Estos ajustes corresponden a un RET670

Ajustes Sencillos

Usuario del reporte COES1

Fecha del Reporte mircoles, 28 de junio de 2017 10:46:09

Nombre de la Ubicacin L-5032

Categora Relay

Nombre L-5032_RED670_P

Descripcin Propietario: ATS

Tipo RED670_xrio_generic

Fabricante ABB

Tipo de la Serie RED670

Ruta Peru > Centro > Chilca_ctm > L-5032 > L-5032_RED670_P > Ajustes

Id. 18666

Nombre Ajustes

Descripcin AS BUILT

Clave Externa

Propietario

Uso del Dispositivo

Firmware

Estado Planning

Creado martes, 07 de abril de 2015 19:18:14

ltimo Cambio jueves, 17 de diciembre de 2015 16:53:20

Atributos adicionales

Nombre Valor
Voltage Level

GlobalNote

Revision Number

Maximo ID

Grupo de Ajustes: IED Configuration

Nombre Descripcin Valor Unidad


Chapter : HW Configuration->BIM_3

BINAME1 User define string for binary BI1 13 characters


input 1

BINAME2 User define string for binary BI2 13 characters


input 2

BINAME3 User define string for binary BI3 13 characters


input 3

BINAME4 User define string for binary BI4 13 characters

Page 1 of 111
Grupo de Ajustes: IED Configuration
Nombre Descripcin Valor Unidad
input 4

BINAME5 User define string for binary BI5 13 characters


input 5

BINAME6 User define string for binary BI6 13 characters


input 6

BINAME7 User define string for binary BI7 13 characters


input 7

BINAME8 User define string for binary BI8 13 characters


input 8

BINAME9 User define string for binary BI9 13 characters


input 9

BINAME10 User define string for binary BI10 13 characters


input 10

BINAME11 User define string for binary BI11 13 characters


input 11

BINAME12 User define string for binary BI12 13 characters


input 12

BINAME13 User define string for binary BI13 13 characters


input 13

BINAME14 User define string for binary BI14 13 characters


input 14

BINAME15 User define string for binary BI15 13 characters


input 15

BINAME16 User define string for binary BI16 13 characters


input 16

Operation Operation Off/ On On

OscRelease Oscilation release limit 30 Hz

OscBlock Oscillation block limit 40 Hz

Chapter : HW Configuration->BOM_4

BONAME1 User define string for binary BO1 13 characters


output 1

BONAME2 User define string for binary BO2 13 characters


output 2

BONAME3 User define string for binary BO3 13 characters


output 3

BONAME4 User define string for binary BO4 13 characters


output 4

BONAME5 User define string for binary BO5 13 characters


output 5

BONAME6 User define string for binary BO6 13 characters


output 6

BONAME7 User define string for binary BO7 13 characters


output 7

BONAME8 User define string for binary BO8 13 characters


output 8

BONAME9 User define string for binary BO9 13 characters


output 9

Page 2 of 111
Grupo de Ajustes: IED Configuration
Nombre Descripcin Valor Unidad
BONAME10 User define string for binary BO10 13 characters
output 10

BONAME11 User define string for binary BO11 13 characters


output 11

BONAME12 User define string for binary BO12 13 characters


output 12

BONAME13 User define string for binary BO13 13 characters


output 13

BONAME14 User define string for binary BO14 13 characters


output 14

BONAME15 User define string for binary BO15 13 characters


output 15

BONAME16 User define string for binary BO16 13 characters


output 16

BONAME17 User define string for binary BO17 13 characters


output 17

BONAME18 User define string for binary BO18 13 characters


output 18

BONAME19 User define string for binary BO19 13 characters


output 19

BONAME20 User define string for binary BO20 13 characters


output 20

BONAME21 User define string for binary BO21 13 characters


output 21

BONAME22 User define string for binary BO22 13 characters


output 22

BONAME23 User define string for binary BO23 13 characters


output 23

BONAME24 User define string for binary BO24 13 characters


output 24

Operation Operation Off/ On On

Chapter : HW Configuration->TRM_9I_3U_31

NAMECH1 User define string for analogue W1_ IL1 13 characters


input 1

RatedTrans1 Rated value on transformer 1 A

CTStarPoint1 ToObject= towards protected ToObject


object, FromObject= the
opposite

CTsec1 Rated CT secondary current 1 A

CTprim1 Rated CT primary current 400 A

NAMECH2 User define string for analogue W1_ IL2 13 characters


input 2

RatedTrans2 Rated value on transformer 1 A

CTStarPoint2 ToObject= towards protected ToObject


object, FromObject= the
opposite

CTsec2 Rated CT secondary current 1 A

Page 3 of 111
Grupo de Ajustes: IED Configuration
Nombre Descripcin Valor Unidad
CTprim2 Rated CT primary current 400 A

NAMECH3 User define string for analogue W1_ IL3 13 characters


input 3

RatedTrans3 Rated value on transformer 1 A

CTStarPoint3 ToObject= towards protected ToObject


object, FromObject= the
opposite

CTsec3 Rated CT secondary current 1 A

CTprim3 Rated CT primary current 400 A

NAMECH4 User define string for analogue W2_ IL1 13 characters


input 4

RatedTrans4 Rated value on transformer 1 A

CTStarPoint4 ToObject= towards protected ToObject


object, FromObject= the
opposite

CTsec4 Rated CT secondary current 1 A

CTprim4 Rated CT primary current 400 A

NAMECH5 User define string for analogue W2_ IL2 13 characters


input 5

RatedTrans5 Rated value on transformer 1 A

CTStarPoint5 ToObject= towards protected ToObject


object, FromObject= the
opposite

CTsec5 Rated CT secondary current 1 A

CTprim5 Rated CT primary current 400 A

NAMECH6 User define string for analogue W2_ IL3 13 characters


input 6

RatedTrans6 Rated value on transformer 1 A

CTStarPoint6 ToObject= towards protected ToObject


object, FromObject= the
opposite

CTsec6 Rated CT secondary current 1 A

CTprim6 Rated CT primary current 400 A

NAMECH7 User define string for analogue WN_ IL 13 characters


input 7

RatedTrans7 Rated value on transformer 1 A

CTStarPoint7 ToObject= towards protected ToObject


object, FromObject= the
opposite

CTsec7 Rated CT secondary current 1 A

CTprim7 Rated CT primary current 100 A

NAMECH8 User define string for analogue CH8 13 characters


input 8

RatedTrans8 Rated value on transformer 1 A

CTStarPoint8 ToObject= towards protected ToObject


object, FromObject= the

Page 4 of 111
Grupo de Ajustes: IED Configuration
Nombre Descripcin Valor Unidad
opposite

CTsec8 Rated CT secondary current 1 A

CTprim8 Rated CT primary current 3000 A

NAMECH9 User define string for analogue CH9 13 characters


input 9

RatedTrans9 Rated value on transformer 1 A

CTStarPoint9 ToObject= towards protected ToObject


object, FromObject= the
opposite

CTsec9 Rated CT secondary current 1 A

CTprim9 Rated CT primary current 3000 A

NAMECH10 User define string for analogue UL1 13 characters


input 10

RatedTrans10 Rated value on transformer 110 V

VTsec10 Rated VT secondary voltage 110 V

VTprim10 Rated VT primary voltage 500 kV

NAMECH11 User define string for analogue UL2 13 characters


input 11

RatedTrans11 Rated value on transformer 110 V

VTsec11 Rated VT secondary voltage 110 V

VTprim11 Rated VT primary voltage 500 kV

NAMECH12 User define string for analogue UL3 13 characters


input 12

RatedTrans12 Rated value on transformer 110 V

VTsec12 Rated VT secondary voltage 110 V

VTprim12 Rated VT primary voltage 500 kV

Chapter : Activate setting group->SETGRPS: 1

ActiveSetGrp ActiveSettingGroup SettingGroup1

MAXSETGR Max number of setting groups 1 No


1- 6

Chapter : Time->Synchronisation->TIMESYNCHGEN: 1

CoarseSyncSrc Coarse time synchronization SNTP


source

FineSyncSource Fine time synchronization SNTP


source

SyncMaster Activate IEDas SNTP- Server


synchronization master

TimeAdjustRate Adjust rate for time Fast


synchronization

Chapter : Time->Synchronisation->SYNCHBIN: 1

ModulePosition Hardware position of IO 3


module for time
synchronization

BinaryInput Binary input number for time 1

Page 5 of 111
Grupo de Ajustes: IED Configuration
Nombre Descripcin Valor Unidad
synchronization

BinDetection Positive or negative edge PositiveEdge


detection

Chapter : Time->Synchronisation->DSTBEGIN: 1

MonthInYear Month in year when daylight March


time starts

DayInWeek Day in week when daylight Sunday


time starts

WeekInMonth Week in month when daylight Last


time starts

UTCTimeOfDay UTC Time of day in seconds 0 s


when daylight time starts

Chapter : Time->Synchronisation->DSTEND: 1

MonthInYear Month in year when daylight March


time ends

DayInWeek Day in week when daylight Sunday


time ends

WeekInMonth Week in month when daylight Last


time ends

UTCTimeOfDay UTC Time of day in seconds 0 s


when daylight time ends

Chapter : Time->Synchronisation->SYNCHIRIG-B: 1

SynchType Type of synchronization Opto

TimeDomain Time domain LocalTime

Encoding Type of encoding IRIG- B

TimeZoneAs1344 Time zone as in 1344 PlusTZ


standard

Chapter : Time->Synchronisation->SYNCHSNTP: 1

ServerIP- Add Server IP- address 172. 16. 0. 140 18 characters

RedServIP- Add Redundant server IP- address 172. 16. 0. 141 18 characters

Chapter : Time->Synchronisation->TIMEZONE: 1

NoHalfHourUTC Number of half- hours from - 10


UTC

Chapter : Power system->TERMINALID: 1

StationName Station name Chilca 18 characters

StationNumber Station number 1

ObjectName Object name R1 18 characters

ObjectNumber Object number 2

UnitName Unit name B1Q46- RED670 18 characters

Page 6 of 111
Grupo de Ajustes: IED Configuration
Nombre Descripcin Valor Unidad
UnitNumber Unit number 1

Chapter : Power system->PRIMVAL: 1

Frequency Rated system frequency 60 Hz

Chapter : Communication->SLM configuration->Rear optical LON port->LONGEN: 1

SubNetAddr LON Subnet address - 1

NodeAddr LON node address - 1

NeuronID LON Neuron ID 18 characters

Chapter : Communication->SLM configuration->Rear optical LON port->ADE: 1

Operation Operation Off

TimerClass Timer class Slow

Chapter : Communication->SLM configuration->Rear optical LON port->LONSPA: 4

Operation Operation Off

SlaveAddress Slave address 30

Chapter : Communication->SLM configuration->Rear optical LON port->HORZCOMM: 1

Operation Operation Off

Chapter : Communication->SLM configuration->Rear optical SPA-IEC port->PROTOCOL: 1

Operation Operation selection Off

Chapter : Communication->SLM configuration->Rear optical SPA-IEC port->SPA: 1

SlaveAddress Slave address 30

BaudRate Baudrate on serial line 9600 Bd

Chapter : Communication->SLM configuration->Rear optical SPA-IEC port->IED61870-5-103: 1

SlaveAddress Slave address 30

BaudRate Baudrate on serial line 9600 Bd

RevPolarity Invert polarity On

CycMeasRepTime Cyclic reporting time of 5


measurments

Chapter : Communication->Station communication->DNP3.0->DNPGEN: 1

Operation Operation mode Off / On Off

Chapter : Communication->Station communication->DNP3.0->CHSERRS485: 1

Operation Operation mode Off

DLinkConfirm Data- link confirm Never

tDLinkTimeout Data- link confirm timeout in s 2 s

DLinkRetries Data- link maximum retries 3

tRxToTxMinDel Rx to Tx minimum delay in s 0 s

ApLayMaxRxSize Application layer maximum Rx 2048


fragment size

ApLayMaxTxSize Application layer maximum Tx 2048


fragment size

BaudRate Baud- rate for serial port 9600 Bd

Page 7 of 111
Grupo de Ajustes: IED Configuration
Nombre Descripcin Valor Unidad
StopBits Stop bits 1

Parity Parity Even

tRTSWarmUp RTS warm- up in s 0 s

tRTSWarmDown RTS warm- down in s 0 s

WireMode RS485 wire mode Two- wire

tBackOffDelay RS485 back- off delay in s 0. 05 s

tMaxRndDelBkOf RS485 maximum back- off 0. 1 s


random delay in s

Chapter : Communication->Station communication->DNP3.0->MSTRS485: 1

Operation Operation Off / On Off

SlaveAddress Slave address 1

MasterAddres Master address 1

ValMasterAddr Validate source (master) Yes


address

AddrQueryEnbl Address query enable Yes

tApplConfTout Application layer confim 10 s


timeout

ApplMultFrgRes Enable application for multiple Yes


fragment response

ConfMultFrag Confirm each multiple Yes


fragment

UREnable Unsolicited response enabled Yes

URSendOnline Unsolicited response sends No


when on- line

UREvClassMask Unsolicited response, event Off


class mask

UROfflineRetry Unsolicited response retries 5


before off- line retry mode

tURRetryDelay Unsolicited response retry 5 s


delay in s

tUROfflRtryDel Unsolicited response off- line 30 s


retry delay in s

UREvCntThold1 Unsolicited response class 1 5


event count report treshold

tUREvBufTout1 Unsolicited response class 1 5 s


event buffer timeout

UREvCntThold2 Unsolicited response class 2 5


event count report treshold

tUREvBufTout2 Unsolicited response class 2 5 s


event buffer timeout

UREvCntThold3 Unsolicited response class 3 5


event count report treshold

tUREvBufTout3 Unsolicited response class 3 5 s


event buffer timeout

DelOldBufFull Delete oldest event when No


buffer is full

Page 8 of 111
Grupo de Ajustes: IED Configuration
Nombre Descripcin Valor Unidad
tSynchTimeout Time synch timeout before 1800 s
error status is generated

TSyncReqAfTout Time synchronization request No


after timeout

DNPToSetTime Allow DNP to set time in IED Yes

Averag3TimeReq Use average of 3 time No


requests

Obj1DefVar Object 1, default variation 1: BISingleBit

Obj2DefVar Object 2, default variation 3: BIChWithRelTime

Obj4DefVar Object 4, default variation 3: DIChWithRelTime

Obj10DefVar Object 10, default variation 2: BOStatus

Obj20DefVar Object 20, default variation 5: BinCnt32WoutF

Obj22DefVar Object 22, default variation 1: BinCnt32EvWoutT

Obj30DefVar Object 30, default variation 3: AI32IntWithoutF

Obj32DefVar Object 32, default variation 1: AI32IntEvWoutF

PairedPoint Enable paired point Yes

tSelectTimeout Select timeout 30 s

Chapter : Communication->Station communication->DNP3.0->CH2TCP: 2

Operation Operation mode Off

ApLayMaxRxSize Application layer maximum Rx 2048


fragment size

ApLayMaxTxSize Application layer maximum Tx 2048


fragment size

TCPIPLisPort TCP/ IP listen port 20000

UDPPortAccData UDP port to accept UDP 20000


datagrams from master

UDPPortInitNUL UDP portfor initial NULL 20000


response

UDPPortCliMast UDP port to remote client/ 0


master

Chapter : Communication->Station communication->DNP3.0->MST1TCP: 2

Operation Operation Off / On Off

SlaveAddress Slave address 1

MasterAddres Master address 1

ValMasterAddr Validate source (master) Yes


address

AddrQueryEnbl Address query enable Yes

tApplConfTout Application layer confim 10 s


timeout

ApplMultFrgRes Enable application for multiple Yes


fragment response

ConfMultFrag Confirm each multiple Yes


fragment

Page 9 of 111
Grupo de Ajustes: IED Configuration
Nombre Descripcin Valor Unidad
UREnable Unsolicited response enabled Yes

URSendOnline Unsolicited response sends No


when on- line

UREvClassMask Unsolicited response, event Off


class mask

UROfflineRetry Unsolicited response retries 5


before off- line retry mode

tURRetryDelay Unsolicited response retry 5 s


delay in s

tUROfflRtryDel Unsolicited response off- line 30 s


retry delay in s

UREvCntThold1 Unsolicited response class 1 5


event count report treshold

tUREvBufTout1 Unsolicited response class 1 5 s


event buffer timeout

UREvCntThold2 Unsolicited response class 2 5


event count report treshold

tUREvBufTout2 Unsolicited response class 2 5 s


event buffer timeout

UREvCntThold3 Unsolicited response class 3 5


event count report treshold

tUREvBufTout3 Unsolicited response class 3 5 s


event buffer timeout

DelOldBufFull Delete oldest event when No


buffer is full

tSynchTimeout Time synch timeout before 1800 s


error status is generated

TSyncReqAfTout Time synchronization request No


after timeout

DNPToSetTime Allow DNP to set time in IED No

Averag3TimeReq Use average of 3 time No


requests

MasterIP- Addr Master IP- address 0. 0. 0. 0 18 characters

MasterIPNetMsk Master IP net mask 255. 255. 255. 255 18 characters

Obj1DefVar Object 1, default variation 1: BISingleBit

Obj2DefVar Object 2, default variation 3: BIChWithRelTime

Obj4DefVar Object 4, default variation 3: DIChWithRelTime

Obj10DefVar Object 10, default variation 2: BOStatus

Obj20DefVar Object 20, default variation 5: BinCnt32WoutF

Obj22DefVar Object 22, default variation 1: BinCnt32EvWoutT

Obj30DefVar Object 30, default variation 3: AI32IntWithoutF

Obj32DefVar Object 32, default variation 1: AI32IntEvWoutF

PairedPoint Enable paired point Yes

tSelectTimeout Select timeout 30 s

tBrokenConTout Broken connection timeout 0 s

Page 10 of 111
Grupo de Ajustes: IED Configuration
Nombre Descripcin Valor Unidad
tKeepAliveT Keep- Alive timer 10 s

Chapter : Communication->Station communication->DNP3.0->CH3TCP: 3

Operation Operation mode Off

ApLayMaxRxSize Application layer maximum Rx 2048


fragment size

ApLayMaxTxSize Application layer maximum Tx 2048


fragment size

TCPIPLisPort TCP/ IP listen port 20000

UDPPortAccData UDP port to accept UDP 20000


datagrams from master

UDPPortInitNUL UDP port for initial NULL 20000


response

UDPPortCliMast UDP port to remote client/ 0


master

Chapter : Communication->Station communication->DNP3.0->MST2TCP: 3

Operation Operation Off / On Off

SlaveAddress Slave address 1

MasterAddres Master address 1

ValMasterAddr Validate source (master) Yes


address

AddrQueryEnbl Address query enable Yes

tApplConfTout Application layer confim 10 s


timeout

ApplMultFrgRes Enable application for multiple Yes


fragment response

ConfMultFrag Confirm each multiple Yes


fragment

UREnable Unsolicited response enabled Yes

URSendOnline Unsolicited response sends No


when on- line

UREvClassMask Unsolicited response, event Off


class mask

UROfflineRetry Unsolicited response retries 5


before off- line retry mode

tURRetryDelay Unsolicited response retry 5 s


delay in s

tUROfflRtryDel Unsolicited response off- line 30 s


retry delay in s

UREvCntThold1 Unsolicited response class 1 5


event count report treshold

tUREvBufTout1 Unsolicited response class 1 5 s


event buffer timeout

UREvCntThold2 Unsolicited response class 2 5


event count report treshold

tUREvBufTout2 Unsolicited response class 2 5 s


event buffer timeout

Page 11 of 111
Grupo de Ajustes: IED Configuration
Nombre Descripcin Valor Unidad
UREvCntThold3 Unsolicited response class 3 5
event count report treshold

tUREvBufTout3 Unsolicited response class 3 5 s


event buffer timeout

DelOldBufFull Delete oldest event when No


buffer is full

tSynchTimeout Time synch timeout before 1800 s


error status is generated

TSyncReqAfTout Time synchronization request No


after timeout

DNPToSetTime Allow DNP to set time in IED No

Averag3TimeReq Use average of 3 time No


requests

MasterIP- Addr Master IP- address 0. 0. 0. 0 18 characters

MasterIPNetMsk Master IP net mask 255. 255. 255. 255 18 characters

Obj1DefVar Object 1, default variation 1: BISingleBit

Obj2DefVar Object 2, default variation 3: BIChWithRelTime

Obj4DefVar Object 4, default variation 3: DIChWithRelTime

Obj10DefVar Object 10, default variation 2: BOStatus

Obj20DefVar Object 20, default variation 5: BinCnt32WoutF

Obj22DefVar Object 22, default variation 1: BinCnt32EvWoutT

Obj30DefVar Object 30, default variation 3: AI32IntWithoutF

Obj32DefVar Object 32, default variation 1: AI32IntEvWoutF

PairedPoint Enable paired point Yes

tSelectTimeout Select timeout 30 s

tBrokenConTout Broken connection timeout 0 s

tKeepAliveT Keep- Alive timer 10 s

Chapter : Communication->Station communication->DNP3.0->CH4TCP: 4

Operation Operation mode Off

ApLayMaxRxSize Application layer maximum Rx 2048


fragment size

ApLayMaxTxSize Application layer maximum Tx 2048


fragment size

TCPIPLisPort TCP/ IP listen port 20000

UDPPortAccData UDP port to accept UDP 20000


datagrams from master

UDPPortInitNUL UDP port for initial NULL 20000


response

UDPPortCliMast UDP port to remote client/ 0


master

Chapter : Communication->Station communication->DNP3.0->MST3TCP: 4

Operation Operation Off / On Off

SlaveAddress Slave address 1

Page 12 of 111
Grupo de Ajustes: IED Configuration
Nombre Descripcin Valor Unidad
MasterAddres Master address 1

ValMasterAddr Validate source (master) Yes


address

AddrQueryEnbl Address query enable Yes

tApplConfTout Application layer confim 10 s


timeout

ApplMultFrgRes Enable application for multiple Yes


fragment response

ConfMultFrag Confirm each multiple Yes


fragment

UREnable Unsolicited response enabled Yes

URSendOnline Unsolicited response sends No


when on- line

UREvClassMask Unsolicited response, event Off


class mask

UROfflineRetry Unsolicited response retries 5


before off- line retry mode

tURRetryDelay Unsolicited response retry 5 s


delay in s

tUROfflRtryDel Unsolicited response off- line 30 s


retry delay in s

UREvCntThold1 Unsolicited response class 1 5


event count report treshold

tUREvBufTout1 Unsolicited response class 1 5 s


event buffer timeout

UREvCntThold2 Unsolicited response class 2 5


event count report treshold

tUREvBufTout2 Unsolicited response class 2 5 s


event buffer timeout

UREvCntThold3 Unsolicited response class 3 5


event count report treshold

tUREvBufTout3 Unsolicited response class 3 5 s


event buffer timeout

DelOldBufFull Delete oldest event when No


buffer is full

tSynchTimeout Time synch timeout before 1800 s


error status is generated

TSyncReqAfTout Time synchronization request No


after timeout

DNPToSetTime Allow DNP to set time in IED No

Averag3TimeReq Use average of 3 time No


requests

MasterIP- Addr Master IP- address 0. 0. 0. 0 18 characters

MasterIPNetMsk Master IP net mask 255. 255. 255. 255 18 characters

Obj1DefVar Object 1, default variation 1: BISingleBit

Obj2DefVar Object 2, default variation 3: BIChWithRelTime

Page 13 of 111
Grupo de Ajustes: IED Configuration
Nombre Descripcin Valor Unidad
Obj4DefVar Object 4, default variation 3: DIChWithRelTime

Obj10DefVar Object 10, default variation 2: BOStatus

Obj20DefVar Object 20, default variation 5: BinCnt32WoutF

Obj22DefVar Object 22, default variation 1: BinCnt32EvWoutT

Obj30DefVar Object 30, default variation 3: AI32IntWithoutF

Obj32DefVar Object 32, default variation 1: AI32IntEvWoutF

PairedPoint Enable paired point Yes

tSelectTimeout Select timeout 30 s

tBrokenConTout Broken connection timeout 0 s

tKeepAliveT Keep- Alive timer 10 s

Chapter : Communication->Station communication->DNP3.0->CH5TCP: 5

Operation Operation mode Off

ApLayMaxRxSize Application layer maximum Rx 2048


fragment size

ApLayMaxTxSize Application layer maximum Tx 2048


fragment size

TCPIPLisPort TCP/ IP listen port 20000

UDPPortAccData UDP port to accept UDP 20000


datagrams from master

UDPPortInitNUL UDP port for initial NULL 20000


response

UDPPortCliMast UDP port to remote client/ 0


master

Chapter : Communication->Station communication->DNP3.0->MST4TCP: 5

Operation Operation Off / On Off

SlaveAddress Slave address 1

MasterAddres Master address 1

ValMasterAddr Validate source (master) Yes


address

AddrQueryEnbl Address query enable Yes

tApplConfTout Application layer confim 10 s


timeout

ApplMultFrgRes Enable application for multiple Yes


fragment response

ConfMultFrag Confirm each multiple Yes


fragment

UREnable Unsolicited response enabled Yes

URSendOnline Unsolicited response sends No


when on- line

UREvClassMask Unsolicited response, event Off


class mask

UROfflineRetry Unsolicited response retries 5


before off- line retry mode

Page 14 of 111
Grupo de Ajustes: IED Configuration
Nombre Descripcin Valor Unidad
tURRetryDelay Unsolicited response retry 5 s
delay in s

tUROfflRtryDel Unsolicited response off- line 30 s


retry delay in s

UREvCntThold1 Unsolicited response class 1 5


event count report treshold

tUREvBufTout1 Unsolicited response class 1 5 s


event buffer timeout

UREvCntThold2 Unsolicited response class 2 5


event count report treshold

tUREvBufTout2 Unsolicited response class 2 5 s


event buffer timeout

UREvCntThold3 Unsolicited response class 3 5


event count report treshold

tUREvBufTout3 Unsolicited response class 3 5 s


event buffer timeout

DelOldBufFull Delete oldest event when No


buffer is full

tSynchTimeout Time synch timeout before 1800 s


error status is generated

TSyncReqAfTout Time synchronization request No


after timeout

DNPToSetTime Allow DNP to set time in IED No

Averag3TimeReq Use average of 3 time No


requests

MasterIP- Addr Master IP- address 0. 0. 0. 0 18 characters

MasterIPNetMsk Master IP net mask 255. 255. 255. 255 18 characters

Obj1DefVar Object 1, default variation 1: BISingleBit

Obj2DefVar Object 2, default variation 3: BIChWithRelTime

Obj4DefVar Object 4, default variation 3: DIChWithRelTime

Obj10DefVar Object 10, default variation 2: BOStatus

Obj20DefVar Object 20, default variation 5: BinCnt32WoutF

Obj22DefVar Object 22, default variation 1: BinCnt32EvWoutT

Obj30DefVar Object 30, default variation 3: AI32IntWithoutF

Obj32DefVar Object 32, default variation 1: AI32IntEvWoutF

PairedPoint Enable paired point Yes

tSelectTimeout Select timeout 30 s

tBrokenConTout Broken connection timeout 0 s

tKeepAliveT Keep- Alive timer 10 s

Chapter : Communication->Station communication->IEC61850-8-1->IEC61850-8-1: 1

Operation Operation Off/ On On

IEDName IED name in IEC61850 system AA2B1Q46A1 18 characters

Page 15 of 111
Grupo de Ajustes: IED Configuration
Nombre Descripcin Valor Unidad
GOOSE Port for GOOSE OEM311_ AB
communication

Chapter : Communication->TCP-IP configuration->Front port & Gateway->ETHFRNT: 1->Front port

IPAddress IP- Address 10. 1. 150. 3 18 characters

IPMask IP- Mask 255. 255. 255. 0 18 characters

Chapter : Communication->TCP-IP configuration->Front port & Gateway->ETHFRNT: 1->Gateway

GWAddress Gateway address 172. 16. 200. 1 18 characters

Chapter : Communication->TCP-IP configuration->Rear OEM - port AB->ETHLANAB: 2

Link Link name to physical OEM311_ AB


hardware

IPAddress IP- Address 172. 16. 46. 2 18 characters

IPMask IP- Mask 255. 255. 0. 0 18 characters

Chapter : Communication->TCP-IP configuration->Rear OEM - port CD->ETHLANCD: 3

Link Link name to physical Off


hardware

IPAddress IP- Address 192. 168. 2. 10 18 characters

IPMask IP- Mask 255. 255. 255. 0 18 characters

Chapter : Analog modules->AISVBAS: 1

PhaseAngleRef Reference channel for phase TRM40- Ch1


angle presentation

Chapter : HMI->LEDGEN: 1

Operation Operation mode for the LED On


function

tRestart Defines the disturbance length 0 s

tMax Maximum time for the 0 s


definition of a disturbance

SeqTypeLED1 Sequence type for LED 1 LatchedAck- S- F

SeqTypeLED2 Sequence type for LED 2 LatchedAck- S- F

SeqTypeLED3 Sequence type for LED 3 LatchedAck- S- F

SeqTypeLED4 Sequence type for LED 4 LatchedAck- S- F

SeqTypeLED5 Sequence type for LED 5 LatchedAck- S- F

SeqTypeLED6 Sequence type for LED 6 LatchedAck- S- F

SeqTypeLED7 Sequence type for LED 7 LatchedAck- S- F

SeqTypeLED8 sequence type for LED 8 LatchedAck- S- F

SeqTypeLED9 Sequence type for LED 9 LatchedAck- S- F

SeqTypeLED10 Sequence type for LED 10 LatchedAck- S- F

SeqTypeLED11 Sequence type for LED 11 LatchedAck- S- F

SeqTypeLED12 Sequence type for LED 12 LatchedAck- S- F

SeqTypeLED13 Sequence type for LED 13 LatchedAck- S- F

SeqTypeLED14 Sequence type for LED 14 LatchedAck- S- F

Page 16 of 111
Grupo de Ajustes: IED Configuration
Nombre Descripcin Valor Unidad
SeqTypeLED15 Sequence type for LED 15 Follow- S

Chapter : HMI->SCREEN: 1->Screen

DisplayTimeout Local HMI display timeout 60 Min

AutoRepeat Activation of auto- repeat (On) On


or not (Off)

ContrastLevel Contrast level for display 0 %

SymbolFont Symbol font for Single Line IEC


Diagram

Chapter : HMI->SCREEN: 1->Functions

EvListSrtOrder Sort order of event list Latest on top

Chapter : Monitoring->DisturbanceReport->RDRE: 1

Operation Operation Off/ On On

PreFaultRecT Pre- fault recording time 0. 5 s

PostFaultRecT Post- fault recording time 1 s

TimeLimit Fault recording time limit 1. 5 s

PostRetrig Post- fault retrig enabled (On) Off


or not (Off)

ZeroAngleRef Trip value recorder, phasor 1 Ch


reference channel

OpModeTest Operation mode during test Off


mode

Grupo de Ajustes: Application Configuration

Nombre Descripcin Valor Unidad


Chapter : Analog modules->3PhaseAnalogGroup->W1_CT_B; SMAI1: 1

GRPNAME Group name for GRP1 in W1_ CT_ B 13 characters


Signal Matrix Tool

AI1NAME Signal name for AI1 in Signal IL1 13 characters


Matrix Tool

AI2NAME Signal name for AI2 in Signal IL2 13 characters


Matrix Tool

AI3NAME Signal name for AI3 in Signal IL3 13 characters


Matrix Tool

AI4NAME Signal name for AI4 in Signal IN optional 13 characters


Matrix Tool

DFTRefExtOut DFT reference for external InternalDFTRef


output

DFTReference DFT reference InternalDFTRef

ConnectionType Input connection type Ph- N

Negation Negation Off

MinValFreqMeas Limit for frequency calculation 10 %


in % of UBase

UBase Base voltage 500 kV

Page 17 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
TYPE 1=Voltage, 2=Current 2 Ch

Chapter : Analog modules->3PhaseAnalogGroup->W1_CT_C; SMAI1: 13

GRPNAME Group name for GRP1 in W1_ CT_ C 13 characters


Signal Matrix Tool

AI1NAME Signal name for AI1 in Signal IL1 13 characters


Matrix Tool

AI2NAME Signal name for AI2 in Signal IL2 13 characters


Matrix Tool

AI3NAME Signal name for AI3 in Signal IL3 13 characters


Matrix Tool

AI4NAME Signal name for AI4 in Signal IN optional 13 characters


Matrix Tool

DFTRefExtOut DFT reference for external InternalDFTRef


output

DFTReference DFT reference InternalDFTRef

ConnectionType Input connection type Ph- N

Negation Negation Off

MinValFreqMeas Limit for frequency calculation 10 %


in % of UBase

UBase Base voltage 500 kV

TYPE 1=Voltage, 2=Current 2 Ch

Chapter : Analog modules->3PhaseAnalogGroup->W1_CT_A; SMAI1: 25

GRPNAME Group name for GRP1 in W1_ CT_ A 13 characters


Signal Matrix Tool

AI1NAME Signal name for AI1 in Signal IL1 13 characters


Matrix Tool

AI2NAME Signal name for AI2 in Signal IL2 13 characters


Matrix Tool

AI3NAME Signal name for AI3 in Signal IL3 13 characters


Matrix Tool

AI4NAME Signal name for AI4 in Signal IN optional 13 characters


Matrix Tool

DFTRefExtOut DFT reference for external InternalDFTRef


output

DFTReference DFT reference InternalDFTRef

ConnectionType Input connection type Ph- N

Negation Negation Off

MinValFreqMeas Limit for frequency calculation 10 %


in % of UBase

UBase Base voltage 500 kV

TYPE 1=Voltage, 2=Current 2 Ch

Chapter : Analog modules->3PhaseAnalogGroup->W1_VT_B; SMAI2: 2

GRPNAME Group name for GRP2 in W1_ VT_ B 13 characters


Signal Matrix Tool

AI1NAME Signal name for AI1 in Signal UL1 13 characters

Page 18 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
Matrix Tool

AI2NAME Signal name for AI2 in Signal UL2 13 characters


Matrix Tool

AI3NAME Signal name for AI3 in Signal UL3 13 characters


Matrix Tool

AI4NAME Signal name for AI4 in Signal UN optional 13 characters


Matrix Tool

DFTReference DFT reference InternalDFTRef

ConnectionType Input connection type Ph- N

Negation Negation Off

MinValFreqMeas Limit for frequency calculation 10 %


in % of UBase

UBase Base voltage 500 kV

TYPE 1=Voltage, 2=Current 1 Ch

Chapter : Analog modules->3PhaseAnalogGroup->W1_CT_C_MEAS; SMAI2: 14

GRPNAME Group name for GRP2 in W1_ CT_ C_ MEAS 13 characters


Signal Matrix Tool

AI1NAME Signal name for AI1 in Signal IL1 13 characters


Matrix Tool

AI2NAME Signal name for AI2 in Signal IL2 13 characters


Matrix Tool

AI3NAME Signal name for AI3 in Signal IL3 13 characters


Matrix Tool

AI4NAME Signal name for AI4 in Signal IN optional 13 characters


Matrix Tool

DFTReference DFT reference InternalDFTRef

ConnectionType Input connection type Ph- N

Negation Negation Off

MinValFreqMeas Limit for frequency calculation 10 %


in % of UBase

UBase Base voltage 500 kV

TYPE 1=Voltage, 2=Current 2 Ch

Chapter : Analog modules->3PhaseAnalogGroup->WN_INCT_A; SMAI2: 26

GRPNAME Group name for GRP2 in WN_ INCT_ A 13 characters


Signal Matrix Tool

AI1NAME Signal name for AI1 in Signal Not used 13 characters


Matrix Tool

AI2NAME Signal name for AI2 in Signal Not used 13 characters


Matrix Tool

AI3NAME Signal name for AI3 in Signal Not used 13 characters


Matrix Tool

AI4NAME Signal name for AI4 in Signal IN 13 characters


Matrix Tool

DFTReference DFT reference InternalDFTRef

ConnectionType Input connection type Ph- N

Page 19 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
Negation Negation Off

MinValFreqMeas Limit for frequency calculation 10 %


in % of UBase

UBase Base voltage 500 kV

TYPE 1=Voltage, 2=Current 2 Ch

Chapter : Analog modules->3PhaseAnalogGroup->W1_VT_C; SMAI3: 3

GRPNAME Group name for GRP3 in W1_ VT_ C 13 characters


Signal Matrix Tool

AI1NAME Signal name for AI1 in Signal UL1 13 characters


Matrix Tool

AI2NAME Signal name for AI2 in Signal UL2 13 characters


Matrix Tool

AI3NAME Signal name for AI3 in Signal UL3 13 characters


Matrix Tool

AI4NAME Signal name for AI4 in Signal UN optional 13 characters


Matrix Tool

DFTReference DFT reference InternalDFTRef

ConnectionType Input connection type Ph- N

Negation Negation Off

MinValFreqMeas Limit for frequency calculation 10 %


in % of UBase

UBase Base voltage 500 kV

TYPE 1=Voltage, 2=Current 1 Ch

Chapter : Analog modules->3PhaseAnalogGroup->W1_INCT_C; SMAI3: 15

GRPNAME Group name for GRP3 in W1_ INCT_ C 13 characters


Signal Matrix Tool

AI1NAME Signal name for AI1 in Signal Not used 13 characters


Matrix Tool

AI2NAME Signal name for AI2 in Signal Not used 13 characters


Matrix Tool

AI3NAME Signal name for AI3 in Signal Not used 13 characters


Matrix Tool

AI4NAME Signal name for AI4 in Signal IN 13 characters


Matrix Tool

DFTReference DFT reference InternalDFTRef

ConnectionType Input connection type Ph- N

Negation Negation Off

MinValFreqMeas Limit for frequency calculation 10 %


in % of UBase

UBase Base voltage 500 kV

TYPE 1=Voltage, 2=Current 2 Ch

Chapter : Analog modules->3PhaseAnalogGroup->W1_Bus1VT_C; SMAI5: 5

GRPNAME Group name for GRP5 in W1_ Bus1VT_ C 13 characters


Signal Matrix Tool

Page 20 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
AI1NAME Signal name for AI1 in Signal UL1 13 characters
Matrix Tool

AI2NAME Signal name for AI2 in Signal UL2 13 characters


Matrix Tool

AI3NAME Signal name for AI3 in Signal UL3 13 characters


Matrix Tool

AI4NAME Signal name for AI4 in Signal Not used 13 characters


Matrix Tool

DFTReference DFT reference InternalDFTRef

ConnectionType Input connection type Ph- N

Negation Negation Off

MinValFreqMeas Limit for frequency calculation 10 %


in % of UBase

UBase Base voltage 500 kV

TYPE 1=Voltage, 2=Current 1 Ch

Chapter : Analog modules->3PhaseAnalogGroup->W1_VT_C_MEAS; SMAI5: 17

GRPNAME Group name for GRP5 in W1_ VT_ C_ MEAS 13 characters


Signal Matrix Tool

AI1NAME Signal name for AI1 in Signal UL1 13 characters


Matrix Tool

AI2NAME Signal name for AI2 in Signal UL2 13 characters


Matrix Tool

AI3NAME Signal name for AI3 in Signal UL3 13 characters


Matrix Tool

AI4NAME Signal name for AI4 in Signal UN 13 characters


Matrix Tool

DFTReference DFT reference InternalDFTRef

ConnectionType Input connection type Ph- N

Negation Negation Off

MinValFreqMeas Limit for frequency calculation 10 %


in % of UBase

UBase Base voltage 500 kV

TYPE 1=Voltage, 2=Current 1 Ch

Chapter : Analog modules->3PhaseAnalogGroup->W1_Bus2VT_C; SMAI7: 7

GRPNAME Group name for GRP7 in W1_ Bus2VT_ C 13 characters


Signal Matrix Tool

AI1NAME Signal name for AI1 in Signal UL1 13 characters


Matrix Tool

AI2NAME Signal name for AI2 in Signal UL2 13 characters


Matrix Tool

AI3NAME Signal name for AI3 in Signal UL3 13 characters


Matrix Tool

AI4NAME Signal name for AI4 in Signal Not used 13 characters


Matrix Tool

DFTReference DFT reference InternalDFTRef

Page 21 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
ConnectionType Input connection type Ph- N

Negation Negation Off

MinValFreqMeas Limit for frequency calculation 10 %


in % of UBase

UBase Base voltage 500 kV

TYPE 1=Voltage, 2=Current 1 Ch

Chapter : Analog modules->3PhaseAnalogGroup->W1_UNVT_C; SMAI9: 9

GRPNAME Group name for GRP9 in W1_ UNVT_ C 13 characters


Signal Matrix Tool

AI1NAME Signal name for AI1 in Signal UL1 optional 13 characters


Matrix Tool

AI2NAME Signal name for AI2 in Signal UL2 optional 13 characters


Matrix Tool

AI3NAME Signal name for AI3 in Signal UL3 optional 13 characters


Matrix Tool

AI4NAME Signal name for AI4 in Signal UN 13 characters


Matrix Tool

DFTReference DFT reference InternalDFTRef

ConnectionType Input connection type Ph- N

Negation Negation Off

MinValFreqMeas Limit for frequency calculation 10 %


in % of UBase

UBase Base voltage 500 kV

TYPE 1=Voltage, 2=Current 1 Ch

Chapter : Analog modules->3PhaseAnalogGroup->W1_CT_D; SMAI10: 10

GRPNAME Group name for GRP10 in W1_ CT_ D 13 characters


Signal Matrix Tool

AI1NAME Signal name for AI1 in Signal IL1 13 characters


Matrix Tool

AI2NAME Signal name for AI2 in Signal IL2 13 characters


Matrix Tool

AI3NAME Signal name for AI3 in Signal IL3 13 characters


Matrix Tool

AI4NAME Signal name for AI4 in Signal IN optional 13 characters


Matrix Tool

DFTReference DFT reference InternalDFTRef

ConnectionType Input connection type Ph- N

Negation Negation Off

MinValFreqMeas Limit for frequency calculation 10 %


in % of UBase

UBase Base voltage 500 kV

Page 22 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
TYPE 1=Voltage, 2=Current 2 Ch

Chapter : Analog modules->3PhaseAnalogGroup->W2_CT_B; SMAI4: 4

GRPNAME Group name for GRP4 in W2_ CT_ B 13 characters


Signal Matrix Tool

AI1NAME Signal name for AI1 in Signal IL1 13 characters


Matrix Tool

AI2NAME Signal name for AI2 in Signal IL2 13 characters


Matrix Tool

AI3NAME Signal name for AI3 in Signal IL3 13 characters


Matrix Tool

AI4NAME Signal name for AI4 in Signal IN optional 13 characters


Matrix Tool

DFTReference DFT reference InternalDFTRef

ConnectionType Input connection type Ph- N

Negation Negation Off

MinValFreqMeas Limit for frequency calculation 10 %


in % of UBase

UBase Base voltage 500 kV

TYPE 1=Voltage, 2=Current 2 Ch

Chapter : Analog modules->3PhaseAnalogGroup->W2_CT_C; SMAI4: 16

GRPNAME Group name for GRP4 in W2_ CT_ C 13 characters


Signal Matrix Tool

AI1NAME Signal name for AI1 in Signal IL1 13 characters


Matrix Tool

AI2NAME Signal name for AI2 in Signal IL2 13 characters


Matrix Tool

AI3NAME Signal name for AI3 in Signal IL3 13 characters


Matrix Tool

AI4NAME Signal name for AI4 in Signal IN optional 13 characters


Matrix Tool

DFTReference DFT reference InternalDFTRef

ConnectionType Input connection type Ph- N

Negation Negation Off

MinValFreqMeas Limit for frequency calculation 10 %


in % of UBase

UBase Base voltage 500 kV

TYPE 1=Voltage, 2=Current 2 Ch

Chapter : Analog modules->3PhaseAnalogGroup->W2_CT_A; SMAI4: 28

GRPNAME Group name for GRP4 in W2_ CT_ A 13 characters


Signal Matrix Tool

AI1NAME Signal name for AI1 in Signal IL1 13 characters


Matrix Tool

AI2NAME Signal name for AI2 in Signal IL2 13 characters


Matrix Tool

AI3NAME Signal name for AI3 in Signal IL3 13 characters

Page 23 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
Matrix Tool

AI4NAME Signal name for AI4 in Signal IN optional 13 characters


Matrix Tool

DFTReference DFT reference InternalDFTRef

ConnectionType Input connection type Ph- N

Negation Negation Off

MinValFreqMeas Limit for frequency calculation 10 %


in % of UBase

UBase Base voltage 500 kV

TYPE 1=Voltage, 2=Current 2 Ch

Chapter : Analog modules->3PhaseAnalogGroup->W2_INCT_A; SMAI5: 29

GRPNAME Group name for GRP5 in W2_ INCT_ A 13 characters


Signal Matrix Tool

AI1NAME Signal name for AI1 in Signal Not used 13 characters


Matrix Tool

AI2NAME Signal name for AI2 in Signal Not used 13 characters


Matrix Tool

AI3NAME Signal name for AI3 in Signal Not used 13 characters


Matrix Tool

AI4NAME Signal name for AI4 in Signal IN 13 characters


Matrix Tool

DFTReference DFT reference InternalDFTRef

ConnectionType Input connection type Ph- N

Negation Negation Off

MinValFreqMeas Limit for frequency calculation 10 %


in % of UBase

UBase Base voltage 500 kV

TYPE 1=Voltage, 2=Current 2 Ch

Chapter : Analog modules->3PhaseAnalogGroup->W2_CT_C_MEAS; SMAI11: 23

GRPNAME Group name for GRP11 in W2_ CT_ C_ MEAS 13 characters


Signal Matrix Tool

AI1NAME Signal name for AI1 in Signal IL1 13 characters


Matrix Tool

AI2NAME Signal name for AI2 in Signal IL2 13 characters


Matrix Tool

AI3NAME Signal name for AI3 in Signal IL3 13 characters


Matrix Tool

AI4NAME Signal name for AI4 in Signal IN optional 13 characters


Matrix Tool

DFTReference DFT reference InternalDFTRef

ConnectionType Input connection type Ph- N

Negation Negation Off

MinValFreqMeas Limit for frequency calculation 10 %


in % of UBase

Page 24 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
UBase Base voltage 500 kV

TYPE 1=Voltage, 2=Current 2 Ch

Chapter : Analog modules->3PhaseAnalogGroup->WN_CT_B; SMAI6: 6

GRPNAME Group name for GRP6 in WN_ CT_ B 13 characters


Signal Matrix Tool

AI1NAME Signal name for AI1 in Signal Not used 13 characters


Matrix Tool

AI2NAME Signal name for AI2 in Signal Not used 13 characters


Matrix Tool

AI3NAME Signal name for AI3 in Signal Not used 13 characters


Matrix Tool

AI4NAME Signal name for AI4 in Signal IN 13 characters


Matrix Tool

DFTReference DFT reference InternalDFTRef

ConnectionType Input connection type Ph- N

Negation Negation Off

MinValFreqMeas Limit for frequency calculation 10 %


in % of UBase

UBase Base voltage 500 kV

TYPE 1=Voltage, 2=Current 2 Ch

Chapter : Analog modules->3PhaseAnalogGroup->WN_CT_C; SMAI6: 18

GRPNAME Group name for GRP6 in WN_ CT_ C 13 characters


Signal Matrix Tool

AI1NAME Signal name for AI1 in Signal Not used 13 characters


Matrix Tool

AI2NAME Signal name for AI2 in Signal Not used 13 characters


Matrix Tool

AI3NAME Signal name for AI3 in Signal Not used 13 characters


Matrix Tool

AI4NAME Signal name for AI4 in Signal IN 13 characters


Matrix Tool

DFTReference DFT reference InternalDFTRef

ConnectionType Input connection type Ph- N

Negation Negation Off

MinValFreqMeas Limit for frequency calculation 10 %


in % of UBase

UBase Base voltage 500 kV

TYPE 1=Voltage, 2=Current 2 Ch

Chapter : Differential protection->TransformerDiff2Wind(PDIF,87T)->T2WPDIF: 1

RatedVoltageW1 Rated voltage of transformer 500 kV


winding 1 (HV winding) in kV

RatedVoltageW2 Rated voltage of transformer 500 kV


winding 2 in kV

RatedCurrentW1 Rated current of transformer 231 A


winding 1 (HV winding) in A

Page 25 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
RatedCurrentW2 Rated current of transformer 231 A
winding 2 in A

ConnectTypeW1 Connection type of winding 1: WYE (Y)


Y- wye or D- delta

ConnectTypeW2 Connection type of winding 2: WYE (Y)


Y- wye or D- delta

ClockNumberW2 Phase displacement between 0 [0 deg]


W2 & W1=HV winding, hour
notation

ZSCurrSubtrW1 Enable zer. seq. current On


subtraction for W1 side, On /
Off

ZSCurrSubtrW2 Enable zer. seq. current On


subtraction for W2 side, On /
Off

TconfigForW1 Two CT inputs (T- config. ) No


for winding 1, YES / NO

CT1RatingW1 CT primary rating in A, T- 400 A


branch 1, on transf. W1 side

CT2RatingW1 CT primary in A, T- branch 2, 400 A


on transf. W1 side

TconfigForW2 Two CT inputs (T- config. ) No


for winding 2, YES / NO

CT1RatingW2 CT primary rating in A, T- 400 A


branch 1, on transf. W2 side

CT2RatingW2 CT primary rating in A, T- 400 A


branch 2, on transf. W2 side

LocationOLTC1 Transformer winding where Not Used


OLTC1 is located

LowTapPosOLTC1 OLTC1 lowest tap position 1


designation (e. g. 1)

RatedTapOLTC1 OLTC1 rated tap/ mid- tap 6


position designation (e. g. 6)

HighTapPsOLTC1 OLTC1 highest tap position 11


designation (e. g. 11)

TapHighVoltTC1 OLTC1 end- tap position with 1


winding highest no- load
voltage

Page 26 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
StepSizeOLTC1 Voltage change per OLTC1 1 %
step in percent of rated
voltage

Chapter : Current protection->PhaseOverCurrent4Step(PTOC,51/67)->OC4PTOC: 1->General

MeasType Selection between DFT and DFT


RMS measurement

Chapter : Current protection->PhaseOverCurrent4Step(PTOC,51/67)->OC4PTOC: 2->General

MeasType Selection between DFT and DFT


RMS measurement

Chapter : Voltage protection->OverVoltage2Step(PTOV,59)->OV2PTOV: 1->General

ConnType TBD PhN DFT

Chapter : Voltage protection->UnderVoltage2Step(PTUV,27)->UV2PTUV: 1->General

ConnType Group selector for connection PhN DFT


type

Chapter : Logic->LogicTimer->TIMER: 11

T Time delay of function 0. 08 s

Chapter : Logic->LogicTimer->TIMER: 12

T Time delay of function 0. 08 s

Chapter : Logic->LogicTimer->TIMER: 13

T Time delay of function 0. 08 s

Chapter : Logic->LogicTimer->TIMER: 14

T Time delay of function 0. 08 s

Chapter : Logic->LogicTimer->TIMER: 15

T Time delay of function 0. 08 s

Chapter : Logic->LogicTimer->TIMER: 16

T Time delay of function 0. 08 s

Chapter : Logic->LogicTimer->TIMER: 17

T Time delay of function 0. 08 s

Chapter : Logic->LogicTimer->TIMER: 5

T Time delay of function 3 s

Chapter : Logic->LogicTimer->TIMER: 6

T Time delay of function 0. 08 s

Chapter : Logic->LogicTimer->TIMER: 7

T Time delay of function 3 s

Chapter : Logic->LogicTimer->TIMER: 8

T Time delay of function 3 s

Chapter : Logic->LogicTimer->TIMER: 9

T Time delay of function 3 s

Chapter : Logic->LogicTimer->TIMER: 10

T Time delay of function 3 s

Page 27 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
Chapter : Logic->LogicTimer->TIMER: 21

T Time delay of function 3 s

Chapter : Logic->LogicTimer->TIMER: 2

T Time delay of function 5 s

Chapter : Logic->LogicTimer->TIMER: 3

T Time delay of function 5 s

Chapter : Logic->LogicTimer->TIMER: 4

T Time delay of function 5 s

Chapter : Logic->LogicTimer->TIMER: 1

T Time delay of function 0. 2 s

Chapter : Control->Commands->VersatileSwitch->VSGGIO: 1

Operation Operation Off / On On

CtlModel Specifies the type for control SBO Enh


model according to IEC 61850

Mode Operation mode Pulsed

tSelect Max time between select and 30 s


execute signals

tPulse Command pulse lenght 0. 2 s

NAME_ UND User define string for ON 13 characters


undetermined position

NAM_ POS1 User define string for position OP 13 characters


1

NAM_ POS2 User define string for position CL 13 characters


2

NAME_ BAD User define string for bad state P11 13 characters

Chapter : Monitoring->ServiceValues(MMXU)->CVMMXU: 1->General

Operation Operation Off / On On

IBase Base setting for current level 400 A


in A

UBase Base setting for voltage level 500 kV


in kV

Mode Selection of measured current L1, L2, L3


and voltage

PowAmpFact Amplitude factor to scale 1


power calculations

PowAngComp Angle compensation for phase 0 Deg


shift between measured I & U

k Low pass filter coefficient for 0


power measurement, U and I

UGenZeroDb Zero point clamping in % of 1 %


Ubase

IGenZeroDb Zero point clamping in % of 1 %


Ibase

UAmpComp5 Amplitude factor to calibrate 0 %

Page 28 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
voltage at 5% of Ur

UAmpComp30 Amplitude factor to calibrate 0 %


voltage at 30% of Ur

UAmpComp100 Amplitude factor to calibrate 0 %


voltage at 100% of Ur

IAmpComp5 Amplitude factor to calibrate 0 %


current at 5% of Ir

IAmpComp30 Amplitude factor to calibrate 0 %


current at 30% of Ir

IAmpComp100 Amplitude factor to calibrate 0 %


current at 100% of Ir

IAngComp5 Angle calibration for current at 0 Deg


5% of Ir

IAngComp30 Angle calibration for current at 0 Deg


30% of Ir

IAngComp100 Angle calibration for current at 0 Deg


100% of Ir

Chapter : Monitoring->ServiceValues(MMXU)->CVMMXU: 1->Apparent power S

SDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

SZeroDb Zero point clamping in 0, 0 m%


001% of range

SHiHiLim High High limit (physical value) 900000000 VA

SHiLim High limit (physical value) 800000000 VA

SLowLim Low limit (physical value) 0 VA

SLowLowLim Low Low limit (physical value) 0 VA

SMin Minimum value 0 VA

SMax Maximum value 1000000000 VA

SRepTyp Reporting type Int deadband

SLimHyst Hysteresis value in % of range 1 %


(common for all limits)

Chapter : Monitoring->ServiceValues(MMXU)->CVMMXU: 1->Active power P

PDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

PZeroDb Zero point clamping in 0, 0 m%


001% of range

PHiHiLim High High limit (physical value) 900000000 W

PHiLim High limit (physical value) 800000000 W

PLowLim Low limit (physical value) - 800000000 W

PLowLowLim Low Low limit (physical value) - 900000000 W

PMin Minimum value - 1000000000 W

PMax Maximum value 1000000000 W

PRepTyp Reporting type Int deadband

PLimHyst Hysteresis value in % of range 1 %

Page 29 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
(common for all limits)

Chapter : Monitoring->ServiceValues(MMXU)->CVMMXU: 1->Reactive power Q

QDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

QZeroDb Zero point clamping in 0, 0 m%


001% of range

QHiHiLim High High limit (physical value) 900000000 VAr

QHiLim High limit (physical value) 800000000 VAr

QLowLim Low limit (physical value) - 800000000 VAr

QLowLowLim Low Low limit (physical value) - 900000000 VAr

QMin Minimum value - 1000000000 VAr

QMax Maximum value 1000000000 VAr

QRepTyp Reporting type Int deadband

QLimHyst Hysteresis value in % of range 1 %


(common for all limits)

Chapter : Monitoring->ServiceValues(MMXU)->CVMMXU: 1->Power factor PF

PFDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

PFZeroDb Zero point clamping in 0, 0 m%


001% of range

PFHiHiLim High High limit (physical value) 3

PFHiLim High limit (physical value) 2

PFLowLim Low limit (physical value) - 2

PFLowLowLim Low Low limit (physical value) - 3

PFMin Minimum value - 1

PFMax Maximum value 1

PFRepTyp Reporting type Int deadband

PFLimHyst Hysteresis value in % of range 1 %


(common for all limits)

Chapter : Monitoring->ServiceValues(MMXU)->CVMMXU: 1->Voltage U

UDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

UZeroDb Zero point clamping in 0, 0 m%


001% of range

UHiHiLim High High limit (physical value) 460000 V

UHiLim High limit (physical value) 450000 V

ULowLim Low limit (physical value) 50000 V

ULowLowLim Low Low limit (physical value) 20000 V

UMin Minimum value 0 V

UMax Maximum value 400000 V

URepTyp Reporting type Int deadband

Page 30 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
ULimHyst Hysteresis value in % of range 1 %
(common for all limits)

Chapter : Monitoring->ServiceValues(MMXU)->CVMMXU: 1->Current I

IDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

IZeroDb Zero point clamping in 0, 0 m%


001% of range

IHiHiLim High High limit (physical value) 900 A

IHiLim High limit (physical value) 800 A

ILowLim Low limit (physical value) - 800 A

ILowLowLim Low Low limit (physical value) - 900 A

IMin Minimum value 0 A

IMax Maximum value 1000 A

IRepTyp Reporting type Int deadband

ILimHyst Hysteresis value in % of range 1 %


(common for all limits)

Chapter : Monitoring->ServiceValues(MMXU)->CVMMXU: 1->Frequency Fr

FrDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

FrZeroDb Zero point clamping in 0, 0 m%


001% of range

FrHiHiLim High High limit (physical value) 65 Hz

FrHiLim High limit (physical value) 63 Hz

FrLowLim Low limit (physical value) 47 Hz

FrLowLowLim Low Low limit (physical value) 45 Hz

FrMin Minimum value 0 Hz

FrMax Maximum value 70 Hz

FrRepTyp Reporting type Int deadband

FrLimHyst Hysteresis value in % of range 1 %


(common for all limits)

Chapter : Monitoring->CurrentPhasors(MMXU)->CMMXU: 1->General

Operation Operation Mode On / Off On

IBase Base setting for current level 400 A


in A

IAmpComp5 Amplitude factor to calibrate 0 %


current at 5% of Ir

IAmpComp30 Amplitude factor to calibrate 0 %


current at 30% of Ir

IAmpComp100 Amplitude factor to calibrate 0 %


current at 100% of Ir

IAngComp5 Angle calibration for current at 0 Deg


5% of Ir

IAngComp30 Angle calibration for current at 0 Deg


30% of Ir

Page 31 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
IAngComp100 Angle calibration for current at 0 Deg
100% of Ir

Chapter : Monitoring->CurrentPhasors(MMXU)->CMMXU: 1->IL1 Amplitude

IL1DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

IL1ZeroDb Zero point clamping in 0, 0 m%


001% of range

IL1HiHiLim High High limit (physical value) 900 A

IL1HiLim High limit (physical value) 800 A

IL1LowLim Low limit (physical value) 0 A

IL1LowLowLim Low Low limit (physical value) 0 A

IL1Min Minimum value 0 A

IL1Max Maximum value 1000 A

IL1RepTyp Reporting type Int deadband

IL1LimHys Hysteresis value in % of range 1 %


and is common for all limits

Chapter : Monitoring->CurrentPhasors(MMXU)->CMMXU: 1->IL1 Angle

IL1AngDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

Chapter : Monitoring->CurrentPhasors(MMXU)->CMMXU: 1->IL2 Amplitude

IL2DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

IL2ZeroDb Zero point clamping in 0, 0 m%


001% of range

IL2HiHiLim High High limit (physical value) 900 A

IL2HiLim High limit (physical value) 800 A

IL2LowLim Low limit (physical value) 0 A

IL2LowLowLim Low Low limit (physical value) 0 A

IL2Min Minimum value 0 A

IL2Max Maximum value 1000 A

IL2RepTyp Reporting type Int deadband

IL2LimHys Hysteresis value in % of range 1 %


and is common for all limits

Chapter : Monitoring->CurrentPhasors(MMXU)->CMMXU: 1->IL2 Angle

IL2AngDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

Chapter : Monitoring->CurrentPhasors(MMXU)->CMMXU: 1->IL3 Amplitude

IL3DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

IL3ZeroDb Zero point clamping in 0, 0 m%


001% of range

IL3HiHiLim High High limit (physical value) 900 A

IL3HiLim High limit (physical value) 800 A

Page 32 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
IL3LowLim Low limit (physical value) 0 A

IL3LowLowLim Low Low limit (physical value) 0 A

IL3Min Minimum value 0 A

IL3Max Maximum value 1000 A

IL3RepTyp Reporting type Int deadband

IL3LimHys Hysteresis value in % of range 1 %


and is common for all limits

Chapter : Monitoring->CurrentPhasors(MMXU)->CMMXU: 1->IL3 Angle

IL3AngDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

Chapter : Monitoring->CurrentPhasors(MMXU)->CMMXU: 2->General

Operation Operation Mode On / Off On

IBase Base setting for current level 400 A


in A

IAmpComp5 Amplitude factor to calibrate 0 %


current at 5% of Ir

IAmpComp30 Amplitude factor to calibrate 0 %


current at 30% of Ir

IAmpComp100 Amplitude factor to calibrate 0 %


current at 100% of Ir

IAngComp5 Angle calibration for current at 0 Deg


5% of Ir

IAngComp30 Angle calibration for current at 0 Deg


30% of Ir

IAngComp100 Angle calibration for current at 0 Deg


100% of Ir

Chapter : Monitoring->CurrentPhasors(MMXU)->CMMXU: 2->IL1 Amplitude

IL1DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

IL1ZeroDb Zero point clamping in 0, 0 m%


001% of range

IL1HiHiLim High High limit (physical value) 900 A

IL1HiLim High limit (physical value) 800 A

IL1LowLim Low limit (physical value) 0 A

IL1LowLowLim Low Low limit (physical value) 0 A

IL1Min Minimum value 0 A

IL1Max Maximum value 1000 A

IL1RepTyp Reporting type Int deadband

Page 33 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
IL1LimHys Hysteresis value in % of range 1 %
and is common for all limits

Chapter : Monitoring->CurrentPhasors(MMXU)->CMMXU: 2->IL1 Angle

IL1AngDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

Chapter : Monitoring->CurrentPhasors(MMXU)->CMMXU: 2->IL2 Amplitude

IL2DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

IL2ZeroDb Zero point clamping in 0, 0 m%


001% of range

IL2HiHiLim High High limit (physical value) 900 A

IL2HiLim High limit (physical value) 800 A

IL2LowLim Low limit (physical value) 0 A

IL2LowLowLim Low Low limit (physical value) 0 A

IL2Min Minimum value 0 A

IL2Max Maximum value 1000 A

IL2RepTyp Reporting type Int deadband

IL2LimHys Hysteresis value in % of range 1 %


and is common for all limits

Chapter : Monitoring->CurrentPhasors(MMXU)->CMMXU: 2->IL2 Angle

IL2AngDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

Chapter : Monitoring->CurrentPhasors(MMXU)->CMMXU: 2->IL3 Amplitude

IL3DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

IL3ZeroDb Zero point clamping in 0, 0 m%


001% of range

IL3HiHiLim High High limit (physical value) 900 A

IL3HiLim High limit (physical value) 800 A

IL3LowLim Low limit (physical value) 0 A

IL3LowLowLim Low Low limit (physical value) 0 A

IL3Min Minimum value 0 A

IL3Max Maximum value 1000 A

IL3RepTyp Reporting type Int deadband

IL3LimHys Hysteresis value in % of range 1 %


and is common for all limits

Chapter : Monitoring->CurrentPhasors(MMXU)->CMMXU: 2->IL3 Angle

IL3AngDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

Chapter : Monitoring->VoltagePhasors(MMXU)->Phase - Phase->VMMXU: 1->General

Operation Operation Mode On / Off On

UBase Base setting for voltage level 500 kV


in kV

Page 34 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
UAmpComp100 Amplitude factor to calibrate 0 %
voltage at 100% of Ur

Chapter : Monitoring->VoltagePhasors(MMXU)->Phase - Phase->VMMXU: 1->UL12 Amplitude

UL12DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

UL12ZeroDb Zero point clamping in 0, 0 m%


001% of range

UL12HiHiLim High High limit (physical value) 450000 V

UL12HiLim High limit (physical value) 420000 V

UL12LowLim Low limit (physical value) 380000 V

UL12LowLowLim Low Low limit (physical value) 350000 V

UL12Min Minimum value 0 V

UL12Max Maximum value 500000 V

UL12RepTyp Reporting type Int deadband

UL12LimHys Hysteresis value in % of range 1 %


and is common for all limits

Chapter : Monitoring->VoltagePhasors(MMXU)->Phase - Phase->VMMXU: 1->UL12 Angle

UL12AnDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

Chapter : Monitoring->VoltagePhasors(MMXU)->Phase - Phase->VMMXU: 1->UL23 Amplitude

UL23DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

UL23ZeroDb Zero point clamping in 0, 0 m%


001% of range

UL23HiHiLim High High limit (physical value) 450000 V

UL23HiLim High limit (physical value) 420000 V

UL23LowLim Low limit (physical value) 380000 V

UL23LowLowLim Low Low limit (physical value) 350000 V

UL23Min Minimum value 0 V

UL23Max Maximum value 500000 V

UL23RepTyp Reporting type Int deadband

UL23LimHys Hysteresis value in % of range 1 %


and is common for all limits

Chapter : Monitoring->VoltagePhasors(MMXU)->Phase - Phase->VMMXU: 1->UL23 Angle

UL23AnDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

Chapter : Monitoring->VoltagePhasors(MMXU)->Phase - Phase->VMMXU: 1->UL31 Amplitude

UL31DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

UL31ZeroDb Zero point clamping in 0, 0 m%


001% of range

UL31HiHiLim High High limit (physical value) 450000 V

UL31HiLim High limit (physical value) 420000 V

Page 35 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
UL31LowLim Low limit (physical value) 380000 V

UL31LowLowLim Low Low limit (physical value) 350000 V

UL31Min Minimum value 0 V

UL31Max Maximum value 500000 V

UL31RepTyp Reporting type Int deadband

UL31LimHys Hysteresis value in % of range 1 %


and is common for all limits

Chapter : Monitoring->VoltagePhasors(MMXU)->Phase - Phase->VMMXU: 1->UL31 Angle

UL31AnDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

Chapter : Monitoring->VoltagePhasors(MMXU)->Phase - Earth->VNMMXU: 1->General

Operation Operation Mode On / Off On

UBase Base setting for voltage level 500 kV


in kV

UAmpComp100 Amplitude factor to calibrate 0 %


voltage at 100% of Ur

Chapter : Monitoring->VoltagePhasors(MMXU)->Phase - Earth->VNMMXU: 1->UL1 Amplitude

UL1DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

UL1ZeroDb Zero point clamping in 0, 0 m%


001% of range

UL1HiHiLim High High limit (physical value) 260000 V

UL1HiLim High limit (physical value) 240000 V

UL1LowLim Low limit (physical value) 220000 V

UL1LowLowLim Low Low limit (physical value) 200000 V

UL1Min Minimum value 0 V

UL1Max Maximum value 300000 V

UL1RepTyp Reporting type Int deadband

UL1LimHys Hysteresis value in % of range 1 %


and is common for all limits

Chapter : Monitoring->VoltagePhasors(MMXU)->Phase - Earth->VNMMXU: 1->UL1 Angle

UL1AnDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

Chapter : Monitoring->VoltagePhasors(MMXU)->Phase - Earth->VNMMXU: 1->UL2 Amplitude

UL2DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

UL2ZeroDb Zero point clamping in 0, 0 m%


001% of range

UL2HiHiLim High High limit (physical value) 260000 V

UL2HiLim High limit (physical value) 240000 V

UL2LowLim Low limit (physical value) 220000 V

UL2LowLowLim Low Low limit (physical value) 200000 V

Page 36 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
UL2Min Minimum value 0 V

UL2Max Maximum value 300000 V

UL2RepTyp Reporting type Int deadband

UL2LimHys Hysteresis value in % of range 1 %


and is common for all limits

Chapter : Monitoring->VoltagePhasors(MMXU)->Phase - Earth->VNMMXU: 1->UL2 Angle

UL2AnDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

Chapter : Monitoring->VoltagePhasors(MMXU)->Phase - Earth->VNMMXU: 1->UL3 Amplitude

UL3DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

UL3ZeroDb Zero point clamping in 0, 0 m%


001% of range

UL3HiHiLim High High limit (physical value) 260000 V

UL3HiLim High limit (physical value) 240000 V

UL3LowLim Low limit (physical value) 220000 V

UL3LowLowLim Low Low limit (physical value) 200000 V

UL3Min Minimum value 0 V

UL3Max Maximum value 300000 V

UL3RepTyp Reporting type Int deadband

UL3LimHys Hysteresis value in % of range 1 %


and is common for all limits

Chapter : Monitoring->VoltagePhasors(MMXU)->Phase - Earth->VNMMXU: 1->UL3 Angle

UL3AnDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

Chapter : Monitoring->CurrentSequenceComponents(MSQI)->CMSQI: 1->General

Operation Operation Mode On / Off On

Chapter : Monitoring->CurrentSequenceComponents(MSQI)->CMSQI: 1->3I0 Amplitude

3I0DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

3I0ZeroDb Zero point clamping in 0, 0 m%


001% of range

3I0HiHiLim High High limit (physical value) 900 A

3I0HiLim High limit (physical value) 800 A

3I0LowLim Low limit (physical value) 0 A

3I0LowLowLim Low Low limit (physical value) 0 A

3I0Min Minimum value 0 A

3I0Max Maximum value 1000 A

3I0RepTyp Reporting type Cyclic

Page 37 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
3I0LimHys Hysteresis value in % of range 5 %
and is common for all limits

Chapter : Monitoring->CurrentSequenceComponents(MSQI)->CMSQI: 1->3I0 Angle

3I0AngDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

3I0AngZeroDb Zero point clamping in 0, 0 m%


001% of range

3I0AngMin Minimum value - 180 Deg

3I0AngMax Maximum value 180 Deg

3I0AngRepTyp Reporting type Cyclic

Chapter : Monitoring->CurrentSequenceComponents(MSQI)->CMSQI: 1->I1 Amplitude

I1DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

I1ZeroDb Zero point clamping in 0, 0 m%


001% of range

I1HiHiLim High High limit (physical value) 900 A

I1HiLim High limit (physical value) 800 A

I1LowLim Low limit (physical value) 0 A

I1LowLowLim Low Low limit (physical value) 0 A

I1Min Minimum value 0 A

I1Max Maximum value 1000 A

I1RepTyp Reporting type Cyclic

I1LimHys Hysteresis value in % of range 5 %


and is common for all limits

Chapter : Monitoring->CurrentSequenceComponents(MSQI)->CMSQI: 1->I1 Angle

I1AngDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

I1AngZeroDb Zero point clamping in 0, 0 m%


001% of range

I1AngMin Minimum value - 180 Deg

I1AngMax Maximum value 180 Deg

I1AngRepTyp Reporting type Cyclic

Chapter : Monitoring->CurrentSequenceComponents(MSQI)->CMSQI: 1->I2 Amplitude

I2DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

I2ZeroDb Zero point clamping in 0, 0 m%


001% of range

I2HiHiLim High High limit (physical value) 900 A

I2HiLim High limit (physical value) 800 A

I2LowLim Low limit (physical value) 0 A

I2LowLowLim Low Low limit (physical value) 0 A

I2Min Minimum value 0 A

Page 38 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
I2Max Maximum value 1000 A

I2RepTyp Reporting type Cyclic

I2LimHys Hysteresis value in % of range 5 %


and is common for all limits

Chapter : Monitoring->CurrentSequenceComponents(MSQI)->CMSQI: 1->I2 Angle

I2AngDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

I2AngZeroDb Zero point clamping in 0, 0 m%


001% of range

I2AngMin Minimum value - 180 Deg

I2AngMax Maximum value 180 Deg

I2AngRepTyp Reporting type Cyclic

Chapter : Monitoring->CurrentSequenceComponents(MSQI)->CMSQI: 2->General

Operation Operation Mode On / Off On

Chapter : Monitoring->CurrentSequenceComponents(MSQI)->CMSQI: 2->3I0 Amplitude

3I0DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

3I0ZeroDb Zero point clamping in 0, 0 m%


001% of range

3I0HiHiLim High High limit (physical value) 900 A

3I0HiLim High limit (physical value) 800 A

3I0LowLim Low limit (physical value) 0 A

3I0LowLowLim Low Low limit (physical value) 0 A

3I0Min Minimum value 0 A

3I0Max Maximum value 1000 A

3I0RepTyp Reporting type Cyclic

3I0LimHys Hysteresis value in % of range 5 %


and is common for all limits

Chapter : Monitoring->CurrentSequenceComponents(MSQI)->CMSQI: 2->3I0 Angle

3I0AngDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

3I0AngZeroDb Zero point clamping in 0, 0 m%


001% of range

3I0AngMin Minimum value - 180 Deg

3I0AngMax Maximum value 180 Deg

3I0AngRepTyp Reporting type Cyclic

Chapter : Monitoring->CurrentSequenceComponents(MSQI)->CMSQI: 2->I1 Amplitude

I1DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

I1ZeroDb Zero point clamping in 0, 0 m%


001% of range

I1HiHiLim High High limit (physical value) 900 A

Page 39 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
I1HiLim High limit (physical value) 800 A

I1LowLim Low limit (physical value) 0 A

I1LowLowLim Low Low limit (physical value) 0 A

I1Min Minimum value 0 A

I1Max Maximum value 1000 A

I1RepTyp Reporting type Cyclic

I1LimHys Hysteresis value in % of range 5 %


and is common for all limits

Chapter : Monitoring->CurrentSequenceComponents(MSQI)->CMSQI: 2->I1 Angle

I1AngDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

I1AngZeroDb Zero point clamping in 0, 0 m%


001% of range

I1AngMin Minimum value - 180 Deg

I1AngMax Maximum value 180 Deg

I1AngRepTyp Reporting type Cyclic

Chapter : Monitoring->CurrentSequenceComponents(MSQI)->CMSQI: 2->I2 Amplitude

I2DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

I2ZeroDb Zero point clamping in 0, 0 m%


001% of range

I2HiHiLim High High limit (physical value) 900 A

I2HiLim High limit (physical value) 800 A

I2LowLim Low limit (physical value) 0 A

I2LowLowLim Low Low limit (physical value) 0 A

I2Min Minimum value 0 A

I2Max Maximum value 1000 A

I2RepTyp Reporting type Cyclic

I2LimHys Hysteresis value in % of range 5 %


and is common for all limits

Chapter : Monitoring->CurrentSequenceComponents(MSQI)->CMSQI: 2->I2 Angle

I2AngDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

I2AngZeroDb Zero point clamping in 0, 0 m%


001% of range

I2AngMin Minimum value - 180 Deg

I2AngMax Maximum value 180 Deg

Page 40 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
I2AngRepTyp Reporting type Cyclic

Chapter : Monitoring->VoltageSequenceComponents(MSQI)->VMSQI: 1->General

Operation Operation Mode On / Off On

Chapter : Monitoring->VoltageSequenceComponents(MSQI)->VMSQI: 1->3U0 Amplitude

3U0DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

3U0ZeroDb Zero point clamping in 0, 0 m%


001% of range

3U0HiHiLim High High limit (physical value) 260000 V

3U0HiLim High limit (physical value) 240000 V

3U0LowLim Low limit (physical value) 220000 V

3U0LowLowLim Low Low limit (physical value) 200000 V

3U0Min Minimum value 0 V

3U0Max Maximum value 300000 V

3U0RepTyp Reporting type Cyclic

3U0LimHys Hysteresis value in % of range 5 %


and is common for all limits

Chapter : Monitoring->VoltageSequenceComponents(MSQI)->VMSQI: 1->3U0 Angle

3U0AngDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

3U0AngZeroDb Zero point clamping in 0, 0 m%


001% of range

3U0AngMin Minimum value - 180 Deg

3U0AngMax Maximum value 180 Deg

3U0AngRepTyp Reporting type Cyclic

Chapter : Monitoring->VoltageSequenceComponents(MSQI)->VMSQI: 1->U1 Amplitude

U1DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

U1ZeroDb Zero point clamping in 0, 0 m%


001% of range

U1HiHiLim High High limit (physical value) 260000 V

U1HiLim High limit (physical value) 240000 V

U1LowLim Low limit (physical value) 220000 V

U1LowLowLim Low Low limit (physical value) 200000 V

U1Min Minimum value 0 V

U1Max Maximum value 300000 V

U1RepTyp Reporting type Cyclic

U1LimHys Hysteresis value in % of range 5 %


and is common for all limits

Chapter : Monitoring->VoltageSequenceComponents(MSQI)->VMSQI: 1->U1 Angle

U1AngDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

Page 41 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
U1AngZeroDb Zero point clamping in 0, 0 m%
001% of range

U1AngMin Minimum value - 180 Deg

U1AngMax Maximum value 180 Deg

U1AngRepTyp Reporting type Cyclic

Chapter : Monitoring->VoltageSequenceComponents(MSQI)->VMSQI: 1->U2 Amplitude

U2DbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

U2ZeroDb Zero point clamping in 0, 0 m%


001% of range

U2HiHiLim High High limit (physical value) 260000 V

U2HiLim High limit (physical value) 240000 V

U2LowLim Low limit (physical value) 220000 V

U2LowLowLim Low Low limit (physical value) 200000 V

U2Min Minimum value 0 V

U2Max Maximum value 300000 V

U2RepTyp Reporting type Cyclic

U2LimHys Hysteresis value in % of range 5 %


and is common for all limits

Chapter : Monitoring->VoltageSequenceComponents(MSQI)->VMSQI: 1->U2 Angle

U2AngDbRepInt Cycl: Report interval (s), Db: 10 Type


In % of range, Int Db: In %s

U2AngZeroDb Zero point clamping in 0, 0 m%


001% of range

U2AngMin Minimum value - 180 Deg

U2AngMax Maximum value 180 Deg

U2AngRepTyp Reporting type Cyclic

Chapter : Monitoring->DisturbanceReport->AnalogSignals(RADR)->A1RADR: 1

NAME1 User define string for analogue W1 CT1 IL1 13 characters


input 1

Operation01 Operation On/ Off On

NomValue01 Nominal value for analogue 400


channel 1

UnderTrigOp01 Use under level trig for Off


analogue cha 1 (on) or not
(off)

UnderTrigLe01 Under trigger level for 50 %


analogue cha 1 in % of signal

OverTrigOp01 Use over level trig for Off


analogue cha 1 (on) or not
(off)

OverTrigLe01 Over trigger level for analogue 200 %


cha 1 in % of signal

NAME2 User define string for analogue W1 CT1 IL2 13 characters


input 2

Page 42 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
Operation02 Operation On/ Off On

NomValue02 Nominal value for analogue 400


channel 2

UnderTrigOp02 Use under level trig for Off


analogue cha 2 (on) or not
(off)

UnderTrigLe02 Under trigger level for 50 %


analogue cha 2 in % of signal

OverTrigOp02 Use over level trig for Off


analogue cha 2 (on) or not
(off)

OverTrigLe02 Over trigger level for analogue 200 %


cha 2 in % of signal

NAME3 User define string for analogue W1 CT1 IL3 13 characters


input 3

Operation03 Operation On/ Off On

NomValue03 Nominal value for analogue 400


channel 3

UnderTrigOp03 Use under level trig for Off


analogue cha 3 (on) or not
(off)

UnderTrigLe03 Under trigger level for 50 %


analogue cha 3 in % of signal

OverTrigOp03 Use over level trig for Off


analogue cha 3 (on) or not
(off)

OverTrigLe03 Overtrigger level for analogue 200 %


cha 3 in % of signal

NAME4 User define string for analogue W1 CT1 IN 13 characters


input 4

Operation04 Operation On/ Off On

NomValue04 Nominal value for analogue 400


channel 4

UnderTrigOp04 Use under level trig for Off


analogue cha 4 (on) or not
(off)

UnderTrigLe04 Under trigger level for 50 %


analogue cha 4 in % of signal

OverTrigOp04 Use over level trig for Off


analogue cha 4 (on) or not
(off)

OverTrigLe04 Over trigger level for analogue 200 %


cha 4 in % of signal

NAME5 User define string for analogue W1 CT NEUT 13 characters


input 5

Operation05 Operation On/ Off Off

NomValue05 Nominal value for analogue 0


channel 5

UnderTrigOp05 Use under level trig for Off


analogue cha 5 (on) or not

Page 43 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
(off)

UnderTrigLe05 Under trigger level for 50 %


analogue cha 5 in % of signal

OverTrigOp05 Use over level trig for Off


analogue cha 5 (on) or not
(off)

OverTrigLe05 Over trigger level for analogue 200 %


cha 5 in % of signal

NAME6 User define string for analogue Not used 13 characters


input 6

Operation06 Operation On/ Off Off

NomValue06 Nominal value for analogue 0


channel 6

UnderTrigOp06 Use under level trig for Off


analogue cha 6 (on) or not
(off)

UnderTrigLe06 Under trigger level for 50 %


analogue cha 6 in % of signal

OverTrigOp06 Use over level trig for Off


analogue cha 6 (on) or not
(off)

OverTrigLe06 Over trigger level for analogue 200 %


cha 6 in % of signal

NAME7 User define string for analogue Not used 13 characters


input 7

Operation07 Operation On/ Off Off

NomValue07 Nominal value for analogue 0


channel 7

UnderTrigOp07 Use under level trig for Off


analogue cha 7 (on) or not
(off)

UnderTrigLe07 Under trigger level for 50 %


analogue cha 7 in % of signal

OverTrigOp07 Use over level trig for Off


analogue cha 7 (on) or not
(off)

OverTrigLe07 Over trigger level for analogue 200 %


cha 7 in % of signal

NAME8 User define string for analogue Not used 13 characters


input 8

Operation08 Operation On/ Off Off

NomValue08 Nominal value for analogue 0


channel 8

UnderTrigOp08 Use under level trig for Off


analogue cha 8 (on) or not
(off)

UnderTrigLe08 Under trigger level for 50 %


analogue cha 8 in % of signal

OverTrigOp08 Use over level trig for Off


analogue cha 8 (on) or not

Page 44 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
(off)

OverTrigLe08 Over trigger level for analogue 200 %


cha 8 in % of signal

NAME9 User define string for analogue Not used 13 characters


input 9

Operation09 Operation On/ Off Off

NomValue09 Nominal value for analogue 0


channel 9

UnderTrigOp09 Use under level trig for Off


analogue cha 9 (on) or not
(off)

UnderTrigLe09 Under trigger level for 50 %


analogue cha 9 in % of signal

OverTrigOp09 Use over level trig for Off


analogue cha 9 (on) or not
(off)

OverTrigLe09 Over trigger level for analogue 200 %


cha 9 in % of signal

NAME10 User define string for analogue Not used 13 characters


input 10

Operation10 Operation On/ Off Off

NomValue10 Nominal value for analogue 0


channel 10

UnderTrigOp10 Use under level trig for Off


analogue cha 10 (on) or not
(off)

UnderTrigLe10 Under trigger level for 50 %


analogue cha 10 in % of signal

OverTrigOp10 Use over level trig for Off


analogue cha 10 (on) or not
(off)

OverTrigLe10 Over trigger level for analogue 200 %


cha 10 in % of signal

Chapter : Monitoring->DisturbanceReport->AnalogSignals(RADR)->A2RADR: 2

NAME11 User define string for analogue Not used 13 characters


input 11

Operation11 Operation On/ off Off

NomValue11 Nominal value for analogue 0


channel 11

UnderTrigOp11 Use under level trig for Off


analogue cha 11 (on) or not
(off)

UnderTrigLe11 Under trigger level for 50 %


analogue cha 11 in % of signal

OverTrigOp11 Use over level trig for Off


analogue cha 11 (on) or not
(off)

OverTrigLe11 Over trigger level for analogue 200 %


cha 11 in % of signal

Page 45 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
NAME12 User define string for analogue WN CT NEUT 13 characters
input 12

Operation12 Operation On/ off On

NomValue12 Nominal value for analogue 800


channel 12

UnderTrigOp12 Use under level trig for Off


analogue cha 12 (on) or not
(off)

UnderTrigLe12 Under trigger level for 50 %


analogue cha 12 in % of signal

OverTrigOp12 Use over level trig for Off


analogue cha 12 (on) or not
(off)

OverTrigLe12 Over trigger level for analogue 200 %


cha 12 in % of signal

NAME13 User define string for analogue W2 CT IL1 13 characters


input 13

Operation13 Operation On/ off On

NomValue13 Nominal value for analogue 400


channel 13

UnderTrigOp13 Use under level trig for Off


analogue cha 13 (on) or not
(off)

UnderTrigLe13 Under trigger level for 50 %


analogue cha 13 in % of signal

OverTrigOp13 Use over level trig for Off


analogue cha 13 (on) or not
(off)

OverTrigLe13 Overtrigger level for analogue 200 %


cha 13 in % of signal

NAME14 User define string for analogue W2 CT IL2 13 characters


input 14

Operation14 Operation On/ off On

NomValue14 Nominal value for analogue 400


channel 14

UnderTrigOp14 Use under level trig for Off


analogue cha 14 (on) or not
(off)

UnderTrigLe14 Under trigger level for 50 %


analogue cha 14 in % of signal

OverTrigOp14 Use over level trig for Off


analogue cha 14 (on) or not
(off)

OverTrigLe14 Over trigger level for analogue 200 %


cha 14 in % of signal

NAME15 User define string for analogue W2 CT IL3 13 characters


input 15

Operation15 Operation On/ off On

NomValue15 Nominal value for analogue 400


channel 15

Page 46 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
UnderTrigOp15 Use under level trig for Off
analogue cha 15 (on) or not
(off)

UnderTrigLe15 Under trigger level for 50 %


analogue cha 15 in % of signal

OverTrigOp15 Use over level trig for Off


analogue cha 15 (on) or not
(off)

OverTrigLe15 Over trigger level for analogue 200 %


cha 15 in % of signal

NAME16 User define string for analogue W2 CT IN 13 characters


input 16

Operation16 Operation On/ off Off

NomValue16 Nominal value for analogue 800


channel 16

UnderTrigOp16 Use under level trig for Off


analogue cha 16 (on) or not
(off)

UnderTrigLe16 Under trigger level for 50 %


analogue cha 16 in % of signal

OverTrigOp16 Use over level trig for Off


analogue cha 16 (on) or not
(off)

OverTrigLe16 Over trigger level for analogue 200 %


cha 16 in % of signal

NAME17 User define string for analogue W2 CT NEUT 13 characters


input 17

Operation17 Operation On/ off On

NomValue17 Nominal value for analogue 400


channel 17

UnderTrigOp17 Use under level trig for Off


analogue cha 17 (on) or not
(off)

UnderTrigLe17 Under trigger level for 50 %


analogue cha 17 in % of signal

OverTrigOp17 Use over level trig for Off


analogue cha 17 (on) or not
(off)

OverTrigLe17 Over trigger level for analogue 200 %


cha 17 in % of signal

NAME18 User define string for analogue W1 VT UL1 13 characters


input 18

Operation18 Operation On/ off On

NomValue18 Nominal value for analogue 288. 7


channel 18

UnderTrigOp18 Use under level trig for Off


analogue cha 18 (on) or not
(off)

UnderTrigLe18 Under trigger level for 50 %


analogue cha 18 in % of signal

Page 47 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
OverTrigOp18 Use over level trig for Off
analogue cha 18 (on) or not
(off)

OverTrigLe18 Over trigger level for analogue 200 %


cha 18 in % of signal

NAME19 User define string for analogue W1 VT UL2 13 characters


input 19

Operation19 Operation On/ off On

NomValue19 Nominal value for analogue 288. 7


channel 19

UnderTrigOp19 Use under level trig for Off


analogue cha 19 (on) or not
(off)

UnderTrigLe19 Under trigger level for 50 %


analogue cha 19 in % of signal

OverTrigOp19 Use over level trig for Off


analogue cha 19 (on) or not
(off)

OverTrigLe19 Over trigger level for analogue 200 %


cha 19 in % of signal

NAME20 User define string for analogue W1 VT UL3 13 characters


input 20

Operation20 Operation On/ off On

NomValue20 Nominal value for analogue 288. 7


channel 20

UnderTrigOp20 Use under level trig for Off


analogue cha 20 (on) or not
(off)

UnderTrigLe20 Under trigger level for 50 %


analogue cha 20 in % of signal

OverTrigOp20 Use over level trig for Off


analogue cha 20 (on) or not
(off)

OverTrigLe20 Over trigger level for analogue 200 %


cha 20 in % of signal

Chapter : Monitoring->DisturbanceReport->AnalogSignals(RADR)->A3RADR: 3

NAME21 User define string for analogue W1 VT UN 13 characters


input 21

Operation21 Operation On/ off Off

NomValue21 Nominal value for analogue 127


channel 21

UnderTrigOp21 Use under level trig for Off


analogue cha 21 (on) or not
(off)

UnderTrigLe21 Under trigger level for 50 %


analogue cha 21 in % of signal

OverTrigOp21 Use over level trig for Off


analogue cha 21 (on) or not
(off)

OverTrigLe21 Over trigger level for analogue 200 %

Page 48 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
cha 21 in % of signal

NAME22 User define string for analogue W1 UN VT UL1 13 characters


input 22

Operation22 Operation On/ off Off

NomValue22 Nominal value for analogue 0


channel 22

UnderTrigOp22 Use under level trig for Off


analogue cha 22 (on) or not
(off)

UnderTrigLe22 Under trigger level for 50 %


analogue cha 22 in % of signal

OverTrigOp22 Use over level trig for Off


analogue cha 22 (on) or not
(off)

OverTrigLe22 Over trigger level for analogue 200 %


cha 22 in % of signal

NAME23 User define string for analogue W1 UN VT UL2 13 characters


input 23

Operation23 Operation On/ off Off

NomValue23 Nominal value for analogue 0


channel 23

UnderTrigOp23 Use under level trig for Off


analogue cha 23 (on) or not
(off)

UnderTrigLe23 Under trigger level for 50 %


analogue cha 23 in % of signal

OverTrigOp23 Use over level trig for Off


analogue cha 23 (on) or not
(off)

OverTrigLe23 Overtrigger level for analogue 200 %


cha 23 in % of signal

NAME24 User define string for analogue W1 UN VT UL3 13 characters


input 24

Operation24 Operation On/ off Off

NomValue24 Nominal value for analogue 0


channel 24

UnderTrigOp24 Use under level trig for Off


analogue cha 24 (on) or not
(off)

UnderTrigLe24 Under trigger level for 50 %


analogue cha 24 in % of signal

OverTrigOp24 Use over level trig for Off


analogue cha 24 (on) or not
(off)

OverTrigLe24 Over trigger level for analogue 200 %


cha 24 in % of signal

NAME25 User define string for analogue W1 UN VT UN 13 characters


input 25

Operation25 Operation On/ off Off

Page 49 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
NomValue25 Nominal value for analogue 0
channel 25

UnderTrigOp25 Use under level trig for Off


analogue cha 25 (on) or not
(off)

UnderTrigLe25 Under trigger level for 50 %


analogue cha 25 in % of signal

OverTrigOp25 Use over level trig for Off


analogue cha 25 (on) or not
(off)

OverTrigLe25 Over trigger level for analogue 200 %


cha 25 in % of signal

NAME26 User define string for analogue Not used 13 characters


input 26

Operation26 Operation On/ off Off

NomValue26 Nominal value for analogue 0


channel 26

UnderTrigOp26 Use under level trig for Off


analogue cha 26 (on) or not
(off)

UnderTrigLe26 Under trigger level for 50 %


analogue cha 26 in % of signal

OverTrigOp26 Use over level trig for Off


analogue cha 26 (on) or not
(off)

OverTrigLe26 Over trigger level for analogue 200 %


cha 26 in % of signal

NAME27 User define string for analogue Not used 13 characters


input 27

Operation27 Operation On/ off Off

NomValue27 Nominal value for analogue 0


channel 27

UnderTrigOp27 Use under level trig for Off


analogue cha 27 (on) or not
(off)

UnderTrigLe27 Under trigger level for 50 %


analogue cha 27 in % of signal

OverTrigOp27 Use over level trig for Off


analogue cha 27 (on) or not
(off)

OverTrigLe27 Over trigger level for analogue 200 %


cha 27 in % of signal

NAME28 User define string for analogue Not used 13 characters


input 28

Operation28 Operation On/ off Off

NomValue28 Nominal value for analogue 0


channel 28

UnderTrigOp28 Use under level trig for Off


analogue cha 28 (on) or not
(off)

Page 50 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
UnderTrigLe28 Under trigger level for 50 %
analogue cha 28 in % of signal

OverTrigOp28 Use over level trig for Off


analogue cha 28 (on) or not
(off)

OverTrigLe28 Over trigger level for analogue 200 %


cha 28 in % of signal

NAME29 User define string for analogue Not used 13 characters


input 29

Operation29 Operation On/ off Off

NomValue29 Nominal value for analogue 0


channel 29

UnderTrigOp29 Use under level trig for Off


analogue cha 29 (on) or not
(off)

UnderTrigLe29 Under trigger level for 50 %


analogue cha 29 in % of signal

OverTrigOp29 Use over level trig for Off


analogue cha 29 (on) or not
(off)

OverTrigLe29 Over trigger level for analogue 200 %


cha 29 in % of signal

NAME30 User define string for analogue Not used 13 characters


input 30

Operation30 Operation On/ off Off

NomValue30 Nominal value for analogue 0


channel 30

UnderTrigOp30 Use under level trig for Off


analogue cha 30 (on) or not
(off)

UnderTrigLe30 Under trigger level for 50 %


analogue cha 30 in % of signal

OverTrigOp30 Use over level trig for Off


analogue cha 30 (on) or not
(off)

OverTrigLe30 Over trigger level for analogue 200 %


cha 30 in % of signal

Chapter : Monitoring->DisturbanceReport->AnalogSignals(RADR)->A4RADR: 4

NAME31 User define string for analogue DIFF IDNS MAG 13 characters
input 31

Operation31 Operation On/ off On

NomValue31 Nominal value for analogue 400


channel 31

UnderTrigOp31 Use under level trig for Off


analogue cha 31 (on) or not
(off)

UnderTrigLe31 Under trigger level for 50 %


analogue cha 31 in % of signal

OverTrigOp31 Use over level trig for Off


analogue cha 31 (on) or not

Page 51 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
(off)

OverTrigLe31 Over trigger level for analogue 200 %


cha 31 in % of signal

NAME32 User define string for analogue DIFF IDL1 MAG 13 characters
input 32

Operation32 Operation On/ off On

NomValue32 Nominal value for analogue 400


channel 32

UnderTrigOp32 Use under level trig for Off


analogue cha 32 (on) or not
(off)

UnderTrigLe32 Under trigger level for 50 %


analogue cha 32 in % of signal

OverTrigOp32 Use over level trig for Off


analogue cha 32 (on) or not
(off)

OverTrigLe32 Over trigger level for analogue 200 %


cha 32 in % of signal

NAME33 User define string for analogue DIFF IDL2 MAG 13 characters
input 33

Operation33 Operation On/ off On

NomValue33 Nominal value for analogue 400


channel 33

UnderTrigOp33 Use under level trig for Off


analogue cha 33 (on) or not
(off)

UnderTrigLe33 Under trigger level for 50 %


analogue cha 33 in % of signal

OverTrigOp33 Use over level trig for Off


analogue cha 33 (on) or not
(off)

OverTrigLe33 Overtrigger level for analogue 200 %


cha 33 in % of signal

NAME34 User define string for analogue DIFF IDL3 MAG 13 characters
input 34

Operation34 Operation On/ off On

NomValue34 Nominal value for analogue 400


channel 34

UnderTrigOp34 Use under level trig for Off


analogue cha 34 (on) or not
(off)

UnderTrigLe34 Under trigger level for 50 %


analogue cha 34 in % of signal

OverTrigOp34 Use over level trig for Off


analogue cha 34 (on) or not
(off)

OverTrigLe34 Over trigger level for analogue 200 %


cha 34 in % of signal

NAME35 User define string for analogue DIFF IBIAS 13 characters


input 35

Page 52 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
Operation35 Operation On/ off On

NomValue35 Nominal value for analogue 400


channel 35

UnderTrigOp35 Use under level trig for Off


analogue cha 35 (on) or not
(off)

UnderTrigLe35 Under trigger level for 50 %


analogue cha 35 in % of signal

OverTrigOp35 Use over level trig for Off


analogue cha 35 (on) or not
(off)

OverTrigLe35 Over trigger level for analogue 200 %


cha 35 in % of signal

NAME36 User define string for analogue REF1 IBIAS 13 characters


input 36

Operation36 Operation On/ off On

NomValue36 Nominal value for analogue 0


channel 36

UnderTrigOp36 Use under level trig for Off


analogue cha 36 (on) or not
(off)

UnderTrigLe36 Under trigger level for 50 %


analogue cha 36 in % of signal

OverTrigOp36 Use over level trig for Off


analogue cha 36 (on) or not
(off)

OverTrigLe36 Over trigger level for analogue 200 %


cha 36 in % of signal

NAME37 User define string for analogue REF1 IDIFF 13 characters


input 37

Operation37 Operation On/ off On

NomValue37 Nominal value for analogue 0


channel 37

UnderTrigOp37 Use under level trig for Off


analogue cha 37 (on) or not
(off)

UnderTrigLe37 Under trigger level for 50 %


analogue cha 37 in % of signal

OverTrigOp37 Use over level trig for Off


analogue cha 37 (on) or not
(off)

OverTrigLe37 Over trigger level for analogue 200 %


cha 37 in % of signal

NAME38 User define string for analogue Not used 13 characters


input 38

Operation38 Operation On/ off Off

NomValue38 Nominal value for analogue 0


channel 38

UnderTrigOp38 Use under level trig for Off


analogue cha 38 (on) or not

Page 53 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
(off)

UnderTrigLe38 Under trigger level for 50 %


analogue cha 38 in % of signal

OverTrigOp38 Use over level trig for Off


analogue cha 38 (on) or not
(off)

OverTrigLe38 Over trigger level for analogue 200 %


cha 38 in % of signal

NAME39 User define string for analogue Not used 13 characters


input 39

Operation39 Operation On/ off Off

NomValue39 Nominal value for analogue 0


channel 39

UnderTrigOp39 Use under level trig for Off


analogue cha 39 (on) or not
(off)

UnderTrigLe39 Under trigger level for 50 %


analogue cha 39 in % of signal

OverTrigOp39 Use over level trig for Off


analogue cha 39 (on) or not
(off)

OverTrigLe39 Over trigger level for analogue 200 %


cha 39 in % of signal

NAME40 User define string for analogue Not used 13 characters


input 40

Operation40 Operation On/ off Off

NomValue40 Nominal value for analogue 0


channel 40

UnderTrigOp40 Use under level trig for Off


analogue cha 40 (on) or not
(off)

UnderTrigLe40 Under trigger level for 50 %


analogue cha 40 in % of signal

OverTrigOp40 Use over level trig for Off


analogue cha 40 (on) or not
(off)

OverTrigLe40 Over trigger level for analogue 200 %


cha 40 in % of signal

Chapter : Monitoring->DisturbanceReport->BinarySignals(RBDR)->B1RBDR: 1->Binary Signals Ch 1-16

NAME1 User define string for binary DIFF TRIP 13 characters


input 1

Operation01 Trigger operation On/ Off On

TrigLevel01 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 1

IndicationMa01 Indication mask for binary Show


channel 1

SetLED01 Set red- LED on HMI for On


binary channel 1

NAME2 User define string for binary DIFF TRIP RES 13 characters

Page 54 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
input 2

Operation02 Trigger operation On/ Off On

TrigLevel02 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 2

IndicationMa02 Indication mask for binary Show


channel 2

SetLED02 Set red- LED on HMI for On


binary channel 2

NAME3 User define string for binary DIF TRP UNRES 13 characters
input 3

Operation03 Trigger operation On/ Off On

TrigLevel03 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 3

IndicationMa03 Indication mask for binary Hide


channel 3

SetLED03 Set red- LED on HMI for On


binary channel 3

NAME4 User define string for binary TRIP NS UNRES 13 characters


input 4

Operation04 Trigger operation On/ Off On

TrigLevel04 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 4

IndicationMa04 Indication mask for binary Hide


channel 4

SetLED04 Set red- LED on HMI for On


binary channel 4

NAME5 User define string for binary TRIP NS SENS 13 characters


input 5

Operation05 Trigger operation On/ Off On

TrigLevel05 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 5

IndicationMa05 Indication mask for binary Hide


channel 5

SetLED05 Set red- LED on HMI for On


binary channel 5

NAME6 User define string for binary DIFF STL1 13 characters


input 6

Operation06 Trigger operation On/ Off Off

TrigLevel06 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 6

IndicationMa06 Indication mask for binary Hide


channel 6

SetLED06 Set red- LED on HMI for Off


binary channel 6

NAME7 User define string for binary DIFF STL2 13 characters


input 7

Operation07 Trigger operation On/ Off Off

Page 55 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
TrigLevel07 Trig on positiv (1) or negative Trig on 0
(0) slope for binary inp 7

IndicationMa07 Indication mask for binary Hide


channel 7

SetLED07 Set red- LED on HMI for Off


binary channel 7

NAME8 User define string for binary DIFF STL3 13 characters


input 8

Operation08 Trigger operation On/ Off Off

TrigLevel08 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 8

IndicationMa08 Indication mask for binary Hide


channel 8

SetLED08 Set red- LED on HMI for Off


binary channel 8

NAME9 User define string for binary DIF I2BLCK L1 13 characters


input 9

Operation09 Trigger operation On/ Off Off

TrigLevel09 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 9

IndicationMa09 Indication mask for binary Hide


channel 9

SetLED09 Set red- LED on HMI for Off


binary channel 9

NAME10 User define string for binary DIF I2BLCK L2 13 characters


input 10

Operation10 Trigger operation On/ Off Off

TrigLevel10 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 10

IndicationMa10 Indication mask for binary Hide


channel 10

SetLED10 Set red- LED on HMI for Off


binary channel 10

NAME11 User define string for binary DIF I2BLCK L3 13 characters


input 11

Operation11 Trigger operation On/ Off Off

TrigLevel11 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 11

IndicationMa11 Indication mask for binary Hide


channel 11

SetLED11 Set red- LED on HMI for Off


binary channel 11

NAME12 User define string for binary DIF I5BLCK L1 13 characters


input 12

Operation12 Trigger operation On/ Off Off

TrigLevel12 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 12

Page 56 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
IndicationMa12 Indication mask for binary Hide
channel 12

SetLED12 Set red- LED on HMI for Off


binary input 12

NAME13 User define string for binary DIF I5BLCK L2 13 characters


input 13

Operation13 Trigger operation On/ Off Off

TrigLevel13 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 13

IndicationMa13 Indication mask for binary Hide


channel 13

SetLED13 Set red- LED on HMI for Off


binary channel 13

NAME14 User define string for binary DIF I5BLCK L3 13 characters


input 14

Operation14 Trigger operation On/ Off Off

TrigLevel14 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 14

IndicationMa14 Indication mask for binary Hide


channel 14

SetLED14 Set red- LED on HMI for Off


binary channel 14

NAME15 User define string for binary IDIFF ALARM 13 characters


input 15

Operation15 Trigger operation On/ Off Off

TrigLevel15 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 15

IndicationMa15 Indication mask for binary Hide


channel 15

SetLED15 Set red- LED on HMI for Off


binary channel 15

NAME16 User define string for binary OPEN CT ALARM 13 characters


input 16

Operation16 Trigger operation On/ Off Off

TrigLevel16 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 16

IndicationMa16 Indication mask for binary Hide


channel 16

SetLED16 Set red- LED on HMI for Off


binary channel 16

Chapter : Monitoring->DisturbanceReport->BinarySignals(RBDR)->B1RBDR: 1->IEC60870-5-103, Ch 1-16

FUNT1 Function type for binary 0 FunT


channel 1 (IEC - 60870- 5-
103)

FUNT2 Function type for binary 0 FunT


channel 2 (IEC - 60870- 5-
103)

FUNT3 Function type for binary 0 FunT

Page 57 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
channel 3 (IEC - 60870- 5-
103)

FUNT4 Function type for binary 0 FunT


channel 4 (IEC - 60870- 5-
103)

FUNT5 Function type for binary 0 FunT


channel 5 (IEC - 60870- 5-
103)

FUNT6 Function type for binary 0 FunT


channel 6 (IEC - 60870- 5-
103)

FUNT7 Function type for binary 0 FunT


channel 7 (IEC - 60870- 5-
103)

FUNT8 Function type for binary 0 FunT


channel 8 (IEC - 60870- 5-
103)

FUNT9 Function type for binary 0 FunT


channel 9 (IEC - 60870- 5-
103)

FUNT10 Function type for binary 0 FunT


channel 10 (IEC - 60870- 5-
103)

FUNT11 Function type for binary 0 FunT


channel 11 (IEC - 60870- 5-
103)

FUNT12 Function type for binary 0 FunT


channel 12 (IEC - 60870- 5-
103)

FUNT13 Function type for binary 0 FunT


channel 13 (IEC - 60870- 5-
103)

FUNT14 Function type for binary 0 FunT


channel 14 (IEC - 60870- 5-
103)

FUNT15 Function type for binary 0 FunT


channel 15 (IEC - 60870- 5-
103)

FUNT16 Function type for binary 0 FunT


channel 16 (IEC - 60870- 5-
103)

INFNO1 Information number for binary 0 InfNo


channel 1 (IEC - 60870- 5-
103)

INFNO2 Information number for binary 0 InfNo


channel 2 (IEC - 60870- 5-
103)

INFNO3 Information number for binary 0 InfNo


channel 3 (IEC - 60870- 5-
103)

INFNO4 Information number for binary 0 InfNo


channel 4 (IEC - 60870- 5-
103)

INFNO5 Information number for binary 0 InfNo

Page 58 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
channel 5 (IEC - 60870- 5-
103)

INFNO6 Information number for binary 0 InfNo


channel 6 (IEC - 60870- 5-
103)

INFNO7 Information number for binary 0 InfNo


channel 7 (IEC - 60870- 5-
103)

INFNO8 Information number for binary 0 InfNo


channel 8 (IEC - 60870- 5-
103)

INFNO9 Information number for binary 0 InfNo


channel 9 (IEC - 60870- 5-
103)

INFNO10 Information number for binary 0 InfNo


channel 10 (IEC - 60870- 5-
103)

INFNO11 Information number for binary 0 InfNo


channel 11 (IEC - 60870- 5-
103)

INFNO12 Information number for binary 0 InfNo


channel 12 (IEC - 60870- 5-
103)

INFNO13 Information number for binary 0 InfNo


channel 13 (IEC - 60870- 5-
103)

INFNO14 Information number for binary 0 InfNo


channel 14 (IEC - 60870- 5-
103)

INFNO15 Information number for binary 0 InfNo


channel 15 (IEC - 60870- 5-
103)

INFNO16 Information number for binary 0 InfNo


channel 16 (IEC - 60870- 5-
103)

Chapter : Monitoring->DisturbanceReport->BinarySignals(RBDR)->B2RBDR: 2->Binary Signals, Ch 17-32

NAME17 User define string for binary DIF BLCKWAVL1 13 characters


input 17

Operation17 Trigger operation On/ Off Off

TrigLevel17 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 17

IndicationMa17 Indication mask for binary Hide


channel 17

SetLED17 Set red- LED on HMI for Off


binary channel 17

NAME18 User define string for binary DIF BLCKWAVL2 13 characters


input 18

Operation18 Trigger operation On/ Off Off

TrigLevel18 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 18

IndicationMa18 Indication mask for binary Hide

Page 59 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
channel 18

SetLED18 Set red- LED on HMI for Off


binary channel 18

NAME19 User define string for binary DIF BLCKWAVL3 13 characters


input 19

Operation19 Trigger operation On/ Off Off

TrigLevel19 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 19

IndicationMa19 Indication mask for binary Hide


channel 19

SetLED19 Set red- LED on HMI for Off


binary channel 19

NAME20 User define string for binary W1 CB TRIP 13 characters


input 20

Operation20 Trigger operation On/ Off On

TrigLevel20 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 20

IndicationMa20 Indication mask for binary Show


channel 20

SetLED20 Set red- LED on HMI for On


binary channel 20

NAME21 User define string for binary W1 CB TRBU 13 characters


input 21

Operation21 Trigger operation On/ Off On

TrigLevel21 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 21

IndicationMa21 Indication mask for binary Show


channel 21

SetLED21 Set red- LED on HMI for On


binary channel 21

NAME22 User define string for binary W1 CB RETRIP 13 characters


input 22

Operation22 Trigger operation On/ Off On

TrigLevel22 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 22

IndicationMa22 Indication mask for binary Hide


channel 22

SetLED22 Set red- LED on HMI for Off


binary channel 22

NAME23 User define string for binary W1 CB PD TRP 13 characters


input 23

Operation23 Trigger operation On/ Off Off

TrigLevel23 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 23

IndicationMa23 Indication mask for binary Hide


channel 23

SetLED23 Set red- LED on HMI for Off

Page 60 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
binary channel 23

NAME24 User define string for binary EXTTRIP_ W1CB 13 characters


input 24

Operation24 Trigger operation On/ Off Off

TrigLevel24 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 24

IndicationMa24 Indication mask for binary Hide


channel 24

SetLED24 Set red- LED on HMI for Off


binary channel 24

NAME25 User define string for binary EXT 50BF STAR 13 characters
input 25

Operation25 Trigger operation On/ Off Off

TrigLevel25 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 25

IndicationMa25 Indication mask for binary Hide


channel 25

SetLED25 Set red- LED on HMI for Off


binary channel 25

NAME26 User define string for binary DRB02- INPUT26 13 characters


input 26

Operation26 Trigger operation On/ Off Off

TrigLevel26 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 26

IndicationMa26 Indication mask for binary Hide


channel 26

SetLED26 Set red- LED on HMI for Off


binary channel 26

NAME27 User define string for binary W1 CB CLOSED 13 characters


input 27

Operation27 Trigger operation On/ Off Off

TrigLevel27 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 27

IndicationMa27 Indication mask for binary Hide


channel 27

SetLED27 Set red- LED on HMI for Off


binary channel 27

NAME28 User define string for binary W1 CB SPRING 13 characters


input 28

Operation28 Trigger operation On/ Off Off

TrigLevel28 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 28

IndicationMa28 Indication mask for binary Hide


channel 28

SetLED28 Set red- LED on HMI for Off


binary input 28

NAME29 User define string for binary W1 IOC TRIP 13 characters

Page 61 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
input 29

Operation29 Trigger operation On/ Off On

TrigLevel29 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 29

IndicationMa29 Indication mask for binary Show


channel 29

SetLED29 Set red- LED on HMI for On


binary channel 29

NAME30 User define string for binary W1 TOC TRIP 13 characters


input 30

Operation30 Trigger operation On/ Off On

TrigLevel30 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 30

IndicationMa30 Indication mask for binary Show


channel 30

SetLED30 Set red- LED on HMI for On


binary channel 30

NAME31 User define string for binary W1 TOC ST L1 13 characters


input 31

Operation31 Trigger operation On/ Off Off

TrigLevel31 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 31

IndicationMa31 Indication mask for binary Hide


channel 31

SetLED31 Set red- LED on HMI for Off


binary channel 31

NAME32 User define string for binary W1 TOC ST L2 13 characters


input 32

Operation32 Trigger operation On/ Off Off

TrigLevel32 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 32

IndicationMa32 Indication mask for binary Hide


channel 32

SetLED32 Set red- LED on HMI for Off


binary channel 32

Chapter : Monitoring->DisturbanceReport->BinarySignals(RBDR)->B2RBDR: 2->IEC60870-5-103, Ch 17-32

FUNCT17 Function type for binary 0 FunT


channel 17 (IEC- 60870- 5-
103)

FUNCT18 Function type for binary 0 FunT


channel 18 (IEC- 60870- 5-
103)

FUNCT19 Function type for binary 0 FunT


channel 19 (IEC- 60870- 5-
103)

FUNCT20 Function type for binary 0 FunT


channel 20 (IEC- 60870- 5-
103)

Page 62 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
FUNCT21 Function type for binary 0 FunT
channel 21 (IEC- 60870- 5-
103)

FUNCT22 Function type for binary 0 FunT


channel 22 (IEC- 60870- 5-
103)

FUNCT23 Function type for binary 0 FunT


channel 23 (IEC- 60870- 5-
103)

FUNCT24 Function type for binary 0 FunT


channel 24 (IEC- 60870- 5-
103)

FUNCT25 Function type for binary 0 FunT


channel 25 (IEC- 60870- 5-
103)

FUNCT26 Function type for binary 0 FunT


channel 26 (IEC - 60870- 5-
103)

FUNCT27 Function type for binary 0 FunT


channel 27 (IEC- 60870- 5-
103)

FUNCT28 Function type for binary 0 FunT


channel 28 (IEC- 60870- 5-
103)

FUNCT29 Function type for binary 0 FunT


channel 29 (IEC- 60870- 5-
103)

FUNCT30 Function type for binary 0 FunT


channel 30 (IEC- 60870- 5-
103)

FUNCT31 Function type for binary 0 FunT


channel 31 (IEC- 60870- 5-
103)

FUNCT32 Function type for binary 0 FunT


channel 32 (IEC- 60870- 5-
103)

INFONO17 Information number for binary 0 InfNo


channel 17 (IEC- 60870- 5-
103)

INFONO18 Information number for binary 0 InfNo


channel 18 (IEC- 60870- 5-
103)

INFONO19 Information number for binary 0 InfNo


channel 19 (IEC- 60870- 5-
103)

INFONO20 Information number for binary 0 InfNo


channel 20 (IEC- 60870- 5-
103)

INFONO21 Information number for binary 0 InfNo


channel 21 (IEC- 60870- 5-
103)

INFONO22 Information number for binary 0 InfNo


channel 22 (IEC- 60870- 5-
103)

Page 63 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
INFONO23 Information number for binary 0 InfNo
channel 23 (IEC- 60870- 5-
103)

INFONO24 Information number for binary 0 InfNo


channel 24 (IEC- 60870- 5-
103)

INFONO25 Information number for binary 0 InfNo


channel 25 (IEC- 60870- 5-
103)

INFONO26 Information number for binary 0 InfNo


channel 26 (IEC - 60870- 5-
103)

INFONO27 Information number for binary 0 InfNo


channel 27 (IEC- 60870- 5-
103)

INFONO28 Information number for binary 0 InfNo


channel 28 (IEC- 60870- 5-
103)

INFONO29 Information number for binary 0 InfNo


channel 29 (IEC- 60870- 5-
103)

INFONO30 Information number for binary 0 InfNo


channel 30 (IEC- 60870- 5-
103)

INFONO31 Information number for binary 0 InfNo


channel 31 (IEC- 60870- 5-
103)

INFONO32 Information number for binary 0 InfNo


channel 32 (IEC- 60870- 5-
103)

Chapter : Monitoring->DisturbanceReport->BinarySignals(RBDR)->B3RBDR: 3->Binary Signals, Ch 33-48

NAME33 User define string for binary W1 TOC ST L3 13 characters


input 33

Operation33 Trigger operation On/ Off Off

TrigLevel33 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 33

IndicationMa33 Indication mask for binary Hide


channel 33

SetLED33 Set red- LED on HMI for Off


binary channel 33

NAME34 User define string for binary W1 IEF TRIP 13 characters


input 34

Operation34 Trigger operation On/ Off On

TrigLevel34 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 34

IndicationMa34 Indication mask for binary Show


channel 34

SetLED34 Set red- LED on HMI for On


binary channel 34

NAME35 User define string for binary W1 REF TRIP 13 characters


input 35

Page 64 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
Operation35 Trigger operation On/ Off Off

TrigLevel35 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 35

IndicationMa35 Indication mask for binary Hide


channel 35

SetLED35 Set red- LED on HMI for Off


binary channel 35

NAME36 User define string for binary W1 REF START 13 characters


input 36

Operation36 Trigger operation On/ Off Off

TrigLevel36 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 36

IndicationMa36 Indication mask for binary Hide


channel 36

SetLED36 Set red- LED on HMI for Off


binary channel 36

NAME37 User define string for binary W1 REF DIROK 13 characters


input 37

Operation37 Trigger operation On/ Off Off

TrigLevel37 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 37

IndicationMa37 Indication mask for binary Hide


channel 37

SetLED37 Set red- LED on HMI for Off


binary channel 37

NAME38 User define string for binary DRB03- INPUT38 13 characters


input 38

Operation38 Trigger operation On/ Off Off

TrigLevel38 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 38

IndicationMa38 Indication mask for binary Hide


channel 38

SetLED38 Set red- LED on HMI for Off


binary channel 38

NAME39 User define string for binary W1 TEF TRIP 13 characters


input 39

Operation39 Trigger operation On/ Off On

TrigLevel39 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 39

IndicationMa39 Indication mask for binary Show


channel 39

SetLED39 Set red- LED on HMI for On


binary channel 39

NAME40 User define string for binary W1 TEF START 13 characters


input 40

Operation40 Trigger operation On/ Off Off

TrigLevel40 Trig on positiv (1) or negative Trig on 1

Page 65 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
(0) slope for binary inp 40

IndicationMa40 Indication mask for binary Hide


channel 40

SetLED40 Set red- LED on HMI for Off


binary channel 40

NAME41 User define string for binary W1 TEF I2BLC 13 characters


input 41

Operation41 Trigger operation On/ Off On

TrigLevel41 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 41

IndicationMa41 Indication mask for binary Hide


channel 41

SetLED41 Set red- LED on HMI for Off


binary channel 41

NAME42 User define string for binary BUCHOLZ TRIP 13 characters


input 42

Operation42 Trigger operation On/ Off On

TrigLevel42 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 42

IndicationMa42 Indication mask for binary Show


channel 42

SetLED42 Set red- LED on HMI for On


binary channel 42

NAME43 User define string for binary TR PRES TRIP 13 characters


input 43

Operation43 Trigger operation On/ Off On

TrigLevel43 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 43

IndicationMa43 Indication mask for binary Show


channel 43

SetLED43 Set red- LED on HMI for On


binary channel 43

NAME44 User define string for binary WIND TEMP TRP 13 characters
input 44

Operation44 Trigger operation On/ Off On

TrigLevel44 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 44

IndicationMa44 Indication mask for binary Show


channel 44

SetLED44 Set red- LED on HMI for On


binary input 44

NAME45 User define string for binary OIL TEMP TRIP 13 characters
input 45

Operation45 Trigger operation On/ Off On

TrigLevel45 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 45

IndicationMa45 Indication mask for binary Show

Page 66 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
channel 45

SetLED45 Set red- LED on HMI for On


binary channel 45

NAME46 User define string for binary RET VALV TRIP 13 characters
input 46

Operation46 Trigger operation On/ Off Off

TrigLevel46 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 46

IndicationMa46 Indication mask for binary Hide


channel 46

SetLED46 Set red- LED on HMI for Off


binary channel 46

NAME47 User define string for binary STAMP REL TRI 13 characters
input 47

Operation47 Trigger operation On/ Off Off

TrigLevel47 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 47

IndicationMa47 Indication mask for binary Hide


channel 47

SetLED47 Set red- LED on HMI for Off


binary channel 47

NAME48 User define string for binary DRB03- INPUT48 13 characters


input 48

Operation48 Trigger operation On/ Off Off

TrigLevel48 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 48

IndicationMa48 Indication mask for binary Hide


channel 48

SetLED48 Set red- LED on HMI for Off


binary channel 48

Chapter : Monitoring->DisturbanceReport->BinarySignals(RBDR)->B3RBDR: 3->IEC60870-5-103, Ch 33-48

FUNCT33 Function type for binary 0 FunT


channel 33 (IEC- 60870- 5-
103)

FUNCT34 Function type for binary 0 FunT


channel 34 (IEC- 60870- 5-
103)

FUNCT35 Function type for binary 0 FunT


channel 35 (IEC- 60870- 5-
103)

FUNCT36 Function type for binary 0 FunT


channel 36 (IEC- 60870- 5-
103)

FUNCT37 Function type for binary 0 FunT


channel 37 (IEC- 60870- 5-
103)

FUNCT38 Function type for binary 0 FunT


channel 38 (IEC- 60870- 5-
103)

Page 67 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
FUNCT39 Function type for binary 0 FunT
channel 39 (IEC- 60870- 5-
103)

FUNCT40 Function type for binary 0 FunT


channel 40 (IEC- 60870- 5-
103)

FUNCT41 Function type for binary 0 FunT


channel 41 (IEC- 60870- 5-
103)

FUNCT42 Function type for binary 0 FunT


channel 42 (IEC- 60870- 5-
103)

FUNCT43 Function type for binary 0 FunT


channel 43 (IEC- 60870- 5-
103)

FUNCT44 Function type for binary 0 FunT


channel 44 (IEC- 60870- 5-
103)

FUNCT45 Function type for binary 0 FunT


channel 45 (IEC- 60870- 5-
103)

FUNCT46 Function type for binary 0 FunT


channel 46 (IEC- 60870- 5-
103)

FUNCT47 Function type for binary 0 FunT


channel 47 (IEC- 60870- 5-
103)

FUNCT48 Function type for binary 0 FunT


channel 48 (IEC- 60870- 5-
103)

INFONO33 Information number for binary 0 InfNo


channel 33 (IEC- 60870- 5-
103)

INFONO34 Information number for binary 0 InfNo


channel 34 (IEC- 60870- 5-
103)

INFONO35 Information number for binary 0 InfNo


channel 35 (IEC- 60870- 5-
103)

INFONO36 Information number for binary 0 InfNo


channel 36 (IEC- 60870- 5-
103)

INFONO37 Information number for binary 0 InfNo


channel 37 (IEC- 60870- 5-
103)

INFONO38 Information number for binary 0 InfNo


channel 38 (IEC- 60870- 5-
103)

INFONO39 Information number for binary 0 InfNo


channel 39 (IEC- 60870- 5-
103)

INFONO40 Information number for binary 0 InfNo


channel 40 (IEC- 60870- 5-
103)

Page 68 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
INFONO41 Information number for binary 0 InfNo
channel 41 (IEC- 60870- 5-
103)

INFONO42 Information number for binary 0 InfNo


channel 42 (IEC- 60870- 5-
103)

INFONO43 Information number for binary 0 InfNo


channel 43 (IEC- 60870- 5-
103)

INFONO44 Information number for binary 0 InfNo


channel 44 (IEC- 60870- 5-
103)

INFONO45 Information number for binary 0 InfNo


channel 45 (IEC- 60870- 5-
103)

INFONO46 Information number for binary 0 InfNo


channel 46 (IEC- 60870- 5-
103)

INFONO47 Information number for binary 0 InfNo


channel 47 (IEC- 60870- 5-
103)

INFONO48 Information number for binary 0 InfNo


channel 48 (IEC- 60870- 5-
103)

Chapter : Monitoring->DisturbanceReport->BinarySignals(RBDR)->B4RBDR: 4->Binary Signals, Ch 49-64

NAME49 User define string for binary QA1 OPEN 13 characters


input 49

Operation49 Trigger operation On/ Off On

TrigLevel49 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 49

IndicationMa49 Indication mask for binary Hide


channel 49

SetLED49 Set red- LED on HMI for Off


binary channel 49

NAME50 User define string for binary QA1 CLOSE 13 characters


input 50

Operation50 Trigger operation On/ Off On

TrigLevel50 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 50

IndicationMa50 Indication mask for binary Hide


channel 50

SetLED50 Set red- LED on HMI for Off


binary channel 50

NAME51 User define string for binary DRB04- INPUT51 13 characters


input 51

Operation51 Trigger operation On/ Off Off

TrigLevel51 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 51

IndicationMa51 Indication mask for binary Hide


channel 51

Page 69 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
SetLED51 Set red- LED on HMI for Off
binary channel 51

NAME52 User define string for binary W2 TOC TRIP 13 characters


input 52

Operation52 Trigger operation On/ Off On

TrigLevel52 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 52

IndicationMa52 Indication mask for binary Show


channel 52

SetLED52 Set red- LED on HMI for On


binary channel 52

NAME53 User define string for binary W2 TOC STL1 13 characters


input 53

Operation53 Trigger operation On/ Off Off

TrigLevel53 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 53

IndicationMa53 Indication mask for binary Hide


channel 53

SetLED53 Set red- LED on HMI for Off


binary channel 53

NAME54 User define string for binary W2 TOC STL2 13 characters


input 54

Operation54 Trigger operation On/ Off Off

TrigLevel54 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 54

IndicationMa54 Indication mask for binary Hide


channel 54

SetLED54 Set red- LED on HMI for Off


binary channel 54

NAME55 User define string for binary W2 TOC STL3 13 characters


input 55

Operation55 Trigger operation On/ Off Off

TrigLevel55 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 55

IndicationMa55 Indication mask for binary Hide


channel 55

SetLED55 Set red- LED on HMI for Off


binary channel 55

NAME56 User define string for binary DRB04- INPUT56 13 characters


input 56

Operation56 Trigger operation On/ Off On

TrigLevel56 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 56

IndicationMa56 Indication mask for binary Show


channel 56

SetLED56 Set red- LED on HMI for On


binary channel 56

Page 70 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
NAME57 User define string for binary DRB04- INPUT57 13 characters
input 57

Operation57 Trigger operation On/ Off Off

TrigLevel57 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 57

IndicationMa57 Indication mask for binary Hide


channel 57

SetLED57 Set red- LED on HMI for Off


binary channel 57

NAME58 User define string for binary W2 IEF2 TRIP 13 characters


input 58

Operation58 Trigger operation On/ Off Off

TrigLevel58 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 58

IndicationMa58 Indication mask for binary Hide


channel 58

SetLED58 Set red- LED on HMI for Off


binary channel 58

NAME59 User define string for binary W2 IOC TRIP 13 characters


input 59

Operation59 Trigger operation On/ Off Off

TrigLevel59 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 59

IndicationMa59 Indication mask for binary Hide


channel 59

SetLED59 Set red- LED on HMI for Off


binary channel 59

NAME60 User define string for binary W2 TEF TRIP 13 characters


input 60

Operation60 Trigger operation On/ Off On

TrigLevel60 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 60

IndicationMa60 Indication mask for binary Show


channel 60

SetLED60 Set red- LED on HMI for On


binary input 60

NAME61 User define string for binary W2 TEF START 13 characters


input 61

Operation61 Trigger operation On/ Off Off

TrigLevel61 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 61

IndicationMa61 Indication mask for binary Hide


channel 61

SetLED61 Set red- LED on HMI for Off


binary channel 61

NAME62 User define string for binary W2 TEF ST FW 13 characters


input 62

Page 71 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
Operation62 Trigger operation On/ Off Off

TrigLevel62 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 62

IndicationMa62 Indication mask for binary Hide


channel 62

SetLED62 Set red- LED on HMI for Off


binary channel 62

NAME63 User define string for binary W2 TEF ST RV 13 characters


input 63

Operation63 Trigger operation On/ Off Off

TrigLevel63 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 63

IndicationMa63 Indication mask for binary Hide


channel 63

SetLED63 Set red- LED on HMI for Off


binary channel 63

NAME64 User define string for binary W2 TEF I2BLC 13 characters


input 64

Operation64 Trigger operation On/ Off On

TrigLevel64 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 64

IndicationMa64 Indication mask for binary Hide


channel 64

SetLED64 Set red- LED on HMI for Off


binary channel 64

Chapter : Monitoring->DisturbanceReport->BinarySignals(RBDR)->B4RBDR: 4->IEC60870-5-103, Ch 49-64

FUNCT49 Function type for binary 0 FunT


channel 49 (IEC- 60870- 5-
103)

FUNCT50 Function type for binary 0 FunT


channel 50 (IEC- 60870- 5-
103)

FUNCT51 Function type for binary 0 FunT


channel 51 (IEC- 60870- 5-
103)

FUNCT52 Function type for binary 0 FunT


channel 52 (IEC- 60870- 5-
103)

FUNCT53 Function type for binary 0 FunT


channel 53 (IEC- 60870- 5-
103)

FUNCT54 Function type for binary 0 FunT


channel 54 (IEC- 60870- 5-
103)

FUNCT55 Function type for binary 0 FunT


channel 55 (IEC- 60870- 5-
103)

FUNCT56 Function type for binary 0 FunT


channel 56 (IEC- 60870- 5-
103)

Page 72 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
FUNCT57 Function type for binary 0 FunT
channel 57 (IEC- 60870- 5-
103)

FUNCT58 Function type for binary 0 FunT


channel 58 (IEC- 60870- 5-
103)

FUNCT59 Function type for binary 0 FunT


channel 59 (IEC- 60870- 5-
103)

FUNCT60 Function type for binary 0 FunT


channel 60 (IEC- 60870- 5-
103)

FUNCT61 Function type for binary 0 FunT


channel 61 (IEC- 60870- 5-
103)

FUNCT62 Function type for binary 0 FunT


channel 62 (IEC- 60870- 5-
103)

FUNCT63 Function type for binary 0 FunT


channel 63 (IEC- 60870- 5-
103)

FUNCT64 Function type for binary 0 FunT


channel 64 (IEC- 60870- 5-
103)

INFONO49 Information number for binary 0 InfNo


channel 49 (IEC- 60870- 5-
103)

INFONO50 Information number for binary 0 InfNo


channel 50 (IEC- 60870- 5-
103)

INFONO51 Information number for binary 0 InfNo


channel 51 (IEC- 60870- 5-
103)

INFONO52 Information number for binary 0 InfNo


channel 52 (IEC- 60870- 5-
103)

INFONO53 Information number for binary 0 InfNo


channel 53 (IEC- 60870- 5-
103)

INFONO54 Information number for binary 0 InfNo


channel 54 (IEC- 60870- 5-
103)

INFONO55 Information number for binary 0 InfNo


channel 55 (IEC- 60870- 5-
103)

INFONO56 Information number for binary 0 InfNo


channel 56 (IEC- 60870- 5-
103)

INFONO57 Information number for binary 0 InfNo


channel 57 (IEC- 60870- 5-
103)

INFONO58 Information number for binary 0 InfNo


channel 58 (IEC- 60870- 5-
103)

Page 73 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
INFONO59 Information number for binary 0 InfNo
channel 59 (IEC- 60870- 5-
103)

INFONO60 Information number for binary 0 InfNo


channel 60 (IEC- 60870- 5-
103)

INFONO61 Information number for binary 0 InfNo


channel 61 (IEC- 60870- 5-
103)

INFONO62 Information number for binary 0 InfNo


channel 62 (IEC- 60870- 5-
103)

INFONO63 Information number for binary 0 InfNo


channel 63 (IEC- 60870- 5-
103)

INFONO64 Information number for binary 0 InfNo


channel 64 (IEC- 60870- 5-
103)

Chapter : Monitoring->DisturbanceReport->BinarySignals(RBDR)->B5RBDR: 5->Binary Signals, Ch 65-80

NAME65 User define string for binary W1 TOV TRIP 13 characters


input 65

Operation65 Trigger operation On/ Off On

TrigLevel65 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 65

IndicationMa65 Indication mask for binary Show


channel 65

SetLED65 Set red- LED on HMI for On


binary channel 65

NAME66 User define string for binary W1 TOV TR2 13 characters


input 66

Operation66 Trigger operation On/ Off On

TrigLevel66 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 66

IndicationMa66 Indication mask for binary Show


channel 66

SetLED66 Set red- LED on HMI for On


binary channel 66

NAME67 User define string for binary W1 TOV START 13 characters


input 67

Operation67 Trigger operation On/ Off Off

TrigLevel67 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 67

IndicationMa67 Indication mask for binary Hide


channel 67

SetLED67 Set red- LED on HMI for Off


binary channel 67

NAME68 User define string for binary W1 TUV TRIP 13 characters


input 68

Operation68 Trigger operation On/ Off On

Page 74 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
TrigLevel68 Trig on positiv (1) or negative Trig on 1
(0) slope for binary inp 68

IndicationMa68 Indication mask for binary Show


channel 68

SetLED68 Set red- LED on HMI for On


binary channel 68

NAME69 User define string for binary W1 TUV TR2 13 characters


input 69

Operation69 Trigger operation On/ Off On

TrigLevel69 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 69

IndicationMa69 Indication mask for binary Show


channel 69

SetLED69 Set red- LED on HMI for On


binary channel 69

NAME70 User define string for binary W1 TUV START 13 characters


input 70

Operation70 Trigger operation On/ Off Off

TrigLevel70 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 70

IndicationMa70 Indication mask for binary Hide


channel 70

SetLED70 Set red- LED on HMI for Off


binary channel 70

NAME71 User define string for binary W1 TRV TRIP 13 characters


input 71

Operation71 Trigger operation On/ Off Off

TrigLevel71 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 71

IndicationMa71 Indication mask for binary Hide


channel 71

SetLED71 Set red- LED on HMI for Off


binary channel 71

NAME72 User define string for binary W1 TRV TR2 13 characters


input 72

Operation72 Trigger operation On/ Off Off

TrigLevel72 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 72

IndicationMa72 Indication mask for binary Hide


channel 72

SetLED72 Set red- LED on HMI for Off


binary channel 72

NAME73 User define string for binary ACTIVE GROUP1 13 characters


input 73

Operation73 Trigger operation On/ Off Off

TrigLevel73 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 73

Page 75 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
IndicationMa73 Indication mask for binary Hide
channel 73

SetLED73 Set red- LED on HMI for Off


binary channel 73

NAME74 User define string for binary ACTIVE GROUP2 13 characters


input 74

Operation74 Trigger operation On/ Off Off

TrigLevel74 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 74

IndicationMa74 Indication mask for binary Hide


channel 74

SetLED74 Set red- LED on HMI for Off


binary channel 74

NAME75 User define string for binary ACT GRP CHNGD 13 characters
input 75

Operation75 Trigger operation On/ Off Off

TrigLevel75 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 75

IndicationMa75 Indication mask for binary Hide


channel 75

SetLED75 Set red- LED on HMI for Off


binary channel 75

NAME76 User define string for binary TEST- ACTIVE 13 characters


input 76

Operation76 Trigger operation On/ Off Off

TrigLevel76 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 76

IndicationMa76 Indication mask for binary Hide


channel 76

SetLED76 Set red- LED on HMI for Off


binary input 76

NAME77 User define string for binary DRB05- INPUT77 13 characters


input 77

Operation77 Trigger operation On/ Off Off

TrigLevel77 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 77

IndicationMa77 Indication mask for binary Hide


channel 77

SetLED77 Set red- LED on HMI for Off


binary channel 77

NAME78 User define string for binary DRB05- INPUT78 13 characters


input 78

Operation78 Trigger operation On/ Off Off

TrigLevel78 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 78

IndicationMa78 Indication mask for binary Hide


channel 78

Page 76 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
SetLED78 Set red- LED on HMI for Off
binary channel 78

NAME79 User define string for binary W2 CCS ALARM 13 characters


input 79

Operation79 Trigger operation On/ Off Off

TrigLevel79 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 79

IndicationMa79 Indication mask for binary Hide


channel 79

SetLED79 Set red- LED on HMI for Off


binary channel 79

NAME80 User define string for binary W1 FUSE FAIL 13 characters


input 80

Operation80 Trigger operation On/ Off On

TrigLevel80 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 80

IndicationMa80 Indication mask for binary Hide


channel 80

SetLED80 Set red- LED on HMI for Off


binary channel 80

Chapter : Monitoring->DisturbanceReport->BinarySignals(RBDR)->B5RBDR: 5->IEC60870-5-103, Ch 65-80

FUNCT65 Function type for binary 0 FunT


channel 65 (IEC- 60870- 5-
103)

FUNCT66 Function type for binary 0 FunT


channel 66 (IEC- 60870- 5-
103)

FUNCT67 Function type for binary 0 FunT


channel 67 (IEC- 60870- 5-
103)

FUNCT68 Function type for binary 0 FunT


channel 68 (IEC- 60870- 5-
103)

FUNCT69 Function type for binary 0 FunT


channel 69 (IEC- 60870- 5-
103)

FUNCT70 Function type for binary 0 FunT


channel 70 (IEC- 60870- 5-
103)

FUNCT71 Function type for binary 0 FunT


channel 71 (IEC- 60870- 5-
103)

FUNCT72 Function type for binary 0 FunT


channel 72 (IEC- 60870- 5-
103)

FUNCT73 Function type for binary 0 FunT


channel 73 (IEC- 60870- 5-
103)

FUNCT74 Function type for binary 0 FunT


channel 74 (IEC- 60870- 5-
103)

Page 77 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
FUNCT75 Function type for binary 0 FunT
channel 75 (IEC- 60870- 5-
103)

FUNCT76 Function type for binary 0 FunT


channel 76 (IEC- 60870- 5-
103)

FUNCT77 Function type for binary 0 FunT


channel 77 (IEC- 60870- 5-
103)

FUNCT78 Function type for binary 0 FunT


channel 78 (IEC- 60870- 5-
103)

FUNCT79 Function type for binary 0 FunT


channel 79 (IEC- 60870- 5-
103)

FUNCT80 Function type for binary 0 FunT


channel 80 (IEC- 60870- 5-
103)

INFONO65 Information number for binary 0 InfNo


channel 65 (IEC- 60870- 5-
103)

INFONO66 Information number for binary 0 InfNo


channel 66 (IEC- 60870- 5-
103)

INFONO67 Information number for binary 0 InfNo


channel 67 (IEC- 60870- 5-
103)

INFONO68 Information number for binary 0 InfNo


channel 68 (IEC- 60870- 5-
103)

INFONO69 Information number for binary 0 InfNo


channel 69 (IEC- 60870- 5-
103)

INFONO70 Information number for binary 0 InfNo


channel 70 (IEC- 60870- 5-
103)

INFONO71 Information number for binary 0 InfNo


channel 71 (IEC- 60870- 5-
103)

INFONO72 Information number for binary 0 InfNo


channel 72 (IEC- 60870- 5-
103)

INFONO73 Information number for binary 0 InfNo


channel 73 (IEC- 60870- 5-
103)

INFONO74 Information number for binary 0 InfNo


channel 74 (IEC- 60870- 5-
103)

INFONO75 Information number for binary 0 InfNo


channel 75 (IEC- 60870- 5-
103)

INFONO76 Information number for binary 0 InfNo


channel 76 (IEC- 60870- 5-
103)

Page 78 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
INFONO77 Information number for binary 0 InfNo
channel 77 (IEC- 60870- 5-
103)

INFONO78 Information number for binary 0 InfNo


channel 78 (IEC- 60870- 5-
103)

INFONO79 Information number for binary 0 InfNo


channel 79 (IEC- 60870- 5-
103)

INFONO80 Information number for binary 0 InfNo


channel 80 (IEC- 60870- 5-
103)

Chapter : Monitoring->DisturbanceReport->BinarySignals(RBDR)->B6RBDR: 6->Binary Signals, Ch 81-96

NAME81 User define string for binary W1 THOL TRIP 13 characters


input 81

Operation81 Trigger operation On/ Off On

TrigLevel81 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 81

IndicationMa81 Indication mask for binary Show


channel 81

SetLED81 Set red- LED on HMI for On


binary channel 81

NAME82 User define string for binary BUCHOLZ TRIP 13 characters


input 82

Operation82 Trigger operation On/ Off On

TrigLevel82 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 82

IndicationMa82 Indication mask for binary Show


channel 82

SetLED82 Set red- LED on HMI for On


binary channel 82

NAME83 User define string for binary PRESSURE TRIP 13 characters


input 83

Operation83 Trigger operation On/ Off On

TrigLevel83 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 83

IndicationMa83 Indication mask for binary Show


channel 83

SetLED83 Set red- LED on HMI for On


binary channel 83

NAME84 User define string for binary WNDG TEMP TRP 13 characters
input 84

Operation84 Trigger operation On/ Off On

TrigLevel84 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 84

IndicationMa84 Indication mask for binary Show


channel 84

SetLED84 Set red- LED on HMI for On


binary channel 84

Page 79 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
NAME85 User define string for binary OIL TEMP TRIP 13 characters
input 85

Operation85 Trigger operation On/ Off On

TrigLevel85 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 85

IndicationMa85 Indication mask for binary Show


channel 85

SetLED85 Set red- LED on HMI for On


binary channel 85

NAME86 User define string for binary WNDG TEMP AL 13 characters


input 86

Operation86 Trigger operation On/ Off On

TrigLevel86 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 86

IndicationMa86 Indication mask for binary Hide


channel 86

SetLED86 Set red- LED on HMI for Off


binary channel 86

NAME87 User define string for binary OIL TEMP AL 13 characters


input 87

Operation87 Trigger operation On/ Off On

TrigLevel87 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 87

IndicationMa87 Indication mask for binary Hide


channel 87

SetLED87 Set red- LED on HMI for Off


binary channel 87

NAME88 User define string for binary OIL LOW AL 13 characters


input 88

Operation88 Trigger operation On/ Off On

TrigLevel88 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 88

IndicationMa88 Indication mask for binary Hide


channel 88

SetLED88 Set red- LED on HMI for Off


binary channel 88

NAME89 User define string for binary OIL HIGH AL 13 characters


input 89

Operation89 Trigger operation On/ Off On

TrigLevel89 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 89

IndicationMa89 Indication mask for binary Hide


channel 89

SetLED89 Set red- LED on HMI for Off


binary channel 89

NAME90 User define string for binary PRES VAL AL 13 characters


input 90

Page 80 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
Operation90 Trigger operation On/ Off On

TrigLevel90 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 90

IndicationMa90 Indication mask for binary Hide


channel 90

SetLED90 Set red- LED on HMI for Off


binary channel 90

NAME91 User define string for binary GAS RELAY AL 13 characters


input 91

Operation91 Trigger operation On/ Off On

TrigLevel91 Trig on positiv (1) or negative Trig on 0


(0) slope for binary inp 91

IndicationMa91 Indication mask for binary Hide


channel 91

SetLED91 Set red- LED on HMI for Off


binary channel 91

NAME92 User define string for binary BUCHOLZ AL 13 characters


input 92

Operation92 Trigger operation On/ Off Off

TrigLevel92 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 92

IndicationMa92 Indication mask for binary Hide


channel 92

SetLED92 Set red- LED on HMI for Off


binary input 92

NAME93 User define string for binary RET VALV AL 13 characters


input 93

Operation93 Trigger operation On/ Off Off

TrigLevel93 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 93

IndicationMa93 Indication mask for binary Hide


channel 93

SetLED93 Set red- LED on HMI for Off


binary channel 93

NAME94 User define string for binary STAMP REL AL 13 characters


input 94

Operation94 Trigger operation On/ Off Off

TrigLevel94 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 94

IndicationMa94 Indication mask for binary Hide


channel 94

SetLED94 Set red- LED on HMI for Off


binary channel 94

NAME95 User define string for binary DRB#- INPUT95 13 characters


input 95

Operation95 Trigger operation On/ Off Off

TrigLevel95 Trig on positiv (1) or negative Trig on 1

Page 81 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
(0) slope for binary inp 95

IndicationMa95 Indication mask for binary Hide


channel 95

SetLED95 Set red- LED on HMI for Off


binary channel 95

NAME96 User define string for binary Not used 13 characters


input 96

Operation96 Trigger operation On/ Off Off

TrigLevel96 Trig on positiv (1) or negative Trig on 1


(0) slope for binary inp 96

IndicationMa96 Indication mask for binary Hide


channel 96

SetLED96 Set red- LED on HMI for Off


binary channel 96

Chapter : Monitoring->DisturbanceReport->BinarySignals(RBDR)->B6RBDR: 6->IEC60870-5-103, Ch 81-96

FUNCT81 Function type for binary 0 FunT


channel 81 (IEC- 60870- 5-
103)

FUNCT82 Function type for binary 0 FunT


channel 82 (IEC- 60870- 5-
103)

FUNCT83 Function type for binary 0 FunT


channel 83 (IEC- 60870- 5-
103)

FUNCT84 Function type for binary 0 FunT


channel 84 (IEC- 60870- 5-
103)

FUNCT85 Function type for binary 0 FunT


channel 85 (IEC- 60870- 5-
103)

FUNCT86 Function type for binary 0 FunT


channel 86 (IEC- 60870- 5-
103)

FUNCT87 Function type for binary 0 FunT


channel 87 (IEC- 60870- 5-
103)

FUNCT88 Function type for binary 0 FunT


channel 88 (IEC- 60870- 5-
103)

FUNCT89 Function type for binary 0 FunT


channel 89 (IEC- 60870- 5-
103)

FUNCT90 Function type for binary 0 FunT


channel 90 (IEC- 60870- 5-
103)

FUNCT91 Function type for binary 0 FunT


channel 91 (IEC- 60870- 5-
103)

FUNCT92 Function type for binary 0 FunT


channel 92 (IEC- 60870- 5-
103)

Page 82 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
FUNCT93 Function type for binary 0 FunT
channel 93 (IEC- 60870- 5-
103)

FUNCT94 Function type for binary 0 FunT


channel 94 (IEC- 60870- 5-
103)

FUNCT95 Function type for binary 0 FunT


channel 95 (IEC- 60870- 5-
103)

FUNCT96 Function type for binary 0 FunT


channel 96 (IEC- 60870- 5-
103)

INFONO81 Information number for binary 0 InfNo


channel 81 (IEC- 60870- 5-
103)

INFONO82 Information number for binary 0 InfNo


channel 82 (IEC- 60870- 5-
103)

INFONO83 Information number for binary 0 InfNo


channel 83 (IEC- 60870- 5-
103)

INFONO84 Information number for binary 0 InfNo


channel 84 (IEC- 60870- 5-
103)

INFONO85 Information number for binary 0 InfNo


channel 85 (IEC- 60870- 5-
103)

INFONO86 Information number for binary 0 InfNo


channel 86 (IEC- 60870- 5-
103)

INFONO87 Information number for binary 0 InfNo


channel 87 (IEC- 60870- 5-
103)

INFONO88 Information number for binary 0 InfNo


channel 88 (IEC- 60870- 5-
103)

INFONO89 Information number for binary 0 InfNo


channel 89 (IEC- 60870- 5-
103)

INFONO90 Information number for binary 0 InfNo


channel 90 (IEC- 60870- 5-
103)

INFONO91 Information number for binary 0 InfNo


channel 91 (IEC- 60870- 5-
103)

INFONO92 Information number for binary 0 InfNo


channel 92 (IEC- 60870- 5-
103)

INFONO93 Information number for binary 0 InfNo


channel 93 (IEC- 60870- 5-
103)

INFONO94 Information number for binary 0 InfNo


channel 94 (IEC- 60870- 5-
103)

Page 83 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
INFONO95 Information number for binary 0 InfNo
channel 95 (IEC- 60870- 5-
103)

INFONO96 Information number for binary 0 InfNo


channel 96 (IEC- 60870- 5-
103)

Chapter : Monitoring->IndicationBits(GGIO)->SP16GGIO: 1

NAMEOR User define string for logic OR MP01- INPUTOR 13 characters


output signal

Chapter : Monitoring->IndicationBits(GGIO)->SP16GGIO: 2

NAMEOR User define string for logic OR MP02- INPUTOR 13 characters


output signal

Chapter : Monitoring->IndicationBits(GGIO)->SP16GGIO: 3

NAMEOR User define string for logic OR MP03- INPUTOR 13 characters


output signal

Chapter : Monitoring->IndicationBits(GGIO)->SP16GGIO: 4

NAMEOR User define string for logic OR MP04- INPUTOR 13 characters


output signal

Chapter : Metering->ThreePhEnergMeas(MMTR)->ETPMMTR: 1

Operation Operation Off/ On Off

StartAcc Activate the accumulation of Off


energy values

tEnergy Time interval for energy 1 Minute


calculation

EALim Active energy limit 1000000 MWh

ERLim Reactive energy limit 1000 MVArh

DirEnergyAct Direction of active energy flow Forward


Forward/ Reverse

DirEnergyReac Direction of reactive energy Forward


flow Forward/ Reverse

tEnergyOnPls Energy accumulated pulse ON 1 s


time in secs

tEnergyOffPls Energy accumulated pulse 0. 5 s


OFF time in secs

EnZeroClamp Enable of zero point clamping On


detection function

LevZeroClampP Zero point clamping level at 10 MW


active Power

LevZeroClampQ Zero point clamping level at 10 MVAr


reactive Power

EAFPrestVal Preset Initial value for forward 0 MWh


active energy

EARPrestVal Preset Initial value for reverse 0 MWh


active energy

ERFPresetVal Preset Initial value for forward 0 MVArh


reactive energy

ERVPresetVal Preset Initial value for reverse 0 MVArh

Page 84 of 111
Grupo de Ajustes: Application Configuration
Nombre Descripcin Valor Unidad
reactive energy

EAFAccPlsQty Pulse quantity for active 100 MWh


forward accumulated energy
value

EARAccPlsQty Pulse quantity for active 100 MWh


reverse accumulated energy
value

ERFAccPlsQty Pulse quantity for reactive 100 MVArh


forward accumulated energy
value

ERVAccPlsQty Pulse quantity for reactive 100 MVArh


reverse accumulated energy
value

Grupo de Ajustes: Setting Group1

Nombre Descripcin Valor Unidad


Chapter : Differential protection->TransformerDiff2Wind(PDIF,87T)->T2WPDIF: 1

Operation Operation Off / On On

SOTFMode Operation mode for switch Off


onto fault

IDiffAlarm Dif. cur. alarm, multiple of 0. 2 IB


base curr, usually W1 curr.

tAlarmDelay Time delay for diff currents 5 s


alarm level

IdMin Section1 sensitivity, multi. of 0. 25 IB


base curr, usually W1 curr.

EndSection1 End of section 1, multiple of 1. 25 IB


Winding 1 rated current

EndSection2 End of section 2, multiple of 3 IB


Winding 1 rated current

SlopeSection2 Slope in section 2 of operate- 25 %


restrain characteristic, in %

SlopeSection3 Slope in section 3 of operate- 50 %


restrain characteristic, in %

IdUnre Unrestr. prot. limit, multiple 10 IB


of Winding 1 rated current

I2/ I1Ratio Max. ratio of 2nd harm. to 12 %


fundamental harm dif. curr. in
%

I5/ I1Ratio Max. ratio of 5th harm. to 15 %


fundamental harm dif. curr. in
%

CrossBlockEn Operation Off/ On for cross- On


block logic between phases

NegSeqDiffEn Operation Off/ On for neg. On


seq. differential protections

IMinNegSeq Neg. seq. curr. must be 0. 1 IB


higher than this level to be
used

Page 85 of 111
Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
NegSeqROA Operate Angle for int. / ext. 60 Deg
neg. seq. fault discriminator

OpenCTEnable Open CT detection feature. On


Open CTEnable Off/ On

tOCTAlarmDelay Open CT: time in s to alarm 3 s


after an open CT is detected

tOCTResetDelay Reset delay in s. After delay, 0. 25 s


diff. function is activated

tOCTUnrstDelay Unrestrained diff. protection 10 s


blocked after this delay, in s

Chapter : Differential protection->LowImpREF(PDIF,87N)->REFPDIF: 1

Operation Operation Off / On Off

IBase Base current 231 A

IdMin Maximum sensitivity in % of 20 %IB


Ibase

ROA Relay operate angle for zero 60 Deg


sequence directional feature

CTFactorPri1 CT factor for HV side CT1 1


(CT1rated/ HVrated current)

CTFactorPri2 CT factor for HV side CT2 1


(CT2rated/ HVrated current)

CTFactorSec1 CT factor for MV side CT1 1


(CT1rated/ MVrated current)

CTFactorSec2 CT factor for MV side CT2 1


(CT2rated/ MVrated current)

Chapter : Current protection->BreakerFailure(RBRF,50BF)->CCRBRF: 1

Operation Operation Off / On On

IBase Base current 231 A

FunctionMode Detection principle for back- Current


up trip

BuTripMode Back- up trip mode 1 out of 3

RetripMode Operation mode of re- trip Retrip Off


logic

IP> Operate phase current level in 50 %IB


% of IBase

I>BlkCont Current for blocking of CB 30 %IB


contact operation in % of
IBase

IN> Operate residual current level 20 %IB


in % of IBase

t1 Time delay of re- trip 0. 01 s

t2 Time delay of back- up trip 0. 15 s

t2MPh Time delay of back- up trip at 0. 15 s


multi- phase start

t3 Additional time delay to t2 for 0. 3 s


a second back- up trip

Page 86 of 111
Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
tCBAlarm Time delay for CB faulty signal 5 s

tPulse Trip pulse duration 0. 2 s

Chapter : Current protection->InstPhaseOverCurrent(PIOC,50)->PHPIOC: 1

Operation Operation Off / On Off

IBase Base current 400 A

OpMode Select operation mode 2- out 1 out of 3


of 3 / 1- out of 3

IP>> Operate phase current level in 200 %IB


% of IBase

StValMult Multiplier for operate current 1


level

Chapter : Current protection->InstPhaseOverCurrent(PIOC,50)->PHPIOC: 2

Operation Operation Off / On Off

IBase Base current 400 A

OpMode Select operation mode 2- out 1 out of 3


of 3 / 1- out of 3

IP>> Operate phase current level in 200 %IB


% of IBase

StValMult Multiplier for operate current 1


level

Chapter : Current protection->InstResidualOverCurrent(PIOC,50N)->EFPIOC: 1

Operation Operation Off / On Off

IBase Base current 400 A

IN>> Operate residual current level 200 %IB


in % of IBase

StValMult Multiplier for operate current 1


level

Chapter : Current protection->InstResidualOverCurrent(PIOC,50N)->EFPIOC: 2

Operation Operation Off / On Off

IBase Base current 400 A

IN>> Operate residual current level 200 %IB


in % of IBase

StValMult Multiplier for operate current 1


level

Chapter : Current protection->PhaseOverCurrent4Step(PTOC,51/67)->OC4PTOC: 1->General

Operation Operation Off / On On

IBase Base current 231 A

UBase Base voltage 500 kV

AngleRCA Relay characteristic angle 55 Deg


(RCA)

AngleROA Relay operation angle (ROA) 80 Deg

StartPhSel Number of phases required for 1 out of 3


op (1 of 3, 2 of 3, 3 of 3)

Page 87 of 111
Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
IMinOpPhSel Minimum current for phase 7 %IB
selection in % of IBase

2ndHarmStab Operate level of 2nd harm 20 %IB


restrain op in % of
Fundamental

Chapter : Current protection->PhaseOverCurrent4Step(PTOC,51/67)->OC4PTOC: 1->Step 1

DirMode1 Directional mode of step 1 (off, Non- directional


nodir, forward, reverse)

Characterist1 Selection of time delay curve IEC Def. Time


type for step 1

I1> Phase current operate level for 130 %IB


step1 in % of IBase

t1 Definitive time delay of step 1 1 s

k1 Time multiplier for the inverse 0. 07


time delay for step 1

t1Min Minimum operate time for 0 s


inverse curves for step 1

I1Mult Multiplier for current operate 2


level for step 1

ResetTypeCrv1 Selection of reset curve type Instantaneous


for step 1

tReset1 Reset time delay used in IEC 0. 02 s


Definite Time curve step 1

tPCrv1 Parameter P for customer 1


programmable curve for step 1

tACrv1 Parameter A for customer 13. 5


programmable curve for step 1

tBCrv1 Parameter B for customer 0


programmable curve for step 1

tCCrv1 Parameter C for customer 1


programmable curve for step 1

tPRCrv1 Parameter PR for customer 0. 5


programmable curve for step 1

tTRCrv1 Parameter TR for customer 13. 5


programmable curve for step 1

tCRCrv1 Parameter CR for customer 1


programmable curve for step 1

HarmRestrain1 Enable block of step 1 from Off


harmonic restrain

Chapter : Current protection->PhaseOverCurrent4Step(PTOC,51/67)->OC4PTOC: 1->Step 2

DirMode2 Directional mode of step 2 (off, Non- directional


nodir, forward, reverse)

Characterist2 Selection of time delay curve IEC Def. Time


type for step 2

I2> Phase current operate level for 606 %IB


step2 in % of IBase

t2 Definitive time delay of step 2 0. 1 s

k2 Time multiplier for the inverse 0. 05

Page 88 of 111
Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
time delay for step 2

I2Mult Multiplier for current operate 2


level for step 2

t2Min Minimum operate time for 0 s


inverse curves for step 2

ResetTypeCrv2 Selection of reset curve type Instantaneous


for step 2

tReset2 Reset time delay used in IEC 0. 02 s


Definite Time curve step 2

tPCrv2 Parameter P for customer 1


programmable curve for step 2

tACrv2 Parameter A for customer 13. 5


programmable curve for step 2

tBCrv2 Parameter B for customer 0


programmable curve for step 2

tCCrv2 Parameter C for customer 1


programmable curve for step 2

tPRCrv2 Parameter PR for customer 0. 5


programmable curve for step 2

tTRCrv2 Parameter TR for customer 13. 5


programmable curve for step 2

tCRCrv2 Parameter CR for customer 1


programmable curve for step 2

HarmRestrain2 Enable block of step 2 from Off


harmonic restrain

Chapter : Current protection->PhaseOverCurrent4Step(PTOC,51/67)->OC4PTOC: 1->Step 3

DirMode3 Directional mode of step 3 (off, Off


nodir, forward, reverse)

Characterist3 Selection of time delay curve ANSI Def. Time


type for step 3

I3> Phase current operate level for 250 %IB


step3 in % of IBase

t3 Definitive time delay of step 3 0. 8 s

k3 Time multiplier for the inverse 0. 05


time delay for step 3

t3Min Minimum operate time for 0 s


inverse curves for step 3

I3Mult Multiplier for current operate 2


level for step 3

ResetTypeCrv3 Selection of reset curve type Instantaneous


for step 3

tReset3 Reset time delay used in IEC 0. 02 s


Definite Time curve step 3

tPCrv3 Parameter P for customer 1


programmable curve for step 3

tACrv3 Parameter A for customer 13. 5


programmable curve for step 3

tBCrv3 Parameter B for customer 0

Page 89 of 111
Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
programmable curve for step 3

tCCrv3 Parameter C for customer 1


programmable curve for step 3

tPRCrv3 Parameter PR for customer 0. 5


programmable curve for step 3

tTRCrv3 Parameter TR for customer 13. 5


programmable curve for step 3

tCRCrv3 Parameter CR for customer 1


programmable curve for step 3

HarmRestrain3 Enable block of step3 from Off


harmonic restrain

Chapter : Current protection->PhaseOverCurrent4Step(PTOC,51/67)->OC4PTOC: 1->Step 4

DirMode4 Directional mode of step 4 (off, Off


nodir, forward, reverse)

Characterist4 Selection of time delay curve ANSI Def. Time


type for step 4

I4> Phase current operate level for 175 %IB


step4 in % of IBase

t4 Definitive time delay of step 4 2 s

k4 Time multiplier for the inverse 0. 05


time delay for step 4

t4Min Minimum operate time for 0 s


inverse curves for step 4

I4Mult Multiplier for current operate 2


level for step 4

ResetTypeCrv4 Selection of reset curve type Instantaneous


for step 4

tReset4 Reset time delay used in IEC 0. 02 s


Definite Time curve step 4

tPCrv4 Parameter P for customer 1


programmable curve for step 4

tACrv4 Parameter A for customer 13. 5


programmable curve for step 4

tBCrv4 Parameter B for customer 0


programmable curve for step 4

tCCrv4 Parameter C for customer 1


programmable curve for step 4

tPRCrv4 Parameter PR for customer 0. 5


programmable curve for step 4

tTRCrv4 Parameter TR for customer 13. 5


programmable curve for step 4

tCRCrv4 Parameter CR for customer 1


programmable curve for step 4

HarmRestrain4 Enable block of step 4 from Off


harmonic restrain

Chapter : Current protection->PhaseOverCurrent4Step(PTOC,51/67)->OC4PTOC: 2->General

Operation Operation Off / On On

Page 90 of 111
Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
IBase Base current 231 A

UBase Base voltage 500 kV

AngleRCA Relay characteristic angle 55 Deg


(RCA)

AngleROA Relay operation angle (ROA) 80 Deg

StartPhSel Number of phases required for 1 out of 3


op (1 of 3, 2 of 3, 3 of 3)

IMinOpPhSel Minimum current for phase 7 %IB


selection in % of IBase

2ndHarmStab Operate level of 2nd harm 20 %IB


restrain op in % of
Fundamental

Chapter : Current protection->PhaseOverCurrent4Step(PTOC,51/67)->OC4PTOC: 2->Step 1

DirMode1 Directional mode of step 1 (off, Non- directional


nodir, forward, reverse)

Characterist1 Selection of time delay curve IEC Def. Time


type for step 1

I1> Phase current operate level for 130 %IB


step1 in % of IBase

t1 Definitive time delay of step 1 1 s

k1 Time multiplier for the inverse 0. 07


time delay for step 1

t1Min Minimum operate time for 0 s


inverse curves for step 1

I1Mult Multiplier for current operate 2


level for step 1

ResetTypeCrv1 Selection of reset curve type Instantaneous


for step 1

tReset1 Reset time delay used in IEC 0. 02 s


Definite Time curve step 1

tPCrv1 Parameter P for customer 1


programmable curve for step 1

tACrv1 Parameter A for customer 13. 5


programmable curve for step 1

tBCrv1 Parameter B for customer 0


programmable curve for step 1

tCCrv1 Parameter C for customer 1


programmable curve for step 1

tPRCrv1 Parameter PR for customer 0. 5


programmable curve for step 1

tTRCrv1 Parameter TR for customer 13. 5


programmable curve for step 1

tCRCrv1 Parameter CR for customer 1


programmable curve for step 1

Page 91 of 111
Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
HarmRestrain1 Enable block of step 1 from Off
harmonic restrain

Chapter : Current protection->PhaseOverCurrent4Step(PTOC,51/67)->OC4PTOC: 2->Step 2

DirMode2 Directional mode of step 2 (off, Non- directional


nodir, forward, reverse)

Characterist2 Selection of time delay curve IEC Def. Time


type for step 2

I2> Phase current operate level for 606 %IB


step2 in % of IBase

t2 Definitive time delay of step 2 0. 1 s

k2 Time multiplier for the inverse 0. 05


time delay for step 2

I2Mult Multiplier for current operate 2


level for step 2

t2Min Minimum operate time for 0 s


inverse curves for step 2

ResetTypeCrv2 Selection of reset curve type Instantaneous


for step 2

tReset2 Reset time delay used in IEC 0. 02 s


Definite Time curve step 2

tPCrv2 Parameter P for customer 1


programmable curve for step 2

tACrv2 Parameter A for customer 13. 5


programmable curve for step 2

tBCrv2 Parameter B for customer 0


programmable curve for step 2

tCCrv2 Parameter C for customer 1


programmable curve for step 2

tPRCrv2 Parameter PR for customer 0. 5


programmable curve for step 2

tTRCrv2 Parameter TR for customer 13. 5


programmable curve for step 2

tCRCrv2 Parameter CR for customer 1


programmable curve for step 2

HarmRestrain2 Enable block of step 2 from Off


harmonic restrain

Chapter : Current protection->PhaseOverCurrent4Step(PTOC,51/67)->OC4PTOC: 2->Step 3

DirMode3 Directional mode of step 3 (off, Off


nodir, forward, reverse)

Characterist3 Selection of time delay curve ANSI Def. Time


type for step 3

I3> Phase current operate level for 250 %IB


step3 in % of IBase

t3 Definitive time delay of step 3 0. 8 s

k3 Time multiplier for the inverse 0. 05


time delay for step 3

t3Min Minimum operate time for 0 s


inverse curves for step 3

Page 92 of 111
Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
I3Mult Multiplier for current operate 2
level for step 3

ResetTypeCrv3 Selection of reset curve type Instantaneous


for step 3

tReset3 Reset time delay used in IEC 0. 02 s


Definite Time curve step 3

tPCrv3 Parameter P for customer 1


programmable curve for step 3

tACrv3 Parameter A for customer 13. 5


programmable curve for step 3

tBCrv3 Parameter B for customer 0


programmable curve for step 3

tCCrv3 Parameter C for customer 1


programmable curve for step 3

tPRCrv3 Parameter PR for customer 0. 5


programmable curve for step 3

tTRCrv3 Parameter TR for customer 13. 5


programmable curve for step 3

tCRCrv3 Parameter CR for customer 1


programmable curve for step 3

HarmRestrain3 Enable block of step3 from Off


harmonic restrain

Chapter : Current protection->PhaseOverCurrent4Step(PTOC,51/67)->OC4PTOC: 2->Step 4

DirMode4 Directional mode of step 4 (off, Off


nodir, forward, reverse)

Characterist4 Selection of time delay curve ANSI Def. Time


type for step 4

I4> Phase current operate level for 175 %IB


step4 in % of IBase

t4 Definitive time delay of step 4 2 s

k4 Time multiplier for the inverse 0. 05


time delay for step 4

t4Min Minimum operate time for 0 s


inverse curves for step 4

I4Mult Multiplier for current operate 2


level for step 4

ResetTypeCrv4 Selection of reset curve type Instantaneous


for step 4

tReset4 Reset time delay used in IEC 0. 02 s


Definite Time curve step 4

tPCrv4 Parameter P for customer 1


programmable curve for step 4

tACrv4 Parameter A for customer 13. 5


programmable curve for step 4

tBCrv4 Parameter B for customer 0


programmable curve for step 4

tCCrv4 Parameter C for customer 1


programmable curve for step 4

Page 93 of 111
Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
tPRCrv4 Parameter PR for customer 0. 5
programmable curve for step 4

tTRCrv4 Parameter TR for customer 13. 5


programmable curve for step 4

tCRCrv4 Parameter CR for customer 1


programmable curve for step 4

HarmRestrain4 Enable block of step 4 from Off


harmonic restrain

Chapter : Current protection->PoleDiscordance(RPLD,52PD)->CCRPLD: 1

Operation Operation Off / On Off

IBase Base current 400

tTrip Time delay between trip 0. 3 s


condition and trip signal

ContSel Contact function selection Off

CurrSel Current function selection Off

CurrUnsymLevel Unsym magn of lowest phase 80 %


current compared to the
highest.

CurrRelLevel Current magnitude for release 10 %IB


of the function in % of IBase

Chapter : Current protection->ResidualOverCurr4Step(PTOC,51N/67N)->EF4PTOC: 1->General

Operation Operation Off / On On

IBase Base value for current settings 231 A

UBase Base value for voltage settings 500 kV

AngleRCA Relay characteristic angle 65 Deg


(RCA)

polMethod Type of polarization Voltage

UPolMin Minimum voltage level for 1 %UB


polarization in % of UBase

IPolMin Minimum current level for 5 %IB


polarization in % of IBase

RNPol Real part of source Z to be 5 ohm


used for current polarisation

XNPol Imaginary part of source Z to 40 ohm


be used for current
polarisation

IN>Dir Residual current level for 10 %IB


Direction release in % of IBase

2ndHarmStab Second harmonic restrain 20 %


operation in % of IN amplitude

BlkParTransf Enable blocking at parallel Off


transformers

UseStartValue Current level blk at parallel IN4>


transf (step1, 2, 3 or 4)

SOTF SOTF operation mode (Off/ Off


SOTF/ Undertime/ SOTF+
undertime)

Page 94 of 111
Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
ActivationSOTF Select signal that shall activate Open
SOTF

StepForSOTF Selection of step used for Step 2


SOTF

HarmResSOTF Enable harmonic restrain Off


function in SOTF

tSOTF Time delay for SOTF 0. 2 s

t4U Switch- onto- fault active time 1 s

ActUnderTime Select signal to activate under CB position


time (CB Pos/ CBCommand)

tUnderTime Time delay for under time 0. 3 s

Chapter : Current protection->ResidualOverCurr4Step(PTOC,51N/67N)->EF4PTOC: 1->Step 1

DirMode1 Directional mode of step 1 (off, Non- directional


nodir, forward, reverse)

Characterist1 Time delay curve type for step IEC Def. Time
1

IN1> Operate residual current level 30 %IB


for step 1 in % of IBase

t1 Independent (defenite) time 1. 4 s


delay of step 1

k1 Time multiplier for the 0. 14


dependent time delay for step
1

IN1Mult Multiplier for scaling the 2


current setting value for step 1

t1Min Minimum operate time for 0 s


inverse curves for step 1

ResetTypeCrv1 Reset curve type for step 1 Instantaneous

tReset1 Reset curve type for step 1 0. 02 s

HarmRestrain1 Enable block of step 1 from On


harmonic restrain

tPCrv1 Parameter P for customer 1


programmable curve for step 1

tACrv1 Parameter A for customer 13. 5


programmable curve for step 1

tBCrv1 Parameter B for customer 0


programmable curve for step 1

tCCrv1 Parameter C for customer 1


programmable curve for step 1

tPRCrv1 Parameter PR for customer 0. 5


programmable curve for step 1

tTRCrv1 Parameter TR for customer 13. 5


programmable curve for step 1

Page 95 of 111
Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
tCRCrv1 Parameter CR for customer 1
programmable curve for step 1

Chapter : Current protection->ResidualOverCurr4Step(PTOC,51N/67N)->EF4PTOC: 1->Step 2

DirMode2 Directional mode of step 2 (off, Non- directional


nodir, forward, reverse)

Characterist2 Time delay curve type for step IEC Def. Time
2

IN2> Operate residual current level 606 %IB


for step 2 in % of IBase

t2 Independent (definitive) time 0. 1 s


delay of step 2

k2 Time multiplier for the 0. 05


dependent time delay for step
2

IN2Mult Multiplier for scaling the 2


current setting value for step 2

t2Min Minimum operate time for 0 s


inverse curves step 2

ResetTypeCrv2 Reset curve type for step 2 Instantaneous

tReset2 Reset curve type for step 2 0. 02 s

HarmRestrain2 Enable block of step 2 from On


harmonic restrain

tPCrv2 Parameter P for customer 1


programmable curve for step 2

tACrv2 Parameter A for customer 13. 5


programmable curve for step 2

tBCrv2 Parameter B for customer 0


programmable curve for step 2

tCCrv2 Parameter C for customer 1


programmable curve for step 2

tPRCrv2 Parameter PR for customer 0. 5


programmable curve for step 2

tTRCrv2 Parameter TR for customer 13. 5


programmable curve for step 2

tCRCrv2 Parameter CR for customer 1


programmable curve for step 2

Chapter : Current protection->ResidualOverCurr4Step(PTOC,51N/67N)->EF4PTOC: 1->Step 3

DirMode3 Directional mode of step 3 (off, Off


nodir, forward, reverse)

Characterist3 Time delay curve type for step ANSI Def. Time
3

IN3> Operate residual current level 33 %IB


for step 3 in % of IBase

t3 Independent time delay of step 0. 8 s


3

k3 Time multiplier for the 0. 05


dependent time delay for step
3

Page 96 of 111
Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
IN3Mult Multiplier for scaling the 2
current setting value for step 3

t3Min Minimum operate time for 0 s


inverse curves for step 3

ResetTypeCrv3 Reset curve type for step 3 Instantaneous

tReset3 Reset curve type for step 3 0. 02 s

HarmRestrain3 Enable block of step 3 from On


harmonic restrain

tPCrv3 Parameter P for customer 1


programmable curve for step 3

tACrv3 Parameter A for customer 13. 5


programmable curve for step 3

tBCrv3 Parameter B for customer 0


programmable curve for step 3

tCCrv3 Parameter C for customer 1


programmable curve step 3

tPRCrv3 Parameter PR for customer 0. 5


programmable curve step 3

tTRCrv3 Parameter TR for customer 13. 5


programmable curve step 3

tCRCrv3 Parameter CR for customer 1


programmable curve for step 3

Chapter : Current protection->ResidualOverCurr4Step(PTOC,51N/67N)->EF4PTOC: 1->Step 4

DirMode4 Directional mode of step 4 (off, Off


nodir, forward, reverse)

Characterist4 Time delay curve type for step ANSI Def. Time
4

IN4> Operate residual current level 17 %IB


for step 4 in % of IBase

t4 Independent (definitive) time 1. 2 s


delay of step 4

k4 Time multiplier for the 0. 05


dependent time delay for step
4

IN4Mult Multiplier for scaling the 2


current setting value for step 4

t4Min Minimum operate time in 0 s


inverse curves step 4

ResetTypeCrv4 Reset curve type for step 4 Instantaneous

tReset4 Reset curve type for step 4 0. 02 s

HarmRestrain4 Enable block of step 4 from On


harmonic restrain

tPCrv4 Parameter P for customer 1


programmable curve for step 4

tACrv4 Parameter A for customer 13. 5


programmable curve step 4

tBCrv4 Parameter B for customer 0


programmable curve for step 4

Page 97 of 111
Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
tCCrv4 Parameter C for customer 1
programmable curve step 4

tPRCrv4 Parameter PR for customer 0. 5


programmable curve step 4

tTRCrv4 Parameter TR for customer 13. 5


programmable curve step 4

tCRCrv4 Parameter CR for customer 1


programmable curve step 4

Chapter : Current protection->ResidualOverCurr4Step(PTOC,51N/67N)->EF4PTOC: 2->General

Operation Operation Off / On On

IBase Base value for current settings 100 A

UBase Base value for voltage settings 500 kV

AngleRCA Relay characteristic angle 65 Deg


(RCA)

polMethod Type of polarization Voltage

UPolMin Minimum voltage level for 1 %UB


polarization in % of UBase

IPolMin Minimum current level for 5 %IB


polarization in % of IBase

RNPol Real part of source Z to be 5 ohm


used for current polarisation

XNPol Imaginary part of source Z to 40 ohm


be used for current
polarisation

IN>Dir Residual current level for 10 %IB


Direction release in % of IBase

2ndHarmStab Second harmonic restrain 20 %


operation in % of IN amplitude

BlkParTransf Enable blocking at parallel Off


transformers

UseStartValue Current level blk at parallel IN4>


transf (step1, 2, 3 or 4)

SOTF SOTF operation mode (Off/ Off


SOTF/ Undertime/ SOTF+
undertime)

ActivationSOTF Select signal that shall activate Open


SOTF

StepForSOTF Selection of step used for Step 2


SOTF

HarmResSOTF Enable harmonic restrain Off


function in SOTF

tSOTF Time delay for SOTF 0. 2 s

t4U Switch- onto- fault active time 1 s

ActUnderTime Select signal to activate under CB position


time (CB Pos/ CBCommand)

Page 98 of 111
Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
tUnderTime Time delay for under time 0. 3 s

Chapter : Current protection->ResidualOverCurr4Step(PTOC,51N/67N)->EF4PTOC: 2->Step 1

DirMode1 Directional mode of step 1 (off, Non- directional


nodir, forward, reverse)

Characterist1 Time delay curve type for step IEC Def. Time
1

IN1> Operate residual current level 60 %IB


for step 1 in % of IBase

t1 Independent (defenite) time 1. 4 s


delay of step 1

k1 Time multiplier for the 0. 14


dependent time delay for step
1

IN1Mult Multiplier for scaling the 2


current setting value for step 1

t1Min Minimum operate time for 0 s


inverse curves for step 1

ResetTypeCrv1 Reset curve type for step 1 Instantaneous

tReset1 Reset curve type for step 1 0. 02 s

HarmRestrain1 Enable block of step 1 from On


harmonic restrain

tPCrv1 Parameter P for customer 1


programmable curve for step 1

tACrv1 Parameter A for customer 13. 5


programmable curve for step 1

tBCrv1 Parameter B for customer 0


programmable curve for step 1

tCCrv1 Parameter C for customer 1


programmable curve for step 1

tPRCrv1 Parameter PR for customer 0. 5


programmable curve for step 1

tTRCrv1 Parameter TR for customer 13. 5


programmable curve for step 1

tCRCrv1 Parameter CR for customer 1


programmable curve for step 1

Chapter : Current protection->ResidualOverCurr4Step(PTOC,51N/67N)->EF4PTOC: 2->Step 2

DirMode2 Directional mode of step 2 (off, Off


nodir, forward, reverse)

Characterist2 Time delay curve type for step IEC Def. Time
2

IN2> Operate residual current level 100 %IB


for step 2 in % of IBase

t2 Independent (definitive) time 0. 2 s


delay of step 2

k2 Time multiplier for the 0. 05


dependent time delay for step
2

IN2Mult Multiplier for scaling the 2

Page 99 of 111
Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
current setting value for step 2

t2Min Minimum operate time for 0 s


inverse curves step 2

ResetTypeCrv2 Reset curve type for step 2 Instantaneous

tReset2 Reset curve type for step 2 0. 02 s

HarmRestrain2 Enable block of step 2 from On


harmonic restrain

tPCrv2 Parameter P for customer 1


programmable curve for step 2

tACrv2 Parameter A for customer 13. 5


programmable curve for step 2

tBCrv2 Parameter B for customer 0


programmable curve for step 2

tCCrv2 Parameter C for customer 1


programmable curve for step 2

tPRCrv2 Parameter PR for customer 0. 5


programmable curve for step 2

tTRCrv2 Parameter TR for customer 13. 5


programmable curve for step 2

tCRCrv2 Parameter CR for customer 1


programmable curve for step 2

Chapter : Current protection->ResidualOverCurr4Step(PTOC,51N/67N)->EF4PTOC: 2->Step 3

DirMode3 Directional mode of step 3 (off, Off


nodir, forward, reverse)

Characterist3 Time delay curve type for step ANSI Def. Time
3

IN3> Operate residual current level 33 %IB


for step 3 in % of IBase

t3 Independent time delay of step 0. 8 s


3

k3 Time multiplier for the 0. 05


dependent time delay for step
3

IN3Mult Multiplier for scaling the 2


current setting value for step 3

t3Min Minimum operate time for 0 s


inverse curves for step 3

ResetTypeCrv3 Reset curve type for step 3 Instantaneous

tReset3 Reset curve type for step 3 0. 02 s

HarmRestrain3 Enable block of step 3 from On


harmonic restrain

tPCrv3 Parameter P for customer 1


programmable curve for step 3

tACrv3 Parameter A for customer 13. 5


programmable curve for step 3

tBCrv3 Parameter B for customer 0


programmable curve for step 3

Page 100 of 111


Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
tCCrv3 Parameter C for customer 1
programmable curve step 3

tPRCrv3 Parameter PR for customer 0. 5


programmable curve step 3

tTRCrv3 Parameter TR for customer 13. 5


programmable curve step 3

tCRCrv3 Parameter CR for customer 1


programmable curve for step 3

Chapter : Current protection->ResidualOverCurr4Step(PTOC,51N/67N)->EF4PTOC: 2->Step 4

DirMode4 Directional mode of step 4 (off, Off


nodir, forward, reverse)

Characterist4 Time delay curve type for step ANSI Def. Time
4

IN4> Operate residual current level 17 %IB


for step 4 in % of IBase

t4 Independent (definitive) time 1. 2 s


delay of step 4

k4 Time multiplier for the 0. 05


dependent time delay for step
4

IN4Mult Multiplier for scaling the 2


current setting value for step 4

t4Min Minimum operate time in 0 s


inverse curves step 4

ResetTypeCrv4 Reset curve type for step 4 Instantaneous

tReset4 Reset curve type for step 4 0. 02 s

HarmRestrain4 Enable block of step 4 from On


harmonic restrain

tPCrv4 Parameter P for customer 1


programmable curve for step 4

tACrv4 Parameter A for customer 13. 5


programmable curve step 4

tBCrv4 Parameter B for customer 0


programmable curve for step 4

tCCrv4 Parameter C for customer 1


programmable curve step 4

tPRCrv4 Parameter PR for customer 0. 5


programmable curve step 4

tTRCrv4 Parameter TR for customer 13. 5


programmable curve step 4

tCRCrv4 Parameter CR for customer 1


programmable curve step 4

Chapter : Current protection->ThermalOverload2TimeConst(PTTR,49)->TRPTTR: 1

Operation Operation Off / On Off

IBase Base current in A 400 A

IRef Reference current in % of 100 %IB


IBASE

Page 101 of 111


Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
IRefMult Multiplication Factor for 1
reference current

IBase1 Base current, IBase1 without 100 %IB


Cooling inpout in % of IBASE

IBase2 Base Current, IBase2, with 100 %IB


Cooling input ON in % of
IBASE

Tau1 Time constant without cooling 60 Min


input in min, with IBase1

Tau2 Time constant with cooling 60 Min


input in min, with IBase2

IHighTau1 Current Sett, in % of IBase1 100 %IB1


for rescaling TC1 by TC1-
IHIGH

Tau1High Multiplier in % to TC1 when 100 %tC1


current is > IHIGH- TC1

ILowTau1 Current Set, in % of IBase1 100 %IB1


for rescaling TC1 by TC1-
ILOW

Tau1Low Multiplier in % to TC1 when 100 %tC1


current is < ILOW- TC1

IHighTau2 Current Set, in % of IBase2 100 %IB2


for rescaling TC2 by TC2-
IHIGH

Tau2High Multiplier in % to TC2 when 100 %tC2


current is >IHIGH- TC2

ILowTau2 Current Set, in % of IBase2 100 %IB2


for rescaling TC2 by TC2-
ILOW

Tau2Low Multiplier in % to TC2 when 100 %tC2


current is < ILOW- TC2

ITrip Steady state operate current 110 %IBx


level in % of IBasex

Alarm1 First alarm level in % of heat 80 %Itr


content trip value

Alarm2 Second alarm level in % of 90 %Itr


heat content trip value

ResLo Lockout reset level in % of 60 %Itr


heat content trip value

ThetaInit Initial Heat content, in % of 50 %


heat content trip value

Warning Time setting, below which 30 Min


warning would be set (in min)

tPulse Length of the pulse for trip 0. 1 s


signal (in msec).

Chapter : Secondary system supervision->CurrentCircuitSupervison(RDIF)->CCSRDIF: 1

Operation Operation Off / On Off

IBase IBase value for current level 400 A


detectors

Ip>Block Block of the function at high 150 %IB

Page 102 of 111


Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
phase current, in % of IBase

IMinOp Minimum operate current 20 %IB


differential level in % of IBase

Chapter : Secondary system supervision->FuseFailure(RFUF)->SDDRFUF: 1

Operation Operation Off / On On

IBase Base current 400 A

UBase Base voltage 500 kV

OpMode Operating mode selection UZsIZs OR UNsINs

3U0> Operate level of residual 30 %UB


overvoltage element in % of
UBase

3I0< Operate level of residual 10 %IB


undercurrent element in % of
IBase

3U2> Operate level of neg seq 30 %UB


overvoltage element in % of
UBase

3I2< Operate level of neg seq 10 %IB


undercurrent element in % of
IBase

OpDUDI Operation of change based On


function Off/ On

DU> Operate level of change in 60 %UB


phase voltage in % of UBase

DI< Operate level of change in 15 %IB


phase current in % of IBase

UPh> Operate level of phase voltage 70 %UB


in % of UBase

IPh> Operate level of phase current 10 %IB


in % of IBase

SealIn Seal in functionality Off/ On On

USealln< Operate level of seal- in 70 %UB


phase voltage in % of UBase

IDLD< Operate level for open phase 5 %IB


current detection in % of IBase

UDLD< Operate level for open phase 60 %UB


voltage detection in % of
UBase

Chapter : Voltage protection->LossOfVoltage(PTUV,27)->LOVPTUV: 1

Operation Operation Off/ On Off

UBase Base voltage 500 kV

UPE Operate voltagein% of base 70 %UB


voltage Ubase

tTrip Operate time delay 7 s

tPulse Duration of TRIP pulse 0. 15 s

tBlock Time delay to block when all 5 s


3ph voltages are not low

Page 103 of 111


Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
tRestore Time delay for enable the 3 s
function after restoration

Chapter : Voltage protection->OverVoltage2Step(PTOV,59)->OV2PTOV: 1->General

Operation Operation Off / On On

UBase Base voltage 500 kV

Chapter : Voltage protection->OverVoltage2Step(PTOV,59)->OV2PTOV: 1->Step 1

OperationStep1 Enable execution of step 1 On

Characterist1 Selection of time delay curve Definite time


type for step 1

OpMode1 Number of phases required for 3 out of 3


op (1 of 3, 2 of 3, 3 of 3) from
step 1

U1> Voltage setting/ start val (DT 120 %UB


& IDMT) in % of UBase, step
1

t1 Definitive time delay of step 1 5 s

tReset1 Reset time delay used in IEC 0. 025 s


Definite Time curve step 1

t1Min Minimum operate time for 5 s


inverse curves for step 1

ResetTypeCrv1 Selection of reset curve type Instantaneous


for step 1

tIReset1 Time delay in IDMT reset (s), 0. 025 s


step 1

k1 Time multiplier for the inverse 0. 05


time delay for step 1

ACrv1 Parameter A for customer 1


programmable curve for step 1

BCrv1 Parameter B for customer 1


programmable curve for step 1

CCrv1 Parameter C for customer 0


programmable curve for step 1

DCrv1 Parameter D for customer 0


programmable curve for step 1

PCrv1 Parameter P for customer 1


programmable curve for step 1

CrvSat1 Tuning param for prog. over 0 %


voltage IDMT curve, step 1

HystAbs1 Absolute hysteresis in % of 0. 5 %UB


UBase, step 1

Chapter : Voltage protection->OverVoltage2Step(PTOV,59)->OV2PTOV: 1->Step 2

OperationStep2 Enable execution of step 2 On

Characterist2 Selection of time delay curve Definite time


type for step 2

OpMode2 Number of phases required for 1 out of 3


op (1 of 3, 2 of 3, 3 of 3) from
step 2

Page 104 of 111


Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
U2> Voltage setting/ start val (DT 150 %UB
& IDMT) in % of UBase, step
2

t2 Definitive time delay of step 2 2 s

tReset2 Reset time delay used in IEC 0. 025 s


Definite Time curve step 2

t2Min Minimum operate time for 5 s


inverse curves for step 2

ResetTypeCrv2 Selection of reset curve type Instantaneous


for step 2

tIReset2 Time delay in IDMT reset (s), 0. 025 s


step 2

k2 Time multiplier for the inverse 0. 05


time delay for step 2

ACrv2 Parameter A for customer 1


programmable curve for step 2

BCrv2 Parameter B for customer 1


programmable curve for step 2

CCrv2 Parameter C for customer 0


programmable curve for step 2

DCrv2 Parameter D for customer 0


programmable curve for step 2

PCrv2 Parameter P for customer 1


programmable curve for step 2

CrvSat2 Tuning param for prog. over 0 %


voltage IDMT curve, step 2

HystAbs2 Absolute hysteresis in % of 0. 5 %UB


UBase, step 2

Chapter : Voltage protection->ResidualOverVoltage2Step(PTOV,59N)->ROV2PTOV: 1->General

Operation Operation Off / On Off

UBase Base voltage 500 kV

Chapter : Voltage protection->ResidualOverVoltage2Step(PTOV,59N)->ROV2PTOV: 1->Step 1

OperationStep1 Enable execution of step 1 On

Characterist1 Selection of time delay curve Definite time


type for step 1

U1> Voltage setting/ start val (DT 30 %UB


& IDMT), step 1 in % of
UBase

t1 Definitive time delay of step 1 5 s

tReset1 Reset time delay used in IEC 0. 025 s


Definite Time curve step 1

t1Min Minimum operate time for 5 s


inverse curves for step 1

ResetTypeCrv1 Selection of reset curve type Instantaneous


for step 1

tIReset1 Time delay in IDMT reset (s), 0. 025 s


step 1

Page 105 of 111


Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
k1 Time multiplier for the inverse 0. 05
time delay for step 1

ACrv1 Parameter A for customer 1


programmable curve for step 1

BCrv1 Parameter B for customer 1


programmable curve for step 1

CCrv1 Parameter C for customer 0


programmable curve for step 1

DCrv1 Parameter D for customer 0


programmable curve for step 1

PCrv1 Parameter P for customer 1


programmable curve for step 1

CrvSat1 Tuning param for prog. over 0 %


voltage IDMT curve, step 1

HystAbs1 Absolute hysteresis in % of 0. 5 %UB


UBase, step 1

Chapter : Voltage protection->ResidualOverVoltage2Step(PTOV,59N)->ROV2PTOV: 1->Step 2

OperationStep2 Enable execution of step 2 On

Characterist2 Selection of time delay curve Definite time


type for step 2

U2> Voltage setting/ start val (DT 45 %UB


& IDMT), step 2 in % of
UBase

t2 Definitive time delay of step 2 5 s

tReset2 Time delay in DT reset (s), 0. 025 s


step 2

t2Min Minimum operate time for 5 s


inverse curves for step 2

ResetTypeCrv2 Selection of reset curve type Instantaneous


for step 2

tIReset2 Time delay in IDMT reset (s), 0. 025 s


step 2

k2 Time multiplier for the inverse 0. 05


time delay for step 2

ACrv2 Parameter A for customer 1


programmable curve for step 2

BCrv2 Parameter B for customer 1


programmable curve for step 2

CCrv2 Parameter C for customer 0


programmable curve for step 2

DCrv2 Parameter D for customer 0


programmable curve for step 2

PCrv2 Parameter P for customer 1


programmable curve for step 2

CrvSat2 Tuning param for prog. over 0 %


voltage IDMT curve, step 2

Page 106 of 111


Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
HystAbs2 Absolute hysteresis in % of 0. 5 %UB
UBase, step 2

Chapter : Voltage protection->UnderVoltage2Step(PTUV,27)->UV2PTUV: 1->General

Operation Operation Off / On Off

UBase Base voltage 500 kV

Chapter : Voltage protection->UnderVoltage2Step(PTUV,27)->UV2PTUV: 1->Step 1

OperationStep1 Enable execution of step 1 Off

Characterist1 Selection of time delay curve Definite time


type for step 1

OpMode1 Number of phases required for 1 out of 3


op (1 of 3, 2 of 3, 3 of 3) from
step 1

U1< Voltage setting/ start val (DT 70 %UB


& IDMT) in % of UBase, step
1

t1 Definitive time delay of step 1 5 s

tReset1 Reset time delay used in IEC 0. 025 s


Definite Time curve step 1

t1Min Minimum operate time for 5 s


inverse curves for step 1

ResetTypeCrv1 Selection of reset curve type Instantaneous


for step 1

tIReset1 Time delay in IDMT reset (s), 0. 025 s


step 1

k1 Time multiplier for the inverse 0. 05


time delay for step 1

ACrv1 Parameter A for customer 1


programmable curve for step 1

BCrv1 Parameter B for customer 1


programmable curve for step 1

CCrv1 Parameter C for customer 0


programmable curve for step 1

DCrv1 Parameter D for customer 0


programmable curve for step 1

PCrv1 Parameter P for customer 1


programmable curve for step 1

CrvSat1 Tuning param for prog. under 0 %


voltage IDMT curve, step 1

IntBlkSel1 Internal (low level) blocking Block of trip


mode, step 1

IntBlkStVal1 Voltage setting for internal 20 %UB


blocking in % of UBase, step
1

tBlkUV1 Time delay of internal (low 0 s


level) blocking for step 1

Page 107 of 111


Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
HystAbs1 Absolute hysteresis in % of 0. 5 %UB
UBase, step 1

Chapter : Voltage protection->UnderVoltage2Step(PTUV,27)->UV2PTUV: 1->Step 2

OperationStep2 Enable execution of step 2 Off

Characterist2 Selection of time delay curve Definite time


type for step 2

OpMode2 Number of phases required for 1 out of 3


op (1 of 3, 2 of 3, 3 of 3) from
step 2

U2< Voltage setting/ start val (DT 50 %UB


& IDMT) in % of UBase, step
2

t2 Definitive time delay of step 2 5 s

tReset2 Reset time delay used in IEC 0. 025 s


Definite Time curve step 2

t2Min Minimum operate time for 5 s


inverse curves for step 2

ResetTypeCrv2 Selection of reset curve type Instantaneous


for step 2

tIReset2 Time delay in IDMT reset (s), 0. 025 s


step 2

k2 Time multiplier for the inverse 0. 05


time delay for step 2

ACrv2 Parameter A for customer 1


programmable curve for step 2

BCrv2 Parameter B for customer 1


programmable curve for step 2

CCrv2 Parameter C for customer 0


programmable curve for step 2

DCrv2 Parameter D for customer 0


programmable curve for step 2

PCrv2 Parameter P for customer 1


programmable curve for step 2

CrvSat2 Tuning param for prog. under 0 %


voltage IDMT curve, step 2

IntBlkSel2 Internal (low level) blocking Block of trip


mode, step 2

IntBlkStVal2 Voltage setting for internal 20 %UB


blocking in % of UBase, step
2

tBlkUV2 Time delay of internal (low 0 s


level) blocking for step 2

HystAbs2 Absolute hysteresis in % of 0. 5 %UB


UBase, step 2

Chapter : Logic->TripLogic(PTRC,94)->SMPPTRC: 1

Operation Operation Off / On On

Program Three ph; single or three ph; 1ph/ 3ph


single, two or three ph trip

Page 108 of 111


Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
TripLockout On: activate output Off
(CLLKOUT) and trip latch,
Off: only outp

AutoLock On: lockout from input Off


(SETLKOUT) and trip, Off:
only inp

tTripMin Minimum duration of trip 0. 07 s


output signal

Chapter : Logic->TripMatrix(GGIO)->TMAGGIO: 1

Operation Operation Off / On On

PulseTime Output pulse time 0. 07 s

OnDelay Output on delay time 0 s

OffDelay Output off delay time 0 s

ModeOutput1 Mode for output , 1 steady or Steady


pulsed

ModeOutput2 Mode for output 2, steady or Steady


pulsed

ModeOutput3 Mode for output 3, steady or Steady


pulsed

Chapter : Logic->TripMatrix(GGIO)->TMAGGIO: 4

Operation Operation Off / On On

PulseTime Output pulse time 0. 07 s

OnDelay Output on delay time 0 s

OffDelay Output off delay time 0 s

ModeOutput1 Mode for output , 1 steady or Steady


pulsed

ModeOutput2 Mode for output 2, steady or Steady


pulsed

ModeOutput3 Mode for output 3, steady or Steady


pulsed

Chapter : Logic->LogicGate->GATE: 21

Operation Operation Off/ On On

Chapter : Control->Synchronizing(RSYN,25)->SESRSYN: 1

Operation Operation Off / On Off

SelPhaseBus1 Select phase for bus1 phase2

SelPhaseBus2 Select phase for bus2 phase2

SelPhaseLine1 Select phase for line1 phase2

SelPhaseLine2 Select phase for line2 phase2

CBConfig Select CB configuration No voltage sel.

UBase Base voltage in kV 400 kV

PhaseShift Phase shift 0 Deg

URatio Voltage ratio 1

OperationSynch Operation for synchronizing Off

Page 109 of 111


Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
function Off/ On

UHighBusSynch Voltage high limit bus for 80 %UB


synchronizing in % of UBase

UHighLineSynch Voltage high limit line for 80 %UB


synchronizing in % of UBase

UDiffSynch Voltage difference limit for 10 %UB


synchronizing in % of UBase

FreqDiffMin Minimum frequency difference 0. 01 Hz


limit for synchronizing

FreqDiffMax Maximum frequency difference 0. 2 Hz


limit for synchronizing

FreqRateChange Maximum allowed frequency 0. 3 Hz/ s


rate of change

tBreaker Closing time of the breaker 0. 08 s

tClosePulse Breaker closing pulse duration 0. 2 s

tMaxSynch Resets synch if no close has 600 s


been made before set time

tMinSynch Minimum time to accept 2 s


synchronizing conditions

OperationSC Operation for synchronism Off


check function Off/ On

UHighBusSC Voltage high limit bus for 80 %UB


synchrocheck in % of UBase

UHighLineSC Voltage high limit line for 80 %UB


synchrocheck in % of UBase

UDiffSC Voltage difference limit in % of 15 %UB


UBase

FreqDiffA Frequency difference limit 0. 01 Hz


between bus and line Auto

FreqDiffM Frequency difference limit 0. 01 Hz


between bus and line Manual

PhaseDiffA Phase angle difference limit 25 Deg


between bus and line Auto

PhaseDiffM Phase angle difference limit 25 Deg


between bus and line Manual

tSCA Time delay output for 0. 1 s


synchrocheck Auto

tSCM Time delay output for 0. 1 s


synchrocheck Manual

AutoEnerg Automatic energizing check DBLL


mode

ManEnerg Manual energizing check Both


mode

ManEnergDBDL Manual dead bus, dead line Off


energizing

UHighBusEnerg Voltage high limit bus for 80 %UB


energizing check in % of
UBase

Page 110 of 111


Grupo de Ajustes: Setting Group1
Nombre Descripcin Valor Unidad
UHighLineEnerg Voltage high limit line for 80 %UB
energizing check in % of
UBase

ULowBusEnerg Voltage low limit bus for 40 %UB


energizing check in % of
UBase

ULowLineEnerg Voltage low limit line for 40 %UB


energizing check in % of
UBase

UMaxEnerg Maximum voltage for 115 %UB


energizing in % of UBase

tAutoEnerg Time delay for automatic 0. 1 s


energizing check

tManEnerg Time delay for manual 0. 1 s


energizing check

Grupo de Ajustes: Setting Group2

Nombre Descripcin Valor Unidad


-- Empty Table --

Grupo de Ajustes: Setting Group3

Nombre Descripcin Valor Unidad


-- Empty Table --

Grupo de Ajustes: Setting Group4

Nombre Descripcin Valor Unidad


-- Empty Table --

Grupo de Ajustes: Setting Group5

Nombre Descripcin Valor Unidad


-- Empty Table --

Grupo de Ajustes: Setting Group6

Nombre Descripcin Valor Unidad


-- Empty Table --