GSNL-HPTS
In general relief valves (control 3 listed on slide 4) are the last line of
defence against overpressure.
Operator response, automatic continuous control and IPF are normally
not taken into account for relief valve sizing (design flow). Reasons:
Operator intervention could be ineffective,
Automtatic control can be on manual, has a wrong setpoint initiation
or could fail open,
IPF could have a failure on demand.
The failure position of control valves shall allow each system to reach
an inherently safe condition during a total instrument air failure
scenario (e.g. overpressure)
Select spring action to:
Maximise cooling
Minimise heat input
Minimise relief quantity
Keep material where it belongs; do not export problems which may
cause a relief to elsewhere
In case of instrument air failure, the control valves will be assumed to
have taken their spring action.
Note 2: When the system is liquid-full, the design pressure of the accumulator vessel downstream of a cooler of a distillation column (vessel
located at significant lower elevation with respect to the location of the relief valve near top of distillation column) shall be increased
for extra liquid head.
Note: Pressure system II is based on P1 pump shutoff. Pressure system III is indicative is case of a potential
run away of R1 (higher pressure than P1 shut off pressure).
Copyright of Shell Projects & Technology RESTRICTED September 2011 14
EXAMPLE 1 (OPEN PRESSURE SYSTEM)
(1)
(4)
(2) (3)
Sloping design pressure profile as used in existing designs. Potential blocked outlet may
raise the pressure to the maximum pressure from the feed pump and/or hydrogen
compressor. Additional safeguards are required (RV- not desirable due to high temperature
and high flow, or IPF such as 1oo3 PZA HH stopping the pressure generating equipment
and stopping heat input).