PRD Calculation Report - Fire Load Case

General Data

Item 100 PSV 001


Is adequate drainage
Scenario Description and fire fighting
equipment provided ?

Calculation Method Wetted (API)


No
Fluid Latent Heat 218.40 kJ/kg

Vessel N1 Vessel N2 Vessel N3

Vessel Active ? 1 0 0

Dimensions specified ? 0
Vessel Type Vertical (Incl. Bottom Head)
Diameter 2.57 m
Vessel Tan / Tan 3.85 m
Level above Tan 3.85 m
Btm Tan from Grade 2.80 m
Flame Height 7.62 m
Piping Contribution 0.0 (%)

Environ. Factor (F) 1.0000


Ins. Therm. Conduct. 0.0000 Kcal/m/h/C
Insulation Thickness 0.00 mm

Exposed Area 45.30 m

Calc'd Heat Input 5825191.23 kJ/h

Calc'd Fire Load 26672.12 kg/h

Totals

Wetted Case Data (Active Vessels Only) Unwetted Case Data

Total Exposed Area 45.30 m Operating Pressure 18.00 barG


Total Heat Input 5825191.23 kJ/h Operating Temperature 223.13 C
Total Fire Load 26672.12 kg/h Wall Temperature 593.30 C