Standard Technical Features of BTG System for Supercritical 660/800 MW Thermal Units

9.1.4 Fuel oil condensate system

Condensate from complete fuel oil plant shall be brought to a common


condensate flash tank in fuel oil unloading area. Drain from this condensate
tank shall be connected to nearest station drain.

9.1.5 Oily water drain system

The oily waste water drains from each steam generator area shall be collected
and suitably treated in an oil separator. The treated outlet water shall not have
oil content more than 10 ppm. The recovered oil from oil separators shall be
led to drain oil tanks/ waste oil collection tanks. Separated water shall be
pumped to effluent treatment plant (outside BTG area) using sump pumps.

9.2 Fuel Oil Preparation and Firing System

9.2.1 The fuel oil preparation and firing system shall be sized based on following
criteria:

Description Requirement
Heavy oil firing LDO firing
i) Purpose of fuel oil Initial start up, coal To facilitate cold strat
firing flame stabilization at up of unit.
start up/ low load.
ii) Type of fuel oil Heavy fuel oil (HFO/ Light diesel oil (LDO).
HPS/ LSHS).
iii) Oil firing system To cater to 30% To cater to 7.5%
capacity BMCR requirements of BMCR requirements of
steam generators steam generators
without any coal firing. without any coal firing.
iv) Oil firing system Common for all steam Common for all steam
configuration generators. generators.

9.2.2 Design/ sizing of various pump shall be based on following criteria:

Design criteria Requirements


HFO pumps LDO pumps Drain Sump
pumps pumps
i) Type of fuel HFO/HPS/ LDO HFO/HPS/ Oil & water
oil to be LSHS LSHS
handled
ii) Pump Oil pour Ambient Oil pour Ambient
suction point point
temp. temperature temperature
iii) Max. temp. 900C Atmospheric 900C 50- 850C
of fuel oil to
be handled