Differential Protection in
Low-Voltage Buses
AN EXPLORATION OF PRINCIPLES AND MODELS
photocredit
Block
in multiple ways. One relay can implement overcurrent
functions 50and 51 as well as differential functions with
50 50 50 50 50 the various circuits and an interlocking scheme simultane-
ously. Such implementations can provide improved speed
and wiring simplicity.
Modern relays also provide fast peer-to-peer commu-
nications using protocols such as the Distributed Network
Protocol, Utility Communications Architecture, or Inter-
national Electrotechnical Commission 61850. Such com-
FIGURE 1. The ZSI scheme. A lower-tier device sends a blocking munications facilitate implementing schemes over longer
signal to an upper-tier device. distances and may further simplify wiring [4], [5].
Blocking schemes, although economical and seem-
upper-tier device is told that the fault is detected and is ingly easy to apply, are usually limited to simple busbar
being interrupted by a lower-tier device, hence it need configurations. It is complicated to implement blocking
not operate at its in-zone protection speed. The upper-tier schemes in complex systems with two or more incomers,
device then applies a delay, which is usually user set, to tie breakers, and varying topology.
allow the lower-tier device to respond and clear the fault.
The upper-tier device is not usually made to be totally Types of Differential Protection
unresponsive to the fault, it is just slowed enough to allow Differential protection can be divided into the following
the lower tier to interrupt first. The upper-tier device five types:
remains poised to provide backup protection should 1) overcurrent differential that operates based on the sum
the lower-tier devices fail to clear the fault. In protec- of the various currents using overcurrent relays
tion relays typically used for MV system protection, the 2) percent-slope overcurrent differential, which is differ-
slower alternate protection in the upper-tier device may be ential protection that calculates a restraint value that is
enabled via an alternate setting group. The signal may be dependent on the magnitude of input currents
a simple hardwired contact closure or a voltage provided 3) low-impedance overcurrent differential with dual per-
by the downstream device, as is the case in some LV trip centage differential slope plus additional mechanisms
units. Different manufacturers will use different signals to improve operational reliability that is relative to
between their devices; and, hence, devices from different sensor inaccuracy and saturation
manufacturers are rarely compatible. Some devices may 4) high-impedance overcurrent-differential function that
implement differentiated signals for different protection routes the summed current from the circuit CTs through
functions, such as ground-fault protection and overcur- a resistor network to develop a voltage.
rent protection. In some applications, especially with 5) networked differential relays that receive synchro-
modern digital relays, serial communications may be used nized, digitized information over communication lines.
to transmit a signal over longer distances. A requirement The following sections of the article will describe these
for this type of scheme to function is that the lower-tier relay types in more detail.
(downstream) device issues the blocking signal before
the upper-tier (upstream) device commits to tripping. Simple Unrestrained Differential
In some cases, that may mean that the upstream device is In a simple differential-relay implementation using an
not able to operate at its fastest protection mode to allow overcurrent protection element, the differential current
time to receive the blocking signal. may be created externally to the relay by summation
When using microprocessor-based multifunctional of all the circuit currents via parallel interconnection
relays, it may become possible to integrate all of the of the various CTs (Figure 2). The external CTs should
required overcurrent functions for one or more cir- be of the same ratio and type. If they are not, a scal-
cuits in one relay. This not only allows a reduction in ing (matching) CT (or several) is needed. This, in turn,
wiring but also shortens the coordination time and may increase the burden for the main CTs and increase
speeds up the operation of the scheme. When using saturation concerns.
one relay for multiple protection modes or multiple CT saturation and inaccuracy are handled via a
circuits, consideration should be given to reliabil- high operational threshold and time delay. This
increasing levels of sophistication to increase opera- ic bus replica (bus image) can be accomplished in
tional reliability, such as percentage differential slopes, software without physically switching secondary
may be called low-impedance-percentage differential current circuits
(Low-Differential
oc
Currents)
Low IR origin of the differential-restraining plane. The advan-
Slope
Pickup
Restraining tage of having a constant percentage restraint speci-
Low Breakpoint
High Breakpoint
Differential Current
flags and develop security logic. In addition, the secu- Check Directional
rity and dependability of the bus differential protection 3 Flag: DIR = ? t2 DIF2 = 1
is improved by implementing fast and robust saturation
2 Operate Block
detection as well as current directional sensing.
Figure 8 depicts the adaptive logic for detecting inter- 1 Low SAT = 1
nal faults versus external through faults using the various t0 Slope IR
t1
sensing and logic mechanisms. Two internal logical flags Pickup
1 2 3 4 5 6
Low Breakpoint
High Breakpoint
are generated and used as differential supervisory logic,
Restraining Current
i.e., a saturation detection flag and a directional flag. The
directional flag indicates if all the currents are flowing
toward the bus or if at least one is not. The saturation flag
is based on the detection of a time difference between the
onset of large currents, reflected in the restraint signal, FIGURE 7. A typical differential/restraint trajectory during external
and the onset of a differential current. If the two arise fault. DIF: differential; DIR: direction; SAT: saturation.
simultaneously, the differential is assumed to be real, but,
if the differential follows the restrained by several mil-
liseconds, it is probable that the differential differences DIF1
AND
During internal fault (i.e., fault within the differential tion. Different manufacturers may implement various
zone), the currents from the circuits feeding the fault ersions of this logic and other algorithms that improve
v
(i 1 and i 2 ) will be more or less in phase (Figure 9). Feeder relay reliability. It is beyond the scope of this article to
currents i 3, i 4, and i 5 drop. The differential/restraint trajec- cover them all in detail.
tory is shown in Figure 10. In such internal fault cases,
the saturation flag is not set, and no directional check is High-Impedance Bus Differential
needed. The algorithm makes a fast decision for opera- High-impedance differential protection responds to a volt-
age across the differential junction point that is usually a
calibrated resistor (see Figure 11). The CTs are required to
i1 have low secondary leakage impedance (completely dis-
tributed windings or toroidal coils). During external faults,
i2 even with severe saturation of some of the CTs, the volt-
i3 age does not rise above a certain level because the other
i4 CTs will provide a lower-impedance path relative to the
i5 relay input impedance.
Id = i1 + i2 + i3 + i4 + i5 The technique, however, is not free from disadvantag-
Id es, the most important of which are the following:
Ir = max(i1, i2, i3, i4, i5) The high-impedance approach requires dedicated CTs,
Ir
which can add cost when implemented at any volt-
t0 t1
age and is of special concern in LV application where
switchgear or switchboard space is more limited.
FIGURE 9. An internal fault and differential and restraint currents.
The technique cannot be easily applied to re-
High Breakpoint
Trip Unit
Trip Unit
function in the relay. This allows the differential func- many modern relays, this is typically a function that is
tion to differentiate a fault in the protected zone from a inversely proportional to the ratio of the fault current
through fault (externalfault). (differential in this case) to the set IOC protection
The PD protection function guarding the LV bus does threshold (a multiple of differential protection thresh-
not need dedicated CTs at each feeder circuit. The block- old). Higher fault current magnitude leads to faster IOC
ing signal from the trip units in the feeder CBs acts like a function operation. (See the bottom diagonal line in
directional logic flag in a low-impedance-percentage dif- Figure 13.)
ferential relay, which allows a trip if a differential current 2) Identify the additional time that the relay uses to sweep
is calculated and no feeder issues a blocking signal. How- input/output and process additional logic prior to
ever, the relay will not issue a trip if a feeder provides asserting a trip. That can be defined as a blocking
a blocking signal, indicating that the fault is external to window. (See the middle diagonal line in Figure 13.)
the protected bus. Depending on the relay used, it may 3) Identify the additional time required for tolerance con-
be possible to implement the protection with CTs at each siderations and to operate the output contacts. This time
tie device shared between PD zones. This scheme could delta will be several milliseconds longer for mechanical
be implemented in ring-bus configurations. Since only output contacts versus solid-state contacts. If there are
the source and ties circuits are monitored, smaller feeder communication delays added by serial communications
circuit CTs are not needed. The scheme requires that the or additional mechanical delays added by lockout relays,
trip units implement a fast ZSI-blocking signal to ensure that should be added as well. (See the top diagonal line
the signal reaches the differential function without need in Figure 13.)
to delay the function artificially. 4) Finally, the CB operation and clearing time is added. For
One risk is if the system is able to step load multiple LV CBs, it is important to consider the operating time of
feeder circuits simultaneously, causing a transient cur- a shunt trip, which may add several milliseconds. For
rent high enough to cross the differential threshold at modern MV vacuum CBs, three cycles are usually
the source circuits but not high enough to cross the enough. Five cycles may be needed for older devices.
threshold of any one feeder. In this case, none of the The top, slightly curved line in Figure 13 represents the
feeders would send a blocking signal to the upstream CB clearing time.
devices. The differential threshold would need to be Figure 13 shows a timing diagram for a differential
set above this level of current, or system controls would algorithm implemented with the instantaneous protection
need to ensure that too many loads are not step loaded of an overcurrent relay superimposed on the LV blocking-
simultaneously. Modern control systems should mini- signal timing and the 2,000-A short time and instanta-
mize this concern. Even if this type of scheme is imple- neous curve that generates the signal.
mented using separately mounted relays, it is strongly A threshold set to 10,000 A as shown in Figure 13 (2.5
recommended that the integral trip units be kept in the times the 4,000-A CT rating) can be blocked from a 2,000-
CBs set to provide adequate backup protection. A feeder. A detailed explanation of this blocking and relay
model can be found in [3]. This threshold could be a sim-
Timing Model for Blocking the Instantaneous ple IOC or a PD sum operated upon by the IOC algorithm.
Element 50 of a Microprocessor Overcurrent Relay As can be seen from this model, the ability to show the
For many LV systems, a sufficiently robust PD scheme blocking signal from the LV CB and the timing require-
could be implemented with an instantaneous multi- ment for the MV relay allows the ZSI-enabled PD zone to
element relay algorithm that can handle the few CT sets be set on top of the curve of the LV CB that is blocking
required for a zone. Most systems can be accommodated the relay. This could be the largest feeder in the zone.
with two sets for a double-ended substation. Fault cur- The question remains of whether this type of PD pro-
rents through sources are limited to one source, and cur- tection may be implemented with a simple instantaneous
rents through ties are limited to the maximum number element without the need for a more sophisticated low-
of sources minus one. A fault ahead of a main incomer impedance differential relay with percentage differential
would also see the total available fault current minus one. restraint and additional logic. The distortion of the CTs can
Based on the small number of CTs and proba- be modeled to ascertain if their performance is sufficient.
ble reasonable fault-current-to-CT ratio, a differen- Figure 14 shows the output of a CT response model that
tial scheme without restraint may be sufficient. If indicates that differential current caused by CT distortion
the instantaneous characteristic can be modeled with 4,000-A CTs for faults up to 55,000 A is approximate-
(Figure 13) to understand the time window to receive ly two times the rated CT output. Models to assess CT per-
and process a blocking signal, then the LV blocking formance are readily available from relay manufacturers.
signal and relay response can be coordinated. For a more complex application or where fault currents
The following are the steps to create the model. are larger multipliers of CT ratings, full differential relays
1) The IOC 50 algorithm fastest possible timing is identi- may be implemented. Full differential relays may be very
fied. This will vary by brand and type of relay, but, in fast and require limited added delay to provide time for
Seconds
and can allocate the CT signals in various ways by using
logical inputs to arbitrate which protection element uses
which CT input and when it is enabled are available. Relay Output
LV CB ZSI Output Signal
Therefore, a scheme as shown in this figure could be Signal Time Model
implemented with one relay. Using two relays would
require two sets of CTs around the tie CB. 0.010
Figure 16 shows a system implemented with a mul-
Relay IOC Blocking
tiple-element relay that is able to provide transformer Window
protection (87T) and several 50 and 51 elements simul- 0.010
Relay IOC Minimum
taneously. The ability to accept various CT inputs and Commit Time
use logical inputs to arbitrate which protection is used 0.001
as the system topology changes allows two relays to 1,000 10,000 100,000
provide transformer differential, bus PD protection, Amperes
timeovercurrent backup protection to the transform- LV CB Pickups; ST = 6,000 A, IOC = 16,000 A
er, and selective instantaneous protection to the LV MV Relay IOC/Differential Pickup = 10,000 A
incoming section simultaneously. CB Operating Time, Three Cycles
No Additional Intentional Delays
40
available, manufacturers will make 30
20
LV trip systems that are able to pro- 10 Seconds
vide much of the complex protec- 0
0.02 100 0.02 0.04 0.06 0.08 0.10
tion capability now only available 20
30
in MV and high-voltage-type pro- 40
50
tective relays. The ability for trip 60
70
units to communicate information 80
is not necessarily enough to provide 90
100
system-level protection and some 110
120 CT1 (Source) = 4,000:5 (C100) Vsat = 100 V
fast control solutions. The more dif- 130
140 CT Burden = 0.7
ficult requirement is for the infor- CT2 (Tie Breaker) = 4,000:5 (C100) Vsat = 100 V
mation from various sources to be CT Burden = 0.5
adequately synchronized and pro- External Fault = 55 kA. DC Offset = 1. X /R = 5
cessed with sufficient frequency so
that networked devices can replace FIGURE 14. The fault currents from incomer and tie-breaker CTs during external fault on the
quivalents neighboring LV bus.
analog devices or digital e
Conclusions
Differential and blocking-based
protection are excellent ways to
achieve an improved protection of
LV Left LV Right
Main Main main buses for both LV and MV sys-
tems. Thinking that bus differen-
LV Tie
tial protection is only for the most
sophisticated high-voltage bus or
is too complicated to consider by
LV Fdr LV Fdr other than the expert utility-systems
Blocking Signals from LV Trips designer is no longer true.
Modern digital relays, particu-
FIGURE 15. A PD scheme implemented with overcurrent relays combined with other larly low-impedance-percentage dif-
overcurrent functions. ferential relays, offer an economic
and relatively simple differential
protection option that can be used
in LV buses to supplement typical
Substation and Transformer protection provided by integral trip
51
Protection
units. This option can even be com-
MV 51 for Transformer Overcurrent
bined with the blocking capability
52 87T Protection (Primary if No
87T, Backup Otherwise) of many downstream trip units to
87T Provides Transformer achieve fast sensitive supplemen-
50PD Protection and Protection for tal protection without the need
Part of Transformer for costly and large additional CTs
Secondary LV Bus within
at each feeder circuit. In simpler
the Zone
50 systems with lower fault currents,
50PD Provides
Transformer Secondary LV multiple-element relays may be
Bus and Main LV Bus used to implement a simple instan-
Protection When the taneous PD function that can be
Incomer and Tie are Closed blocked from the LV feeder trips.
LV Main LV 50 Provides Fast Other multifunction relays are able
Protection of Transformer
LV Tie Secondary Bus And Main
to offer transformer differential as
Bus if Tie is Open well as multiple overcurrent 51 and
Will Require One Relay for instantaneous 50 elements that can
LV Fdr Each Transformer for 87T also be used in simple systems to
simultaneously provide transformer
and bus PD protection as well as
FIGURE 16. A PD implemented with overcurrent relays, other overcurrent functions, and selective instantaneous protection
transformer differential. when the bus has a single source.
T he protection engineer must
that require direct sensor input from multiple circuit understand the timing of the various algorithms and
points. Furthermore, the increasing use of air-core signals required to implement the system. A work-
sensors that are integral to the CBs provides a way able model of the varying signals and time-versus-fault
current is required. Implementing networked trip units 2015 IEEE Petroleum and Chemical Industry Committee
or equivalent protocols may also provide a cost-effective Conference. This article was reviewed by the IAS Petro-
and size-effective way to execute differential protection leum and Chemical Industry Committee.
for improved protection speed and protection sensitivity
without negatively impacting system selectivity. References
It is not the intent of this article to suggest that MV [1] B. Kasztenny, L. Sevov, and G. Brunello, Digital low-impedance bus
differential protectionReview of principles and approaches, in Proc.
relays supplant integral trip units that are normally pro- 51st Annu. Conf. Protective Relay Engineers, College Station, TX, 2001.
vided with LV CBs. Integral trip units provide several [2] Recommended Practice for the Application of Low-Voltage Circuit
advantages, such as being able to operate self-powered Breakers in Industrial and Commercial Power Systems, IEEE 3004.5-2014.
[3] M. E. Valdes and J. J. Dougherty, Advances in protective device inter-
and listed with the CBs so it is known that they cannot be locking for improved protection and selectivity, IEEE Trans. Ind. Appl.,
set beyond the ability of the CB to interrupt or withstand vol. 50, no. 3, pp. 16391648, 2014.
the fault current. Relays should be used to provide supple- [4] A. Apostolov, IEC 61850 based bus protectionPrinciples and bene-
fits, in Proc. 2009 IEEE Power & Energy Society General Meeting, pp. 16.
mental protection that improves the overall protection [5] T&D World. (2000, May). Protocol choices for the substation: Trans-
provided for the system. mission and distribution. [Online]. Available: http://tdworld.com/archive/
protocol-choices-substation
[6] National Electrical Code 2014, NFPA 70.
Author Information [7] S. Pavavicharn and G. Johnson, A review of high-impedance and low-
Lubomir Sevov is with GE Digital EnergyMultilin, impedance differential relaying for bus protection, in Proc. IEEE 67th
Markham, Ontario, Canada. Marcelo Valdes (Marcelo. Annu. Conf. Protective Relay Engineers, pp. 723737, 2014.
[8] J. Holbach, Comparison between high impedance and low imped-
Valdes@GE.com) is with GE Industrial Solutions, Cary, ance bus differential protection, in Proc. 2009 Power Systems Conf.,
North Carolina. Sevov and Valdes are Senior Members pp.116.
of the IEEE. This article first appeared as Consider-
ation for Differential Protection in LV Buses at the