be more than 60 m from a 4 m wide access
way to permit approach offire control appliances.
4.7.1.4 The water shall be sufficient to meet the
specified fire protection demand in accordance 4.3.1.3 The distances listed intablel6 applyto
with the requirements of the Uniform Building By- properties that have protection for exposures as
Laws. defined. If there are exposures, and such

45
MS 761:1982

protection for exposures does not exist, the


(b) the building has an exterior wall with a fire
distances in column 4 shall be doubled.
resistance rating of not less than 2 hours and
4.8.1.4 When total quantity stored does not having no opening to above ground areas within
3 m horizontally of such storage and no openings
exceed 50% of maximum per pile, the distances in
to below ground areas within 15 m horizontally of
columns 4 and 5 may be reduced 50%. but to not
such storage.
less than 1 m.

4.8.2 A maximum of 4.160 litres of liquids in 4.8.2.1 The quantity of liquids stored adjacent
closed containers and portable tanks may be to a building protected in accordance with
stored adjacent to a building located on the same 4.8.2(b) may exceed that permitted in 4.8.2,
premises and under the same management provided the maximum quantity per pile does not
provided that: exceed 4.160 litres and each pile is separated by
a 3 m minimum clear space along the common
(a) the building is limited to a one-storey wall.
building of fire-resistive or non-combustible
construction and is devoted principally to the 4.8.2.2 Where the quantity stored exceeds the
storage and handling of liquids; or 4,160 litres permitted adjacent to the building

Table 16. Outdoor liquid storage in containers and portable tanks

1 2 3 4 5

Portable tank storage


Container storage- max. per pile
Class max. per pile (Litres) (Note 5) Distance Distance to property Distance to Street, alley.
between piles line that can be built - or a public way (m)
Litres Height Litres Height or racks upon (m) (Notes 6 & 7) (Note 8)
(Notes 3 & 6) (m) (Notes 3 & 6) (m) (m)

IA 4,160 3 8,320 2.1 1.5 15 3

lB 8,320 3.7 16,650 4.2 1.5 15 3

IC 16,650 3.7 33,300 4.2 1.5 15 3

II 33,300 3.7 66,600 4.2 1.5 7.5 2.3

Ill 83,300 5.5 166,600 4,2 1.5 3 2.3

NOTE 5. See 4.8.1 - i regarding mixed class storage.

NOTE 6. See 4.8.1.3 regarding protection for exposures.

NOTE 7. See 4.8.1.4 for smaller pile sizes.

NOTE 8. For storage in racks. the quantity limits per pile do appiy, but the rack arrangement shall be limited to a maximum of 1.5 m in length
and two rows or 2.8 m in depth.

48
MS 761:1982

given in 4.8.2(a), or the provisions of 4.8.2(b) 5.1.2 This section shall not apply to chemical
cannot be met, a minimum distance in plants. refineries or distilleries, as defined. which
accordance with column 4 of table 1 6 shall be are covered in section 9.
maintained between buildings and nearest
container or portable tank. 5.1,3 Where portions of such plants involve
chemical reactions such as oxidation, reduction,
4.8.3 The storage area shall be graded in a halogenation. hydrogenation, alkylation, poly-
manner to divert possible spills away from the merization, and other chemical processes. those
buildings or other exposures or shall be portions of the plant shall be in accordance with
surrounded by a curb at least 1 50 mm high. section 8.
When curbs are used, provisions shall be made
for draining of accumulations of ground or rain
water or spills of liquids. Drain shallterminate at a 5.2 INCIDENTAL STORAGE OR USE OF
safe location and shall be accessibleto operation LIQUIDS
under fire conditions.
5.2.1 Sub-clause 5.2 shall be applicable to
those portions of an industrial plant where the
4.8.4 Storage area shall be protected against
use and handling of liquids is only incidental to
tampering or trespassers where necessary and
the principal business, such as automobile
shall be kept free of weeds, debris and other
assembly, construction of electronic equipment,
combustible materials not necessary to the
furniture manufacturing or other similar
storage.
activities.

5.2.2 Liquids shall be stored in tanks or closed


containers.

5.2.2.1 Except as provided in 5.2.2.2 and


5.2.2.3, all storage shall comply with section 4.
SECTION FIVE: INDUSTRIAL PLANTS 5.2.2.2 The quantity of liquid that may be
located outside of an inside storage room or
5.1 APPLICATION storage cabinet or in any one fire compartment of
a building, shall not exceed the greater of that
5.1.1 This section shall apply to those industrial given in (a), (b). (c) or (d) below:
plants where
(a) a supply for one day;
(a) the use of liquids is incidental to the
principal business (see 5.2); or (b) 95 litres of Class IA liquids in containers;

(b) liquids are handled or used only in unit (c) 450 litres Class lB. IC, II or Ill liquids in
physical operations such as mixing. drying. containers;
evaporating. filtering, distillation and similar
operations which do not involve chemical (d) one portable tank not excet~ding2500 litres
reaction (see 5.3). of Class 18, IC. Class Ii or Class Ill liquids.

47
MS 761 :1982

5.2.2.3 Where large quantities of liquids are (e) by gravity through an approved self-closing
necessary, storage may be in tanks, which shall valve or self-closing faucet.
comply with the applicable requirements of
section 2, and 5.3, 5.4, 5.5, 5.6, 5.7 and 5.8.. 5.2.4.5 Transferring liquids by means of
pressurizing the container with air is prohibited.
5.2.3 Areas in which liquids are transferred Transferring liquids by pressure of inert gas is
from one tank or container to another container permitted only if controls, including pressure
shall be separated from other operations in the relief devices. are provided to limit the pressure
building by adequate distance or by construction so it cannot exceed the design pressure of the
having adequate fire resistance, Drainage or vessel, tank or container.
other means shall be provided to control spills.
Adequate natural or mechanical ventilation shall
be provided. The Uniform Building By-Laws 5.3 UNIT PHYSICAL OPERATIONS
provides information on the design and installa-
tion of mechanical ventilation. 5.3.1 Sub-clause 5.3 shall be applicable in
those portions of industrial plants where liquids
5.2.4 Handling liquids at point of final use. are handled or used in unit physical operations
such as mixing, drying, evaporating, filtering,
5.2.4.1 Class I and Class II liquids shall be kept distillation, and similar operations which do not
in covered containers when not actually in use. involve chemical change. Examples are plants
compounding cosmetics. pharmaceuticals,
5.2.4.2 Where liquids are used or handled, solvents. cleaning fluids, insecticides and similar
except in closed containers, means shall be types of activities.
provided to dispose promptly and safely of
leakage or spills. 5.3.2 Industrial plants shall be located so that
each building or unit of equipment is accessible
5.2.4.3 Class I liquids may be used only where from at least one side for fire fighting and fire
there are no open flames or other sources of control purposes. Buildings shall be located with
ignition within the possible path of vapour travel. respect to lines of adjoining property which may

5.2.4.4 Class I and Class II liquids shall be be built upon as set forth in 8.2.1 and 8.2.1.1.
drawn from or transferred into vessels, con- except that the blank wall referred to in 8.2.1.1
tainers, or portable tanks within a building only shall have a fire resistance rating of at least two
from; hours.

(a) original shipping containers with a capacity 5.3.3 Areas where unstable liquids are handled
of 20 litres or less; or or small scale unit chemical processes are carried
on shall be separated from the remainder of the
(b) from safety cans; or plant by a fire wall having a fire resistance rating
of not less than two hours.
(c) through a closed piping system; or
5.3.4 Drainage
(d) from a portable tank or container by means
ofa device drawingthroughanopeniflg inthetop 5.3.4.1 Emergency drainage systems shall be
of the tank or container; or provided to direct flammable or combustible

48
MS761 :1982

liquid leakage and fire protection water to a safe 5.3.6 The storage, transfer and handling of
location. This may require curbs. scuppers. or liquids shall comply with 8.4 of section 8.
special drainage systems to control the spread of
fire (see 2.2.3.1).
5.4 TANK VEHICLE AND TANK CAR LOADING
5,3.4.2 Emergency drainage system, if con- AND UNLOADING
nected to public sewers or discharged in public
waterways, shall be equipped with traps or 5.4.1 Tank vehicle and tank car loading or
separators. unloading facilities shall be separated from
aboveground tanks, warehouses, other plant
5.3.4.3 The industrial plant shall be designed buildings or nearest line of adjoining property
and operated to prevent the normal discharge of which can be built upon byadistanceof7.Smfor
flammable or combustible liquids into public Class I liquids and 4.5 m for Class II and Class Ill
waterways. public sewers, or adjoining property. liquids measured from the nearest position of any
fill stem. Buildings for pumps or shelters -for
5.3.5 Ventilation personnel can be a part of the facility. Operations
of the facility shall comply with the appropriate
5.3.5.1 Areas as-defined in 5.3.1 using Class I portions of 6.3 of section 6.
liquids shall be ventilated at rate of not less than
0.3 m3 per minute per square metre of solid floor
area. This shall be accomplished by natural or
5.5 FIRE CONTROL
mechanical ventilation with discharge or exhaust
to a safe location outside of the building.
5.5.1 Portable fire extinguishment and control
Provision shall be made for introduction of make-
equipment shall be provided in such quantities
up air in such a manner as not to short circuit the
and types as are needed forthe special hazards of
ventilation. Ventilation shall be arranged to
operation and storage. MS 566 : Pt. 3. Code of
include all floor areas or pits where flammable
practice for fire fighting installations and
vapours can collect. Local or spot general
equipment Part 3 : Portable fire extinguisher
ventilation may be needed for the control of
provides information as to the suitability of
special fire or health hazards. Such ventilation, if
various types of extinguishers and their number
provided. may be utilized for up to 75% of the and location.
required ventilation. The Uniform Building By-
Laws provide information on this subject.
5.5.2 Water shall be available in volume and at
5.3.5.2 Equipment used in a building and the adequate pressure to supply water hose streams,
ventilation of building shall be designed so as to foam-producing equipment, aUtomatic sprinklers
limit flammable vapour-air mixtures under or water spray systems as the need is indicated by
normal operating conditions to the interior of the special hazards of operation. dispensing and
equipment, and to not more than 1 .5 m from storage.
equipment which exposes Class I liquids to the
air. Examples of such equipment are dispensing 5.5.3 Special extinguishing equipment such as
stations, open centrifuges, plant and frame filters, that utilizing foam, inert gas. or dry chemical shall
open vacuum filters and surfaces of open be provided as the need is indicated by the special
equipment. hazards Of operation, dispensing and storage.

49
MS 761:1982

5.5.4 Where the need is indicated by special 5.7 ELECTRICAL EQUIPMENT


hazards of operatJon, liquid processing
equipment, major piping, and supporting steel 5.7.1 This section, 5.7, shall apply to areas
shall be protected by approved water spray where Class I liquids are stored or handled or
systems, deluge systems, approved fire resistant where Class II or Class Ill liquids are stored or
coatings, insulation or any combination of these. handled at a temperature above their flash points
The Uniform Building By-Laws provide informa- (see 1.1.3). For areas where Class Il or Class Ill
tion on this subject. liquids only are stored or handled at a
temperature below their flash points, the elect-
5.5.5 All plant fire protection facilities shall be rical equipment may be installed in accordance
adequately maintained and periodically in- with the requirements of the Electricity
spected and tested to make sure they are always Regulations. 1951 (Revised 1977) ,fo r ordinary
in satisfactory operating condition, and they will areas; however, care shall be used in locating
serve their purpose in time of emergency. electrical apparatus to prevent hot metal from
falling into open equipment.

5.6 SOURCES OF IGNITION 5.7.2 All electrical equipment and wiring for
use in classified areas specified in table 1 7 shall
5.6.1 Precautions shall be taken to preventthe comply with the following:
ignition of flammable vapours. Sources of
ignition include but are not limited to open (a) British Standards Specifications and Codes
flames; lightning; smoking; cutting and welding; of Practice Relating to equipment for use in
hot surfaces; frictional heat; static, electrical and hazardous areas -(see appendix D), or
mechanical sparks; spontaneous ignition.
including heat-producing chemical reactions; (b) Institute Of Petroleum Model Code of Safe
and radiant heat. Practice Electrical Safety Code, or
-

5.6.2 Class I liquids shall not be dispensed into (c) Any equivalent standards or codes accept-
metal containers unless the nozzle or fill pipe is in able to the relevant authority.
electrical contact with the container. This can be
accomplished by maintaining metallic contact 5.7.3 So far as it applies, table 1 7 shall be used
during filling, by a bond wire between them, or by to delineate and classify areas forthe purpose of
other conductive path having an electrical installation of electrical equipment under normal
resistance not greater than 1 Q6 ohms. Bonding is circumstances. In the application of classified
not required where a container is filled through a areas, a classified area shall not extend beyond
closed system, or the container is made of glass an unpierced floor, wall. roof or other solid
or other nonconducting material. NFPA 77, partition. The classification of hazardous areas is
defined in appendix C.
Recommended practice on static electricity,
provides information on static protection;
MS - Code of practice for protection
5.7.4 The area classifictions listed in table 1 7
of structures against Iightning~providesinforma- are based on the premise that the installation
tion on lightning protection. meets the applicable requirements of this code in
all respects. Should this not be the case, the
authority having jurisdiction shall have the
Maiaysian Standard in the course of preparation.

50
MS 761:1982

Table 17. Electrical equipment classified areas Industrial plants

Classification of hazardous
.
.
Extent of classified area
areas (see appendix C)

installed in Zone 1 Area within 1.5 m of any edge


5.3.5.2 where of such equipment, extending in
vapour-air mixtures all directions.
normal

Zone 2 Area between 1.5 m and 2.5 m


of any edge of such equipment,
extending in all directions. Also,
area up to 1 m above floor or
ground level within 1.5 m to
7.5 m horizontally from any
edge of such equipment.*

of the type Zone 1 Area within 1 m of any edge of


where such equipment, extending in
vapour-air mixtures all directions.
normal

Zone 2 Area between 1 m and 2.5 m


of any edge of such equipment
extending in all directions. Also,
area up to 1 m above floor or
ground level within 1 m to
3 m horizontally from any edge
of such equipment.

ABOVEGROUND** .

roof and Zone 2 Within 3 m from shell, ends or


roof of tank. Area inside bunds
to level of top of bund.
Zone 1 Within 1.5 m open end of vent,
extending in all directions.
Zone 2 Area between 1.5 m and 3 m
from open end of vent, extend-
ing in all directions.
Zone 1 Area above the roof and within
the shell.

CONTAINER

indoors with Zone 1 Within 1 m of vent and fill


ventilation opening, extending in all
directions.
Zone 2 Area between 1 m and 1 .5 m
from vent or fill opening,
extending in all directions.
Also up to 450 mm above floor
or ground level within a hori-
zontal radius of 3 m from vent
or fill opening.

~Thereleaseof Class I liquids may generate vapours to the extent thatthe entire building, and possibly a zone surrounding it.
should be considered a Zone 2 area.

For Tanks-underground, see 7.5 of section 7.

51
MS761 :1982

Table 17. (Contd.)

Classification of hazardous Extend of classified


.
area
.
areas (see appendix C)

BLEEDERS, WITH-
FITTINGS,
SIMILAR

Zone 2 Within 1.5 m of any edge


of such devices, extending in
all directions. Also up to 1 m
above floor ground level with-
in 7.5 m horizontallyfromany
edge of such devices.
Zone 2 Within 1 m of any edge of
such devices, extending in all
directions. Also up to450 mm
above ground level within
- horizontally from any edge of
such devices.

mechanical Zone 1 Entire area within pit if any


part is within a Zone 1 or 2
classified area.
Zone 2 Entire area within pit if any
part is within a Zone 1 or 2
- area.
v~Ives,fittings Zone 2 Entire pit.
not within a
area

DITCHES, Zone 2 Area up to 450 mm above


ditch, separator or basin. Also
BASINS 450 mm above ground within
4.5 m horizontally from and
edge.

52
MS 761 :1982

authority to determine the extent of the classified fire protection equipment can be brought to bear
areas. on any part of flammable or combustible liquid
storage, use, or any unit physical operation.
5.7.5 Extent of classified areas shall be as
shown in table 17. 5.9.3 Combustible waste material and residues
in a building or unit operating area shall be kept to
5.7.6 Where the provisions of 5.7.1. 5.7.2, a minimum, stored in covered metal receptacles
5.7.3. 5.7.4 and 5.7.5 require the installation of and disposed of daily.
electrical equipment suitable for Zone 1 or Zone
2. ordinary electrical equipment including 5.9.4 Ground area around buildings and unit
switchgear may be used if installed in a room or operating areas shall be kept free of weeds. trash
enclosure which is maintained under positive or other unnecessary combustible materials.
pressure with respect to the c.l.assified area.
Ventilation makeup air shall be uncontaminated
by flammable vapours.

5.8 REPAIRS TO EQUIPMENT SECTION SIX: BULK PLANTS

5.8.1 Hot work, such as welding or cutting 6.1 STORAGE


operations, use of spark-producing power tools,
and chipping operations shall be permitted only 6.1.1 Class I liquids shall be stored in closed
under supervision of an individual in responsible containers, or in storage tanks aboveground
charge. The individual in responsible charge shall outside of buildings, or underground in accor-
make an inspection of the area to be sure that it is dance with section 2.
safe for the work to be done and that safe
procedures will be followed for the work 6.1.2 Class II and Class III liquids shall be stored
specified. NFPA 327. Standard procedures for in containers, or in tanks within buildings or
the standard for cleaning or safeguarding small aboveground outside of buildings. or under-
tanks and containers, and NFPA 36. Standard for ground in accordance with section 2.
solvent extraction plants. provide information on
6.1.3 Containers of liquids when piled one
such operations.
upon the other shall be separated by dunnage
sufficient to provide stability and to prevent
excessive stress on container walls. The heightof
5.9 HOUSEKEEPING pile shall be consistent with stability and strength
5.9,1 Maintenance and operating practices of containers.
shall be in accordance with established pro-
6.1.4 Pipingr valves and fittings. Piping
cedures which will tend to control leakage and
systems shall be in accordance with section 3.
prevent the accidental escape of flammable or
combustible liquids. Spills shall be cleaned up
promptly.
6.2 BUILDINGS

5.9.2 Adequate aisles shall be maintained for 6.2.1 Exits. Rooms in which liquids are stored
unobstructed movement of personnel and so that or handled by pumps shall have exit facilities

53
MS 761 :1982

arranged to prevent occupants being trapped in that can be built upon by a distance of 7.5 m for
the event of fire. The Uniform Building By-Laws Class I liquids and 4.5 m for Class II and Class Ill
provides information on the number and location liquids measured from the nearest position of any
of exits. fill spout. Buildings for pumps or shelters for
personnel may be a part of the facility.
6.2.2 Ventilation
6.3.2 Equipment such as piping. pumps, and
6.2.2.1 Ventilation shall be provided for all meters used for the transfer of Class I liquids
rooms, buildings, or enclosures in which Class I between storage tanks and the fill stem of the
liquids are pumped or dispensed. Design of loading rack shall not be used for the transfer of
ventilation system shall take into account the Class II or Class Ill liquids.
relatively high specific gravity of the vapours.
8.3.3 Except for Class Ill liquids, valves used for
Ventilation may be provided by adequate
the final control for filling tankvehicles shall be of
openings in outside walls at floor level un-
the self-closing type and manually held open
obstructed except by louvers or coarse screens.
Where natural ventilation is inadequate except where automatic means are provided for
mechanical Ventilation shall be provided. The shutting off the flow when the vehicle is full or
Uniform Building By-Laws provides information after filling of a preset amount.
on the installation of mechanical exhaust
systems. 6.3.4 Static protection. Bonding facilities for
protection against static sparks during the
6.2.2.2 Class I liquids shall not be stored or loading of tank vehicles through open domes
handled within a building having a basement or shall be provided:
pit into which flammable vapours may travel.
(a) where Class I liquids are loaded or
unless such area is provided with ventilation
designed to prevent the accumulation of (b) where Class II or Class Ill liquids are loaded
flammable vapours therein.
into vehicles which may contain vapours from
previous cargoes of Class I liquids.
6.2.2.3 Containers of Class I liquids shall not
be drawn from or filled within buildings unless
6.3.4.1 Protection as required in 6.3.4 shall
provision is made to prevent the accumulation of
consist of a metallic bond wire permanently
flammable vapours in hazardous concentrations.
electrically connected to the fill stem or to some
Where mechanical ventilation is required, it shall
part of the rack structure in electrical contact with
be kept in operation while flammable liquids are
the fill stem. The free end of such wire shall be
being handled. -
provided with a clamp or equivalent device for
convenient attachment to some metallic part in
electrical contact with the cargo tank of the tank
vehicle.
6.3 LOADING AND UNLOADING FACILITIES
6.3.4.2 Such bonding connection shall be
6.3.1 Tank vehicle and tank car loading or made fast to the vehicle or tank before dome
unloading facilities shall be separated from covers are raised and shall remain in place until
aboveground tanks, warehouses, other plant filling is completed and all dome covers have
buildings or nearest line of adjoining property been closed and secured.

54
MS 761 :1982

6.3.4.3 Bonding as specified in 6.3.4. 6.3.4.1 cargoes of Class I liquids. Temporary bonding is
and 6.3.4.2 is not required: not required between the tank car and the rack or
piping during either loading or unloading
(a) where vehicles are loaded exclusively with irrespective of the class of liquid handled.
products not having a static accumulating
tendency. such as asphalts including cutback 6.3.6 Container filling facilities. Class I liquids
asphalts, most crude oils, residual oils and water shall not be dispensed into metal containers
soluble liquids; unless the nozzle orfill pipe is in electrical contact
with the container. This can be accomplished by
(b) where no Class I liquids are handled at the maintaining metallic contact during filling,- by a
loading facility and the tank vehicles loaded are bond wire between them, or by other conductive
used exclusively for Class II and Class Ill liquids; path having an electrical resistance not greater
than 106 ohms. Bonding is not required where a
(c) where vehicles are loaded or unloaded container is filled through a closed system, or is
througki closed bottom or top connections made of glass or other non-conducting material.
whether the hose or pipe is conductive or non- NFPA 77, Recommended practice on static
conductive. -
electricity, provides information on static
protection. -
6.3.4.4 Filling through open domes into the
tanks of tank vehicles or tank cars that contain
vapour-air mixtures within the flammable range.
6.4 WHARVES
or where the liquid being filled can form such a
mixture, shall be by means of a downspout which 6.4.1 The term wharf shall mean any wharf,
extends near the bottom of the tank. This pier, bulkhead or other structure over or
precaution is not required when loading liquids contiguous to navigable water, the primary
which are nonaccumulators of static charges. function of which is the transfer of liquid cargo in
NFPA 77 Recommended practice on static bulk between shore installations and any tank
electricity, provides additional information on vessel, ship, barge. lighter boat or other mobile
static electricity protection. floating craft; and this section shall apply to all
such installations except Marine Service Stations
6.3.5 Stray currents. Tank car loading facilities as covered in section 7. If liquids are handled in
where flammable and combustible liquids are bulk quantities across general purposes piers or
loaded or unloaded through open domes shall be wharves NFPA 87, Standard for the construction
protected against stray currents by permanently and protection of piers and wharves, shall be
bonding the pipe to at least one rail and to the
followed.
rack structure, if of metal. Multiple pipes entering
the rack area shall be permanently electrically 6.4.1.1 Package cargo of liquids, including full
bonded together. In addition, in areas where and empty drums, bulk fuel and stores may be
excessive stray currents are known to exit, all pipe handled over a wharf during cargo transfer at
entering the rack area shall be provided with such times and places as agreed upon by the
insulating sections to electrically isolate the rack wharf superintendent or representative and the
piping from the pipe lines. These precautions are senior deck officer on duty.
not necessarywhere Class II or Class Ill liquids are
handled exclusively and there is no probability 6.4.1.2 Wharves at which liquid cargoes are to
that tank cars will contain vapours from previous be transferred in bulk quantities to or from tank

55
MS 761:1982

vessels shall be at least 30 m from any bridge over 6.4.5.1 Flexibility of piping shall be assured by
a navigable waterway. or from an entrance to or appropriate layout and arrangement of piping
superstructure of any vehicular or railroad tunnel supports so that motion of the wharf structure
under a waterway. The termination of the wharf resulting from wave action, currents, tides or the
loading or unloading fixed piping shall be at least mooring of vessels will not subject the pipe to
60 m from a bridge or from an entrance to or repeated strain beyond the elastic limit.
superstructure of a tunnel.
6.4.5.2 Pipe joints depending upon the friction
6.4.2 Substructure and deck shall be sub- characteristics of combustible materials or
stantially designed for the use intended. Deck grooving of pipe ends for mechanical continuity
may employ any material which will afford the of piping shall not be used. -

desired combination of flexibility, resistance to


shock, durability, strength and fire resistance. 6.4.5.3 Swivel joints may be used in piping to
which hoses are connected, and for articulated
6.4.3 Tanks used exclusively for ballast water or swivel-joint transfer systems, provided that the
Class II or Class Ill liquids may be installed on design is such that the mechanical strength of the
suitably designed wharves. joint will not be impaired if the packing material
should fail, as by exposure to fire.

6.4.4 Loading pumps capable of building up 6.4.5.4 Piping systems shall contain a
pressures in excess of the safe working pressure sufficient number of valves to operate the system
of cargo hose or loading arms shall be provided properly and to control the flow of liquid in
with by-passes, relief valves, or other arrange- normal operation and in the event of physical
ment to protect the loading facilities against damage.
excessive pressure. Relief devices shall be tested
at not rn-ore than yearly intervals to determine that 6.4.5.5 In addition to the requirements of
they function satisfactorily at the pressure at 6.4.5.4, each line conveying Class I and Class II
which they are set. liquids leading to a wharf shall be provided with a
readily accessible block valve located on shore
near the approach to thewharf and outside of any
6.4.4.1 All pressure hoses and couplings shall
bunded area. Where more than one line is
be inspected at intervals appropriate to the
involved, the valves shall be grouped in one
service. With the hose extended, test the hose and
location.
couplings using the in service maximum
operating pressures. Any hose showing material
6.4.5.6 Means of easy access shall be provided
deteriorations. signs of leakage, or weakness in
for cargo line vaives located below the wharf
its carcass or at the couplings shall be withdrawn
deck.
from service and repaired or discarded.
6.4.5.7 Pipe lines on wharves shall be
6.4.5 Piping, valves and fittings shall be in adequately bonded and grounded if Class I and
accordance with section 3. with the following Class II liquids are handled. If excessive stray
exceptions and additions. currents are encountered, insulating joints shall

56
MS761 :1982

be installed. Bonding and grounding connections 6.4.7.1 Mechanical work shall not be per-
on all pipe lines shall be located on wharf side of formed on the wharf during cargo transfer, except
hose riser insulating flanges. if used. and shall be under special authorization based on a review of
accessible for inspection. the area involved, methods to be employed, and
precautions necessary.
6.4.5.8 Hose or articulated swivel-joint pipe
connections used for cargo transfpr shall be
capable of accommodating the combined effects
of change in draft and maximum tidal range. and
mooring lines shall be kept adjusted to prevent 6.5 ELECTRICAL EQUIPMENT
surge of the vessel from placing stress on the
cargo transfer system. 6.5.1 This section 6.5, shall apply to areas
where Class I liquids are stored or handled. For
6.4.5.9 Hose shall be supported so as to avoid areas where Class II or Class Ill liquids only are
kinking and damage from chafing. stored or handled, the electrical equipment may
be installed in accordance with the requirements
6.4.6 Suitable portable fire extinguishers of 9
of the Electricity Regulations. 1951 (Revised
kg BC dry chemical type shall be located within
1977) for Ordinary areas.
23 m of those portions of the facility where fires
are likely to occur, such as hose connections.
pumps and separator tanks. 6.5.2 All electrical equipment and wiring for
use in classified areas specified in table 1 8 shall
6.4.6.1 -Where piped water is, available, ready- domply with the following:
connected fire hose in size appropriate for the
water supply shall be provided so that manifolds (a) British Standards Specifications and Codes
where connections are made and broken can be of Practice relating to equipment for use in
reached by at least one hose stream. hazardous areas (see appendix D). or

6.4.6.2 Material shall not be placed on wharves (b) Institute of Petroleum Model Code of Safe
in such a manner as to obstruct access to fire
Practice - Electrical Safety Code, or
fighting equipment or important pipe line control
valves.
(c) Any equivalent standards or codes accept-
6.4.6.3 Where the wharf is accessible to able to the relevant authority.
vehicle traffic, an unobstructed roadway to the
shore end of the wharf shall be maintained for 6.5.3 So far as it applies table 18 shall be used
access of fire fighting appliances. to delineate and classify areas for the purpose of
installation of electrical equipment under normal
6.4.7 Loading or discharging shall not com- circumstances. In the application of classified
mence until wharf superintendent or repre- area, a classified area shall not extend beyond an
sentative and officer in charge of tank vessel unpierced wall, roof or other solid partition. The
agree that tank vessel is properly moored and all classification of hazardous locations is defined in
connections are properly made. appendix C.

57
MS 761:1982

Table 18. Electrical equipment classified areas bulk plants

. Classification of hazardous .
Location Extent of classified area
areas (see appendix C)

TAM( VEHICLE AND


TANK CAR*
Loading through Zone 1 Within 1 m of edge of dome,
open dome extending in all directions.

Zone 2 Area between 1 m and 4.5 m


from edge of dome, extending
in all directions.

Loading through bottom Zone 1 Within 1 m of point of venting


connections within to atmosphere extending in
atmospheric venting all directions.

Zone 2 Area between 1 m and 4.5 m


- from point of venting to
atmosphere, extending in all
directions. Also up to450 mm
above ground within a hori-
zontal radius of 3 m from
point of loading connection.

Loading through closed dome Zone 1 Within 1 m of open end of


- with atmospheric venting vent, extending in all
directions.

Zone 2 Area between 1 m and 4.5 m


from open end of vent, ex-
tending in all directions. Also
within 1 m of edge of dome,
extending in all directions.

Loading through closed dome Zone 2 Within 1 m of point of con-


with vapour recovery nection of both fill and vapour
lines, extending in all
- directions.

Bottom loading with vapour Zone 2 Within I m of point of con-


recovery or any bottom nections extending in all
unloading directions. Also up to450 mm
above ground within a
horizontal radius of 3 m from
point of connection.

When ciassifying extent of area, consideration shall be given to the fact that tankcars or tank vehicles may be spotted at
varying points. Therefore, the extremities of the loading or unloading positions shall be used.

58
MS761 :1982

Table 18. (Contd,)

Location Classification of hazardous Extent of cIassified~area


areas (see appendix C)

DRUM AND CONTAINER


FILLING
Outdoors, or indoors with - Zone 1 Within 1 m of vent and fill
adequate ventilation opening, extending in all
directions.

Zone 2 Area between 1 m and 1.5 m


from vent or fill opening,
extending in all directions.
Also, 450 mm above floor or
ground level within a
horizontal radius of 3 m
from vent or fill opening.

TANK~ABOVEGROLjND*
Shell, Ends, or Roof and Bund Zone 2 With 3 m from shell, ends or
area roof of tank. Area inside
bunds to level of top of bund.

Vent Zone 1 With 1.5 m of open end of


vent, extending in all
- diretions.
Zone 2 Area between 1.5 m and 3 m
from open end of vent,
extending in all directions.
Floating roof Zone 1 Area above the roof and
within the shell.

PITS
Without mechanical ventilation Zone 1 Entire area within pit if any
part is within a Zone 1 or 2
area.-

With mechanical ventilation Zone 2 Entire area within pit if any


part is within a Zone 1 or 2
area.

Containing, valves fittings or Zone 2 Entire pit.


piping, and not within a Zone 1
or 2 area

For Tanks-underground, see 7.5 of section 7.

59
MS 761 :1982

Table 18. (Contd..)

Classification of hazardous Extend of classified area


Location areas (see appendix C)

PUMPS, BLEEDERS, WITH-


DRAWAL FIT1INGS, METERS
AND SIMILAR DEVICES -

Indoors Zone 2 Within 1.5 m of any edge


of such devices, extending in
all directions. Also up to
1 m above floor or ground
level within 7.5 m horizontal-
ly from any edge of such
devices.

Outdoors Zone 2 Within 1 m of any edge of


such devices, extending in all
directions. Also up to 450mm
above ground level within 3m
horizontally from any edge of
such devices.

STORAGE AND REPAIR Zone 1 All pits or spaces below floor


GARAGE FOR TANK VEHICLES level.

Zone 2 Area up to 450 mm above


floor or ground level for entire
storage or repair garage.

DRAINAGE DITCHES, Zone 2 Area up to 450 mm above


SEPARATORS, IMPOUNDING ditch, separator or basin. Also
BASINS up to 450 mm above ground
within 4.5 horizontally from
any edge.

GARAGES FOR OTHER Ordinary if there is any opening to


THAN TANK VEHICLES these roomswithin the extent
of an outdoor classified area,
the entire room shall be
classified the same as the
area classification at the
point of the opening.

OUTDOOR DRUM STORAGE Ordinary

INDOOR WAREHOUSING Ordinary If there is any opening to


WHERE THERE IS NO these rooms within theextent
FLAMMABLE LIQUID ofan indoor classified area,
TRANSFER the room shall be classified
the same as if the wall, curb
or partition did not exist.

OFFICE AND REST ROOMS Ordinary

60
MS761 :1982

6.5.4 The area classifications listed in 6.5.3 available to locations where fires are likely to
shall be based on the premise thatthe installation occur.
meets the applicable requirements of the
flammable and combustible liquids code in all
respects. Should this not be the case, the
authority having jurisdiction shall have the
authority to classify the extent of the classified
area.
SECTION SEVEN: SERVICE STATIONS

6.6 SOURCES OF IGNITION 7.1 APPLICATION

6.6.1 Class I liquids shall not be handled, 7.1 .1 This section applies to both automotive
drawn, or dispensed where flammable vapours and marine service stations. Reference shall also
may reach a source of ignition. Smoking shall be be made to NFPA 302. Fire protection standard
prohibited except in designated localities. NO for motor craft, for safety precautions while
SMOKING signs shall be conspicuously posted fueling at marine service stations and to
where hazard from flammable vapours is NFPA 303. Fire protection standard for marinas
normally present; MS -~ Code of and boatyards. for additional requirements
Practice for protection of structures against applicable to marine service stations.
lightning.

6.7 DRAINAGE AND WASTE DISPOSAL 7.2 STORAGE

6.7.1 Provision shall be made to prevent liquids 7.2.1 General provisions


which can be spilled at loading or unloading
points from entering public sewers and drainage 7.2.1.1 Liquids shall be stored in approved
systems, or natural waterways. Connection to closed containers not exceeding 225 litres
such sewers, drains. or waterways by which capacity. in tanks in special enclosures as
liquids might enter shall be provided with described in 7.2.2. in aboveground tanks as
separator boxes or other approved means provided for in 7.2.1.5, or in tanks located
whereby such entry is precluded. Crankcase underground as in 2.3. Vent pipes on tanks
drainings and liquids shall not be dumped into storing gasoline - shall be in accordance with
sewers, but shall be stored in tanks or tight drums 2.3.5.1. 2.3.5.2 and 2.3.5.6. as applicable, and
outside of any building until removed from the shall discharge only upward in order to disperse
premises. vapours. (See also 7.6.3.4).

7.2.1.2 Aboveground tanks, located at an


6.8 FIRE CONTROL adjoining bulk plant, may be connected by piping
to service station underground tanks if, in
6.8.1 Suitable fire-control devices, such as addition to valves at aboveground tanks, a valve is
small hose or portable fire extinguishers, shall be also installed within control of service station
personnel. Apparatus dispensing Class I liquids
~Malaysian5tandard in the course of preparation. into the fuel tanks of motor vehicles of the public

61
MS 761:1982

shall not be located at a buk plant unless the tank outlet shall be equipped with a device,
separated by a fence or similar barrier from the such as a solenoid valve, positioned adjacent to
area in which bulk operations are conducted. and downstream from the valve specified in
2.2.7.1, SO installed and adjusted that liquid
7.2.1.3 Class I liquids shall not be stored or cannot flow by gravity from the tank in case of
handled within a building having a basement or piping or hose failure when the dispenser is not in
pit into which flammable vapours can travel, use.
unless such area is provided with ventilation
which will prevent the accumulation offlammable 7.2.2. Special enclosures
vapours therein.
7.2.2.1 When installation of tanks in accor-
7.2.1.4 Accurate daily inventroy records shall dance with section 2.3 is impractical because of
be maintained and reconciled on all Class I liquid property or building limitations, tanks for liquids
and diesel fuel storage tanks for indication of may be installed in buildings if enclosed as
possible leakage from tanks or piping. The described in 7.2.2.2 and upon specific approval
records shall be kept at the premises. available for of the authority having jurisdiction.
inspection by the enforcing authority, and shall
include, as a minimum, records showing by 7.2.2.2 Enclosure shall be substantially liquid
product, daily reconciliation between sales, use, and vapour-tight without backfill. Sides, top and
receipts. and inventory on hand. If there is more bottom of the enclosure shall be of reinforced
than one system consisting of a tank(s) serving concrete at least 150 mm thick. with openings for
separate pump(s) or dispenser(s) for any product, inspection through the top only. Tank con-
the reconciliation shall be maintained separately nections shall be so piped or closed that neither
for each tank system. vapours nor liquid can escape into the enclosed
space. Means shall be provided to use portable
7.2.1.5 Tanks supplying marine service equipment to discharge to the outside any liquid
stations and pumps not integral with the dis- or vapours which might accumulate should
pensing unit shall be on shore or on a pier of the leakage occur.
solid-fill type except as provided in (a) and (b).
7.2.2.3 At automotive service stations provided
(a) Where shore location would require ex-
in connection with tenant or customer parking
cessively long supply lines to dispensers, the
facilities at or below ground level in large
authority having jurisdiction may authorize the
buildings of commercial. mercantile or
installation of tanks on a pier provided that
residential occupancy, tanks containing Class I
applicable portions of section 2 relative to
liquids installed in accordance with 7:2.2.2 shall
spacing, bunding and piping are complied with
not exceed 22,700 litres individual or 68.000
and the quantity so stored does not exceed 4,1 60
litres aggregate capacity.
litres aggregate capacity.

(b) Shore tanks supplying marine service 7.2.3 Inside buildings


stations may be located aboveground where rock
ledges or high water tables make underground 7.2.3.1 Except where stored in tanks as
tanks impractical. provided in 7.2.2.. no Class I liquids shall be
stored within any service station building except
7.2.1.6 Where tanks are at an elevation which in closed containers of aggregate capacity not
produces a gravity head on the dispensing unit. exceeding 450 litres. One container not exceed-

62
MS761 :1982

ing 225 litres capacity equipped with an 7.3.2 Remote pumping systems
approved pump is permitted.
7.3.2.1 This section shall apply to systems for
7.2.3.2 Class I liquids may be transferred from dispensing Class I liquids where such liquids are
one container to another in lubrication or service transferred from storage to individual or multiple
rooms of a service station building provided the dispensing units by pumps located elsewhere
electrical installation complies with table 1 9. See than at the dispensing units.
also 7.7.1 for other possible sources of ignition.
7.3.2.2 Pumps shall be designed or equipped
7.2.3.3 Class II and Class Ill liquids may be so that no part of the system will be subjected to
stored and dispensed inside service station pressures above its allowable working pressure.
buildings from tanks of not more than 450 litres Each pump shall have installed on the discharge
each. side an approved leak detection device which will
provide an indication if the piping and dispensers
are not essentially liquid-tight.
7.3 PIPING, VALVES AND FITTINGS
7.3.2.3 Pumps installed above ground, outside
7.3.1 The design, fabrication, assembly. test of buildings, shall be located not less than 3 m
and inspection of the piping system shall be in from lines of adjoining property which can be
accordance with section 3 except that, where built upon, and not less than 2.3 m from any
dispensing is from a floating structure, suitable building opening. When an outside pump
lengths of oil-resistant flexible hose may be location is impractical, pumps may be installed
employed between the shore piping and the inside buildings as provided for dispensers in
piping on the floating structure as made 7.4.1.2. or in pits as provided in 7.3.2.4. Pumps
necessary by change in water level or shore line. shall be substantially anchored and protected
against physical damage.
7.3.1.1 Where excessive stray currents are
encountered. piping handling Class I and Class II
7.3.2.4 Pits for subsurface pumps or piping
liquids at marine service stations shall be
manifolds of submersible pumps shall withstand
electrically insulated from the shore piping.
the external forces to which they can be subjected
7.3.1.2 Piping shall be located so as~to be without damage to the pump, tank or piping. The
protected from physical damage. pit shall be no larger than necessary for
inspection and maintenance and shall be
7.3.1.3 A readily accessible valve to shut off the provided with a fitted cover.
supply from shore shall be provided in each
pipeline at or near the approach to the pier and at 7.3.2.5 An approved rigidly anchored
the shore end of each marine pipeline adjacent to emergency shutoff valve, incorporating a
the point where a flexible hose is attached. fusible link or other thermally actuated device,
designed to close automatically in event of severe
7.3.1 .4 After completion of the installation, impact or fire exposure shall be properly installed
including any paving, that section of the pressure in the supply line at the base of each individual
piping system between the pump discharge and island-type dispenser or at the inlet of each
the connection for the dispensing facility shall be overhead dispensing unit. If a coupling in-
tested for at least 30 minutes at the maximum corporating a slip-joint feature is used to join the
operating pressure of the system. emergency valve to the dispenser piping the

63
MS761 :1982

emergency valve shall automatically close before 7.4.2 Emergency power cut-off. A clearly
the slip joint can disengage. The automatic identified and easily accessible switch(es) or
closing feature of this valve shall be checked at circuit breaker(s) shall be provided at a location
the time of initial installation and at least once a remote from dispensing devices. including
year thereafter by manually tripping the hold- remote pumping systems, to shut off the powerto
open linkage. all dispensing devices in the event of an
emergency.

7.4 FUEL DISPENSING SYSTEM-


7.4.3 Fuel dispensing units
7.4.1 Location
7.4.3.1 Class I liquids shall be transferred from
7.4.1.1 Dispensing devices at an automotive tanks by means of fixed pumps designed and
service station shall be so located that all parts of equipped to allow control of the flow and prevent
the vehicle being served will be on the premises of leakage or accidental discharge.
the service station. Openings beneath dispenser
7.4.3.2 Dispensing devices for Class I liquids
enclosure shall be sealed to prevent the flow of
shall be approved.
leaking fuel to lower building spaces. Dispensing
devices at marine service stations may be located
7.4.3.3 A control shall be provided that will
on open piers, wharves, or floating docks or on
permit the pump to operate only when a
shore or on piers of the solid-fill type and shall be
dispensing nozzle is removed from its bracket or
located from other structures so as to provide
normal position with respect to the dispensing
room for safe ingress and egress of craft to be
unit, and the switch on this dispensing unit is
fuelded. Dispensing units in all cases shall be at
manually actuated. This control shall also stop
leat 6 m from any activity involving fixed sources
the pump when all nozzles have been returned,
of ignition.
either, to their brackets or to the normal non-
7.4.1.2 Approved dispensing units may be dispensing position.
located inside buildings upon specific approval
7.4.3.4 Liquids shall not be dispensed by
of the authority having jurisdication. The dis-
pensing area shall be separated from other areas applying pressure to drums, barrels and similar
in a manner approved by the authority having containers. Approved pumps taking suction
jurisdiction. The dispensing area shall be through the top of the container or approved
self-closing faucets shall b e used.
provided with an approved mechanical or gravity
ventilation system.
7.4.3.5 The dispensing unit and its piping,
7.4.1 .3 When dispensing units are located except those attached to containers, shall be
below ground. only approved mechanical ventila- mounted on a concrete island or protected
tion shall be used and the entire dispensing area against collision damage by suitable means. If
shall be protected by approved automatic located indoors, the dispenser shall also be
sprinkler system. Ventilating systems shall be mounted either on a concrete island or protected
electrically interlocked with gasoline dispensing against collision damage by suitable means and
units so that the dispensing units cannot be shall be located in a position where it cannot be
operated unless the ventilating fan motors are struck by a vehicle that is out of control
energized. descending a ramp or other slope.

84
MS761 :1982

7.4.4 Vapour recovery systems adjacent property lines which can be built upon,
except as provided for in 7.4.5.7. Vapour
7.4.4.1 Dispensing devices incorporating
processing equipment shall be located a
provisions for vapour recovery shall be approved.
minimum of 6 m from dispensing devices.
Processing equipment shall be protected against
7.4.4.2 Hose nozzle valves used on vapour
physical damage by the provision of guard rails,
recovery systems shall be approved.
curbs, or fencing.
7.4.4.3 Means shall be provided in the vapour
7.4.5.7 Where the required distance to
return path from each dispensing outlet to
adjacent property lines which can be built upon
prevent the discharge of vapours when the hose
as specified in 7.4.5.6 cannot be obtained,
nozzle valve is in its non-dispensing position.
means shall be provided to protect vapour pro-
7.4.5 Vapour processing systems cessing equipment against fire exposures. Such
means may include protective enclosures which
7.4.5.1 Vapour processing system com- extend at least 450 mm above the equipment,
ponents consisting of hose nozzle valves, blowers constructed of fire resistant or noncombustible
or vacuum pumps. flame arresters or systems for materials, installation in below ground spaces, or
prevention of flame propagation. controls, and protection with an approved water spray system.
vapour processing equipmentshall be individual- If protective enclosures or below ground spaces
ly approved for use in a specified manner. are used, positive means shall be provided to
ventilate the volume within the enclosure to
7.4.5.2 Dispensing devices used with a vapour prevent pocketing of flammable vapours. In no
processing system shall be approved. case shall vapour processing equipment so pro-
tected be located with 2.3 m of adjacent property
7.4.5.3 Means shall be provided in the vapour lines which can be built upon.
return path from each dispensing outlet to
prevent the discharge of vapours when the hose 7.4.5.8 Electrical equipment shall be in
nozzle valve is in its normal non-dispensing accordance with table 1 9.
position.
7.4.5.9 Vents on vapour processing systems
7.4.5.4 Vapour processing systems employing shall be not less than 4 m above adjacent ground
blower-assist shall not be used unless the system level, with outlet~so directed and located that
is designed to prevent flame propagation flammable vapours will not accumulate or travel
through system piping, processing equipment to an unsafe location or enter buildings.
and tanks.
7.4.5.10 Combustion or open flame type
7.4.5.5 If a component is likely to contain a devices shall not be installed in a classified area.
flammable vapour-air mixture under operating See table 1 9.
conditions, and can fail in a manner to ignite the
mixture, it shall be designed to withstand an
internal explosion without failure to the outside. 7.5 ELECTRICAL EQUIPMENT

7.4.5.6 Vapour processing equipment shall be 7.5.1 This section, 7.5, shall apply to areas
located outside of buildings at least 2.3 m from where Class I liquids are stored, handled or

65
MS761 :1982

dispensed. For areas where Class II or Class Ill All electrical equipment integral with the dispen-
liquids are stored, handled or dispensed. the sing hose or nozzles shall be suitable for use in
electrical equipment may be installed in Zone I areas.
accordance with the requirements of the
Electricity Regulations. 1951 (Revised 1977) for 7.5.3 Table 1 9 shall be used to delineate and
ordinary areas. classify areas for the purpose of installation of
electrical equipment under normal circum-
7.5.2 All electrical equipment and wiring for stances. A classified area shall not extend beyond
use in classified areas specified in table 1 9 shall an unpierced wall, roof or other solid partition.
comply with the following: The classification of hazardous areas is defined in
appendix C.
(a) British Standards Specifications and Codes
7.5.4 The area classifications listed in table 1 9
(b) Institute of Petroleum Model Code of Safe shall be based on the premisethatthe installation
Practice Electrical Safety Codes, or meets the applicable requirements of this Code in
all respects. Should this not be the case, the
(c) Any equivalent standards or codes accept- authority having jurisdiction shall have the
able to the relevant authority. authority to determine the extent of the classified
area.

Table 19. Electrical equipment classified areas Service stations

Classification of hazardous Extent of classified area


Location
areas (see appendix C)

UNDERGROUND TANK
Fill opening Zone 1 Any pit, box or space below
ground level any part of
which is within the Zone 1 or
2 area,

Zone 2 Up to 450 m above ground


level within a horizontal
radius of 3 m from a loose
fill connection and within a
horizontal radius of 1 .5 m
from a tight fill connection.

Vent Discharging upward Zone 1 Within 1 m of open end of


vent, extending in all
directions.

Zone 2 Area between 1 m and 1.5 m


of open end of vent,extending
in all directions.

66
MS761 :1982

Table 19. (contd.)

Location Classification of hazardous Extent of classified area


areas see appendix C

DISPENSING UNITS
(except overhead type)
Pits Zone 1 Any pit, box or space below
ground level, any part of
which is within the Zone 1 or
2 area.

Dispenser Zone 1 The area within a dispenser


enclosure up to 1.2 m
vertically above the base
except that area defined as
Zone 2. Any area within a
nozzle boot.

Zone 2 Areas within a dispenser


enclosure above the Zone 1
area. Areas within a
dispenser enclosure isolated
from Zone 1 by a solid parti-
tion or a solid nozzle boot but
not completely surrounded by
Zone 1 area. Within 450 mm
horizontally in all directions
from the Zone 1 area located
within the dispenser
enclosure.
Within 450 mm horizontally
in all directions from the
opening of a nozzle boot not
isolated by a vapour-tight
partition, except that the
classified area need not be
extended around 900 or
greater corner.

Outdoor Zone 2 Up to 450 mm above ground


level within 6 m
horizontally of any edge of
enclosure.
- INDOOR
with mechanical ventilation Zone 2 Up to 450 mm above ground
or floor level within 6 m
horizontally of any edge of
enclosure.

with gravity ventilation Zone 2 Up to 450 mm above ground


or floor level within 7.5 m
horizontally of any edge of
enclosure.

67
MS761 :1982

Table 19. (Contd.)

Classification of hazardous Extent of classified area -


Location areas see appendix C

DISPENSING UNITS, Zone 1 Within the dispenser


OVERHEAD TYPE enclosure and 450 mm in all
directions from the enclosure
where not suitably cut off by
ceiling or wall. All electrical
equipment integral with the -

dispensing hose or nozzle.

Zone 2 An area extending 600 mm


horizontally in all directions
beyond the Zone 1 area and
- extending to ground below
- this classified area,

Zone 2 - Up to 450 mm above ground


level within 6 m horizontally
measured from a point
vertically below the edge of
~ any dispenser enclosure.

REMOTE PUMP OUTDOOR Zone 1 Any pit, box or space below


ground level if any part is
within a horizontal distance
of 3 m from any edge of
pump.
I I
Zone 2 Within 1 m of any edge of
- pump, extending in all
- directions. Also up to 450mm
above ground level within 3 m
horizontally from any edge of
pump.

REMOTE PUMP INDOOR Zone 1 Entire area within any pit.

Zone 2 Within 1.5 m of any edge of,


pump, extending in all
directions. Also up to 1 m
above floor or ground level
within 7.5 m horizontally
from any edge of pump.

68
MS761 :1982

Table 19. (Contd.)

Classification of hazardous Extent of lassified area


Location
areas (see appendix C)

LUBRICATION OR
SERVICE ROOM
with dispensing Zone 1 Any pit within any un-
~ ventilated area.

Zone 2 Any pit with ventilation.

Zone 2 Area up to 450 mm above


floor or ground level and 1 m
horizontally from a
lubrication pit.

Dispenser for Zone 2 Within 1 m of any fill or


Class I liquids dispensing point, extending
in all directions.

LUBRICATION OR
SERV1CE ROOM
without dispensing zone 2 Entire area within any pit
used for lubrication or
~ similar services where
Class I liquids may be
released.

Zone 2 Area up to 450 mm above


any such pit, and extending a
distance of 1 m horizontally
from any edge of the pit.

SPECIAL ENCLOSURE Zone 1 Entire enclosure.


INSIDE BUILDING PER
7.2.2

SALES, STORAGE AND Ordinary If there is any opening to


REST ROOMS these rooms within the extent
of a Zone 1 area, the entire
~ room shall be classified as
Zone 1.

VAPOUR PROCESSING Zone 1 Any pit, box or space below


SYSTEMS PITS ground level, any part of
which is within a Zone 1 or 2
area or which houses any
equipment used to transport
or process vapours.

VAPOUR PROCESSING Zone 2 Within any protective


EQUIPMENT LOCATED enclosure housing vapour
WITHIN PROTECTIVE processing equipment.
ENCLOSURES
(see 7.4.5.7)

69
MS 761:1982

Table 19. (Contd.)

Location Classification of hazardous Extent of classified area


areas (see appendix C)

VAPOUR PROCESSING Zone 2 The space within 450 m in all


EQUIPMENT NOT WITHIN directions of equipment con-
PROTECTIVE ENCLOSURES taming flammable vapour or
(excluding piping and liquid extending to ground
combustion devices) level. Up to 450 mm above
ground level within 3 m
horizontally of the vapour
processing equipment.

EQUIPMENT ENCLOSURES Zone 1 Any area within the


enclosure where vapour or
liquid is present under
normal operating conditions.

Zone 2 The entire area within the


enclosure other than Zone 1.

VACUUM ASSIST Zone 2 The space within 450 mm


BLOWERS in all directions extending to
ground level. Up to 450 above
ground level within 3 m
horizontally.

7.6 OPERATIONAL REQUIREMENTS 7.6.1.3 Overhead-type dispensing units shall


be provided with an approved automatic-closing
7.6.1 Fuel delivery nozzles type hose nozzle valve without a latch-open
device. An approved automatic-closing type hose
nozzl,e valve with latch-open device may be used if
7.6.1 An approved automatic-Closing type the design of the system is such that the hose
hose nozzle valve with latch-open device is nozzle valve will close automatically in the event
permitted on any island-type dispenser the valve is released from a fill opening or upon
accessible to the public onlywhen all dispensing impact with a driveway.
of Class I liquids is to be done by the service
station attendant.
7.6.1.4 Dispensing nozzles used at marine
service stations shall be of the automatic-closing
7.6.1.2 If the dispensing of Class I liquids at a type without a latch-open device.
service station available and open to the public is
to be done by a person other than the service 7.6.1 .5 Hose nozzle valves of either the manual
station attendant, the nozzle shall bean approved or automatic-closing type for dispensing Class I
automatic-closing type without a latch-open liquids into a container shall be manually held
device. open during the dispensing operation. -

70
MS761 :1982

7.6.2 Attendance or supervision of dis- than the service station attendant, and may
pensing. include facilities available for sale of other retail
products.
7.6.2.1 Each service station open to the public
shall have an attendant or supervisor on duty 7.6.3.2 Approved dispensing devices such as,
whenever the station is open for business. but not limited to, coin-operated, card-operated
and remote controlled types are permitted at self-
7.6.2.2 Approved self-service dispensing service stations.
devices are permitted at service stations available
and open to the public provided that all 7.6.3.3 All self-service stations shall have at
dispensing of Class I liquids by a person other. least one attendant on duty while the station is
than the service station attendant is under the open to the public. The attendants primary
supervision and control of a qualified attendant function shall be to supervise, observe and
and the dispensing nozzle is an approved control the dispensing ofClasslliquids while said
automatic closing type without a latch-open liquids are actually being dispensed.
device.
7.6.3.4 It shall be the responsibility of the
7.6.2.3 Dispensing of Class I liquids at loca- attendant to control sources of ignition; and
tions not open to the public does not require and immediately handle accidental spills and fire
attendant or supervisor. Such locations may be extinguishers if needed.. The attendant or
used by commercial, industrial. governmental or supervisor on duty shall be mentally and
manufacturing establishments for fueling physically capable of performing the functions
vehicles used in connection with their and assuming the responsibility prescribed in this
businesses. section.

7.6.2.4 The provisions of 7.2.1 .1 shall not


7.6.3.5 Emergency controls specified in 7.4.2
prohibit the temporary use of movable tanks in
shall be installed at a location acceptable to the
conjunction with the dispensing of flammable or
authority having jurisdiction, but controls shall
combustible liquids into the fuel tanks of motor
not be more than 30 m from dispensers.
vehicles or other motorized equipment on
premises not normally accessible to the public. 7.6.3.6 Operating instructions shall be con-
Such installations shall only be made under spicuously posted in the dispensing area.
permit from the enforcing authority. The permit
shall include a definite time limit.
7.6.3.7 The dispensing area shall at all times be
7.6.2.5 The dispensing of Class I and Class II in clear view of the attendant and the placing or
liquids in the open from a tank vehicle to a motor allowing of any obstacle to come between the
vehicle is prohibited. dispensing area and the attendant control area
shall be prohibited. The attendant shall at all
7.6.3 Self-service stations times be able to communicate with persons in the
dispensing area.
7.63.1 Self-service station shall mean that
portion of property where liquids used as motor 7.6.3.8 Hose nozzle valves used at a self-sevice
fuels are stored and subsequently dispensed station for the dispensing of Class I liquids shall
from fixed approved dispensing equipment into be approved automatic-closing types without a
the fuel tanks of motor vehicles by persons other latch-open device.

71
MS761 :1982

7.6.3.9 Warning signs shall be conspicuously dispenser. undeground fill pipe opening, and
posted in the dispensing area incorporating the lubrication or service room.
following or equivalent wording:

(a) NO SMOKING.

(b) STOP ENGINE.

7.6.4 Drainage and waste disposal SECTION EIGHT: PROCESSING PLANTS

7.6.4.1 Provision shall be made in the area 8.1 APPLICATION


where Class I liquids are dispensed to prevent
8.1.1 This section shall apply to those plants or
spilled liquids from flowing into the interior of
buildings which contain chemical operations
service station buildings. Such provision may be
such as oxidation, reduction, halogenation.
by grading driveways, raising doors sills, or other
hydrogenation. alkylation. polymerization, and
equally effective means.
other chemical processes but shall not apply to
7.6.4.2 Crankcase drainings and liquids shall chemical plants, refineries or distilleries as
not be dumped into sewers, streams or adjoining defined which are covered in section 9.
property. but shall be stored in tanks or drums
outside any building until removed from the
premises.
8.2 LOCATION

8.2.1 The location of each processing vessel


7.7 SOURCES OF IGNITION
shall be based upon its liquid capacity. Process-
ing vessels shall be located, with respect to
7.7.1 In addition to the previous restrictions of
distances to lines of adjoining propertywhich can
this section, the following shall apply: Tl5ere shall
be built upon. in accordance with table 20, except
be no smoking or open flames in the areas used
when the processing plant is designed in
for fueling, servicing fuel systems for internal
accordance with 8.2.2.
combustion engines, receiving or dispensing of
Class I liquids. Conspicuous and legible signs
prohibiting smoking shall be posted within sight
Table 20. Location of processing vessels
of the customer being served. The motors of all
from property lines
equipment being fueled shall be shut off during
the fueling operation except for emergency
Processing vessels with
generators. pumps. etc. where continuing opera- emergency relief Stable Unstable
tion is essential. venting to permit liquids liquids
pressure

7.8 FIRE CONTROL Not in excess Table 6* 2 times


17 kPa (gauge) . table 6

7.8.1 Each service station shall be provided Over 17 kPa (gauge) 1 times 4 times
with at least one approved 9 kg BC dry chemical table 6* table 6*
type fire extinguisher located so that an
extinguisher will be within 30 m of each pump. Double distances where protection of exposure is not perovided.

72
MS761 :1982

8.2.2. The distances required in 8.2.1 may be liquid leakage and fire protection water to a safe
waived when the vessels are housed within a location. This may require curbs. scuppers. or
building and the exterior wall facing the line of special drainage systems to control the spread of
adjoining property which can be built upon is a fire (see 2.2.3.1).
blank wall having a fire resistance rating of not
less than four hours. When Class IA or unstable 8.3.2.2 Emergency drainage systems, if con-
liquids are handled, the blank wall shall have nected to public sewers or discharged into public
explosion resistance in accordance with good waterways, shall be equipped with traps or
engineering practice (see 8.3.4). separators.

8.3.2.3 The processing plant shall be designed


and operated to prevent the normal discharge of
8.3 PROCESSING BUILDING flammable or combustible liquids to public
waterways, public sewers, or adjoining property.
8.3.1 Construction
8.3.3 Ventilation
8.3.1.1 Processing buildings shall be of fire-
resistive or noncombustible. Except as provided
8.3.3.1 Enclosed processing buildings handl-
in 8.2.2. or in the case of explosion resistantwalls
ing Class I or Class II liquids shall be ventilated at
used in conjunction with explosion relieving
a rate of not less than 0.3 m3 per minute per
facilities (see 8.3.4), load-bearing walls shall be
prohibited. Buildings handling Class I or Class II square metre of solid floor area. This shall be
accomplished by natural or mechanical ventila-
liquids shall be without basements or covered
tion with discharge or exhaust to a safe location
pits. Processing buildings are normally limited in
outside of the building. Provision shall be made
height and area, depending upon the type of
for introduction of make-up air in such a manner
construction and private fire protection provided,
as not to short circuit the ventilation. Ventilation
to minimize the possibility of fire of such extent as
shall be arranged to include all floor areas or pits
to jeopardize public safety. Processing buildings
with numerous accessible exterior openings offer where flammable vapours may collect. Local or
favourable features for fire fighting. Provision for spot general ventilation may be needed for the
control of special fire or health hazards. Such
smoke and heatventing may be desirableto assist
ventilation, if provided, can be utilized for up to
access for fire fi~hting.NFPA 204, Guide for
75% of the required ventilation. The Uniform
smoke and heat venting provides information on
Building By-Laws provides information on this
this subject.
subject.
8.3.1.2 Areas shall have adequate exitfacilities
arranged to prevent occupants from being 8.3.3.2 Equipment used in a building and the
ventilation of the building shall be designed so as
trapped in the event of fire. Exits shall not be
exposed -by the drainage facilities described in to limit flammable vapour-air mixtures under
8.3.2. The Uniform Building By-Laws, provides normal operating conditions to the interior of
equipment, and to not more than 1 .5 m from
information on this subject.
equipment which exposes Class I liquids to the
8.3.2 Drainage air. Examples of such equipment are dispensing
stations., open centrifuges, plate and frame filters.
8.3.2.1 Emergency drainage systems shall be open vacuum filters, and surfaces of open
provided to direct flammable or combustible. equipment.

73
MS761 :1982

8.3.4 Explosion relief. Areas where Class IA or area shall be at least 100 mm below the
unstable liquids are processed shall have surrounding floor. As a minimum each opening
explosion venting through one or more of the shall be provided with an approved self-closing
following methods: 1 hour fire door or an approved fire damper.
The room shall be liquidtight where the walls join
(a) open air construction; the floor.

(b) lightweight walls and roof; 8.4.1.4 The storage of liquids in containers
shall be in accordance with the applicable
(c) lightweight wall panels and roof hatches; provisions of section 4.

(d) windows of explosion venting type.


8.4.2 Piping, valves and fittings

8.4.2.1 Piping, valves and fittings shall be in


8.4 LIQUID HANDLING
accordance with section 3.
8.4.1 Storage
8.4.2.2 Approved flexible connectors may be
8.4.1.1 The storage of liquids in tanks shall be used where vibration exists or where frequent
in accordance with the applicable provisions of movement is necessary. Approved hose may be
Section 2. used at transfer stations.

8.4.1.2 If the storage of liquids in outside 8.4.2.3 Piping containing liquids shall be
aboveground or underground tanks is not identified.
practical beacuse of government regulations,
8.4.3 Transfer
temperature considerations or production con-
siderations, tanks may be permitted inside of
8.4.3.1 The transfer of large quantities of
buildings or structures in accordance with the
liquids shall be through piping by means of
applicable provisions of section 2. Production
pumps or water displacement. Except as required
considerations necessitating storage inside of
in process equipment, gravity flow shall not be
buildings include but are not limited to high
used. The use of compressed air as a transferring
viscosity, purity, sterility, hydroscopic ity,
medium shall be prohibited.
sensitivity to temperature change. and need to
Store temporarily pending completion of sample 8.4.3.2 Positive displacement pumps shall be
analysis. provided with pressure relief discharging back to
the tank or to pump suction.
8.4.1.3 Storage tanks inside of buildings shall
be permitted only in areas at or above ground 8.4.4 Equipment.
which have adequate drainage and are separated
from the processing area by construction having 8.4.4.1 Equipment shall be designed and
a fire resistance rating of at least two hours. Day arranged to prevent the unintentional escape of
tanks, running tanks and surge tanks are liquids and vapours and to minimize the quantity
permitted in process areas. Openings to other escaping in the event of accidental release.
rooms or buildings shall be provided with non-
combustible Iiquidtight raised sills or ramps at 8.4.4.2 Where the vapour space of equipment
least 100mm in height, or thefloor in the storage is usually within the flammable range, the

74
MS761 :1982

probability of explosion damage to the equipment 8.6.2.2 Hydrants shall be provided in


can be limited by inerting. by providing an accordance, with accepted good practice.
explosion suppression system, or by designing MS 484, Code of practice for hydrant systems,
the equipment to contain the peak explosion provides information on this subject.
pressure which can be modified by explosion
relief. Where the special hazards of operation, 8.6.2.3 Hose connected to a source of water
sources of ignition. or exposures indicate a need, shall be installed so that all vessels. pumps, and
consideration shall be given to providing other equipment containing flammable or com-
protection by one or more of the above means. bustible liquidscan be reached with at least one
NFPA 69, Explosion prevention systems, hose stream. Nozzles that are capable of
provides information on inerting. discharging a water spray shall be provided. The
Uniform Building By-Laws. provides information
on this subject.
8.5 TANK VEHICLE AND TANK CAR LOADING
AND UNLOADING 8.6.2.4 Processing plants shall be protected by
an approved automatic sprinkler system or
8.5.1 Tank vehicle and tank car loading or equivalent extinguishing system. If special ex-
unloading facilities shall be separateul from tinguishing system. If special extinguishing
aboveground tanks, warehouses, other plant systems including but not limited to those
buildings or nearest line of adjoining property employing foam, carbon dioxide or dry chemical
which can be built upon by a distance of 7.5 m for are provided, approved equipment shall be used
Class I liquids and 4.5 m for Class II and Class III and installed in accordance with the require-
liquids measured from the nearest position of any ments of the Uniform Building By-Laws.
fill stem. Buildings for pumps or shelters for
personnel may be a partofthefacility. Operations 8.6.3 An approved means of prompt notifica-
of the facility shall comply with the appropriate tion of fire to those within the plant and the public
portions of 6.3 of section 6. fire department available shall be provided.

8.6.4 All plant fire protection facilities shall be


8.6 FIRE CONTROL adequately maintained and periodically inspect-
ed and tested to make sure they are always in
8.6.1 Approved portable fire extinguishers of satisfactory operating condition and they will
appropriate size. type and number shall be serve their purpose in time of emergency.
provided. MS 566 : Pt. 3. Firefighting installation
and equipment. Part 3 : Portable fire
extinguisher. provides information on this 8.7 SOURCES OF IGNITION
subject.
8.7.1 General.
8.6.2 Where the special hazards of operation or
exposure indicate a need, the following fire 8.7.1.1 Precautions shall be taken to prevent
control provisions shall be provided. the ignition of flammable vapours. Sources of
ignition include but are not limited to open
8.6.2.1 A reliable water supply shall be flames; lightning; smoking; cutting and weld-
available in pressure and quantity adequate to ing; hot surfaces; fractional heat; static. electrical
meet the probable fire demands. and mechanical sparks; spontaneous ignition; in-

75
MS761 :1982

cluding heat-producing chemical reactions; and 8.8 ELECTRICAL EQUIPMENT


radiant heat.
8.8.1 The provisions of 5.7 shall apply.
8.7.1.2 Class I liquids shall not be dispensed
into metal containers unless the nozzle orfill pipe
is in electrical contact with the containers. This 8.9 HOUSEKEEPING
can be accomplished by maintaining metallic
contact during filling, by a bond wire between 8.9.1 Maintenance and operating practices
them, or by other conductive path having an shall be in accordance with established pro-
electrical resistance not greater than 1 06 ohms. cedures which will tend to control leakage and
Bonding is not required where a container is filled prevent the accidental escape of liquids. Spills
through a closed system. orthe container is made shall be cleaned up promptly.
of glass or other nonconducting material.
8.9.2 Adequate aisles shall be maintained for
NFPA 77. Recommended practice on static
unobstructed movement of personnel and sothat
electricity, provides information on static pro-
fire protection equipment can be brought to bear
tection; MS __________ Code of practice for
,

protection of structures against lightning~, on any part of the processing equipment.


provides information on lightning protection.
8.9.3 Combustible waste material and residues
8.7.2 Maintenance and repair in a building or operating area shall be kept to a
minimum, stored in closed waste cans, and
8.7.2.1 When necessary to do maintenance disposed of daily.
work in a liquid processing area, the work shall be
authorized by a responsible member of super- 8.9.4 Ground area around buildings and
vision. operating areas shall be kept free of tall grass.
weeds, trash or other combustible materials.
8.7.2.2 Hot work, such as welding or cutting
operations, use of spark-producing power tools,
and chipping operations shall be permitted only
under supervision of an individual in responsible
charge. The individual in responsible charge shall
make an inspection of the area to be sure that it is SECTION NINE: REFINERIES, CHEMICAL
safe for the work to be done and that safe PLANTS AND DISTILLERIES
procedures will be followed for the work
specified. NFPA 327, Standard procedures for 9.1 STORAGE
cleaning or safeguarding small tanks and
containers, NFPA 36, Standards for solvent 9.1.1 Liquids shall be stored in tanks. in
extraction plants, NFPA 51, Standards for the containers, or in portable tanks. Tanks shall be
installation and operation of oxygen-fuel gas installed in accordance with section 2 of this
system for welding and cutting. provide informa- code.
tion on such operations.
9.1.2 Tanks for the storage of liquids in tank
farms and in locations other than process areas
shall be located in accordance with 2.2.1 and
Malaysian Standard in the course of preparation. 2.2.2.

76
MS761 :1982

9.1.3 Piping, valves and fittings. Piping SECTION TEN: STORAGE ON FARMS AND
systems shall be in accordance with section 3. ISOLATED CONSTRUCTION PROJECTS

9.2 WHARVES 10.1 APPLICATION

9.2.1 Wharves handling flammable or com-


bustible liquids shall be in accordance with 6.4. 10.1.1 This section applies to the storage on
farms or in rural areas of flammable and
combustible liquids having a flash point below
9.3 LOCATION OF PROCESS UNITS 93.4C (200F). It is also applicable to the storage
of flammable and combustible liquids at rural
9.3.1 Process units shall be located so thatthey construction and rural earth-movirig projects,
are accessible from at least one side for the including gravel pits and borrow pits, where it is
purpose of fire control. Where the topographical customary to obtain fuels in bulk and dispense or
conditions are such that liquids can flow from a transfer them under control of the owner or
processing area so as to constitute a fire hazard to contractor and where isolation from other
property of others, provision shall be made to structures and temporary use make it un-
divert or impound the flow by curbs, drains, or necessary. in the opinion of the authority having
other suitable means. jurisdiction, to require compliance with the more
rigid requirements of the other sections.

9.4 FIRE CONTROL

10.2 TYPES OF APPROVED STORAGE


9.4.1 Portable fire extinguishment and control
equipment shall be provided in such quantities
and types as are needed for the special hazards of 10.2.1 Storage of flammable and combustible
operation and storage. MS 566 : Pt. 3. Fire liquids in rural areas for private use shall be
fighting installation and equipment. Part 3 permitted in any of the following:
Portable fire extinguisher. provides information
as to the suitability of various types of (a) in aboveground or underground tanks or in
extinguishers. containers in accordance with section 2 or
section 4;
9.4.2 Water shall be available in volume and at
adequate pressure to supply water hose streams. (b) in containers of 225 litres or less capacity
foam producing equipment. automatic spfinklers each in accordance with 10.3;
or water spray systems as the need is indicated by
the special hazards of operation and storage. (c) in tanks of 226 to 4.1 60 litres capacity each
in accordance with 10.4.
9.4.3 Special extinguishing equipment such as
that utilizing foam. inert gas. or dry chemical shall
be provided as the need is indicated by the special 10.2.2 Storage areas shall be kept free of
hazards of operation and storage. weeds and extraneous combustible material.
Open flames and smoking shall not be permitted
9.4.4 Smoking shall be permitted only in in flammable or combustible liquids storage
approved areas. areas.

77
MS761 :1982

10.3 INDIVIDUAL CONTAINERS OF 225 LITRES 10.4.1.1 A fill opening shall be provided and
OR LESS CAPACITY EACH shall be equipped with a closure designed sothat
it may be locked.
10.3.1 Storage shall be in metal DOT or other
approved containers of 225 litres or less capacity 10.4.1.2 A vent having a free opening of at least
each. Discharge devices requiring pressure on 38 mm diameter shall be provided to relievesuch
the container are prohibited. Pumping devices or vacuum or pressure as will develop in normal
faucets used for dispensing flammable and operation or from exposure to fire. For tanks
combustible liquids shall be well maintair~edto exceeding 1 .040 litres capacity. see 2.2.5 for
prevent leakage. Individual containers shall not additional information relative to required
be interconnected and shall be kept closed when capacity of emergency relief venting for fire
not in use. exposure (Note 9).

10.3.2 Containers as provided in this section Vents shall be arranged to discharge in such a
storing Class I flammable liquids shall be stored way as to prevent localized overheating of. or
cutside at least 3 m from any building or may be flame impingement on. any part of the tank in the
stored inside a building used exclusively for the event vapours from such vents are ignited.
storage of flammable and combustible liquids
NOTE 9. Based upon limiting internal tank pressure to 120%of 17 kPa
and located at least 3 m from any other building.
(gauge) using an orifice coefficient of 0.8 and an environmentai factor
Buildings used for the storage of Class I of 0.6. The environmentai factor of 0.6 recognizes the limited time a
flammable liquids shall be provided with cross smail tank is subjected to fire exposure and some loss of fuel by
ventilation with at least 2 vents of 400 cm2 of area absorption into the soil. The above factors may be used when
calculating the vent size for tanks larger than 1.040 litres.
each placed at floor level.
10.4.1.3 Tanks as provided in this section shall
be kept outside and at least 1 2 m from any
10.4 TANKS OF 226 to 4,160 LITRES CAPACITY building, and shall be so located or such
EACH - - - - additional distance from buildings shall be
provided, as will insure that any vehicle,
10.4.1 Flammable and combustible liquids in equipment. or container being filled directlyfrom
aboveground tanks of 226 to 4.160 litres such tank will be at least 12 m from any building.
capacity shall be stored outside buildings in tanks
of single-compartment design constructed in 10.4.1.4 Tanks as provided in this section may
accordance with accepted engineering practice. be either tanks with top openings only or tanks
Joints shall be riveted and caulked, riveted and elevated for gravity discharge. -

welded, or welded. Tank heads over 2 m in


diameter shall be dished, stayed, braced or 10.4.2 Tanks with top opening only. Tanks
reinforced. Tanks shall meet the following: constructed and located as provided above may
be designed with all openings in the top of the
tank and in such event shall be mounted and
Capacity Minimum thickness of steel equipped as follows:
litres mfrs. std. gauge no.

(a) Stationary tanks shall be mounted on


226 to 2,000 14 timbers or blocks approximately 1 50 mm in
2,001 to 4,160 12 height so asto protect the bottom of the tank from

78
MS761 :1982

corrosion from contact with the ground and when of earth or near the edge of a cut bankto provide
so placed, be in a stable position; -or movable the necessary elevation and shall be supported
tanks may be equipped with attached metal legs on timbers or blocks for stability and to prevent
resting on shoes or runners designed so that the corrosion by contact with the ground.
tank is supported in a stable position and so that
- theentiretankanditssupportsmaybemovedasa (c) Bottom opening for gravity discharge shall
unit. be equipped with a valve located adjacent to the
tank shell which will close automatically in the
(b) Tanks shall be equipped with a tightly and event of fire through the operation of an effective
permanently attached approved pumping device heat actuated releasing device. If this valve
having an approved hose of sufficient length for cannot be operated manually. it shall be
filling vehicles, equipment or containers to be supplemented by a second valve which can be.
served from the tank. Either the pump or the hose The gravity discharge outlet shall be provided
shall be equipped with a padlock to its hanger to with an approved hose equipped with a self-
prevent tampering. An effective antisiphoning closing valve at the discharge end. of a type than
device shall be included in the pump discharge can be padlocked to its hanger to prevent
unless a self-closing nozzle is provided. Siphons tampering.
or ~nternaI pressure discharge devices are
prohibited.
10.5 MARKING OF TANKS AND CONTAINERS
10.4.3 Tanks elecated for gravity discharge.
Tanks constructed and located as provided above 10.5.1 Tanks and containers for the storage of
may be designed with a connection in the bottom flammable and combustible liquids aboveground
or the end of the tank for gravity dispensing of shall be conspituously marked with the
flammable and combustible liquids and shall be name of the product which they contain and
mounted and equipped as follows: FLAMMABLE KEEP FIRE AND FLAME AWAY.

Tanks of 226 to 4,160 litres capacity shall bear


(a) Supports to elevate the tank for gravity the additional marking KEEP 12 METRES FROM
discharge shall be of adequate strength and BUILDINGS.
design to provide stability. Supports may be of
steel or of wood.
NOTE 10. Clearance of 12 metres from buildings shouid also apply to
(b) Alternately the tank may be placed on a pile other combustible structures, haystacks, etc.

79
MS 761:1982

Appendix A
Abandonment or removal of underground tanks

Al. INTRODUCTION Al.4 In cases where tanks rendered tem-


porarily out of service or permanently
Al .1 Care is required not only in the handling abandoned, records should be kept of tank size,
and use of flammable or combustible liquids but location, date of abandonment, and method used
also in abandoning tanks which have held for placing the abandoned tank in a safe
flammable or combustible liquids. This is condition.
particularly true of underground service station
tanks which are most frequently used for the Al.5 Procedures for carrying out each of-the
storage of motor fuel and occasionally for the above methods of disposing of underground
storage of other flammable or combustible tanks are described in the following clauses. No
liquids, such as crankcase drainings (which may cutting torch or other flame or spark producing
contain some gasoline). Through.carelessness or equipment shall be used until the tank has been
curiosity, explosions have occurred because completely purged or otherwise rendered safe. In
flammable or combustible liquid tanks had not each case. the numbered steps given shall be
been properly conditioned before being carried out successively.
abandoned.

A1.2 In order to prevent accidents caused by A2. RENDERING TANKS TEMPORARILY OUT
-improper conditioning. -it is recommended that OF SERVICE
the procedures outlined below be followed when
underground tanks are removed, abandoned or
A2.1 Cap the fill line, gauge opening, and pump
temporarily taken out of service.
suction, secure against tampering.
A1.3 Underground tanks taken out of service
may be safeguarded or disposed of by any one of A2.2 Leave the vent line open.
the three following means:

(a) Placed in a temporarily out of service A3. ABANDONING UNDERGROUND TANKS IN


condition. Tanks should be rendered temporarily PLACE
out of service only when it is planned that they
will be returned to active service within a A3.1 Remove all flammable or combustible
reasonable period or pending removal or liquid from the tank and from all connecting lines.
abandonment within 90 days.
A3.2 Disconnect the suction, inlet, gauge, and
(b) Abandoned in place. with proper safe- vent lines.
guarding.
A3.3 Fill the tank completely with an inert solid
(C) Removed. material. Cap remaining underground piping.

80
MS 761: 1982

A4. REMOVAL OF UNDERGROUND TANKS should be retested for flammable vapours, and, if
necessary, rendered gas free. After junking and
A4.l Remove all flammable or combustible before releasing to junk dealer, a sufficient
liquids from tank and from connecting lines. number of holes or openings should be made in it
to render it unfit for further use. NFPA 327,
A4.2 Disconnect the suction, inlet, gauge. and Standard. Procedures for cleaning or safe-
vent lines; remove sections of connecting lines guarding small tanks and containers, provides
which are not to be used further and cap or plug information on safe procedures for such
inlets, outlets, and leaks if any. After removal, the operations.
tank may be gas freed on-the premises if it can be
done safety at that locationor may be transported
to an area not accessible to th.e public and the gas
freeing completed at that location. A6. REUSE OF UNDERGROUND TANKS

A6.1 Used tanks which are to be reused for


A5. DISPOSAL OF TANKS flammable or combustible liquid service shall
meet all the requirements of this Code for the
A5.l If a tank is to be disposed of as junk, it installation of underground tanks.

81
MS 761:1982

- Appendix B

Protection of tanks containing flammable or combustible -liquids in -

locations that may be flooded

81. APPLICATION capacity, provided, however, that the submerged


part of the tank shall not exceed 21/2 times the
~ The provisions herein are recommended diameter; or;
for the protection of tanks containing flammable
(b) As an alternative to the foregoing, adequate
or combustible liquids that may become buoyant
noncombustible structural guides, designed to
due to a rise in the level of thewatertable or due to
permit the tank to float vertically without loss of
their location in an area that may be subjected to
product, shall be provided.
flooding.

B2.2 Horizontal tanks.

B2. ABOVEGROUND TANKS B2.2.1 Independent water supply facilities


shall be provided at locations where there is no
B2.l Vertical tanks ample and dependable public water supply
available for loading partially empty tanks with
B2.1 .1 No aboveground vertical storage tank
water.
containing a flammable or combustible liquid
shall be located so that the allowable liquid level B2.2.2 Each horizontal tank so located that
within the tank is belowthe established maximum more than 70% of its storage capacity will be
flood stage, unless the tank is provided with a submerged at the established flood stage. shall
guiding structure such as described in clause B6.
be anchored, attached to a foundation of
concrete or of steel and concrete, of sufficient
B2.1 .2 Independent water supply facilities
weight to provide adequate load for the tank when
shall be provided at locations where there is no
filled with flammable or combustible liquid and
ample and dependable public water supply
submerged by flood waters to the established
available for loading partially empty tanks with
flood stage. or adequately secured by other
water.
means.
82.1.3 In addition to the preceding require-
ments, each tank so located that more than 70%. 82.3 Other types of tanks
but less than 100%. of its allowable liquid storage
B2.3.1 Spherical and spheroidal tanks shall be
capacity will be submerged at the established
protected by applicable methods as specified for
maximum flood stage, shall be safeguarded by
either vertical or horizontal tanks.
one of the following methods:

(a) Tank shall be raised. or its height shall be


increased, until its top extends above the 83. UNDERGROUND TANKS
maximum flood stage a distance equivalent to
30% or more of its allowable liquid storage B3.1 At locations where there is no ample and

82
MS 761 :1 982

dependable water supply. or where filling of 85.2 The self-contained power and pumping
underground tanks with liquids is impracticable unit shall be so located or so designed that
because of the character of their contents, their pumping into tanks may be carried on
use, or for other reasons, each tank shall be continuously throughout the rise in flood waters
safeguarded against movement when empty and from a level 3m belowthe lowesttanktothe level
submerged by high ground water orflood waters of the potential flood stage.
by anchoring, weighting with concrete or other
approved solid loading material, or securing by 85.3 Capacity of the pumping unit shall be such
other means. Each such tank shall be so that the rate of rise of water in all tanks shall be
constructed and installed that it will safely resist equivalent to the established potential average
external pressures due to high ground water or rate of rise of flood waters at any stage.
flood waters.
85.4 Each independent pumping unit shall be
83.2 At locations where there is an ample and tested periodically to insure that it is in
dependable water supply available. underground satisfactory operating condition.
tanks containing flammable or combustible
liquids. so installed that more than 70% of their
storage capacity will be submerged at the 86. STRUCTURAL GUIDES
maximum flood stage, shall be so anchored,
weighted, or secured by other means as to 86.1 Structural guides for holding floating
prevent movement of such tanks when filled with tanks above their foundations shall be so
flammable or combustible liquids, and sub- designed that there will be no resistance to the
merged by flood waters to the established flood free rise of a tank, and shall be constructed of
stage. noncombustible material.

86.2 The strength of the structure shall be


84. PIPE CONNECTIONS adequate to resist lateral movement of a tank
subject to a horizontal force in any direction
B4~1 Pipe connections below the allowable equivalent to not less than 1 200 N/rn2 acting on
liquid level in a tank shall be provided with valves the projected vertical cross-sectional area of the
or cocks located as closely as practicable to the tank.
tank shell. Such valves and their connections to
tanks shall be of steel or other material suitable 86.3 Where tanks are situated on exposed
for use with the liquid being stored. Cast iron shall points or bends in a shore line where swift
not be permitted. currents in flood water will be present. the
structures shall be designed to withstand a unit
force of not less than 2400 N/rn2.

85. INDEPENDENT WATER SUPPLY FACILITIES


B7. SAFE PRACTICES
B5.1 At locations where an independent water
supply is required. it shall be entirely independent 87.1 Water Loading
of public power and water supply. Independent
source of water shall be available when flood B7.1.1 The filling of a tank to be protected by
waters reach a level not less than 3m below the water loading shall be started as soon as flood
bottom of the lowest tank on a property. waters reach a dangerous flood stage. The rate of

83
MS761 :1982

filling shall be at least equal to the rate of rise of 87.2.3 If a tank is equipped with a swing line,
the flood water (or the established average the swing pipe shall be raised to and secured at its
potential rate of rise), highest position.

B7.1.2 Sufficient fuel to operate the water


pumps shall be available at all times to insure B8. INSPECTION
adequate power to fill all tankage with water.
88.1 The authority having jurisdiction shall
B7.1 .3 All valves on connecting pipe lines shall make periodic inspections of all plants where the
be closed and locked in closed position when storage of flammable or combustible liquids is
water loading has been completed. such as to require compliance with the foregoing
requirements, in order to assure the following:
87.2 Floating tanks
(a) That all flammable or combustible liquid
87.2.1 Where structural guides are provided storage tanks are in compliance with these
for the protection of floating tanks, all rigid requirements and so maintained.
connections between tanks and pipe lines shall
be disconnected and blanked off or blinded (b) That detailed printed instructions of what to
before the flood waters reach the bottom of the do in flood emergencies are properly posted.
tank, unless control valves and their connections
to the tank are of a type designed to prevent (c) That station operators and other employees
breakage between,the valve and the tank shell. depended upon to carry out such instructions are
thoroughly informed as to the location and
87.2.2 All valves attached to tanks other than operation of such valves and other equipment
those used in connection with water loading necessary to effect the intent of these
operations shall be closed and locked, requirements.

84
MS761 :1982

Appendix C
Classification of hazardous areas

Cl. SCOPE Zone 1. An area in which a dangerous atmos-


phere is likely to occur in normal operating
Cl .1 This applies to the classification of conditions.
hazardous areas in which flammable gases or
vapours are or may be present in the air in Zone 2. An area in which a dangerous atmos-
quantities sufficient to produce explosive or phere can occur only in abnormal conditions and
ignitible mixtures, Areas are classified depending not in normal operation.
on the properties of the flammable vapours,
NOTE 11. The definitions for the area classification are based on the
liquids or gases which may be present and the
general definitions given in B5 5345:Part2 and have been interpreted
likelihood that a flammable or combustible in the light of the particular conditions that apply in the petroleum
concentration or quantity is present. Each room. industry.

section or area shall be considered individually in


determining its classification.
C2.3 By implication an area that is not
classified zone 0. 1 or 2 is deemed to be a non-
hazardous or safe area with respect to this code.
In safe areas normal industrial types of electrical
C2. CLASSIFICATION OF HAZARDOUS AREAS
apparatus can be installed.

C2.1 In order to determine the type of electrical


equipment appropriate to a particular situation, it
is necessary to classify the area according to the
C3. ELECTRICAL EQUIPMENT
degree of probability of the presence of a
dangerous atmosphere. i.e. an atmosphere
containing a significant quantity of flammable C3.1 Electrical equipment is conveniently
gas or vapour in a concentration capable of divided into various types which can thep be
ignition. related to use in the various zones defined in
C2.2. The types of electrical equipment which
may be used in the various zones are:
C2.2 Hazardous areas are classified into the
following zones as defined (Note 11): (a) Zone 0. Only intrinsically safe certified
apparatus and circuits.
Zone 0. An area in which any flammable
atmosphere is continously present, or present for
~B55345 : Part 2. Code of Practice for the selection, installation and
long periods, in concentrations within the lower maintenance of electricai apparatus, for use in potentially explosive
and upper limits of flammability. atmospheres (other than mining applications or explosive processing
and manufacture).
Part 2 : Classification of hazardous areas.

85
MS 761 :1982

(b) Zone 7. (i) Specially selected industrial, non-


incentive or restricted breathing equipment.
() Intrinsically safe certified apparatus and
circuits.
(ii) Flame-proof equipment. (ii) All types of equipment for use in Zone 0 or
(iii) Increased safety equipment. Zone 1.
(iv) Pressurized and continuous dilution
equipment. Electrical equipment must be tested and certified
by the relevant authority as being intrinsically
(c) Zone 2. safe. flameproof. etc.

86
MS761 :1982

Appendix D

List of reference standards

Dl. MALAYSIAN STANDARDS

MS 484 Code of Practice for hydrant systems

MS 538 Method of test forvapour pressure of petroleum products


(Reid Method)

MS 541 Method for determination of penetration of bituminous


materials

MS 563 Method of test for distillation of petroleum products

MS 566 : Pt. 3 Fire fighting installations and equipment. Part 3:Portable


fire extinguisher

MS 648 Method of test for flash point by the Abel apparatus

MS 686 Method of test for flash and fire points by Pensky-


Martens Closed Tester

MS 683 Class labels for dangerous goods

MS Code of Practice for protection of structures against


lightn ing*

D2. UNITED STATES NATIONAL FIRE PROTECTION ASSOCIATION

NFPA 15 Standard for water sprayfixed systems for fire protection

NFPA 36 Standard for solvent extraction plants

NFPA 45 Standard on fire protection for laboratories using


chemicals

NFPA 51 Standard for the installation and operation of oxygen-


fuel gas systems for welding and cutting

NFPA 69 Explosion prevention systems

Malaysian Standards in the course of preparation.

87
MS761 :1982

NFPA 77 Recommended practice on static electricity

NFPA 87 Standard for the construction and protection of piers


and wharves

NFPA 204 Guide for smoke and heat venting

NFPA 231C Rack storage of materials

NFPA 302 Fire protection standard for motor craft

NFPA 303 Fire protection standard for marinas and boatyards

NFPA 327 Standard procedures for the standard for cleaning or


safeguarding small tanks and containers

NFPA 386 Standard on portable shipping tanks

NFPA 704 Standard system for the identification of the fire


hazards of materials

D3. AMERICAN PETROLEUM INSTITU1E

API Std. No. 1 2B Specification for bolted production tanks

API Std. No. 1~2D Specification for large welded production tanks

API Std. No. 1 2F Specification for small welded production tanks

API Std. No. 620 Recommended rules for the design and construction of
large, welded, low-pressure storage tanks

API Std. No. 650 Specification for welded steel tanks

API Std. No. 2000 Venting atmospheric and low-pressure storage tanks

D4. AMERICAN NATIONAL STANDARD INSTITUTE

ANSI B31 American National Standard Code for pressure piping

ANSI B3 1 .3 Petroleum refinery piping

ANSI B31 .4 Liquid petroleum transportation piping systems

88
MS761 :1982

D5. AMERICAN SOCIETY FOR TESTING, AND MATERIALS

ASTM A395 Ferritic ductile iron pressure retaining casings for use
at elevated temperatures

ASTM 092 Cleveland open cup test method

ASTM 03243 Standard methods of test for flash point of aviation tur-
bine fuels by Setaflash Closed Tester

ASTM 03278 Standard method of test for flash point of liquids by Se-
taflash Closed Tester

D6. AMERICAN SOCIETY OF MECHANICAL ENGINEERS

ASME Boiler and pressure vessel code

D7. UNDERWRITER LABORATORIES INC.

UL 58 Standard for steel underground tanks for flammable and


combustible liquids

UL 80 Standard for steel inside tanks for oil burner fuel

UL 1 42 Standard for steel aboveground tanks for flammable and


and combustible liquids

D8. REGULATIONS

Uniform Building By-Laws 1 976; Street, Drainage and Building Act, 1 974.
Building Act, 1974.

Electricity Regulations. 1951 (Revised 1977);


Electricity Act. 1 949 (Act 11 6)

Code of Federal Regulations [United States Department of Transportation


(DOT) Regulations..7.

89
MS761 :1982

D9. BRITISH STANDARDS

BS 4683 Specification for electrical apparatus for explosive atmospheres.


Part 2: The construction and testing of flameproof enclosures of
electrical apparatus.

BS 5345 Code of Practice for the selection, installation and maintenance of


electrical apparatus for use in potentially explosive atmospheres
(other than mining applications or explosive processing and manu-
facture)
Part 1: Basic requirements for all parts of the Code
Part 2: Classification of hazardous areas.

Part 3: Installation and maintenance requirements for electrical


apparatus with type of protection d. Flameproof enclosure

Part 4: Installation and maintenance requirements for electrical


apparatus with type of protection i. Intrinsically safe electrical
apparatus and systems.

Part 6: Installation and maintenance requirements for electrical


apparatus with type of protection e. Increased safety.

Part 7: Installation and maintenance requirements for electrical


apparatus with type of protection N.

Part 8: Installation and maintenance requirements for electrical


apparatus with type of protection e. Special protection.

BS 5500 Specification for unfired fusion welded pressure vessels.

90
TANDA-TANDA STANDARD SIRIM
Tanda-tanda Standard SIRIM seperti yang tertera di bawah adalah tanda-tanda pengesahan
dagangan berdaftar. Tanda-tanda ini hanya boleh digunakan oleh mereka yang dilesenkan
di bawah skim tanda pengesahan yang dijalankan oleh SIRIM mengikut nombor Standard
Malaysia yang berkaitan. Kewujudan tanda-tanda ini pada atau berkaitan dengan sesuatu
barangan adalah sebagai jaminan bahawa barangan tersebut telah dikeluarkan melalui satu
sistem penyeliaan, kawalan dan ujian, yang dijalankan semasa pengeluaran. Ini termasuk
pemeriksaan berkala kerja-kerja pengeluaran menurut skim tanda pengesahan SIRIM yang
dibentuk untuk menentukan bahawa barangan tersebut menepati Standard Malaysia.

Keterangan-keterangan lanjut mengenai syarat-syarat lesen boleh didapati dari:

Ketua Pengarah
Institut Standard dan Penyelidikan Perindustrian Malaysia
Persiaran Dato Menteri, Seksyen 2, Peti Surat 7035
40911 Shah Alam
Selangor Darul Ehsan

SIRIM STANDARD MARKS


The SIRIM standard marks shown above are registered certification trade marks. They may
be used only by those licensed under the certification marking scheme operated by SIRIM
and in conjunction with relevant Malaysian Standard number. The presence of these Marks
on or relation to a product is assurance that the goods have been produced under a system
of supervision, control and testing, operated during production, and including periodical
inspection of the producers works in accordance with the certification marking scheme of
SIRIM designed to ensure compliance with a Malaysian Standard.

Further particulars of the terms of license may be obtained from:

Director-General
Standards and Industrial Research Institute of Malaysia
Persiaran Dato Menteri, Section 2. P.O.Box 7035
40911 Shah Alam
Selangor Darul Ehsan

3
MS ISO/TR 9007 : 1993
INSTITUT STANDARD DAN PENYELIDIKAN PERINDUSTRIAN MALAYSIA

Institut Standard dan Penyelidikan Perindustrian Malaysia (SIRIM) telah ditubuhkan hasil dari cantuman Institut
Piawaian Malaysia (SIM) dengan Institut Negara bagi Penyelidikan Sains dan Perusahaan (NISIR) di bawah
Undang-Undang Malaysia Akta 157 pada 16hb. September 1975:Akta Institut Standard dan Penyelidikan
Perindustrian Malaysia (Perbadanan) 1975. Institut ini diletakhak dengan kuasa untuk memamju dan
menjalankan penyelidikan perindustrian dan untuk menyedia dan memajukan standard-standard bagi barangan-
barangan, proses-proses, amalan-amalan dan perkhidmatan-perkhidmatan; dan bagi mengadakan peruntukan
bagi perkara-perkara yang bersampingan atau berkaitan dengan maksud-maksud itu.

Satu daripada tugas-tugas Institut ini adalah menyediakan Standard-Standard Malaysia dalam bentuk
penentuan-penentuan bagi bahan-bahan, keluaran-keluaran, kaedah-kaedah ujian, kod-kod amalan yang
sempurna dan selamat, sistem penamaan dan lain-lain. Standard-Standard Malaysia disediakan oleh
jawatankuasa-jawatankuasa perwakilan yang menyelaras keupayaan pengilang dan kecekapan pengeluaran
dengan kehendak-kehendak yang munasabah dari pengguna. Ia menuju ke arah mencapai kesesuaian bagi
maksud, memudahkan pengeluaran dan pengedaran, kebolehsalingtukaran gantian dan pelbagai pilihan yang
mencukupi tanpa pembaziran.

Standard-Standard Malaysia disediakan hanya setelah penyiasatan yang lengkap menujukkan bahawa sesuatu
projek itu disahkan sebagai yang dikehendaki dan berpadanan dengan usaha yang terlibat. Hasil ini berasaskan
persetujuan sukarela dan memberi pertimbangan kepada kepentingan pengeluar dan pengguna. Standard-
Standard Malaysia adalah sukarela kecuali is dimestikan oleh badan-badan berkuasa melalui peraturan-
peraturan, undang-undang persekutuan dan tempatan atau cara-cara lain yang sepertinya.

Institut ini beroperasi semata-mata berasaskan tanpa keuntungan. Ia adalah satu badan yang menerima bantuan
kewangan dari Kerajaan, kumpulan wang dari bayaran keahlian, hasil dari jualan Standard-Standard dan
terbitan-terbitan lain, bayaran-bayaran ujian dan bayaran-bayaran lesen untuk mengguna Tanda Pengesahan
SIRIM dan kegiatan-kegiatan lain yang berhubung dengan Penstandardan, Penyelidikan Perindustrian dan
Khidmat Perunding.

STANDARDS AND INDUSTRIAL RESEARCH INSTITUTE OF MALAYSIA

The Standard and Industrial research Institute of Malaysia (SIRIM) is established with the merger of the
Standards Institution of Malaysia (SIM) and the National Institute for Scientific and Industrial Research (NISIR)
th
under the Laws of Malaysia Act 157 on 16 . September 1975: Standards and Industrial Research Institute of
Malaysia (Incorporation) Act 1975. The Institute is vested with the power to provide for the promotion and
undertaking of industrial research and for the preparation and promotion of standards for commodities,
processes, practices and services; and to provide for matters incidental to or connected with those purposes.

One of the functions of the Institute is to prepare Malaysian Standards in the form of specifications for materials
and products, methods of testing, codes of sound and safe practice, nomenclature, etc. Malaysian Standards are
prepared by representative committees which co-ordinate manufacturing capacity and production efficiency with
the users reasonable needs. They seek to achieve fitness for purpose, simplified production and distribution
replacement interchangeability, and adequate variety of choice without wasteful diversify.

Malaysian Standards are prepared only after a full enquiry has shown that the project is endorsed as a desirable
one and worth the effort involved. The work is based on voluntary agreement, and recognition of the community
of interest of producer and consumer. The use of Malaysian Standards is voluntary except in so far as they are
made mandatory by statutory authorities by means of regulations, federal and local by-laws or any other similar
ways.

The Institute operates entirely on a non-profits basis. It is a grant aided body receiving financial aid from the
Government, funds from membership subscriptions and proceeds from sales of Standards and other
publications, fees and licence fees for the use of SIRIM Certification Mark and other activities associated with
Standardization, Industrial Research and Consultancy Services.

Anda mungkin juga menyukai