This document summarizes the zone sizing for the air system "BLOCK LOAD BARKA MALL" which serves 1 zone covering a total floor area of 14,291.3 sqm for a mall located in Masqat, Oman. The zone has a maximum cooling load of 1,330 kW and minimum airflow of 1,37718 L/s. There is 1 main zone containing 38 internal spaces/zones including a food court, retail shops, and common areas. Each internal space is listed with its cooling load, airflow, floor area and other details.
This document summarizes the zone sizing for the air system "BLOCK LOAD BARKA MALL" which serves 1 zone covering a total floor area of 14,291.3 sqm for a mall located in Masqat, Oman. The zone has a maximum cooling load of 1,330 kW and minimum airflow of 1,37718 L/s. There is 1 main zone containing 38 internal spaces/zones including a food court, retail shops, and common areas. Each internal space is listed with its cooling load, airflow, floor area and other details.
This document summarizes the zone sizing for the air system "BLOCK LOAD BARKA MALL" which serves 1 zone covering a total floor area of 14,291.3 sqm for a mall located in Masqat, Oman. The zone has a maximum cooling load of 1,330 kW and minimum airflow of 1,37718 L/s. There is 1 main zone containing 38 internal spaces/zones including a food court, retail shops, and common areas. Each internal space is listed with its cooling load, airflow, floor area and other details.
Air System Name ......... BLOCK LOAD BARKA MALL Number of zones ............................................................. 1 Equipment Class ............................................... UNDEF Floor Area ............................................................. 14291.3 m Air System Type ................................................ SZCAV Location .................................................... Masqat, Oman Sizing Calculation Information Zone and Space Sizing Method: Zone L/s .......................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec Space L/s ...................... Individual peak space loads Sizing Data ...................................................... Calculated
Zone Sizing Data
Maximum Design Minimum Time Maximum Zone
Cooling Air Air of Heating Floor Sensible Flow Flow Peak Load Area Zone Zone Name (kW) (L/s) (L/s) Load (kW) (m) L/(s-m) Zone 1 1330.0 137718 137718 Oct 1300 136.9 14291.3 9.64
Zone Terminal Sizing Data
No Zone Terminal Sizing Data required for this system.