Anda di halaman 1dari 30

Sinamics

G130 / G150 / S150


Options

Siemens AG 2008 Subject to change without prior notice


Siemens AG 2008 Subject to change without prior notice

The SINAMICS S150 System


An overview of the electrical options

System
overview  Options at the input
Technical data

Power Block  DC link options


Mechanical
system

Motors
 Options at the output

Options
Options
 Safety and protection options
General control

Closed-loop
control  Options for the chemical industry
Tools Comiss.
Communication
 DRIVE-CLiQ
Diagnostics
Application

Version: 19.11.2008 sin-g150-4-06-e.ppt I DT LD


Siemens AG 2008 Subject to change without prior notice

Electrical options
Customer benefits

System
overview

Technical data

Power Block

Mechanical
system

Motors Features Customer benefits


An extensive number of  Already included, for example:
Options
Options features/functions even in the basic  Main contactor, circuit-breaker from 800 A
version
 EMC filter, 2nd environment acc. to EN 61800-3
General control
 Clean Power Filter
Closed-loop  PROFIBUS
control  Advanced Operator Panel
Tools Comiss. Extensive range of options to  Thermistor and PT100 evaluation units
additionally adapt the drive to  EMERGENCY STOP Categories 0 and 1
Communication customer requirements
 Insulation monitor for IT line supplies
Diagnostics  Expanded customer interface
Application  Rotary pulse encoder connection
 Sinusoidal filter
Version:
Options 19.11.2008 sin-g150-4-06-e.ppt
for the chemical industry  NAMUR terminal strip I DT LD
Siemens AG 2008 Subject to change without prior notice

Electrical options
Basic structure and options
Line supply connection

System Main breaker with


overview fuses <800 A
Technical data Main contactor < 800 A
Power Block
Circuit-breaker
> 800A
Mechanical
system Active Interface Mod.
Motors Active Line Module
Motor Module
Options
Options
Encoder interface
General control
Customer options
Closed-loop
control Motor connection

Tools Comiss. Motor reactor, filter


Communication
Standard Option
Diagnostics
Application  In its basic version, our SINAMICS S150 already has an extensive range of features
and functions.
 The cabinet can be adapted
Version: 19.11.2008
to special applications using the appropriate option(s).
sin-g150-4-06-e.ppt I DT LD
Siemens AG 2008 Subject to change without prior notice

Selection matrix (excerpt)


Electrical options L00 L08 L13 L19 L22 L23 L26
System L00 EMC radio interfer. suppr. filter, Class A1 (TN, TT line supplies)
overview
L08 Output filter
Technical data L13 Main contactor (I < 800 A)
L19 Connection for external auxiliaries, controlled, max. 10 A
Power Block L22 Without line reactor in the output range < 500 kW (being prepared 3
L23 2% line reactor, required from 500 kW 2
Mechanical L26 Main breaker/switch including fuses or circuit-breaker > 800 A)
system L45 Emergency Off pushbutton in the cabinet door
L50 Cabinet lighting with socket outlet
Motors L55 Anti-condensation heating for the standard cabinet
L57 Emerg. Off, Category 0, 230VAC / 24V DC, uncontrolled shutdown 1 1
Options
Options L59 Emergency Off, Category 1, 230 V AC, controlled shutdown 1 1
L60 Emergency Off, Category 1, 24 V DC, controlled shutdown 1 1
General control
1 Either L13 or L26 circuit-breaker ) is required for currents > 800 A
Closed-loop 2 Only required for powers > 500 kW
control 3 Only for a sufficiently low ratio between the sys. fault level and rated drive converter outpu
Tools Comiss.
Inadm issible com binations
Communication A com bination of L13 / L26 is only possible for currents <800 A
Diagnostics
Application Options can exclude or require each other (i.e. in specific combinations).

Version: 19.11.2008 sin-g150-4-06-e.ppt I DT LD


Siemens AG 2008 Subject to change without prior notice

Safety, protection functions and interfaces


Expanded
System
overview
customer terminal G61
Technical data
Encoder module SMC30 K50
Power Block
Thermistor-motorprotection
Mechanical alarm L83
system
Thermistor-motorprotection
Motors fault L84
Options
Options
PT100-evaluation L86
General control
Em.-Stop combination
Closed-loop category 0 L57
control
Em.- Stop combination
Tools Comiss.
category 1 L59
Communication
Diagnostics Insulation monitor L87
Application
A wide range of options supplements the protection functions inherent in software
as well
Version: as the interfaces tosin-g150-4-06-e.ppt
19.11.2008 control the drive. I DT LD
Siemens AG 2008 Subject to change without prior notice

Line side options


Line supply L26 Load disconnector up to 800A
System
to disconnect the voltage with mounted
overview
electronic fuses
Technical data for cable and drive converter protection
L26 Circuit-breaker >800A to 1600A
Power Block
M to disconnect the drive converter and as cable
up to 800A
protection
Mechanical
system L00 EMC radio interference suppression
800 -1600 A
filter Class A1
Motors In conjunction with the line reactor, to
reduce the radio interference voltage.
Options
Options
L13 Main contactor (1 or 3 in parallel up to 800 A)
General control
to isolate the drive converter from the line
supply
Closed-loop
control
L22 Option no line reactor for P < 500kW:
This is only permissible for an adapted low line
Tools Comiss. system fault level.
Communication L23 Line reactor VK=2% for > 500kW
Diagnostics (the reactor is incl. as standard up to 500kW)
Protects the drive converter against
Application
excessively high current harmonics
Protects the other loads by reducing the
Version: 19.11.2008 sin-g150-4-06-e.ppt harmonics fed back into the line supply.I DT LD
Siemens AG 2008 Subject to change without prior notice

Electrical options
Options at the input
Main breaker including fuses L26
System  Up to 800A, a main breaker
overview including fuses can be optionally
used.
Technical data
 From 800 A onwards, the motor-
Power Block operated circuit-breaker is included
as standard.
Mechanical  Main and bypass contactor are
system always part of the Active Interface
Module AIM or the Line Connection
Motors
Module LCM
Options
Options Which system fault level?
 The ratio between the system fault Drive converter
General control
level and the drive converter power connection point
S "
Closed-loop should be in the range R sc = 20 .. k line
control 100.
 For values below 20, it can be Line Converter
Tools Comiss. Line feeder Line reactor
assumed that higher harmonics will inductance
Communication be fed back into the line supply.
Diagnostics The main breaker and line reactor are part of the basic equipment of the SINAMICS S150.
For cabinet units up to 800A, a main breaker with fuses can be optionally used. The circuit-
Application
breaker is standard above 800A.
Filter to filter-out harmonics (Clean Power Filter) and EMC filter, Category C3 (industry) are
Version: 19.11.2008
included sin-g150-4-06-e.ppt
in the basic equipment of the SINAMICS S150. I DT LD
Siemens AG 2008 Subject to change without prior notice

Line reactor: yes or no?


 Up to 500 kW, as standard with line reactor
 Option L22: without line reactor for
- low system fault levels
System
- when using a transformer which is matched to the drive converter output
overview
Drive converter
connection point
Technical data Sk"line
Power Block
Line Converter
Line feeder Line reactor
Mechanical inductance
system  Above 500 kW, as standard, without line reactor, as most drives are
operated through a transformer due to the harmonics
Motors
 Option L23: with line reactor for
- excessively high system level at the cabinet >500kW
Options
Options
Transformer Drive converter
connection point connection point

General control Sk2"line Stransfomer S k1"

Closed-loop Line Converter


control Line feeder
inductance uk transformer
= %
Tools Comiss.
Output Line reactor Option code, Line reactor Option code,
Communication can be omitted line reactor required line reactor
omitted
Diagnostics <200 kW RSC < 43 L22 RSC > 43 --
Application 200 ... 500 kW RSC < 33 L22 RSC > 33 --
>500 kW RSC < 20 -- RSC > 20 L23
Version: 19.11.2008 RSC =sin-g150-4-06-e.ppt
Skline / ( drive converter output in KW*1.08 ) I DT LD
Siemens AG 2008 Subject to change without prior notice

Breaking unit for regenerative operation

System
overview
M
Technical data
When braking, the kinetic energy
Power Block is converted into heat in a brake
C
resistor which must be externally
Mechanical mounted:
system L61 PD = 100 kW
Motors Braking chopper L62 PD = 200 kW
with external brake
Options
Options resistor
D
Max. braking PBrake,max P3
General control P [kW] 1.
power
P3 = 6PD
Closed-loop This calculation is sufficient for single brak-
control ing operations (emerg. off, end of shift,...)
P20 = 4 PD
Tools Comiss.
Average
Communication 2.
braking power
P PD
Diagnostics PD The continuous load must also be
Application determined for frequent braking:
3 20 30 90 t [s]

Version: 19.11.2008 sin-g150-4-06-e.ppt I DT LD


Siemens AG 2008 Subject to change without prior notice

Braking unit for regenerative operation


Braking Module & Braking Resistor
 In normal operation with the Active Infeed, the
System regenerative energy when braking is fed back into the line
overview
supply.
Technical data  The braking unit is available in 2 ratings: 100/200kW.
 The unit comprises two modules:
Power Block - chopper
- resistor
Mechanical
system

Motors

Options
Options

General control

Closed-loop
control

Tools Comiss.
Communication
Diagnostics
Application

Version: 19.11.2008 sin-g150-4-06-e.ppt I DT LD


Siemens AG 2008 Subject to change without prior notice

Filters on the motor side


Reducing the voltage stress at the motor
U
System
overview
t
Technical data du/dt= 5 ... 10kV/s

Power Block
Sinusoidal filter L15
Mechanical If an almost sinusoidal voltage is required at the motor a
system sinusoidal filter can be used without having to use a
Motors
special cable and without having to de-rate the motor. At
the same time, the additional pulse frequency noise is
Options
Options eliminated.
M Special features:
General control  Only 380..480 V, to 250 kW and 500600V to
Closed-loop 132kW
control  Pulse frequency: 2 kHz  4 kHz
 Current de-rating, approx. 15%
Tools Comiss.
Communication dV/dt filter is being prepared L10
Diagnostics
In addition to the voltage strength of the motor, the environment can also define the
Application use of options (hazardous zones). Please enquire regarding options L15.

Version: 19.11.2008 sin-g150-4-06-e.ppt I DT LD


Siemens AG 2008 Subject to change without prior notice

Electrical options
At the DC link
Braking Module & Braking Resistor
 In normal operation with the Active Infeed,
System the regenerative energy when braking is fed back into the line
overview supply.
 If the drive must be shutdown in a controlled fashion even when
Technical data
the power fails, an additional braking unit is required.
Power Block  The braking unit is available in 2 ratings: 100/200kW.
 The unit comprises two modules: - chopper
Mechanical - resistor
system

Motors

Options
Options

General control

Closed-loop
control

Tools Comiss.
Communication Braking unit P20=100 kW for: 75 132 kW L61
Diagnostics
Application
Braking unit P20=200 kW for: > 132kW L62
The Active Infeed regenerates the braking energy back into the line supply.
A braking
Version: unit is only required
19.11.2008 in special operating cases.
sin-g150-4-06-e.ppt I DT LD
Siemens AG 2008 Subject to change without prior notice

Increased voltage stress

System
overview M
Technical data
U The wave
Power Block
is reflected
t at the motor
Mechanical du/dt= 5 ... 10kV/s
system
The wave
Motors is reflected
at the drive
Options
Options converter The voltage rise can be
considered just like the Voltage characteristic at the motor:
General control propagation of a wave 2VDC link is briefly obtained when the
(physics: propagated wave) wave crests are superimposed. The
Closed-loop wave is dissipated after approx. 1s
control as a result of the cable resistance.

Tools Comiss.
Critical for:
 Third-party motors with poor insulation or unknown voltage strength (electric strength)
Communication  line supply V > 500 V.
Diagnostics
Counter-measures:
Application  Voltage limiting filter (output dv/dt filter): dv/dt < 5 kV/s
 Sinusoidal filter: Sinusoidal current and voltage with 5% distortion factor.
Version: 19.11.2008 sin-g150-4-06-e.ppt I DT LD
Siemens AG 2008 Subject to change without prior notice

Electrical options
Options at the output
Protecting the drive converter for long motor cables
System Equivalent circuit diagram of the cable with parasitic Drive converter output voltage:
overview inductances and capacitances
M U
Technical data

Power Block t
Non-shielded Shielded
cable in a duct/tray cable Drive converter output current:
Mechanical
system
I
Motors Maximum cable lengths
Protoflex Shielded Non-shielded t
Options
Options
EMV 3 plus (NYCWY) (NYY)
General control 330 m 300m 330m

Closed-loop
control
 As the length of the motor cable increases, then so does its cable capacitance.
Tools Comiss.  The PWM commutating operations result in re-charging currents of the power
capacitances that are superimposed on the actual motor current and additionally load
Communication
the drive converter.
Diagnostics  Also for non-shielded cables, a capacitance depending on how the cable is routed
Application must be taken into account.
 In order to protect the drive converter, the maximum cable lengths shown must
be carefully maintained. sin-g150-4-06-e.ppt
Version: 19.11.2008 I DT LD
Siemens AG 2008 Subject to change without prior notice

Safety functions: emergency stop category 0

System
overview Emergency Stop
combination
Technical data

Power Block
OFF 2 Opens the main breaker
Mechanical OFF2 = safe standstill
system Safe stop Power is
pulse inhibit disconnected
Motors
Motor coasts down
EMERGENCY STOP button L45
Options
Options
The EMERGENCY STOP button with protective collar is mounted in the door of the
General control drive converter cabinet and its contacts fed to a terminal strip.
The EMERGENCY STOP functions, Category 0 or 1, can be activated in conjunction
Closed-loop with options L57, L59 and L60.
control

Tools Comiss. EMERGENCY STOP, Category 0 L57


Communication
EMERGENCY STOP, Category 0 for non-controlled stopping according to EN 60 204.
Diagnostics The function includes disconnecting the voltage at the drive converter output via the line
Application contactor, bypassing the electronics via a safety combination in compliance with
EN60204-1. The motor then coasts down. The pushbutton circuit can be changed-over
from 230V AC to 24V DC using
Version: 19.11.2008
the appropriate jumpers.
sin-g150-4-06-e.ppt I DT LD
Siemens AG 2008 Subject to change without prior notice

Safety functions: emergency stop category 1

System
overview Emergency Stop t = 0.5..30s Emergency Stop
combination timer element
Technical data

Power Block OFF 3 OFF 2 Opens the


main breaker
Mechanical OFF2 = safe standstill Safe stop Power
Fast stop
system OFF3 = fast stop pulse inhibit pulse inhibit disconnected
Motors Motor brakes along Motor is shutdown
the fast stop ramp after t
Options
Options

General control

Closed-loop
EMERGENCY STOP, Category 1 (AC 230 V) L59
control

Tools Comiss. EMERGENCY STOP, Category 1 (DC 24 V) L60


Communication
EMERGENCY STOP, Category 1 for controlled stopping according to EN 60 204.
Diagnostics This function includes stopping a drive using a fast stop along a down ramp that is
Application parameterized by the user.
The power is then disconnected as described under EMERGENCY STOP, Category 0.
Version: 19.11.2008 sin-g150-4-06-e.ppt I DT LD
Siemens AG 2008 Subject to change without prior notice

Protective functions: thermistor motor protection

System External alarm 1


overview

Technical data

Power Block

Mechanical
system

Motors
External fault 1
Options
Options

General control Thermistor motor protection device (alarm) L83


Closed-loop Thermistor motor protection device with PTB Certification for PTC temperature sensors
control (PTC resistors, type A) for alarm.
Tools Comiss.
Communication Thermistor motor protection device (trip) L84
Diagnostics Thermistor motor protection device with PTB Certification for PTC temperature sensors
Application (PTC resistors, type A) for trip.
The power supply for the thermistor motor protective devices and the evaluation is taken
from the drive converter.
Version: 19.11.2008 sin-g150-4-06-e.ppt I DT LD
Siemens AG 2008 Subject to change without prior notice

Protective functions: PT100 evaluation unit


External alarm 1
System
overview
External fault 1
Technical data

Power Block

Mechanical
system

Motors

Options
Options

General control
Evaluation unit for PT100 resistors L86
Closed-loop
control  Monitoring function for up to 6 sensors
 Limit values can be freely programmed for every channel
Tools Comiss.  Measuring channels are split-up into two groups, each 3 channels. (e.g. 3 PT100 in the
Communication stator windings and 2 PT100 in the motor bearings)
 The output relays are integrated into the internal fault and shutdown circuit of the drive.
Diagnostics  The messages can also be retrieved on the customer side using two freely-assignable
Application fault signaling relays.
 2 freely programmable analog outputs (0/4-20 mA or 0/2-10 V) to connect to a higher-
level19.11.2008
Version: control. sin-g150-4-06-e.ppt I DT LD
Siemens AG 2008 Subject to change without prior notice

Operation in insulated grids

System
overview

Technical data

Power Block

Mechanical
system

Motors

Options
Options

General control
TN-C IT
Grounded line supplies Non-grounded line supply
Closed-loop
control
AC drive converters have, in addition to the line filter and reactor options, an integrated
Tools Comiss. basic interference suppression circuit as standard. Harmonics are dissipated to the
grounded line supply through a common PE
Communication
Diagnostics
Non-grounded line supplies use an insulation monitor. In order that the basic interference
Application suppression of the drive converter does not result in a trip, this must be de-activated:
Release the screw connection at the front of the basic drive unit. Thats it!
Version: 19.11.2008 sin-g150-4-06-e.ppt I DT LD
Siemens AG 2008 Subject to change without prior notice

Insulation monitoring for IT-line supplies

Ground fault monitoring at the output for TN line supplies provided as standard
System
overview A ground fault at the output that results in fault currents (e.g. insulation faults) is
detected by the summed current monitoring function which in turn trips the drive
Technical data converter.
For IT line supplies, first faults do not result in a response..
Power Block

Ground fault monitoring Insulation monitoring


Mechanical for insulated line supplies
for grounded line supplies:
system
3-phase Insulation
Motors actual value
current sensing monitor
Options
Options
Insulation
M
fault
General control
Insulation monitoring L87
Closed-loop
If the drive converter is connected to an isolated line supply, then an insulation monitor
control
must be used.
Tools Comiss. This device monitors all of the circuits that are electrically connected to one another for
an insulation fault. The insulation resistance as well as all of the insulation faults in the
Communication
DC link and on the motor side of the drive converter are detected.
Diagnostics Two response values can be set (between 1 k ...10 M).
Application When a response value is fallen below, an alarm signal is output at a terminal. (This is
then processed in the control system on the plant/system side.)
The EMC filter can be de-activated
Version: 19.11.2008
by withdrawing the jumper at the power module!
sin-g150-4-06-e.ppt I DT LD
Siemens AG 2008 Subject to change without prior notice

Namur-terminal strip for chemical industry


 According to the requirements and directives of the Standards Committee for
System instrumentation and control technology in the chemical industry (Namur
overview recommendation NE37).
 The inputs and outputs connected to the terminals fulfill the requirements
Technical data
for Function extra low voltage and protective separation PELV*.
Power Block  The option B00 includes the following function groups:
- Terminal strip X2 with electrical isolation
Mechanical
- EMERGENCY STOP, Category 0, 24V DC with additional terminal strip
for forced disconnection from the line supply and automatic start
system
(corresponds to. L57)
B00
Motors - Thermistor motor protection device, trip (corresponds to L84)
- Terminals to externally connect 24V DC with PELV
Options
Options  When required, the EMERGENCY STOP button (option L45) should be
ordered
General control 24V DC supply with protective separation (PELV)
Closed-loop  An additional 24V DC power supply to supply the EMERGENCY STOP
control combination including a control circuit. + B02
 B02 is only possible in conjunction with B00.
Tools Comiss.
Communication
Third-party output, external auxiliaries (uncontrolled)
 Fused 10A outlet with V=Vline supply for motor fans. (L19=controlled)
Diagnostics
 B03 is only possible in conjunction with B00.
+ B03
Application
*)
PELV =
Caution: In conjunction with B00, B02, B03, the following
options19.11.2008
Version: cannot be selected: L57, L59, L60, L83, L84, L87, L19.
sin-g150-4-06-e.ppt Protective Earth Low Voltage
I DT LD
Siemens AG 2008 Subject to change without prior notice

Terminal interface and encoder interface

System
overview

Technical data

Power Block

Mechanical
system

Motors
Control Power TM31 TM31 SMC30 Geber
Options
Options Unit Module Standard Option Option

General control
Expanded customer interface
 The customer interface can be expanded using a second TM31.
Closed-loop  As for the first TM31, the following inputs/outputs are available: G61
control
8 DI, 4 DI/DO, 2AI, 2AO, 2 relay, 1 KTY/PTC
Tools Comiss.  There is no factory pre-assignment.

Communication Sensor Module Cabinet-Mounted SMC30 (TTL, HTL)


Diagnostics  This is used to sense the actual motor speed for the closed-loop Vector control.
Application  Various settings for different rotary pulse encoders: K50
 Signal (unipolar, bipolar), signal level (HTL, TTL), track monitoring (without,
A/B),
Version: zero pulse (24V unipolar,
19.11.2008 as for the A/B track), number of pulses (2048,..)
sin-g150-4-06-e.ppt I DT LD
Siemens AG 2008 Subject to change without prior notice

Basic design and options

System
Line supply input
overview
Line isolator with
Technical data fuses <800 A

Power Block
Main contactor <800 A
Mechanical
system Circuit breaker
> 800A ~
Motors
~ =

Options
Options
Motor module

General control
Customers options
Closed-loop =
Motor output
control ~
~
Tools Comiss. LC-filter, sine-filter
Communication
Standard Option
Diagnostics
Application  Sinamics G150 is generously equipped even in basic design.
 Using options the cabinet can be adapted to suit special requirements. .
Version: 19.11.2008 sin-g150-4-06-e.ppt I DT LD
Siemens AG 2008 Subject to change without prior notice

G150 - Design: version A and version C

System Version A contains, in the lefthand side of the


overview cabinet :
 the line supply connection panel,
Technical data  the input options,
Power Block  a field for customer options
in the righthand side of the cabinet
Mechanical
 the power module
system  the output filter
 the motor connection panel
Motors
Version C is reduced to the righthand
Options
Options side of the cabinet :
 the line supply connection panel,
General control  the power module
 the line reactor
Closed-loop
 the motor connection panel.
control

Tools Comiss. The operating company mounts/installs


the remaining line supply components in
Communication
a central MCC for additional loads
Diagnostics Version A
Application The output reactor is not required due to
the fact that the drive unit can be
Version: 19.11.2008
Version C
sin-g150-4-06-e.ppt
installed close to the motor.. I DT LD
Siemens AG 2008 Subject to change without prior notice

G150 - Options for design version A or C

System
overview
The selection of
Technical data options suggests
design version A or
Power Block
C.
Mechanical
system

Motors

Options
Options

General control

Closed-loop
control

Tools Comiss.
Communication
Diagnostics
Application

Version: 19.11.2008 sin-g150-4-06-e.ppt I DT LD


Siemens AG 2008 Subject to change without prior notice

G150 - Options for design version A or C

System
overview
The selection of
Technical data options suggests
design version A or
Power Block
C.
Mechanical
system

Motors

Options
Options

General control

Closed-loop
control

Tools Comiss.
Communication
Diagnostics
Application

Version: 19.11.2008 sin-g150-4-06-e.ppt I DT LD


Siemens AG 2008 Subject to change without prior notice

Safe Torque Off (STO)

System Description of functions


overview This function prevents the drive from restarting unexpectedly in accordance with EN
60204-1, Section 5.4. Safe Torque Off disables the drive pulses and disconnects the
Technical data
power supply to the motor (corresponds to Stop Category 0 of EN 60204-1). The drive
Power Block is reliably torque-free. This state is monitored internally in the drive.#

Mechanical Application, customer benefits


system STO has the immediate effect that the drive cannot supply any torque-generating
energy. STO can be used wherever the drive will reach a standstill in a sufficiently
Motors
short time based on the load or when coasting down of the drive will not have any
relevance for safety.
Options
Options

General control

Closed-loop
control

Tools Comiss.
Communication
Diagnostics
Application

Version: 19.11.2008 sin-g150-4-06-e.ppt I DT LD


Siemens AG 2008 Subject to change without prior notice

Saftey Integrated

System Description of functions


overview The Safe Stop 1 function can safely stop the drive in accordance with EN60204-1, Stop Category 1.
When the SS1 function is selected, the drive brakes along a quick stop ramp (OFF3) and
Technical data automatically activates the Safe Torque Off when the parameterized safety delay timer runs down.
Application,customerbenefits
Power Block
When the stop function of the drive is activated and it does not come to a halt quickly enough due to
the load inertia, it can be actively braked by the converter. This integrated quick braking function
Mechanical eliminates the need for costly mechanical brakes that are subject to wear.
system

Motors

Options
Options

General control

Closed-loop
control The safety functions of SINAMICS G130 and G150 fulfill the requirements of:
 Stop Category 3 according to EN 954-1 / EN ISO 13849-1
Tools Comiss.
 Safety Integrity Level (SIL) 2 according to EN 61508
Communication  Performance Level (PL) d according to EN ISO 13849-1
Diagnostics Furthermore are the Safety Integrated functions of SINAMICS G130 and G150 normally certified by
independend institutions. A list of all certified components can be ordered by your local Siemens
Application partner.

Version: 19.11.2008 sin-g150-4-06-e.ppt I DT LD


Siemens AG 2008 Subject to change without prior notice

Connecting safety functions


SINAMICS G150: Option K82
System In order to integrate STO+SS1 safety functions into a plant/machine environment, a wide range of
overview limitations & constraints must be carefully observed. Option K82 allows simple integration into the plant or
machine.
Technical data Challenges:
 Accessibility of the component terminals
Power Block  Cable cross-sections that can be connected
 Auxiliary voltage required
Mechanical  Variable plant voltages
system  Variable plant wiring
 Secured feedback signal paths
Motors
Solution:
 Connection to a standardized customer terminal block
Options
Options
 Cable cross-sections up to 2.5mm are possible
 An auxiliary voltage is not required
General control
 The OFF switch can be directly connected
Closed-loop  Variable supply voltage from 24V DC to 230V AC
control  Concept for simple plant wiring
 Same configuration in spite of different option versions
Tools Comiss.
Communication
Diagnostics
Application