Anda di halaman 1dari 4

Edition No.

12 July 2002

ENGINEERING
S Y S T E M S O L U T I O N S

Optimal Air Systems


T
his issue of Engineering
System Solutions considers
whether one of the HVAC
industrys most valued design
Benefits And Design Tips
parameters is truly the best While low temperature air distribution duct and air handler face areas, and up
parameter for all buildings. While systems are not new, their use has to a 23% reduction in supply fan
generally been limited to grocery stores motor BHP.
the use of 55F is based on and other temperature and humidity
maintaining acceptable humidity The downside is that the colder supply
sensitive applications. However, as
air temperature requires more
control in a building, it does not greater emphasis is placed on reducing
refrigeration work and reduces the
necessarily offer the best annual building construction costs and
number of hours in a year when
equipment room and ceiling plenum
energy performance or capital cost. economizer operation can be used. For
space, many architects and building
example, lowering the supply air
In many cases, a lower supply air owners/developers are becoming
setpoint from 55F to 50F removes
interested in the technology for offices
temperature is at least as efficient the opportunity to cool the building
and other commercial buildings.
and will offer significant capital with outdoor air when the ambient
What Is Optimal Air? drybulb is between 55F and 50F.
savings. This article is about finding
Most air conditioning designs are based With integrated economizers, some
the best balance point and designing on supplying 55F air to the space. cooling effect can be gained, but
the system. Cooling supply air to 55F generally supplemental mechanical cooling will
provides the required humidity ratio to be required.
McQuay also has an Application maintain space conditions at 75F and
Guide (AG 31-005) on Optimal Air The Optimal Air or Balance Point is
50% Relative Humidity. In short,
the lowest supply air temperature that
Design that can be downloaded from cooling air to 55F provides reasonable
can be used without increasing the
www.mcquay.com or ordered from humidity control. Warmer supply air
annual operating cost of the building.
temperatures will lead to a humid or
your local McQuay Representative. While it is typically 48F to 52F, every
clammy environment when it is humid
Your local McQuay Representative building is different and annual energy
outdoors.
analysis is required.
has the Energy Analyzer software
Cooling supply air below 55F
used to perform the annual energy offers the potential for significant Figure 1 Annual HVAC Energy Usage
analyses used in this newsletter and capital savings in many applications.
they are willing to assist you in any As the supply air temperature is Fans Chillers
48% 38%
reduced, the supply air volume is
analysis you may require on your
reduced proportionally. That is, a
next building project. 10% increase in supply air delta T Pumps
(space setpoint minus the supply air 12%
Hugh Crowther
Director of Applications temperature) will result in a 10% Towers
McQuay North America drop in required supply air volume. 2% Continued on next page.
This allows a 10% reduction in
Optimal Air Advantages volume. This represents a very large conditions. ASHRAE Standard 55,
To illustrate the benefits of Optimal capital savings in reduced duct sizes, Thermal Conditions for Human
Air systems, lets consider a 10 story, air handling units and fan motors. Occupancy, covers in detail the correct
200,000 ft2 office building in Chicago. temperature and humidity ranges so
Refrigeration
The HVAC system is VAV with a that 80% of the occupants engaged in
The refrigeration work increased as
chiller plant. The design supply air light office work should be satisfied.
expected due to the lowered suction
temperature is 55F. In this example pressure required by the chillers, the Table 2 shows an annual energy analysis
the fan work actually exceeds the increased load from the ventilation air for the same 10-story office building in
chiller work on an annual basis (which must be cooled to a lower Chicago based on a 49F supply air
because the fans must operate enthalpy than 55F supply air temperature and a space temperature
whenever the building is occupied. systems) and the increased operating ranging from 75F to 77F. Raising the
space temperature to 77F provides an
Table 1 Annual Energy Analysis (55F to 45F supply air temperature range) 8% reduction in design supply air
SAT TSP Supply Air Design CWST Perfor- Room Chiller Fan Total volume. It also lowers the annual energy
Volume Cooling mance Setpoint Work Work Work usage by 6%. The energy savings are due
F "w.c. cfm Tons F kW/ton F kWh/yr kWh/yr kWh/yr to lowered cooling loads (the indoor
55 3 152,686 473 44 0.55 75 219,605 202,736 422,341
versus outdoor temperature difference is
54 3.02 145,415 475 43.6 0.554 75 226,594 194,061 420,655
53 3.04 138,805 477 43.2 0.558 75 236,352 186,175 422,527
smaller) and an increase in the amount
52 3.06 132,770 479 42.8 0.562 75 241,228 178,975 420,203 of available economizer hours.
51 3.08 127,238 481 42.4 0.566 75 248,661 172,375 421,036
50 3.1 122,149 483 42 0.57 75 255,777 166,303 422,080
Sound
49 3.12 117,451 485 41.6 0.574 75 261,285 160,698 421,983 Because of the reduced supply air
48 3.14 113,101 486 41.2 0.578 75 269,044 155,508 424,552 volume in Optimal Air systems, the
47 3.16 109,061 488 40.8 0.582 75 276,512 150,689 427,201 fan(s) and motor(s) can be smaller,
46 3.18 105,301 490 40.4 0.586 75 286,605 146,202 432,807 which lowers the sound power levels of
45 3.2 101,791 492 40 0.59 75 292,832 142,014 434,846
the air handling units. Lower sound
power levels require less attenuation,
Table 1shows the annual energy analysis hours to offset the reduced
which can lower both the static
as the supply air temperature is lowered economizer operation.
pressure drops and capital costs.
in 1F increments down to 45F. The The design refrigeration load actually
following adjustments were made to Indoor Air Quality
went up slightly. This is due to
more accurately reflect changes in Using the Optimal Air approach does
increased enthalpy load from the
equipment requirements or not require any special requirements to
ventilation air, offset slightly by the
performance because the supply air meet ASHRAE Standard 62.1. Lower
reduced fan motor heat gain.
temperature is being lowered: space relative humidity can actually help
Space Design Temperature and reduce the possibility of mold growth.
The total static pressure is slowly Related Comfort
increased to offset the deeper coils ASHRAE Standard 90.1 Compliance
The above example is based on
required for colder air. As shown in the above example, the
maintaining 75F in the occupied
goal is to not increase the annual
The chiller plant efficiency slowly space. Because the supply air has been
energy usage in the building so that
decreases. lowered to 49F, the space Relative
Optimal Air systems comply with
Humidity (RH) has also been lowered.
Reviewing the total annual work shows Standard 90.1 requirements. Section
With a 90% sensible heat ratio, the
the building load staying level until 6.3 of ASHRAE Standard 90.1 allows
space RH is now 40%. At this RH,
49F. Beyond that point, the loss of a credit for fan motor brake
the space temperature can be raised to
economizer hours causes the energy use horsepower when using the Optimal
77F while still maintaining acceptable
to increase. Comparing the 55F supply Air concept.
air design to the 49F supply air design
Table 2 Annual Energy Analysis (75F to 77F space temperature range)
leads to the following conclusions:
SAT TSP Supply Air Design CWST Perfor- Room Chiller Fan Total
Fan Energy and Duct Sizing Volume Cooling mance Setpoint Work Work Work
The 49F supply air design shows a F "w.c. cfm Tons F kW/ton F kWh/yr kWh/yr kWh/yr
23% reduction in design supply air 49 3.12 117,451 485 41.6 0.574 75 261,285 160,698 421,983
49 3.12 112,549 480 41.6 0.574 76 255,231 153,695 408,926
49 3.12 107,997 475 41.6 0.574 77 249,350 147,438 396,788
Design Considerations temperature must be 2F to 3F
When Using Optimal Air lower than the supply air
Unlike low temperature air systems, temperature.
Optimal Air requires very little changes Both drawthrough and
in design methodology versus blowthrough arrangements will
conventional HVAC systems. Buildings work in Optimal Air systems
with high sensible heat ratios are excellent and both have advantages. The
candidates for Optimal Air. sensible heat ratio provided by
Load Calculations blowthrough equipment is a
The first step in designing an Optimal good match for buildings with
Air system is to identify the supply air high sensible heat ratios (such as
balance point, which will become the office buildings).
supply air temperature. This requires Air Distribution and Diffuser
some form of annual energy analysis. Selection
McQuays Energy Analyzer can be Figure 4 Separation Distance vs.
Introducing colder air does affect Supply Air Temperature
used to quickly find the balance point. air distribution and diffuser
Most buildings can be evaluated in less selection. Since Optimal Air is typically Primary System Selection
than an hour. Once the supply air only 5F to 8F less than conventional In an Optimal Air system, the primary
temperature is identified, the rest of the systems, standard diffusers will work but system must be capable of providing the
building load analysis is the same as in a they will perform a little differently. low supply air temperature. While this is
conventional design. Linear diffusers tend to offer the best not a problem with chiller and air
performance since they have higher handling systems, it can present some
Secondary System Selection
supply air velocities than lay-in type unique challenges to rooftop or vertical
Conventional secondary system design
diffusers. self-contained units. Typical unitary
will work fine for Optimal Air.
equipment cannot provide the lower
Standard VAV is the most common, 1.20 supply air temperatures. However,
but fan assisted VAV boxes are also
applied products such as McQuays
used. This is often predicated on the 1.00
RoofPak rooftop units or the SWP
Percent Drop In Separation

need to address skin heat loss during 0.80 indoor vertical self-contained units have
winter months.
the necessary flexibility in DX coils and
Distance

0.60
Blowthrough Or Drawthrough refrigeration components to meet the
The main objective of Optimal Air is to 0.40
lower supply air temperature
increase the temperature difference 0.20 requirement.
between the supply air and the space
0.00 Other Design Considerations
temperature to reduce the required
Duct condensation is a perceived
55 54 53 52 51 50 49 48 47 46 45
supply air volume. The supply air Supply Air Temperature (F)
concern because of the colder supply air
temperature is the temperature of the Separation Distance
temperature. However, because the space
air as it leaves the air handling unit and
Figure 3 Separation Distance RH is also lower, the difference between
enters the ductwork not as it leaves
the duct surface temperature and the
the coil.
A key parameter that must be monitored space dewpoint is about the same for
This is a very important consideration is the separation distance relative to both conventional and Optimal Air
because a supply fan will add enough throw (see Figure 3). For conventional systems.
heat to raise the supply air temperature systems, most designers treat these two Infiltration is a bigger concern for
about 2F to3F. Because blowthrough as the same. However, as the supply air Optimal Air systems. Moist, warm air
air handling units have the supply fan temperature is lowered and the supply leaking into the building is more likely
upstream of the cooling coil, their leaving air density increases, the separation
to condense on Optimal Air supply air
air temperature off the cooling coil is the distance will decrease from the throw.
ductwork than a conventional design.
same as the supply air temperature as it Figure 4 shows the change in separation Duct heat gain is another issue. As a
enters the ductwork. On the other hand, distance as the supply air temperature is
result, many applications will require
drawthrough units add the fan heat lowered. The goal is to have an more duct insulation.
downstream from the cooling coil. To acceptable separation distance at both
compensate, the coil leaving air maximum and minimum air flow.
Continued on back page.
continued from page 3.

Conclusions annual energy analysis must be considerations for Optimal Air systems.
While 55F supply air works well as a performed. The rest of the HVAC design Contact your McQuay Representative for
design parameter, it may not be the most is similar to a conventional design using a copy of this and other Application
efficient operating point or provide the standard air diffusion products. Applied Guides or visit www.mcquay.com. In
lowest capital cost. Lowering the design unitary products are recommended addition, the annual energy analysis can
supply air temperature until the annual because the lowered supply air be performed by your local McQuay
energy usage starts to climb is a good temperature requires more flexibility from Representative using McQuays Energy
method for optimizing an HVAC system the HVAC equipment. Analyzer.
design. McQuay has produced an Application
Reviewing the design load calculations Guide on Optimal Air Design (AG31-
only will not provide the answer. An 005) which provides detailed design

For comments or suggestions, please call or write:


Chris Sackrison, Editor
McQuay International
13600 Industrial Park Boulevard
Minneapolis, MN 55441
Phone: (763) 553-5419
E-mail: chris.sackrison@mcquay.com
For more information on McQuay products and services, or to speak with your local representative, call (800) 432-1342, or visit our web page at www.mcquay.com.
2002 McQuay International

Anda mungkin juga menyukai