Design Criteria:
Importance Factor I
Category III, special occupancy = 2.9
Seismic Zone Factor 2
Zone 4 = 0.40
Structural System Factor Rw
Rw = 10
Soil Profile Factor S = 1.25
CT = C/RW
Computation of Loadings:
Slab = 160 mm. (thickness)
Beam = 300mm x 400mm (base x height)
Column = 600mm x 600mm. (Column Dimension)
Dead Loads per Floor:
Tributary Area = (5m. x 23m.) =115m2
Roof Loading
23.54
Slab 0.125m. kN/m3 115m2 338.3875kN
Beam 0.25m 0.4m. 23.54 kN/m3 52m 122.408kN
3
Column 0.25m 0.4m 23.54 kN/m 45m 105.93kN
Ceiling 0.29 kN/m2 115m2 33.35kN
2
Utility 0.04 kN/m 115m2 4.6kN
Finishing 0.77 kN/m2 115m2 88.55kN
Perimeter
Wall 2.6 kN/m2 115 m2 299kN
Partition 2.1 kN/m2 115 m2 241.5kN
Total Load 1233.72 kN
W = total seismic dead load
Rw = 10 for Concrete Moment Resisting Frame System (NSCP 2001 Ed.)
Z = 0.4
I=1
(0.4)(1)(2.74)(5395.077 )
v=
= 10
Wxhx ( )
=
Floor V-Ft Wx (kN) hx(m) (kN.m)
Note: the value of C should not exceed 2.75 and this value may be used for any structure without
regard to soil type of structure period. Except for those requirement where code prescribed are
scale up by 3 ( ) the minimum value of the ratio shall be 0.075.
8
Description: A Two-Storey BPO Building which is square in plan has a series of special moment
resisting frames around the perimeter of the building. The floor loads and the frame dimensions
are shown in figure. The static seismic analysis was done in order to analyze the effects of
seismic and wind forces to the structure. The computed design stresses, and support reactions
will be used later for the design of structural components of the building. Portal Method was used
by the researchers for the structural analysis of Special Moment Resisting Frame.
Design Criteria:
Importance Factor I
Category III, special occupancy = 2.9
Seismic Zone Factor 2
Zone 4 = 0.40
Structural System Factor Rw
Rw = 10
Soil Profile Factor S = 1.25
CT = C/RW
Computation of Loadings:
Slab = 160 mm. (thickness)
Beam = 300mm x 400mm (base x height)
Column = 600mm x 600mm. (Column Dimension)
Wxhx ( )
=
Floor V-Ft Wx (kN) hx(m) (kN.m)
Note: the value of C should not exceed 2.75 and this value may be used for any structure without
regard to soil type of structure period. Except for those requirement where code prescribed are
scale up by 3 ( ) the minimum value of the ratio shall be 0.075.
8