sibilities SITE TEST REPORT Date :


Legend Contractors name: Advance Customer:
CSD Energy Company (AECC) NG-SA
Contract No. :
Name of substation: 115/13.8KV Khafji Substation - 5 31131152/00
Page 1 of 2
LOCK-OUT RELAY
Make: Equip. No.: Dwg. Ref.: Record No.:

1. GENERAL DATA AND INFORMATION.

Panel No: Designation LOR


Make Electro switch Type 7810F
Serial No: Aux: Voltage 110 - 125 V DC
Application Trip Lock out relay
Model No:

2 .MECHANICAL CHECKS AND VISUAL INSPECTION. (Tick if verified)

ITEM DESCRIPTION REMARKS


1. Inspect for any physical damage or defects.
2. Verify connections as per approved drawing.
3. Check tightness of all connections.
4. Check case earthing

3. ELECTRICAL TEST.
a. FUNCTION TEST:

ITEM DESCRIPTION REMARKS


1. Indication/Target check, Reset checked.
2. All contacts checked.

b. PICKUP TEST

COIL VOLTAGE (V DC) CURRENT (mA) LIMITS


OPERATE 30 70 V
RESET

C. OPERATING TIME TEST:

TEST DATE:
TESTING ENGINEER CSD- Engineer

Signature: ________________ Signature: ________________


Name : ________________ Name : ________________
SITE TEST REPORT Date :
Contractors name: Advance Customer:
Energy Company (AECC) NG-SA
Contract No. :
Name of substation: 115/13.8KV Khafji Substation - 5 31131152/00
Page 2 of 2
LOCK-OUT RELAY
Make: Equip. No.: Dwg. Ref.: Record No.:

VOLTAGE RESETTING
OPERATING RESETTING OPERATING
APPLIED (V LIMIT (ms)
TIME (ms) TIME (ms) LIMITS (ms)
DC)
< 11 < 80
125

d. OPERATING COIL RESISTANCE TEST:

Resistance Measured () Limits


93 115

E. OPERATING CURRENT TEST

OPERATING COIL RESET COIL


VOLTAGE APPLIED (V DC)
(mA)

CAUTION: DO NOT GIVE VOLTAGE TO THE LOCK OUT RELAY COIL SLOWLY, TO
PICK UP THE COIL.

4. TEST EQUIMENTS USED:

ITEM Test Equipment Serial Number Calibration date Calibration due date
1
2

TEST DATE:
TESTING ENGINEER CSD- Engineer

Signature: ________________ Signature: ________________


Name : ________________ Name : ________________