Anda di halaman 1dari 10

IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 24, NO.

5, MAY 2009 1223

An Optimization-Based Algorithm for Shunt Active


Filter Under Distorted Supply Voltages
Koteswara Rao Uyyuru, Mahesh K. Mishra, Member, IEEE, and Arindam Ghosh, Fellow, IEEE

AbstractIn this paper, an optimization-based control algo- are effectively alleviated by using a shunt active power filter
rithm for the compensation of steady-state load under distorted (APF) [2]. The selection of control strategy for the APF plays
supply voltages is presented. For balanced and sinusoidal supply an important role to get the desired compensation character-
voltages, load compensation using shunt active filter produces per-
fect harmonic cancellation (PHC) and unity power factor (UPF) istics. The two main control strategies for load compensation
source currents. However, when the supply voltages are distorted, are perfect harmonic cancellation (PHC) and unity power fac-
compensation for PHC will not provide UPF, as the harmonics in tor (UPF) [3][13]. The PHC strategy results in distortion-free
the supply voltages are not utilized for delivering the average power. source currents and it is proved that under this strategy, APF
In the same way, to achieve UPF source currents, the compensated provides better performance [3]. Implementation of a UPF con-
source currents should have the same harmonics, unbalance, shape,
and be in phase with the respective supply voltages, thereby vio- trol strategy gives minimum rms values of source current for a
lating the perfect harmonic cancellation objective. Hence, there given average load power [4]. The main advantage of UPF is
should be an optimal operation between these two important com- that it can preserve the damping provided by the resistive part
pensation characteristics. The optimization-based control algo- of the compensated load. This damping effect is required in
rithm presented in this paper gives the best power factor while the case of resonance phenomena, particularly in the voltage-
satisfying the constraints such as total harmonic distortion limits
and average power balance of source currents. It is also flexible to distorted grids, failing which, severe voltage distortion results
adopt different compensation characteristics based upon the sup- at the point of common coupling (PCC) [8].
ply voltage conditions. MATLAB and its optimization toolbox are Under balanced and sinusoidal supply voltages, both UPF
used for simulation studies and solving the nonlinear optimization and PHC strategies result in similar compensation characteris-
problem, respectively. The algorithm is validated by using a proto- tics. But under distorted supply voltages, these two important
type of digital signal processor (TMS320F2812PGFA)-based shunt
active power filter. Detailed experimental results are presented. attributes of load compensation cannot be achieved simulta-
neously. The control strategy for UPF demands that the com-
Index TermsActive power filter (APF), digital signal processor pensated source currents have to be of same shape, harmonics,
(DSP), load compensation, optimization, perfect harmonic cancel-
lation, unity power factor. unbalance, and in phase with the respective phase voltages,
which will not ensure perfect harmonic cancellation. Similarly,
PHC strategy will not allow any harmonic component in the
I. INTRODUCTION compensated source currents. It is also possible to compensate
the unbalance and reactive part of the load current under this
HE DEMAND from the electricity consumers for good
T quality of power supply is ever increasing due to the pro-
liferation of sensitive loads. This is often a challenging task.
strategy. However, UPF cannot be achieved by this strategy, be-
cause the supply voltage harmonics are not utilized to supply
average load power. Most of the existing works on shunt ac-
The widespread use of adjustable-speed drives, static power
tive power filters under distorted supply voltages adopts either
converters such as single-phase and three-phase rectifiers, and
one of the two control strategies (PHC or UPF). In order to
a large number of power-electronics-based equipments cause
utilize the advantages of both the strategies, there should be an
distortion in the source currents. The loads such as induction
optimal operation between these two important compensation
furnaces and motors increase the rating of the equipments used
characteristics.
in the power system. Single phasing and unequal distribution
Through the evaluation of PHC and UPF strategies, an op-
of loads among three phases cause excessive neutral current to
timal and flexible control strategy is proposed in [6]. In this
flow in the system [1]. Though conventional load compensation
method, a two-step process is adopted to get the desired source
using passive filters is simple to design and operate, it has draw-
currents. First, the actual voltages are processed through filters,
backs like resonance, overloading, and detuning. Moreover, it
whose gains are optimized and tuned to get desired voltages.
is not suitable for fast changing loads. The aforesaid problems
These voltages are then multiplied by a constant conductance
to get the reference source currents, thus resulting in the aver-
Manuscript received September 1, 2008; revised November 3, 2008. Current age power being equal to the load average power. This method
version published April 17, 2009. Recommended for publication by Associate employs pq theory that is quite computation intensive. Also, it
Editor J. R. Rodriguez.
K. R. Uyyuru and M. K. Mishra are with the Department of Electrical Engi- generates some additional harmonics in the extracted reference
neering, Indian Institute of Technology Madras, Chennai 600 036, India (e-mail: currents under distorted supply voltages [14]. It also involves
ee06s007@iitm.ac.in; mahesh@ee.iitm.ac.in). multiple transformations (abc to and to abc), which
A. Ghosh is with the School of Engineering Systems, Queensland University
of Technology, Brisbane, Qld. 4001, Australia (e-mail: a.ghosh@qut.edu.au). will increase the computational time. G. W. Chang et al. pro-
Digital Object Identifier 10.1109/TPEL.2008.2011908 posed a steady-state optimized load compensation algorithm

0885-8993/$25.00 2009 IEEE


1224 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 24, NO. 5, MAY 2009

to meet IEEE-519 harmonic current limits and other alternate (3n + 3) radian according to the positive, negative, zero se-
performance indices [15], [16]. However, their research is lim- quences, respectively, for a fundamental frequency of ra-

ited to simulation studies only. dian [18]. In this case, v + 0
sa (t), v sa (t), and v sa (t) in (2) will
In [17], a nonlinear optimization technique is employed to have 3n + 1, 3n + 2 and 3n + 3 harmonics, respectively. How-

get the optimal performance between total harmonic distortion ever, for an unbalanced distorted system, v + sa (t), v sa (t), and
0
(THD) limits and the UPF. The algorithm employs a one-step v sa (t) will contain all the harmonics of the source voltages.
process to get the reference source currents. However, in this The balanced steady-state voltage harmonic components can
control algorithm, the authors assumed that the supply voltages be determined by using the following expressions. For 3n + 1
are balanced, but distorted. As the presence of unbalance in harmonic order, it is written as follows:
the supply voltages is a common phenomenon, this algorithm
t +T
+ 2 1
j ((3n +1) t /2)
cannot be used in such cases. V sa (3n +1) = v+sa (t)e dt (3)
In this paper, a new load compensation algorithm based on op- T t1
timization and extraction of balanced components using Fourier where n = 0, 1, . . . , k. The term t1 is an arbitrary instant and
transform is proposed. This algorithm works effectively not T is the time period of the cycle. The integration is carried out
only under balanced distorted supply voltages, but also under using a moving average technique to settle any change in supply
unbalanced conditions. The Fourier transform is used to get the voltages within one cycle, assuming that the source voltages
balanced set of voltages from the unbalanced distorted supply may contain both even and odd harmonics. From the previous
voltages. The desired source currents are computed by multiply- expression |V + sa (3n +1) | and V sa (3n +1) can be obtained. The
 +

ing the balanced set of voltages with the conductance factors, balanced 3n +2 harmonic voltages are given by
which are obtained from the optimization process. For better dy-
t +T
2 1
namic response, a moving average filter is adopted to calculate V sa (3n +2) = v
sa (t)e
j ((3n +2) t /2)
dt (4)
average load power as well as balanced set of supply voltages. T t1
In the following section, the extraction of balanced set of volt- where n = 0, 1, . . . , k. From the previous expression,
ages from available unbalanced distorted supply voltages using |V
sa(3n +2) | and V sa(3n +2) can be obtained. Similarly, the

Fourier transform is presented. 3n + 3 harmonic voltages are obtained as follows:

t +T
2 1
II. EXTRACTION OF THE BALANCED SET OF VOLTAGES FROM 0
V sa (3n +3) = v 0sa (t)ej ((3n +3) t /2) dt (5)
UNBALANCED DISTORTED SUPPLY VOLTAGES T t1
Let the unbalanced and distorted voltages be represented by where n = 0, 1, . . . , k. From the previous expression,
|V 0sa(3n +3) | and  V 0sa(3n +3) can be calculated.
 k

Vm an sin (n t + v an )
Therefore, the balanced quantities in the case of unbalanced
vsa (t) =


and distorted supply voltages are (6)(8), as shown at the bottom
n =1

 k of the next page, where n = 0, 1, . . . , k in (6)(8). The three-
vsb (t) = Vm bn sin (n t + v bn ) . (1) phase balanced set of voltages in the case of unbalanced and


n =1
distorted supply voltages can be written as
 k


Vm cn sin (n t + v cn )

k
vsc (t) = 
vsa (t)= +
(vsa(3n 0
n =1 +1) (t)+vsa(3n +2) (t)+vsa(3n +3) (t))
n =0
In (1), the subscript s denotes the supply, subscripts a, b, c are
the three phases of the system, m denotes the maximum or peak 
k
 + 0
vsb (t)= (vsb(3n +1) (t)+vsb(3n +2) (t)+vsb(3n +3) (t))
value, and n denotes the harmonic number. The maximum har-
n =0
monic number considered in the source voltage is denoted by k.
Let us denote the phase-a instantaneous positive sequence, 
k
 + 0
negative sequence, and zero sequence voltages by vsa +
(t), vsa (t), vsc (t)= (vsc(3n +1) (t)+vsb(3n +2) (t)+vsc(3n +3) (t)). (9)
0 n =0
and vsa (t), respectively. These sequence voltages are expressed
using symmetrical component theory as follows: Since all the quantities on the right-hand side of (9) are balanced,
  
0 vsa , vsb and vsc form balanced quantities for the distorted and
v sa (t) 1 1 1 vsa (t)
1 unbalanced supply voltages.
v+sa (t)
= 1 a a2 vsb (t) . (2)
3
vsa (t) 1 a2
a vsc (t) III. OPTIMIZATION TECHNIQUE TO GET THE
Here, a is the complex operator with a value of e j 2 /3
. The CONDUCTANCE FACTORS
sequence components given earlier are denoted by bold-faced In order to get the desired optimal performance between unity
letters as they are complex quantities and function of time. The power factor and THD limits of source currents, an optimization
zero sequence components are not complex quantities; however, technique is employed [17]. This algorithm is applicable only
they are represented by bold-faced letters to maintain uniformity when the supply voltages are balanced and distorted. For the
in equations. In a balanced distorted system, the harmonics of unbalanced and distorted supply voltages, this algorithm gives
order 3n + 1, 3n + 2, 3n + 3 rotate at (3n + 1), (3n + 2), unbalanced compensated source currents. Hence, in order to get
UYYURU et al.: OPTIMIZATION-BASED ALGORITHM FOR SHUNT ACTIVE FILTER UNDER DISTORTED SUPPLY VOLTAGES 1225


balanced compensated source currents, the algorithm is modi- In the previous equation, Vsan is the rms value of the nth -
fied by using the extracted balanced set of voltages (9) instead of 
order balanced harmonic voltage component, Vsa1 is the rms
actual supply voltages. The optimization process for unbalanced 
value of the balanced fundamental voltage, Isan is the rms value
distorted supply voltages of phase-a is given as follows. of the nth -order balanced harmonic current component, ITHD
Let the desired source current for phase-a be given by is the harmonic limit on the source current, and Plavg is the
k average load power, which is computed by the moving average

 + + technique. It will take a maximum of one cycle if both voltage
isa (t) = k1 (vsa1 )+kn (vsa(3n +1) )
n =1 and current have even harmonics. If the voltage and current
have only odd harmonics, then half cycle data will be sufficient

k
for computation. The necessary conditions for constrained local
0
+ (vsa(3n +2) (t)+vsa(3n +3) (t))
n =0
minima of L are that the first-order derivatives with respect to
the variables present in the function must be zero. Therefore
(10)
L
where k1 , and kn are conductance factors for the fundamen- = y 1 [2k1 (x (ITHD )2 ) ] = 0 (13)
k1
tal and the harmonics, respectively. By controlling these fac-
tors, the THD content in source current can be controlled. The L
= yn [2kn (x + ) ] = 0 (14)
Lagrangian multiplier technique is used to get the conductance kn
factors for the minimum apparent power by satisfying the men-  
where x = n1 ((Vsan )2 ), yn = (Vsan )2 .
tioned constraints.

The general Lagrangian function is formed as follows:
L Plavg n
 2  2
= (Vsa1 ) k1 + (Vsan ) kn = 0 (15)
L=f +r+s (11) 3 2

L  2
where L is the Lagrangian function, f is the objective func- n
 2  2
tion, and and are the Lagrangian multipliers. The terms r = kn (Vsan ) (ITHD )2 k12 (Vsa1 ) = 0. (16)
2
and s are the equality and inequality constrains, respectively. In
the optimization technique, the objective function is to minimize By solving (13)(16), using the MATLAB optimization tool
the apparent power that will directly influence power factor. The box, k1 , kn , , and are obtained for an optimum power factor
equality constraint in the optimization process is that the desired within acceptable THD limit of source current. The conduc-
source currents should supply the load average power, while the tance factors k1 and kn are responsible for shaping the source
inequality constraint puts a specified limit on the THD. There- currents according to the constraints specified. These values are
fore, the Lagrange function to minimize the apparent power is substituted in (10) to get the desired source current for phase-a.
formulated as Similarly, desired currents for b and c phases can be calculated

n 
n with the same conductance factors. Therefore, there is no need
 2  2
L= (Vsan ) (Isan ) to perform optimization for the other two phases. This will re-
1 1 duce computation time of reference currents and ensure that the

Plavg 
n average source power is equal to the average load power. This
 2  2
+ (Vsa1 ) k1 + (Vsan ) kn is another feature of the proposed algorithm. After getting the
3 2 desired source currents, the compensator currents for the three
n
 phases are obtained from the following equations:
 2 2  2
+ kn2 (Vsan ) (ITHD ) k12 (Vsa1 ) . (12)
2 i 
f a = ila isa , i 
f b = ilb isb , i 
f c = ilc isc . (17)


sa (3n +1) | sin((3n + 1) (t) + V sa (3n +1) )
+
vsa (3n +1) (t) = 2|V +  +



sa (3n +1) | sin((3n + 1) (t 2/3) + V sa (3n +1) )
+
vsb (3n +1) (t) = 2|V +  +
(6)



sa (3n +1) | sin((3n + 1) (t + 2/3) + V sa (3n +1) )
+
vsc (3n +1) (t) = 2|V +  +



vsa (3n +2) (t) = 2|V 
sa (3n +2) | sin((3n + 2) (t) + V sa (3n +2) )



vsb (3n +2) (t) = 2|V sa (3n +2) | sin((3n + 2) (t 2/3) + V sa (3n +2) )
 (7)


v
sc (3n +2) (t) = 2|V | sin((3n + 2) (t + 2/3) +  V
sa (3n +2) ) sa (3n +2)

sa (3n +3) | sin((3n
0 0 0
vsa (3n +3) (t) = 2|V + 3) (t) +  V sa (3n +3) )


0
vsb (3n +3) (t) = 2|V 0sa (3n +3) | sin((3n + 3) (t 2/3) +  V 0sa (3n +3) ) (8)


0
vsc (t) = 2|V 0
| sin((3n + 3) (t + 2/3) +  V0 )
(3n +3) sa (3n +3) sa (3n +3)
1226 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 24, NO. 5, MAY 2009

Fig. 2. Schematic of three-phase, four-wire compensated system.

Fig. 3. (a) Supply voltages for case 1. (b) Supply voltages for case 2. (c) Load
Fig. 1. Flowchart for the extraction of reference compensator currents using
currents for case 1. (d) Load currents for case 2.
proposed optimization control algorithm.

ideal and it consists of three ideal current sources that are shown
These compensating currents are then realized by using the in Fig. 2.
current-controlled voltage source inverter (VSI) with hystere- For the simulation study, two cases of supply voltages
sis current control technique. When the load changes from one are considered: in case 1, balanced distorted voltages and in
level to another, the conductance factors obtained for the previ- case 2, unbalanced distorted supply voltages. For these two
ous load cannot be used. For the new load, again the optimization cases, the supply voltages are expressed in (18) and (19),
process has to be run to get the new conductance factors. Then, respectively.
these values can be utilized in the compensation algorithm. As Case 1: Balanced Distorted Supply Voltages
the optimization process cannot give instantaneous result, it is
possible to shift the compensation from optimization control vsa = 359.25 sin(t) + 64.66 sin(5t) + 35.92 sin(7t)
algorithm to PHC or UPF operation until the new conductance vsb = 359.25 sin(t 1200 ) + 64.66 sin(5 (t 1200 ))
factors are known, and hence, there is no interruption in the com-
pensation. The flowchart for the extraction of balanced voltages + 35.92 sin(7(t 1200 ))
and the process of optimization is shown in Fig. 1. vsc = 359.25 sin(t + 1200 ) + 64.66 sin(5 (t + 1200 ))
+ 35.92 sin(7(t + 1200 )). (18)
IV. SIMULATION RESULTS WITH IDEAL COMPENSATOR
Case 2: Unbalanced Distorted Supply Voltages
In this section, detailed simulation studies for a three-phase
four-wire system are presented to explain the PHC and UPF vsa = 359.25 sin(t) + 64.66 sin(5t) + 35.92 sin(7t)
strategies along with the previously discussed optimized con-
vsb = 287.4 sin(t 1200 ) + 53.88 sin(5 (t 1200 ))
trol algorithm. A schematic of a three-phase, four-wire compen-
sated system is shown in Fig. 2. The three-phase load may be + 46.70 sin(7(t 1200 ))
unbalanced and nonlinear. A shunt APF (or compensator) and
vsc = 431.1 sin(t + 1200 ) + 89.81 sin(5 (t + 1200 ))
the load are connected at the point called the PCC. For the sake
of illustrating the concept, the compensator is considered to be + 89.81 sin(7(t + 1200 )). (19)
UYYURU et al.: OPTIMIZATION-BASED ALGORITHM FOR SHUNT ACTIVE FILTER UNDER DISTORTED SUPPLY VOLTAGES 1227

TABLE I
SUPPLY VOLTAGE, LOAD CURRENT, AND POWER FACTOR DATA

no longer zero. The reference source currents are proportional


to the actual supply voltages. For phase-a, the source current is
given as follows:
vsa
isa = 2 2 + v 2  Plavg . (21)
vsa + vsb sc
2
Here, the symbol  represents the running mean of (vsa +
2 2
vsb + vsc ) over a period and its value is constant at every instant.
In the previous expression, Plavg is also constant. Therefore, the
Fig. 4. (a) Source currents for case 1. (b) Source currents for case 2. source currents resemble the supply voltages. The compensated
source currents for this strategy are shown in Fig. 5(a) and (b),
The load considered for the simulation consists of an unbalanced respectively. This operation results in UPF. If the mean of the
2 2 2
linear load and a three-phase full-bridge diode rectifier, which (vsa + vsb + vsc ) term is not considered, dissimilar harmonics
draws nonlinear load currents from the supply. The supply volt- will be present in voltages and currents, and hence, UPF opera-
ages and the corresponding load currents are shown in Fig. 3. tion cannot be achieved.
Details of these parameters, i.e., rms values, THDs, power factor
are given in Table I. Before describing the optimization control C. Proposed Optimization Control Algorithm
algorithm, the results of PHC and UPF strategies are presented In the previous two control strategies, one compensates the
using instantaneous symmetrical component theory under both current harmonics but does not provide unity power factor and
the cases of supply voltages. the other gives unity power factor but without compensation of
current harmonics and unbalance. Thus, these schemes do not
A. PHC Strategy fulfill the aims of compensation and representing two extremes
In this strategy, the fundamental positive sequence voltages of compensation characteristics. Hence, the optimization con-
are extracted from the supply. These voltages are then used to trol strategy is employed to get an optimal performance between
calculate reference source currents by using instantaneous sym- the PHC and UPF strategies. However, the characteristics of
metrical component theory [9]. The phase-a reference source these strategies can be obtained as special cases of the proposed
current is expressed as follows: optimization control algorithm. This is achieved by specifying
desired source current THD limits 0% and the same as voltage
+
vsa1 vsa1
0
THDs, for the PHC and UPF strategies, respectively. The com-
i+
sa1 = Plavg . (20)
+2
(vsa1 + vsb1 + vsc1
+2 +2 0 )2 )
3(vsa1 pensated source currents for THD limits of 5% and 10% are
0 shown in Fig. 6.
In the previous equation vsa1 is the zero sequence voltage and
its value is equal to zero as the considered supply voltages in (20)
V. ANALYSIS OF THE SIMULATION RESULTS
are fundamental positive sequence (balanced) voltages. Here,
+2 +2 +2
the important aspect is that the term (vsa1 + vsb1 + vsc1 ) is con- For the simulation studies, the rms, THD values of supply
stant at every instant. Hence, reference source currents resemble voltages and load currents, power factor values are given in
the fundamental positive sequence voltages with a scaling factor. Table I. The performances of the PHC, UPF strategies and pro-
Using this strategy, the compensated source currents become si- posed optimal control algorithm (OCA) are given in Tables II
nusoidal and balanced. The compensated source currents for the and III under the two supply voltage conditions (case 1 and
two cases are shown in Fig. 4(a) and (b), respectively. Though case 2). Here, nonunity power factor and nonperfect harmonic
source currents for both the cases look similar, their magnitudes cancellation are represented by NUPF and NPHC, respectively.
are different, as observed from Tables II and III.

B. UPF Strategy A. PHC Strategy


In this strategy, the denominator of (20) is replaced by a mean In this strategy, the source currents obtained are balanced and
value of sum of squared supply voltages. Also, the compensation the THDs in the source currents are zero as given in Table II. The
0
for the zero sequence voltages is not provided; therefore, vsa compensator rating for this strategy is minimum compared to
term is eliminated in the numerator and the denominator. As a the other strategies. However, power factor is not unity, though
consequence of this, the neutral current after compensation is the source currents are sinusoidal as the harmonic component in
1228 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 24, NO. 5, MAY 2009

TABLE II
SIMULATION RESULTS OF THE STRATEGIES UNDER BALANCED AND DISTORTED SUPPLY VOLTAGES (CASE 1)

TABLE III
SIMULATION RESULTS OF THE STRATEGIES UNDER UNBALANCED AND DISTORTED SUPPLY VOLTAGES (CASE 2)

Fig. 5. (a) Source currents for case 1 (b) Source currents for case 2.

supply voltages does not contribute to the average load power,


which, in turn, increases the apparent power. The value of the
power factor totally depends upon the supply voltage distortion.
It can be verified from the following derivation:
  Fig. 6. Source currents for (a) 5% THD under case 1, (b) 5% THD under
average load power Plavg
pf = case 2, (c) 10% THD under case 1, and (d) 10% THD under case 2.
Vrm s Irm s
V1 I1 cos 1 + V2 I2 cos 2 + V3 I3 cos 3 + + Vn In cos n
=   . where THDv is the total harmonic distortion of supply voltage
V12 + V22 + V32 + + Vn2 I12 + I22 + I32 + + In2
[19].
(22)

In order to compensate the total reactive power, the phase B. UPF Strategy
displacement between voltage and current at each harmonic Under this strategy, the damping provided by the load can
level must be zero, i.e., 1 = 2 = 3 = = n = 0. For be retained by shaping the source currents similar to the sup-
this strategy, the source current is free from harmonics; hence, ply voltages, which will play an important role in the case of
I2 = I3 = = In = 0. By substituting these values in (22), resonance phenomenon. The harmonic components, which are
the power factor becomes similar in the supply voltages and source currents, contribute
1 to the average load power to make the power factor unity. This
pf =  can be verified from (22). In order to get UPF, the currents
1 + THD2v have to be scaled to the voltages, i.e., In = kVn , where k is the
UYYURU et al.: OPTIMIZATION-BASED ALGORITHM FOR SHUNT ACTIVE FILTER UNDER DISTORTED SUPPLY VOLTAGES 1229

TABLE IV
PARAMETERS FOR THE EXPERIMENTAL STUDY

Fig. 7. Power circuit diagram for experimental studies on a shunt active power
filter prototype model developed in laboratory.

conductance of the compensated load. Then (pf ), is as shown


at the bottom of this page.
The rms values of the source currents under this strategy
are less, but the compensator rating is high compared to all
other strategies, as given in Table II. The other drawback of this
strategy is that the distortion and unbalance in the currents are
same as in the supply voltages.

C. Optimization Control Algorithm


For the proposed optimization control algorithm, THD limits
of 5% and 10% in the compensated source currents are con- Fig. 8. Block diagram for various blocks used in experimental setup.
sidered. First, 5% THD is allowed as per the IEEE-519 Stan-
dard [20]. From the results given in Table II, it can be seen
VI. EXPERIMENTAL RESULTS
that the rms values of source currents are in between the UPF
(minimum) and PHC (maximum) strategies by satisfying the The previously proposed ideas have been verified by conduct-
standards of distortion current limit. The compensator rating ing detailed experiments on a shunt active filter prototype model
and power factor are also optimized between UPF (maximum) developed in the laboratory. The power circuit considered for the
and PHC (minimum) strategies. After that, 10% THD limit is experimental analysis is shown in Fig. 7. In order to get the de-
kept as a constraint to check the performance of the algorithm sired supply voltage, a programmable power source-305 AMX is
and the results are shown in Tables III and IV. Though reduction used. The total load consists of two parts; one is the unbalanced
in rms values of source currents and increase in power factor linear load and another is the 3-phase diode bridge rectifier load
values are favorable for this limit of THD, the distortion in the as described in Table IV. The shunt active filter is realized by an
source current violates IEEE-519 Standards and the compen- H-bridge VSI. This topology is chosen due to its advantage of
sator rating is increased. having only one dc storage capacitor and its independent control
From the results of the optimization control algorithm, by of each phase compensator current. This eliminates the problem
considering different distortion limits as constraints, it is learned of dc voltage unbalance. The Y-connected transformers are used
that by taking 5% THD limit as constraint in the source, the al- to prevent the short-circuit of the dc storage capacitor for cer-
gorithm gives the balanced source currents with the best power tain switching combinations of power switches in the H-bridge
factor and satisfies the IEEE-519 Standards. Though the advan- VSI. Here, VSI is chosen instead of the current source inverter,
tage of reduction in rms values of source current and improve- due to the less complicated circuit and better filtering of load
ment in the power factor are marginal in the UPF strategy and the currents [22]. The various blocks used in the implementation of
optimization control algorithm, these methods allow the preser- the control algorithm are shown in Fig. 8. The supply voltages,
vation of resistive part of the compensated load. This resistive dc bus voltage, load currents, and filter currents are transformed
part plays an important role in diminishing the harmonic propa- to 5 V range using the Hall effect voltage and current trans-
gation in the distribution system, which occurs due to harmonic ducers. These are further processed through signal conditioning
resonance [21]. circuit to convert to 03 V range compatible to 12-bit ADC

V1 (kV1 ) + V2 (kV2 ) + V3 (kV3 ) + + Vn (kVn )


pf =   = 1.
V12 + V22 + V32 + + Vn2 (kV1 )2 + (kV2 )2 + (kV3 )2 + + (kVn )2
1230 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 24, NO. 5, MAY 2009

Fig. 9. (a) Supply voltages for case 1. (b) Load currents for case 1. (c) Supply Fig. 12. OCA for 5% THD. (a) Source currents for case. 1 (b) Compensator
voltages for case 2. (d) Load currents for case 2. currents for case 1. (c) Source currents for case 2. (d) Compensator currents for
case 2.

Fig. 10. PHC strategy. (a) Source currents for case 1. (b) Compensator currents Fig. 13. OCA for 10% THD. (a) Source currents for case 1. (b) Compensator
for case 1. (c) Source currents for case 2. (d) Compensator currents for case 2. currents for case 1. (c) Source currents for case 2. (d) Compensator currents for
case 2.

and this can be implemented in the DSP itself. But in the case of
a nonstiff source, the source voltage contains switching harmon-
ics, and thus, the problem of multiple zero crossings will arise.
Hence, a dedicated synchronizing circuit is used to alleviate this
problem and to synthesize the quantities in the time domain,
synchronous with the phase-a voltage [23]. A dead time of
3.2 s required by the IPM PM50RVA120 is provided by the
Fig. 11. UPF strategy source currents for case 1. blanking circuit to avoid the simultaneous conduction of the
IGBTs in the same leg. In the figure, an optoisolation circuit is
channels of DSP-TMS320F2812PGFA. The voltages and cur- used to isolate the signal level circuit from the power circuit.
rents are sampled by the digital signal processor (DSP) at the A protection circuit is used to prevent any abnormal operation
rate of 460 samples per cycle (at a sampling frequency 23 kHz). in terms of overrated voltage and current quantities, by stop-
In order to determine the frequency, the zero crossing instants ping the gate pulses from blanking the circuit. The DSP is pro-
of the source voltage should be known. Extraction of this zero grammed in code composer studio (CCS) on the host computer
crossing instants is not a problem under the stiff voltage source for implementing the control strategies.
UYYURU et al.: OPTIMIZATION-BASED ALGORITHM FOR SHUNT ACTIVE FILTER UNDER DISTORTED SUPPLY VOLTAGES 1231

TABLE V
EXPERIMENTAL RESULTS FOR OPTIMIZATION CONTROL ALGORITHM

For the balanced distorted (case 1) supply voltages, 50 V strategy gives the best compromise between the PHC and UPF
rms (L-N) and 20% THD are considered for each phase. In strategies. For illustrating the performance of the optimization
the unbalanced and distorted (case 2) supply voltages, 50 V, algorithm in compensating the source currents for the given
60 V, 40 V rms (L-N) and THDs of 25%, 20%, 15% are taken THD, the results of compensation for 10% THD limit are shown
for the phases a, b, and c respectively. The parameters of the in Fig. 13(a)(d).
unbalanced nonlinear load and compensated system are given The source current THD limits specified in the algorithm
in Table IV. The programmed supply voltages for both the cases are met with little deviation, owing to the switching frequency
are given in (23) and (24). These are shown in Fig. 9(a) and ripples caused by the current modulation technique. However,
(c), respectively. Load currents for both the cases are shown in this effect can further be reduced by the use of an LCL
Fig. 9(b) and (d). filter [24]. The experimental results of the optimization control
Case 1: Balanced Distorted Supply Voltages algorithm for two cases of supply voltages are given in Table V.
For balanced distorted supply, following voltages are generated: It can be observed from the table that the source current rms
values are less and power factor is more for THD limits close to
vsa = 70 sin(t) + 11 sin(5t) + 8.3 sin(7t) the supply voltage THDs.
vsb = 70 sin(t 1200 ) + 11 sin(5t + 1200 )
VII. CONCLUSION
+ 8.3 sin(7t 1200 )
It has been shown that under distorted supply voltages any
vsc = 70 sin(t + 1200 ) + 11 sin(5t 1200 )
effort to increase the power factor results in increased THD of
+ 8.3 sin(7t + 1200 ). (23) source currents and total compensation for current harmonics
does not provide the unity power factor. In this paper, an op-
Case 2: Unbalanced Distorted Supply Voltages timization control algorithm is proposed to get a compromise
The following voltages are considered for this case: between achieving unity power factor and THD current limits
vsa = 68.60 sin(t) + 8.32 sin(5t) + 15.10 sin(7t) with compensation of reactive power and unbalance. This con-
trol algorithm can be used under both balanced and unbalanced
vsb = 83.18 sin(t 1200 ) + 14.97 sin(5t + 1200 ) distorted supply voltages. The compensation characteristics of
+ 7.48 sin(7t 1200 ) three control strategies, i.e., PHC, UPF, and optimization-based
algorithm are compared. Experimental verification was carried
vsc = 55.92 sin(t + 1200 ) + 7.27 sin(5t 1200 ) out on a reduced-scale prototype of DSP-TMS320F2812PGFA-
+ 4.47 sin(7t + 1200 ). (24) based shunt APF. From the results, it is clear that the proposed
optimization control algorithm renders the best possible com-
In order to show the ability of the algorithm in achieving promise between the power factor and the harmonic distortion
the desired compensation characteristics, different THD limits along with preserving the resistive part of the compensated load.
on the compensated source currents were imposed. First, 0%
THD (PHC strategy) is taken and the corresponding results for REFERENCES
both the balanced distorted and unbalanced distorted cases are
shown in the Fig. 10(a)(d). In this strategy, the source currents [1] G. W. Mack and S. Santoso, Understanding power system harmonics,
IEEE Power Eng. Rev., vol. 21, no. 11, pp. 811, Nov. 2001.
are compensated for total harmonics, unbalance, and reactive [2] H. Akagi, Y. Kanazawa, and A. Nabae, Instantaneous reactive power
power of the load. The UPF strategy source currents for the compensators comprising switching devices without energy storage com-
balanced distorted case are shown in Fig. 11. From the figure, ponents, IEEE Trans. Ind. Appl., vol. IA-20, no. 3, pp. 625630, May/Jun.
1984.
it can be observed that the source currents have the same shape [3] M. Aredes, J. Hafner, and K. Heumann, Three-phase four-wire shunt
as the supply voltage except for the switching frequency ripple, active filter control strategies, IEEE Trans. Power Electron., vol. 12,
which is present due to the hysteresis current control of the no. 2, pp. 311318, Nov. 1997.
[4] A. Cavallani and G. C. Montarani, Compensation strategies for shunt
VSI. Figs. 12(a)(d) show the source and compensated currents active-filter control, IEEE Trans. Power Electron., vol. 9, no. 6, pp. 587
for the THD limit of 5%, which is IEEE-519 compliant. This 593, Nov. 1994.
1232 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 24, NO. 5, MAY 2009

[5] D. Gonzalez, J. Balcells, S. Lovera, and R. Lima, Comparison between [23] L. P. Kunjumuhammed and M. K. Mishra, A control algorithm for single-
unity power factor and instantaneous power theory control strategies ap- phase active power filter under non-stiff voltage source, IEEE Trans.
plied to a three phase active power filter, in Proc. 24th Annu. Conf. IEEE Power Electron., vol. 21, no. 3, pp. 822825, May 2006.
Ind. Electron. Soc., Aachen, Germany, Oct.1998, vol. 2, pp. 843847. [24] B. Bolsens, K. D. Brabandere, J. V. D. Keybus, J. Driesen, and R. Belma,
[6] S. M.-R. Rafiei, H. A. Toliyat, R. Ghani, and T. Gopalarathnam, An Model-based generation of low distortion currents in grid-coupled PWM-
optimal and flexible control strategy for active filtering and power factor inverters using an LCL output filter, IEEE Trans. Power Electron.,
correction under nonsinusoidal line voltages, IEEE Trans. Power Del., vol. 21, no. 4, pp. 10321040, Jul. 2006.
vol. 16, no. 2, pp. 297305, Apr. 2001.
[7] S. J. Huang and J. C. Wu, A control algorithm for three-phase three-wired
active power filters under non ideal mains voltages, IEEE Trans. Power
Electron., vol. 14, no. 4, pp. 753760, Jul. 1999.
[8] T. E. Nunez-Zuniga and J. A. Pomilio, Shunt active power filter syn- Koteswara Rao Uyyuru received the B.Tech. de-
thesizing resistive loads, IEEE Trans. Power Electron., vol. 17, no. 2, gree from Jawaharlal Nehru Technological Univer-
pp. 273278, Mar. 2002. sity, Hyderabad, India, in 2003. He is currently work-
[9] K. Karthikeyan and M. K. Mishra, A novel load compensation algorithm ing toward the Ph.D. degree in the Department of
under unbalanced and distorted supply voltages, Int. J. Emerging Electr. Electrical Engineering, Indian Institute of Technol-
Power Syst., vol. 8, no. 5, pp. 118, 2007, Article 1. ogy (IIT) Madras, Chennai, India.
[10] P. Salmeron and R. S. Herrera, Distorted and unbalanced systems com- From 2003 to 2004, he was a Lecturer in Sri.
pensation within instantaneous reactive power framework, IEEE Trans. Adsumilli Aswardha Narayana Murthy (AANM)
Power Del., vol. 21, no. 3, pp. 16551662, Jul. 2006. and Sri. Valluripalli Venkata Rama Seshadri Rao
[11] C. C. Chen and Y. Y. Hsu, A novel approach to the design of a shunt active (VVRSR) Polytechnic, Gudlavalleru, India. From
filter for an unbalanced three-phase four-wire system under nonsinusoidal 2004 to 2005, he was an Assistant Engineer in the
conditions, IEEE Trans. Power Del., vol. 15, no. 4, pp. 12581264, Oct. Southern Power Distribution Company, Andhra Pradesh Ltd., Tirupathi, India.
2000. His current research interests include power quality, power electronic devices,
[12] M. I. M. Montero, E. R. Cadaval, and F. B. Gonzalez, Comparison of and power electronics applications in power systems.
control strategies for shunt active power filters in three-phase four-wire
systems, IEEE Trans. Power Electron., vol. 22, no. 1, pp. 229236, Jan.
2007.
[13] J. F. Petit, G. Robles, and H. Amars, Current reference control for shunt
active power filters under nonsinusoidal voltage conditions, IEEE Trans.
Power Del., vol. 22, no. 4, pp. 22542261, Oct. 2007. Mahesh K. Mishra (S00M02) received the
[14] L. S. Czarnecki, On some misinterpretations of the instantaneous reactive B.Tech. degree from the College of Technology,
power theory, IEEE Trans. Power Electron., vol. 19, no. 3, pp. 828836, Pantnagar, India, in 1991, the M.E. degree from the
May 2004. University of Roorkee, Roorkee, India, in 1993, and
[15] G. W. Chang, A new approach for optimal shunt active power filter the Ph.D. degree in electrical engineering from the
control considering alternative performance indices, IEEE Trans. Power Indian Institute of Technology, Kanpur, India, in
Del., vol. 21, no. 1, pp. 406413, Jan. 2006. 2002.
[16] G. W. Chang, C.-M. Yeh, and W.-C. Chen, Meeting IEEE-519 current He has teaching and research experience of 17
harmonics and power factor constraints with a three-phase three-wire years. For about ten years, he was in the Electrical
active power filter under distorted source voltages, IEEE Trans. Power Engineering Department, Visvesvaraya National In-
Del., vol. 21, no. 3, pp. 16481654, Jul. 2006. stitute of Technology, Nagpur, India. He is currently
[17] S. George and V. Agarwal, A DSP based optimal algorithm for shunt an Assistant Professor in the Department of Electrical Engineering, Indian In-
active filter under nonsinusoidal supply and unbalanced load conditions, stitute of Technology Madras, Chennai, India. His current research interests
IEEE Trans. Power Electron., vol. 22, no. 2, pp. 593601, Mar. 2007. include power distribution systems, power electronics, and control systems.
[18] G. Chicco, P. Postolache, and C. Toader, Analysis of three-phase systems Dr. Mahesh is a Life Member of the Indian Society of Technical Education
with neutral under distorted and unbalanced conditions in the symmetrical (ISTE).
component-based framework, IEEE Trans. Power Del., vol. 22, no. 1,
pp. 674683, Jan. 2007.
[19] IEEE Trial-Use Standard Definitions for the Measurement of Electric
Power Quantities Under Sinusoidal, Nonsinusoidal, Balanced, or Unbal-
anced Conditions, IEEE Standard 1459-2000, Jun. 2000. Arindam Ghosh (S80M83SM93F06) received the Ph.D. degree in elec-
[20] IEEE Recommended Practices and Requirements for Harmonic Control trical engineering from the University of Calgary, Calgary, AB, Canada, in 1983.
in Electrical Power Systems, IEEE Standard 519-1992, 1993. He is currently a Professor of power systems at Queensland University of
[21] H. Akagi, H. Fujita, and K. Wada, A shunt active filter based on voltage Technology, Brisbane, Qld., Australia. From 1985 to 2006, he was with the
detection for harmonic termination of a radial power distribution line, Department of Electrical Engineering, Indian Institute of Technology (IIT),
IEEE Trans. Ind. Appl., vol. 35, no. 3, pp. 638645, May/Jun. 1999. Kanpur, India. He held visiting positions with Nanyang Technological Univer-
[22] M. Routimo, M. Salo, and H. Tuusa, Comparison of voltage-source and sity, Singapore, the University of Queensland, Brisbane, and Queensland Uni-
current-source shunt active power filters, IEEE Trans. Power Electron., versity of Technology. His current research interests include control of power
vol. 22, no. 2, pp. 636643, Mar. 2007. systems and power-electronic devices.

Anda mungkin juga menyukai