Anda di halaman 1dari 1

1 2 3 4 5 6 7 8

5427PK114-SLT-U-132-GIS-4001- DS

01 16/06/2017 ADDITIONAL GAS COMPARTMENT ADDED IN BC&VT - A.SANKAR S.KARTHIKEYAN RAMAKUMAR


00 19/05/2017 FIRST ISSUE - A.SANKAR S.KARTHIKEYAN RAMAKUMAR
Rev Date Description ECN Nbr Prepared Reviewed Approved
132KV SALT LAKE GIS 132KV SALT LAKE AIS TARFO.-01 BUS VT BUS COUPLER TARFO.-02 KASBA-01 KASBA-02 Scale : NTS Unit : mm Format : A2 D. Authority : CHT
=E01 =E02 =E03 =E04A =E04 =E05 =E06 =E07 EC Nbr : - Q.Level : -- Local Unit : CHT 132/33/11 KV GIS GRID SUB-STATION AT SALT LAKE
Created : A.SANKAR 16/06/2017 132kV GIS-COMBINED GAS LINE &
Reviewed : S.KARTHIKEYAN 16/06/2017
SINGLE LINE DIAGRAM
Approved : PENTA RAMAKUMAR 16/06/2017
F Sheet : 1/1 Rev. F

Product type : F35 GD149 GD34A000287 01

1)2)
Q8

2)
Q9/Q53

G9
P2

E
C5 E
C4
C3
T1-D1
C2
C1
P1

Q0 G0

G4 G3

Q2/Q52 Q1/Q51
D D

G2 G1

BB-2
G21 G22 G23 G24 G25 G26 G27 G28 G29

BB-1
G11 G12 G13 G14 132kV, 2000A, 31.5KA,3 sec. AL. BUSBAR G15 G16 G17 G18 G19

EQUIPMENT DATA SYSTEM PARAMETERS APPLICABLE STANDARDS S.No SYMBOL DENOMINATION


DEVICE QTY DESCRIPTION ALSTOM
CODE REF.TYPE Nominal Current, Ir - Bus Bar / Buscoupler = 2000 A
High Voltage Alternating Current Circuit Breaker IEC 62271-100
132kV, 3Ph, 50Hz,2000A, 31.5kA 3S Nominal Current, Ir - Trafo. Bays, Line Bays = 2000 A High Voltage Alternating Current Disconnector 1 Circuit-breaker
Q1/Q51
C 14 Nos Motor Operated Combined F35-DES IEC 62271-102 C
Q2/Q52 System Voltage = 132 kV & Earthing Switch
Disconnector / Earthing Switch
132kV, 3Ph, 50Hz,2000A, 31.5kA 3S Rated Voltage, Ur = 145 kV Gas Insulated Metal Enclosed Switchgear IEC 62271-203
Motor Operated Combined F35-DES IEC 62271-209 3-Position Disconnector /
Q9/Q53 Rated Short Circuit Current, Ik for 3 Sec = 31.5 kA HV Cable Connection 2
06 Nos Disconnector / Insulated Earthing Earthing Switch
Rated Making current, Ip = 80 kA Current Transformers IEC 61869-2
Switch
132kV, 3Ph, 50Hz, 2000A, 31.5kA 3S
Voltage Transformers IEC 61869-3 2)
Rated Power Frequency withstand voltage = 275 kV 3-Position Disconnector /
Q10/Q51 Motor Operated Combined SF6 Gas IEC 60376 3
2 Nos F35-DES Insulated Earthing Switch
Disconnector / Insulated Earthing Rated Lightning Impulse withstand voltage = 650 kV
Q20/Q52 Pressure Vessel CENELEC
Switch
1) 2)
Insulated Earthing Switch
Notes:-
4
with Making Capacity
132kV, 3Ph, 50Hz,2000,31.5kA 3S F35-CB
Q0 07 Nos
Circuit Breaker CURRENT TRANSFORMER DATA Ith = 31.5kA,3sec Idyn = 80kA 2. All Gas Compartments are Equipped with Gas Density
132kV, 3Ph, 50Hz, 31.5kA 3S Qty Alstom Ratio Class Output Vkp Ie @ Vk Rct @ 75 C 5 Monitor, Pressure Relief Device & Gas Filling Valve.
Bay CT no Core (A) (V) (mA) Current Transformer
Q8,Q15,Q25 08 Nos Motor Operated High Speed F35-HSES (No) Ref (VA) (Ohms)
Earthing Switch
1 A 1000 - 800 - 400/1 0.2 20 - - -
B =E01 Reference:- B

132kV, 1Ph, 50Hz, 2500A =E02 2 B 1000 - 800 - 400/1 PS - 1500-1200-600 30-37.5-75 5-4-2 6 Voltage Transformer
12 Nos
Dry type Cable Box
F35-OB =E03 GIS Equipment Layout : GD34A000295,REV-00
T1-D1 06 3 B 1000 - 800 - 400/1 PS - 1500-1200-600 30-37.5-75 5-4-2
=E05 Colour: GIS-Housing : RAL 7038
=E06 4 B 1000 - 800 - 400/1 PS - 1500-1200-600 30-37.5-75 5-4-2 Colour: Local Control Cubicle : RAL 7038
132/0.11kV, 3 Ph., 50Hz, =E07 7 Gas tight Barrier
T15,T25 02 Nos F35-VT
Voltage Transformer 5 B 1000 - 800 - 400/1 PS - 1500-1200-600 30-37.5-75 5-4-2

=E04 T2-D2 01
1 C 2000-1600/1 0.2 20 - - - Gas Monitoring Levels:-
2 D 2000-1600/1 PS - 2000-1600 30-37.5 8-6.4 8
Cable Connection Nominal Pressure : 6.3 bar
Refill Pressure : 5.8 bar
VOLTAGE TRANSFORMER DATA 3 D 2000-1600/1 PS - 2000-1600 30-37.5 8-6.4
Lockout Pressure : 5.5 bar
VT Qty Ratio Output 1 C 2000-1600/1 0.2 20 - - - Gas Chamber with
Bay Description Core Class 9
No No (kV) (VA) Gx...Gxx Gas Density Monitors
=E04 T3-D3 01 2 D 2000-1600/1 PS - 2000-1600 30-37.5 8-6.4 (All chambers)
132 0.11
1 0.2 50
T15 3 D 2000-1600/1 PS - 2000-1600 30-37.5 8-6.4
=E05 Bus VT 02
T25 132 0.11 3P 50
2 EXTENDED CURRENT RATINGS (k x In) = 120 % All values are highest tap ratio
PROJECT
A A
* CT CORE DETAILS SHALL BE RESUBMITTED AFTER THE APPROVAL OF CT SIZING CALCULATION Name
Date
Sign. SUB-STN
Name
Date
Sign. LOA No
Name
Date
Sign.
Name AS SK RK DRAWING 132kV GIS - COMBINED GAS LINE & SINGLE LINE DIAGRAM
R1 GAS COMPARTMENT ADDED IN BUSCOUPLER Date 16.06.17 16.06.17 16.06.17 TITLE
AND BUS VT Sign.
Name AS SK RK
Date 18.05.17 19.05.17 19.05.17 TOTAL SH.
R0 FIRST SUBMISSION DRAWING NO. SH.No. REV.
1
Sign.
A2
5427PK114-SLT-U-132-GIS-4001-
GD34A000294 DS SCALE
REFERENCE DESCRIPTION LEGEND REV. DESCRIPTION DRAWN APPROVED STATUS 1 OF 1 01
NTS

1 2 3 4 5 6 7 8

Anda mungkin juga menyukai