Anda di halaman 1dari 7

IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 29, NO.

6, NOVEMBER 2014 3041

Analytical Method for Short-Term Voltage Stability


Using the Stability Boundary in the P-V Plane
K. Kawabe, Member, IEEE, and K. Tanaka

AbstractShort-term voltage stability is one of the issues of con- Slip of the induction motor.
cern for power system operations. As dispersed power generation
is connected to middle- and low-voltage transmission networks, the Inertia constant of the induction motor.
development of analytical methods will become more important.
This paper describes a stability boundary line in the P-V plane Load factor of the induction motor.
of the load bus for the analysis of short-term voltage stability. By Electromagnetic torque of the induction motor.
comparing the operating point of the load with the boundary line,
we can visually determine the acceleration or deceleration state Mechanical torque of the induction motor.
of the induction motor, thereby clearly explaining the short-term
voltage instability phenomena. In addition, the idea of the stability Positive constant.
boundary is applied to voltage stability assessment and emergency Conductance of the constant impedance load.
controls such as reactive power compensation. Numerical simula-
tions are carried out for a single-load infinite-bus system to explain Conductance of the induction motor load.
the basic theory of the proposed method and to provide examples
of its application.
I. INTRODUCTION
Index TermsInduction motors, reactive power control, short-
term voltage stability, stability analysis.
S HORT-TERM voltage stability is one of the issues of con-
cern during the transient region after a large disturbance
in a power system [1]. Short-term voltage stability is less well-
NOMENCLATURE known than rotor angle stability, also known as transient sta-
bility, owing to its lower frequency of occurrence. Difficulties in
Differential operator with respect to time. modeling the dynamic load, which can significantly contribute
to voltage collapse, and setting parameters have also deterred
Terminal voltage of the induction motor.
power system operators from analyzing the short-term voltage
Stator current of the induction motor. stability in practical power systems. On the other hand, the basic
Rotor current of the induction motor. mechanism of short-term voltage stability caused by the dy-
namic characteristics of induction motor loads is discussed in
Stator flux linkage of the induction motor. [2] and [3]. Several papers have investigated analytical methods
Rotor flux linkage of the induction motor. for short-term voltage stability [4][6]. It is also pointed out that
short term voltage stability is closely related to rotor angle sta-
Stator resistance of the induction motor.
bility [7], [8].
Rotor resistance of the induction motor. As dispersed power generation such as photovoltaic power
Stator leakage reactance of the induction motor. generation is connected to middle- and low-voltage transmis-
sion networks, short-term voltage stability may deteriorate be-
Rotor leakage reactance of the induction motor. cause renewable power generation is connected via converters
Exciting reactance of the induction motor. and is prone to stop operation after a voltage sag. Therefore, the
development of an analytical method for short-term voltage sta-
Standard frequency.
bility will become more important to comprehend the impact of
Rotor speed of the induction motor. dispersed power generation on short-term voltage stability and
to develop countermeasures.
This paper describes a novel analytical method for short-
Manuscript received November 17, 2013; revised February 02, 2014; ac-
term voltage stability that is motivated by [3] and [4], in which
cepted March 17, 2014. Date of publication April 04, 2014; date of current
version October 16, 2014. This work was supported in part by CREST pro- the authors propose an analytical method using the transient
gram, Creation of Fundamental Theory and Technology to Establish a Coop- P-V curves of the targeted load bus. Although the transient P-V
erative Distributed Energy Management System and Integration of Technolo-
curves present the transmission characteristics of the system to
gies across Broad Disciplines toward Social Application, of Japan Science and
Technology Agency (JST). Paper no. TPWRS-01381-2013. the load bus during the transient period, they do not show the
The authors are with the Graduate School of Science and Engineering, Uni- state of the induction motor load because the stability boundary
versity of Toyama, Gofuku 3190, Japan.
is not located at the nose point of the transient P-V curve, unlike
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. the static P-V curve. The authors in [3] pointed out that the sta-
Digital Object Identifier 10.1109/TPWRS.2014.2313152 bility boundary is not located at the nose point of the transient

0885-8950 2014 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
3042 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 29, NO. 6, NOVEMBER 2014

P-V curve. However, its precise position in the P-V plane has
not been demonstrated at present. In this paper, we describe a
stability boundary in the P-V plane. The analytical method de-
veloped using the stability boundary and transient P-V curves
enables us to clearly explain the short-term voltage stability. In
addition, the idea of a stability boundary is applied to short-term Fig. 1. Equivalent circuit for the induction motor load.
voltage stability assessment and emergency controls such as re-
active power compensation. Numerical simulations are carried
out for a single-load infinite-bus system to explain the basic TABLE I
DATA FOR THE INDUCTION MOTOR LOAD
theory of the proposed method and to provide examples of the
application of this method.

II. DYNAMIC LOAD MODEL

A. Dynamic Load Model The electromagnetic torque is derived from (1)(8) by ne-
The dynamic load model at a load center is assumed to be glecting the time-derivative terms as shown in (10) at the bottom
composed of an induction motor load and a constant impedance of the page.
load that are connected in parallel. The ratio of the induction The mechanical torque is assumed to be a quadratic function
motor load at a load center has a large impact on the short-term of the rotor speed, as expressed in (11), considering that a large
voltage stability. In this study, this ratio is set at 60%, even part of induction motor loads in Japan are composed of pumps,
though the composition of the loads varies with the load cen- compressors, and blower fans in the industrial sectors:
ters, the season, and the time of the day.
(11)
Fig. 1 shows the equivalent circuit of the induction motor.
Table I summarizes the machine-based data for the induction
motor. The induction motor equations used in this study are ex- B. Load Characteristics in the P-V Plane
pressed in (1)(8) and were derived in [9] for the transient anal-
ysis. Here, the electrical and magnetic variables are shown for In the analysis of the voltage stability in the P-V plane, where
- axes rotating at the standard frequency : P and V represent the active power consumption and the mag-
nitude of the terminal voltage of the load, respectively, the op-
(1) erating point of the load lies at the intersection of the P-V curve
and the load characteristic curve. The change in the load charac-
(2)
teristic curve with respect to the change in the induction motor
(3) speed is briefly explained in the following discussion.
(4) The load characteristic curve of the dynamic load model is
(5) given by (12):
(6)
(12)
(7)
(8) Fig. 2 shows the change in with respect to the change in
for the dynamic load model with an induction motor ratio
In this study, the induction motor load is modeled as a first-order of 60%. For increases as is decreased from
model that neglects the transient term of the magnetic flux in to . For decreases as is decreased
(1)(4) to focus on the fundamental characteristic of the load for from to . Here, the rotor speed that achieves the
the development of the new analytical method. Therefore, the maximum value of the conductance is defined as . Therefore,
swing equation in (9) is considered to represent the dynamics of the graph of the load characteristic curve changes as deceler-
the load: ates, as shown in Fig. 3. In this study, deceleration is assumed to
be caused by a large disturbance such as a three-line-to-ground
(9) (3LG) fault.

(10)
KAWABE AND TANAKA: ANALYTICAL METHOD FOR SHORT-TERM VOLTAGE STABILITY 3043

Fig. 2. Relationship between the rotor speed and the conductance of the induc-
tion motor. Fig. 5. Change in the voltage at the load bus. (a) s. (b) s.

Fig. 3. Change in the load characteristics for the deceleration of an induction


motor. (a) . (b) .

Fig. 6. Analysis via the transient P-V curves.

on the basic mechanism of the voltage instability phenomena


Fig. 4. Single-load infinite-bus system. and the basic concept of the transient P-V curve.

B. Transient P-V Curve Analysis


III. TRANSIENT P-V CURVE Fig. 6 illustrates the changes in the operating point of the load
in the P-V plane and also shows the transient P-V curves for the
A. Numerical Example of a Voltage Collapse load bus in the normal and emergency states. The P-V curve in
A numerical simulation for a single-load infinite-bus system the normal state represents to the P-V curve before and after the
(Fig. 4) is carried out to show the short-term voltage insta- voltage sag.
bility phenomena and to explain the transient P-V curve. In The transient P-V curve proposed in [4] can be depicted for
Fig. 4, the extra-high-voltage (EHV) network is represented by given time steps during the transient period by changing the slip
the infinite bus, and the dynamic characteristics of the genera- of the induction motor load over the entire operating range. The
tors are neglected to focus on the short-term voltage stability. transient P-V curve represents the power transfer capability to
The short-term voltage stability depends on the dynamic char- the load at a given time and visually indicates the short-term
acteristics of the induction motor load and the power transfer voltage stability at each time. Therefore, it is helpful to explain
characteristics of the transmission system to the load. The ag- the change of the operating point of the load during the transient
gregated load center is modeled by the dynamic load that is period. This is because the bus voltage is prone to lose stability
connected through the aggregated transmission and subtrans- when the operating point lies in the lower region of the curve.
mission lines. The total power consumption at the load center When a fault occurs in the EHV network, the transient P-V
is shown in Fig. 4. The bus voltages in the normal state are con- curve shrinks to the lower left, as seen in Fig. 6. The induction
trolled within the appropriate range by the on-load tap-changing motor is decelerating during the fault, and the operating point
transformers and the shunt capacitors at buses 2, 4, and 6. shifts downward as the graph of the load characteristic curve
A 3LG fault in the EHV network is represented by specifying changes, as shown in Fig. 3(a). The operating point recovers
the voltage of the infinite bus from 1.01 to 0.50. The voltage re- upward by clearing the fault at 0.07 s, while it continues to shift
covers to 1.01 after the fault is cleared. Fig. 5 shows the results downward by clearing the fault at 0.10 s.
of the load bus voltage for faults with different fault clearing
times . If the fault clearing time increases from 0.07 s to C. Weak Point of the Transient P-V Curve
0.10 s, the result is a voltage collapse. Here, we neglect pro- It is observed in Fig. 6 that the voltage can recover, even
tection systems such as a load-shedding control system to focus though the operating point enters the lower-half part of the P-V
3044 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 29, NO. 6, NOVEMBER 2014

Fig. 7. Torque-speed characteristics of the induction motor load.


Fig. 8. Change in the rotor speed for each region of the load characteristic
curve.

curve. In other words, the stability boundary is not located at the


nose point of the transient P-V curve, as it is for the static P-V
curve. Therefore, the analysis using the transient P-V curve does
not provide any information about the state of the dynamic load,
which determines the direction of change of the operating point
at each time. In the numerical examples, Fig. 6 cannot explain
why the operating points of the load in the two cases move in
different directions owing to the slight difference in the fault
clearing time.

IV. STABILITY BOUNDARY IN THE P-V PLANE

A. Physical Explanation
The change of the operating point of the dynamic load is dom-
inated by the acceleration of the induction motor. The operating
point moves downward along the P-V curve when the acceler-
ation is negative because the load characteristic curve changes,
as shown in Fig. 3. The acceleration is determined by the bal-
ance of the torques in (9).
Fig. 7 represents the torquespeed characteristics of the in-
duction motor loads. The motor accelerates in the region where
the remainder of the torque is positive, while it decelerates in
the other regions. The characteristic curve changes depending
on the terminal voltage because the electromagnetic torque is a Fig. 9. Stability boundary of the dynamical load in the P-V plane. (a)
function of and , as defined in (10). For a given speed of the . (b) .
induction motor load, there exists a terminal voltage at which
the remainder of the torque is zero. Here, we define an induc-
tion motor speed, , for which the remainder of the torque is for each operating range in Fig. 9 for the sake of explanation,
zero at a terminal voltage of 0.4 p.u. although the two stability boundaries are continuous.
Fig. 8 represents the load characteristic curve for . The stability boundary in Fig. 9(a) divides the region above
The terminal voltage of 0.4 p.u. determines the boundary point the load characteristic curve at into two areas. The left
on the load characteristic curve. For the range where the voltage side of the region represents the unstable region where the in-
is above 0.4 p.u., the induction motor accelerates because the re- duction motor decelerates, while the other side represents the
mainder of the torque is positive, as seen in Fig. 7. The induction stable region. The stability boundary for the operating range of
motor decelerates in the range below the boundary point. also defines the stable and unstable regions, as
By plotting the boundary points for the operating range of shown in Fig. 9(b). Here, the region below the load character-
the induction motor , we obtain the proposed istic curve for does not need to be considered because
stability boundary that enables us to distinguish the sign of the the operating point cannot lie in this region, as shown in Fig. 3.
time derivative of the induction motor speed in the P-V plane.
Fig. 9 shows the stability boundary for the dynamic load. As B. Mathematical Procedure
shown in Fig. 3, the load characteristic curve shifts downwards The stability boundary is the locus of the boundary points
as the induction motor decelerates within the range of on the load characteristic curve for the operating range of the
and then shifts upwards as it continues to decelerate within induction motor . The boundary point for
the range of . The stability boundary is depicted is obtained as follows:
KAWABE AND TANAKA: ANALYTICAL METHOD FOR SHORT-TERM VOLTAGE STABILITY 3045

Fig. 10. Stability boundary analysis and transient P-V curves for the stable case Fig. 11. Stability boundary analysis and transient P-V curves for the unstable
( s). case ( s). The tangent point of the transient P-V curve to the load
characteristic curve is the operating point at .

1) Calculate the terminal voltage at which by boundary. Therefore, the induction motor continues to decel-
(13) derived from (9)(11). Although it is assumed the erate even after fault clearing, and the operating point of the
industrial motor has speed-squared mechanical torque load shifts downwards along the P-V curve.
characteristics, the proposed method can also be applied to As shown in the numerical examples, the proposed stability
other types of motors, such as air-conditioner compressor boundary enables us to clearly explain the short-term voltage
motors, with near-constant torque-speed characteristics behavior because it visually shows the state of the induction
[10] by modifying (11) and therefore (13), shown at the motor load at each operating point.
bottom of the page. The stability boundary also enables us to know the unstable
2) Calculate the active power consumption from (12) equilibrium point (UEP) on the transient P-V curve, as shown
using and . in Figs. 10 and 11. By substituting the power consumption and
As described above, the stability boundary is calculated voltage at the UEP into (12), it is possible to derive the crit-
using only the parameters of the loads. Thus, the computational ical induction motor speed corresponding to the UEP. For a
burden is independent of the sizes of the transmission and single aggregated motor load, the voltage stability of the system
subtransmission systems. is determined by .

C. Stability Boundary and Transient PV Curve Analysis V. APPLICATION OF THE STABILITY BOUNDARY

The proposed stability boundary is applied to the numerical A. Short-Term Voltage Stability Assessment
examples in Fig. 6. Fig. 10 shows the results for the stable case. Fig. 12 describes the stability boundary, transient P-V curve,
The operating point in the normal state lies at the in- and load characteristic curve at for short-term voltage
tersection of the stability boundary with the transient P-V curve. stability assessment of the test system in Fig. 4 with different
This intersection is the stable equilibrium point. The operating induction motor ratios to the total load. Note that the arrows
point jumps to the lower left owing to the 3LG fault at s. on the P-V curve represent the gradient at each operating point
The operating point during the fault is in the unstable region at and are determined by comparing each operating point and the
the left side of the stability boundary. Therefore, the induction corresponding stability boundary.
motor decelerates, and the operating point shifts to the lower In Fig. 12(a), there are two stable equilibrium points (SEPs)
left. After the fault clearing at s, the operating point and a UEP that are the intersection points of the stability
jumps to the upper right. Then, the operating point moves up- boundary and the transient P-V curve. The load operates at SEP
ward along the P-V curve because the operating point lies in the 1 in the normal state. For system conditions with a high induc-
stable region at the right side of the boundary. Note that only tion motor ratio, a voltage collapse can occur if the operating
the stability boundary for the range of is shown point of the load enters the part of the P-V curve lower than the
in Fig. 10 because the induction motor load operates within this UEP. In the unstable case, the operating point moves towards
range in the numerical example. SEP 2.
Fig. 11 shows the results for the unstable case. Unlike On the other hand, there is only one SEP for system condi-
the stable case, the operating point after the fault clearing at tions with a low induction motor ratio, as shown in Fig. 12(b).
s lies in the unstable region at the left side of the The results indicate that a voltage collapse does not occur, even

(13)
3046 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 29, NO. 6, NOVEMBER 2014

Fig. 13. Voltage instability phenomena caused by a disconnection of a trans-


mission route.

Fig. 12. Stability boundary and transient P-V curve for induction motor ratios
of (a) 60% and (b) 20%. The tangent point of the transient P-V curve to the load
characteristic curve is the operating point at . (a) Induction motor ratio: Fig. 14. Prevention of the voltage instability phenomena by reactive power
60%. (b) Induction motor ratio: 20% compensation.

2) Calculate the critical voltage under which the induc-


though the induction motor load significantly decelerates owing
tion motor decelerates and leads to the voltage collapse by
to a voltage sag.
substituting in (13).
As shown in the numerical examples, the positional relation-
3) Execute the power flow calculation where the bus speci-
ship between the stability boundary and the transient P-V curve
fication of the load bus is and . Here, the
can help us understand the short-term voltage stability of the
induction motor speed is set at , and the load is consid-
load center without performing a time-domain numerical sim-
ered as a constant impedance. The calculation obtains the
ulation. This positional relationship can also be useful for the
reactive power flow into the load bus. is the min-
short-term voltage stability assessment of each load center.
imum required value of the reactive power compensation.
Assuming that the reactive power compensation triggers at
B. Reactive Power Compensation
s in the numerical example, is calculated as
The idea of the stability boundary can be applied to calculate 0.157 p.u. by the previously described method.
the critical value of an emergency control action such as reactive Fig. 14 shows the results in the P-V plane when a reactive
power compensation to avoid a short-term voltage collapse. power of 0.16 p.u. is injected at s. Owing to the
Assuming a disconnection of a transmission route in the EHV control action at , the operating point jumps to the
network in Fig. 3 by doubling the impedance between buses 1 upper right. The voltage recovers to the new equilibrium point
and 2 at , a short-term voltage collapse occurs without any because it is located at the right side of the stability boundary.
emergency control action. Fig. 13 shows the voltage instability Here, in the proposed method corresponds to the voltage
phenomenon caused by the fault. The P-V curve shrinks to the of the intersection point between the stability boundary and the
left of the stability boundary owing to the fault, and thus, the load characteristic curve at .
operating point of the load shifts to the lower left. Note that can be regarded as the critical delay time for
Given that reactive power compensation at bus 6 is triggered the reactive power injection of to avoid the voltage collapse.
at , the minimum required value of the reactive power In other words, the critical delay time can also be calculated
is calculated as follows. from the given amount of reactive power compensation by the
1) Obtain the induction motor speed at by a same idea. The critical values can be useful for a fast stability
time-domain numerical simulation in advance or an online estimation to trigger other emergency control actions such as
state estimation. load shedding.
KAWABE AND TANAKA: ANALYTICAL METHOD FOR SHORT-TERM VOLTAGE STABILITY 3047

VI. CONCLUSION [6] Z. Wang, X. Wang, and C. Y. Chung, An analytical method for cal-
culating critical voltage sag clearance time of induction motors, IEEE
We propose a stability boundary line in the P-V plane of the Trans. Power Del., vol. 27, no. 4, pp. 24122414, Oct. 2012.
load bus for the analysis of short-term voltage stability. By com- [7] E. G. Potamianakis and C. D. Vournas, Short-term voltage instability:
paring the operating point of the load with the boundary line, we Effects on synchronous and induction machines, IEEE Trans. Power
Syst., vol. 21, no. 2, pp. 791798, May 2006.
can visually determine the acceleration or deceleration state of [8] K. Kawabe and A. Yokoyama, Study on short-term voltage stability
the induction motor. On the other hand, the transient P-V curve improvement using batteries on extra-high voltage network, in Proc.
IEEE PES PowerTech 2013, Grenoble, France, 2013, A5357KK.
can indicate the transfer characteristics of the transmission net- [9] H. C. Stanley, An analysis of the induction machine, AIEE Trans.,
work to the load. The proposed analytical method using both vol. 57, no. 12, pp. 751757, Dec. 1938.
of them enables us to clearly explain the short-term voltage be- [10] B. J. A. Diaz de Leon II and C. W. Taylor, Understanding and solving
short-term voltage stability problems, in Proc. 2002 IEEE Power Eng.
havior. The idea of the stability boundary can also be useful Soc. Summer Meeting, Chicago, IL, USA, 2002, vol. 2, pp. 745752.
for other applications such as voltage stability assessment and
emergency control.
In our future work, the proposed analytical method should
K. Kawabe (M12) was born in Tokyo, Japan, in
be developed for more practical power systems considering 1984. He received the B.S. degree from Waseda
generators and a more detailed model of induction motor loads. University, Tokyo, Japan, in 2007, and the M.S. and
Ph.D. degrees from the University of Tokyo, Tokyo,
In addition, the proposed method will be applied to investigate Japan, in 2009 and 2012, respectively.
the undesirable impact of dispersed power generation on the He has been with the Graduate School of Science
short-term voltage stability and to develop countermeasures. and Engineering, University of Toyama, Gofuku,
Japan, since 2012 as a visiting assistant professor in
REFERENCES charge of power system engineering.
[1] P. Kundur, J. Paserba, V. Ajjarapu, G. Andersson, A. Bose, C.
Canizares, N. Hatziargyriou, D. Hill, A. Stankovic, C. Taylor, T. Van
Cutsem, and V. Vittal, Definition and classification of power system
stability, IEEE Trans. Power Syst., vol. 19, no. 2, pp. 13871401,
May 2004. K. Tanaka was born in Fukuoka, Japan, in 1951. He
[2] A. E. Hammad and M. Z. El-Sadek, Prevention of transient voltage received the B.S., M.S., and Dr.Eng. degrees from
instabilities due to induction motor loads by static VAR compen- the graduate school of Kyushu University, Fukuoka,
sators, IEEE Trans. Power Syst., vol. 4, no. 3, pp. 11821190, Aug. Japan, in 1974, 1976, and 1996, respectively.
1989. He joined the Central Research Institute of Electric
[3] Y. Sekine and H. Ohtsuki, Cascaded voltage collapse, IEEE Trans. Power Industry (CRIEPI) in 1976 and served as vis-
Power Syst., vol. 5, no. 1, pp. 250256, Feb. 1990. iting researcher at the University of Texas, Arlington,
[4] H. Ohtsuki, A. Yokoyama, and Y. Sekine, Transient P-V curves used TX, USA, from 1981 to 1982. He served as a visiting
for analysis of transient voltage stability, in Proc. 10th-PSCC, Graz, professor at Tohoku University from 2006 to 2009.
Austria, 1990, pp. 12021209. He has been with the Graduate School of Science and
[5] C. D. Vournas and G. A. Manos, Modelling of stalling motors during Engineering, University of Toyama, Gofuku, Japan,
voltage stability studies, IEEE Trans. Power Syst., vol. 13, no. 3, pp. since 2012 as a visiting professor in charge of power system engineering.
775781, Aug. 1998. Dr. Tanaka was given the Outstanding Paper Award of IEE of Japan in 1993.

Anda mungkin juga menyukai