Anda di halaman 1dari 1

8.3.

4 Verification of insulation resistance


For PTTA which have not been subjected to a dielectric test according to Sub-clauses 8.2.2 or
8.3.2, an insulation measurement using an insulation measuring device at a voltage of at least 500 V IS 8623 part 1
shall be carried out.
In this case, the test is deemed satisfactory if the insulation resistance between circuits and
exposed conductive parts is at least 1 000 R/V per circuit referred to nominal voltage to earth of
these circuits.
51