Requisition sheet for SAFETY/RELIEF VALVES Contr. Job No.

: page:
General Full nozzle-type steel safety/relief valve, closed bonnet with screwed cap unless otherwise specified
Pressure codes SP = set pressure
MRP = maximum relief pressure
Fluid codes N = non-corrosive
Co = corrosive
Fluid phase codes L = liquid
S = steam
G = vapour
Back pressure If variable back pressure is higher than 10% of set pressure, specify balanced type safety/relief valve
If variable back pressure is equal to or less than 10% of set pressure, specify conventional type safety/relief valve; set pressure shall be equal to spring pressure
If back pressure is constant, conventional type safety/relief vavle shall be specified; spring pressure shall be equal to set pressure minus back pressure
Type and size As specified below; to be checked by manufacturer
Special requirements A- screwed cap and test rod
B- bolted cap and regular lifting gear
C- bolted cap and packed lifting gear
D- bolted cap, packed lifting gear and test rod
X- open bonnet, if required by local regulations
Y- vented bonnet, if required by local regulations
Connections Inlet and outlet flanged ANS class 300 RF and 150 RF respectively, unless otherwise specified
Pressure N Relief Max. L or MW Back pressure Special Size Material
Item Quant. Tag No. bar ga or temp. flow S or or bar ga Valve req. Orifice cm2 Remarks
Co. kgs G density type codes Inlet Outlet Body Trim
SP MRP C kg/m3 Variable Constant in. Calc. Actual in.

REMARKS ON REVISIONS Made by: Equipment: SAFETY/RELIEF VALVES Rev. Letter


Checked by: Date:
Approved by: Plant: Signature:
Consignee:
NOTE: At a later date supplier will be invited to complete a Spare Parts List and Interchangeability Eng. by: Sheet No. 1 cont'd on sheet No.
Record (SPIR) for all equipment supplied. Principal: Req No.
DEP 31.36.90.93-Gen., sheet 1/2, dated 06/2000
Requisition sheet for SAFETY/RELIEF VALVES Contr. Job No.: page:
Pressure N Relief Max L or MW Back pressure Special Size Material
Item Quant. Tag No. bar ga or temp. flow S or or bar ga. Valve req. Orifice cm2 Remarks
Co. kgs G density type codes Inlet Outlet Body Trim
SP MRP C kg/m3 Variable Constant in. Calc. Actual in.

Eng. by: Sheet No. 2 cont'd on sheet No.


Principal: Req No.
DEP 31.36.90.93-Gen., sheet 2/2, dated 06/2000