a r t i c l e i n f o a b s t r a c t
Article history: The load voltage and frequency should be controlled under steady state and transient conditions in off
Received 28 November 2016 grid applications. Power quality and power management is very important task for rural communities
Revised 16 March 2017 under erratic wind and load conditions. This paper presents a coordinated Proportional resonant (PR)
Accepted 20 March 2017
and battery energy controller for enhancement of power quality and power management in direct drive
Available online xxxx
standalone wind energy system. The dynamic performance of standalone direct drive Permanent Magnet
Synchronous Generator (PMSG) is investigated with the proposed control scheme under various operat-
Keywords:
ing conditions such as fluctuating wind with step increase and decrease in wind velocity, balanced and
PMSG
Proportional resonant (PR) controller
unbalanced load conditions. The proposed PR control strategy with battery energy controller also ensures
Battery energy controller effective power balance between wind and battery source in order to fulfill the load demand. The supe-
Power quality riority of the proposed control strategy is confirmed by comparing with the traditional vector control
Power management strategy under fluctuating wind and load conditions through MATLAB/SIMULINK platform.
2017 Karabuk University. Publishing services by Elsevier B.V. This is an open access article under the CC
BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).
http://dx.doi.org/10.1016/j.jestch.2017.03.010
2215-0986/ 2017 Karabuk University. Publishing services by Elsevier B.V.
This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).
Please cite this article in press as: D.K.V. Sagiraju et al., Dynamic performance improvement of standalone battery integrated PMSG wind energy system
using proportional resonant controller, Eng. Sci. Tech., Int. J. (2017), http://dx.doi.org/10.1016/j.jestch.2017.03.010
2 D.K.V. Sagiraju et al. / Engineering Science and Technology, an International Journal xxx (2017) xxxxxx
power management. However, these control strategies are effec- also depends on turbine hub height as the wind speed tends to
tive under balanced linear loads and ineffective with unbalanced be higher as height increases from ground level.
loads. In all the aforementioned control strategies, SRF (Syn- The tip speed ratio of wind turbine is given by [6]
chronous Reference Frame) PLL is utilized to extract the phase
xm R
angle of load voltage under balanced and unbalanced grid condi- TSR kOPT 2
tions. However, SRF PLL works well for balanced load conditions
vw
and is not satisfactory under unbalanced load conditions. When where xm is the machine angular speed (in rad/s), R is turbine blade
load voltage becomes unbalanced, the negative sequence voltage radius (in m).
component creates double frequency oscillations in the generator Substituting vw from (2) into (1), the wind turbine output power
torque, and developes high stress in mechanical drive train system. can be written as
In this unbalanced condition, proper synchronization with load 3
xm R
voltage and accurate and precise information is required for the Pt 0:5qAC p 3
controller. Hence, to mitigate the negative sequence effect due to k
unbalanced loads, the authors [25,26] proposed dual vector control
strategy for standalone wind energy system. The dual vector con- 2.2. PMSG modeling
trol scheme can be implemented in dual positive and negative ref-
erence frames to extract both positive as well as negative sequence This subsection is devoted to explain about the mathematical
components from an unbalanced load voltage vector. However, the modelling of PMSG in dq-reference frame. The dq0 Parks transfor-
disadvantage of decomposition of load quantities into sequence mation is used to simplify the analysis of synchronous machinery
components involves complex transformations, which in turn models, and was first introduced by R. H. Park [8]. The mathemat-
introduce the time delay that affects the controller performance. ical model of the PMSG is related to the classical synchronous
The authors [14,23,34,24] presented fuzzy and predictive con- machine. The PMSG is modeled with an assumption of
trol schemes to improve the dynamic performance of standalone sinusoidal-distributed windings and neglecting saturation, eddy
PMSG under variable wind and load conditions. However, these currents, and hysteresis losses [9]. By Applying park transforma-
control schemes are not effective under unbalanced load condi- tion, the PMSG stator voltage from the abc to dq0 conversion is
tions. Under unbalanced load conditions, the Fuzzy and predictive written as
controller have to be realized in two synchronous reference frames 2 3 2 32 3
to extract the positive and negative sequence components sepa- Vd r cos hr cos hr 23p cos hr 23p V
6 7 26 6 a7
rately. Moreover, the complexity as well as the computational bur- 4 Vq 5 4 sin hr sin hr 23p sin hr 23p 7 54 V b 5
3 p p p
den on the controller increases. To overcome these problems and V0 2 2 2 Vc
2 2 2
to upgrade the system performance, the authors
4
[4,13,29,28,27,18,33] have proposed proportional resonant control
to improve the dynamic response for DFIG (Doubly Fed Induction Inverse Parks transformation is:
Generator) wind energy system under balanced, unbalanced and 2 3 2 p 32 3
distorted conditions. However, in the above mentioned literature, Va r cos hr sin hr 2
2
Vd
26 p 7
6 7 6 p 2 76 V 7
the authors have focussed only on power quality issues and not 4 Vb 5 cos hr 32
sin hr 23p 4 q 5 5
considered power management and reliability aspects. Hence, this
34
2 5
p
Vc cos hr 23p sin hr 23p 2
2 V0
paper explores a coordinated proportional resonant and battery
energy controller for standalone battery integrated PMSG to In (4) and (5), V abc and V dq represents the PMSG stator voltages
enhance power quality and power management under variable and V 0 0. Under balanced conditions, the stator voltage equation
wind and load conditions. The efficacy of the proposed control of the PMSG in dq-axes reference frame can be expressed as fol-
approach is manifested by analysing with the typical vector control lows [15]
strategy using Matlab/Simpower system.
d
The paper is formulated as follows. Section 2 explicates the V d Rg Ld id xe Lq iq 6
wind turbine and PMSG modeling. The proposed test system and dt
the proposed control scheme is discussed in Section 3. Section 4
d
elucidates the result analysis and finally Section 5 draws V q Rg Lq iq xe wsd 7
conclusion. dt
where Vd and Vq are the instantaneous stator voltages in the dq-
axes reference frame; id and iq are the direct and quadrature stator
2. Wind turbine and PMSG modeling currents of PMSG in dq frame; Ld and Lq are inductances on the
direct and quadrature axis; Rg is resistance of stator; xe is the elec-
2.1. Wind turbine modeling trical angular speed of the rotor; wsd is the stator flux linkage on d-
axis.
The wind turbine power at any wind speed is given by [5] Stator flux linkages in d and q axis can be written as
1 wsd Ld id wm 8
Pt qAv 3w C p k; b 1
2
wsq Lq iq 9
where A is swept area covered by turbine blade (in m2), Cp is wind Eqs. (6) and (7) can be rewritten as
turbine power coefficient as a function of tip speed ratio k and pitch
angle b (in degrees), q is air density factor in (kg/m3), Vw is wind d
V gd Rg id w xe wsq 10
speed (in m/s). dt sd
The turbine power mainly depends on various factors such as
d
maximum power coefficient, air density factor, swept area of V gq Rg iq w xe wsd 11
blades and wind speed .The power extraction from wind turbine dt sq
Please cite this article in press as: D.K.V. Sagiraju et al., Dynamic performance improvement of standalone battery integrated PMSG wind energy system
using proportional resonant controller, Eng. Sci. Tech., Int. J. (2017), http://dx.doi.org/10.1016/j.jestch.2017.03.010
D.K.V. Sagiraju et al. / Engineering Science and Technology, an International Journal xxx (2017) xxxxxx 3
The electrical speed rotation of PMSG is given by 3. Proposed system and control strategies
Please cite this article in press as: D.K.V. Sagiraju et al., Dynamic performance improvement of standalone battery integrated PMSG wind energy system
using proportional resonant controller, Eng. Sci. Tech., Int. J. (2017), http://dx.doi.org/10.1016/j.jestch.2017.03.010
4 D.K.V. Sagiraju et al. / Engineering Science and Technology, an International Journal xxx (2017) xxxxxx
Please cite this article in press as: D.K.V. Sagiraju et al., Dynamic performance improvement of standalone battery integrated PMSG wind energy system
using proportional resonant controller, Eng. Sci. Tech., Int. J. (2017), http://dx.doi.org/10.1016/j.jestch.2017.03.010
D.K.V. Sagiraju et al. / Engineering Science and Technology, an International Journal xxx (2017) xxxxxx 5
unbalanced load conditions, the load voltage contains sinusoidal The proposed control strategy is displayed in Fig. 5. The pro-
quantities of both positive sequence component and negative posed approach composed of PI controller in the outer voltage loop
sequence component in single stationary reference frame. Hence and proportional resonant controller in the inner loop of load side
the PR controller with proper tuning is capable of controlling both converter. The phase angle of load voltage is extracted using PLL.
the positive and negative sequence currents simultaneously in the The sinusoidal load currents are transformed to stationary ab sig-
stationary reference frame. nals by abc to ab transformation. In the outer voltage loop, DC link
The block diagram of PR controller is depicted in Fig. 3. voltage across the capacitor is compared with reference DC voltage
The transfer function of Proportional Resonant Controller is and mismatch is processed by PI regulator to set Id. The reference
load voltage is correlated with measured load voltage and mis-
2kri s match is processed through PI controller to generate Iq. The direct
Hab s kp 25
s2 x2r and quadrature reference currents are transformed to Ia and Ib
using dq to ab transformation to control the DC link and load volt-
where kp denotes the proportional gain, kri represents the resonant
age. The stationary reference current signals are given as input to
gain and xr is resonant frequency.
PR controller. The reference current signals are compared with
The important feature of PR controller is that it can achieve very
measured current signals which are extracted from abc to ab
high gain close to the resonant frequency and hence, it is capable of
transformation are processed through PR controller
eliminating the steady state error between the reference and mea-
sured control signal. The dynamic performance of the controller is 2kri x
determined with the proper tuning of its controller parameters. V ab kp 2 iab iab 26
s xr 2
The parameters are adjusted by performing the frequency response
analysis. Fig. 4 shows Bode plot of the transfer function of the PR The PR controller generates stationary voltage reference signals
controller given in (25). The magnitude characteristic is plotted Vab and are transformed back to abc voltage components Vabc to
with kp = 1, and for different values of integral resonant gains at generate the gate signals for inverter.
xr = 314 rad/s as shown in Fig. 4. The band width depends on inte-
gral gain of the resonant term as shown in Fig. 4. Large value of res-
3.2.3. Battery energy control strategy for Bi-directional converter for
onant gain leads to wider bandwidth and small value results in
power sharing
narrow bandwidth. Fig. 4 illustrates that, PR controller with small
The battery energy storage is interfaced to the DC link through
resonant gain offers very high gain in a narrow frequency band
bi-directional DC/DC buck-boost converter. The Primary objective
close to the resonant frequency can effectively track the AC signals
of Bi-directional DC-DC converter is to maintain the DC link voltage
to reduce the steady state error between measured and reference
as well as ensures the power balance between wind and battery to
signal and ensures better dynamic response of the controller.
meet the load power. The proposed battery energy control scheme
for bi-directional converter is presented in Fig. 6. In this control
technique, the outer loop regulates the DC-link voltage by compar-
ing the reference DC link voltage with the actual DC link voltage.
The mismatch is processed by PI regulator to set the reference bat-
tery current for the inner loop. The battery reference current is
compared with original battery current and the mismatch is pro-
cessed by PI regulator. The PI controller output is passed through
PWM (Pulse Width Modulated) generator which generates the gate
signals to trigger the upper and lower switches of DC-DC converter
to control Power in and out of battery.
When wind power is greater than the load power, the excess
power is stored in the DC link. The excess power generated by
the wind generator passes through the dc bus, and if any power
imbalance occurs, this would appear as a variation in the dc bus
Fig. 3. Block diagram of PR controller.
voltage. As a result, the DC link voltage as well as the current flow-
ing through battery increases. The reference battery current set by
the outer voltage loop is compared with the current flowing
through battery and the error is processed through PI regulator.
Based on the error signal, the PI controller generates the appropri-
ate value to generate a suitable pulse-width modulation (PWM)
signal for the switches. In this scenario, the upper switch Q1 is
turned ON and the lower switch Q2 is turned OFF with diode D1,
D2 reverse biased as shown in Fig. 7. During this interval, the con-
verter operates in buck mode and transfer power to the battery
bank. In this context, bi directional converter acts as buck con-
verter and the battery moves into charged mode of operation.
When the wind power is less than the load power, less energy is
accumulated in the DC link. Hence, the DC link voltage and current
flowing through the battery decreases. The current flowing
through the battery is compared with reference battery current.
The error is processed by the PI regulator. Based on PI controller
output, the PWM generator generates the gate signals for switches
in the bi-directional converter. In this scenario, the lower switch
Q2 is turned ON and the upper switch Q1 is turned OFF with diode
Fig. 4. Bode plot of PR controller. D1, D2 reverse biased as shown in Fig. 8. The inductor gets fully
Please cite this article in press as: D.K.V. Sagiraju et al., Dynamic performance improvement of standalone battery integrated PMSG wind energy system
using proportional resonant controller, Eng. Sci. Tech., Int. J. (2017), http://dx.doi.org/10.1016/j.jestch.2017.03.010
6 D.K.V. Sagiraju et al. / Engineering Science and Technology, an International Journal xxx (2017) xxxxxx
charged initially. Once the inductor gets fully charged, the switches
Q2 and Q1 are turned off. The diode D1 of the upper switch Q1
starts conducting as shown in Fig. 8. The converter in this case Sup-
plies power to the DC-link voltage. During this time, the converter
operates in boost mode and the battery moves into discharged
mode of operation
The charging and discharging conditions of the battery are
dependent on State of Charge (SOC). In the proposed battery con-
trol scheme, when battery SOC exceeds 50%, BESS (Battery Energy
Storage System) delivers the deficit power to load. When the SOC is
less than 90%, then the battery absorbs the excess power and oper-
Fig. 7. Bi-directional DC/DC converter in buck mode. ates in charging mode.
Please cite this article in press as: D.K.V. Sagiraju et al., Dynamic performance improvement of standalone battery integrated PMSG wind energy system
using proportional resonant controller, Eng. Sci. Tech., Int. J. (2017), http://dx.doi.org/10.1016/j.jestch.2017.03.010
D.K.V. Sagiraju et al. / Engineering Science and Technology, an International Journal xxx (2017) xxxxxx 7
4. Simulation results and discussion 4.1. Dynamic performance improvement of PMSG under variable wind
and load conditions: (Increase in wind velocity and step change in
The proposed system has been simulated in MATLAB/SIMULINK linear balanced load condition)
environment. The following cases are considered to investigate the
performance of standalone direct drive PMSG using the proposed The fluctuating load and variable wind variation is considered
control method. The results accomplished through the proposed to assess the performance of standalone PMSG. Wind velocity
control are compared with the conventional vector control. shown in Fig. 9(a) is initially set at 8 m/s and it changes from
Please cite this article in press as: D.K.V. Sagiraju et al., Dynamic performance improvement of standalone battery integrated PMSG wind energy system
using proportional resonant controller, Eng. Sci. Tech., Int. J. (2017), http://dx.doi.org/10.1016/j.jestch.2017.03.010
8 D.K.V. Sagiraju et al. / Engineering Science and Technology, an International Journal xxx (2017) xxxxxx
8 m/s to 14 m/s at t = 0.3 s. The load switching with step increase results using conventional vector control and proposed control
and decrease in load has been considered at t = 0.3 s and t = 0.6 s. strategy are shown in Fig. 10(ae). The effectiveness of proposed
The corresponding increase in load current, load power and wind control strategy to sustain the voltage and frequency within the
power are depicted in Fig. 9(bd). bounds is confirmed from Fig. 10(a) and (b). The DC link voltage
The deviation in wind and load will influence the load voltage, depicted in Fig. 10(c) is also well regulated and stays within 5%
frequency, dc link voltage and PMSG parameters. The simulation of rated value regardless of wind and load variations. As a result
Please cite this article in press as: D.K.V. Sagiraju et al., Dynamic performance improvement of standalone battery integrated PMSG wind energy system
using proportional resonant controller, Eng. Sci. Tech., Int. J. (2017), http://dx.doi.org/10.1016/j.jestch.2017.03.010
D.K.V. Sagiraju et al. / Engineering Science and Technology, an International Journal xxx (2017) xxxxxx 9
Please cite this article in press as: D.K.V. Sagiraju et al., Dynamic performance improvement of standalone battery integrated PMSG wind energy system
using proportional resonant controller, Eng. Sci. Tech., Int. J. (2017), http://dx.doi.org/10.1016/j.jestch.2017.03.010
10 D.K.V. Sagiraju et al. / Engineering Science and Technology, an International Journal xxx (2017) xxxxxx
of increase in wind speed, the respective increase in electromag- Fig. 10. In contrast, the classical PI controller has been imple-
netic torque and rotor speed are seen in Fig. 10(d) and (e). mented in dq reference frame with cross coupling terms between
Fig. 10(d)(e) illustrate that there is less variation in electromag- d and q axis. Hence, the Vector- PI controller cannot track sinu-
netic torque and rotor speed under varying wind and load condi- soidal signals and could not eliminate the steady state error. Fur-
tion. The proposed method implemented in stationary reference ther, the cross coupling effect between d and q axis deteriorates
frame offers very high gain around the resonant frequency with the performance of PI controller. Hence, large variations in load
proper selection of resonant gain. Hence the proposed method is and machine parameters is seen in Fig. 10.
capable of tracking the sinusoidal signals easily and eliminating The power sharing of PMSG Battery energy system under unsta-
the steady state error in the control and reference signal. Therefore ble wind (decrease in wind) and variable load condition is shown
with the proposed control strategy, the steady state error in load in Fig. 11. At t = 0.3 s, the drop in wind speed and increase in real
and machine parameters can be greatly reduced as shown in power load creates the mismatch in generation and load balance
Please cite this article in press as: D.K.V. Sagiraju et al., Dynamic performance improvement of standalone battery integrated PMSG wind energy system
using proportional resonant controller, Eng. Sci. Tech., Int. J. (2017), http://dx.doi.org/10.1016/j.jestch.2017.03.010
D.K.V. Sagiraju et al. / Engineering Science and Technology, an International Journal xxx (2017) xxxxxx 11
leads to under generation. Due to insufficient power generation at tery changes its mode of operation from charging to discharging
low wind speeds, the wind power could not supply enough power. mode. The load shedding at t = 0.6 s, creates mismatch between
The reduction in wind power output is depicted in Fig. 11(a). The generation and load leads to over generation. At t = 0.6 s, the bat-
increase in load power due to step increase in load is shown in tery changes its mode of operation from discharging mode to
Fig. 11(b). The battery delivers deficit power to meet the increase charging mode as shown in Fig. 11(d) to ensure stable supply of
in load demand at t = 0.3 s as seen in Fig. 11(c). At t = 0.3 s, the bat- load. The state of charge of the battery slightly decreases and
(c) DC
C link voltage
(d) Electro
omagnetic torque
Please cite this article in press as: D.K.V. Sagiraju et al., Dynamic performance improvement of standalone battery integrated PMSG wind energy system
using proportional resonant controller, Eng. Sci. Tech., Int. J. (2017), http://dx.doi.org/10.1016/j.jestch.2017.03.010
12 D.K.V. Sagiraju et al. / Engineering Science and Technology, an International Journal xxx (2017) xxxxxx
increases when change in wind and load occur as shown in Fig. 11 4.2. Dynamic performance improvement of PMSG under variable wind
(e). Fig. 11(f) shows that, the battery voltage slightly decreases by with unbalanced load conditions (decrease in wind velocity and
small amount during charging period at t = 0.3 s and increases dur- unbalanced load condition)
ing discharging period at t = 0.6 s. The proposed control strategy
ensures the power sharing to maintain reliable supply to the loads The variable wind with drop in wind velocity from 12 m/s to
under variable wind and load conditions. 6 m/s is considered at t = 0.3 s as portrayed in Fig. 12(a). The corre-
sponding wind power due to decrease in wind velocity is shown in
Fig. 12(b). The unbalanced load current is depicted in Fig. 12(c).
Due to the negative sequence component of load current under
unbalanced load condition, the load current contains some har-
monic component. The FFT (Fast Fourier Transform) analysis has
been performed to show the percentage of harmonic present in
the load current. The harmonic component of load current is
depicted in Fig. 12(d).
The simulation results using PR and PI control strategy are
shown in Fig. 13(ae). From Fig. 13(ae), it is evident that, the
effect of unbalanced load causes pulsating oscillations in load fre-
quency, electromagnetic torque, rotor speed and DC link voltage
(a) Wind power
which will reduce the life of the turbine shaft. Under unbalanced
load conditions, the load current contains sinusoidal quantities of
both positive and negative sequence component in single station-
ary reference frame. The proposed method with proper tuning of
PR control parameters is capable of controlling both the positive
and negative sequence currents simultaneously in single stationary
reference frame. Hence, from Fig. 13(ae), it can be noticed that,
the pulsating pulsations in frequency, dc-link voltage, electromag-
netic torque and rotor hub speed are minimized under unbalanced
(b) Load Power load conditions.
The power sharing of PMSG Battery energy system under unsta-
ble wind (increase in wind) and variable load condition is shown in
Fig. 14. The increase in wind speed and load at t = 0.3 s creates mis-
match between generation and load leads to over generation. The
corresponding increase in wind and load power is illustrated in
Fig. 14(a) and Fig. 14(b). Due to increase in wind velocity at
t = 0.3 s, the battery transits its mode of operation from discharging
to charging mode due to excess wind generation. Hence, battery
(c) Battery power current and power delivered by battery is reduced at t = 0.3 s, as
shown in Fig. 14(c) and Fig. 14(d). The drop in wind velocity and
the load connection at t = 0.6 s creates mismatch between genera-
tion and load leads to under generation. Hence, at t = 0.6 s, due to
deficit wind power the battery moves from charging to discharging
mode to meet the load demand. As a result, battery current and
power delivered by battery increases at t = 0.6 s, as shown in
Fig. 14(c) and (d). Fig. 14(e) illustrates that, the battery state of
charge (SOC) changes with battery charge/discharge condition to
(d) Battery current ensure power balance in the system. Fig. 14(f) shows that, the bat-
tery voltage slightly increases by small amount during charging
period at t = 0.3 s and decreases during discharging period at
t = 0.6 s. From simulation results it is shown that, the proposed
battery energy controller acts as an auxiliary source to maintain
power management in the system.
5. Conclusion
(e) State of charge of battery
This paper has presented a coordinated proportional resonant
and battery energy controller to improve power quality and power
management in standalone battery integrated PMSG wind energy
system. The robustness of the proposed controller to improve the
dynamic performance of PMSG is demonstrated under various
operating conditions. The simulation results have demonstrated
that, the proposed control scheme shows good dynamic perfor-
mance under variable wind and load conditions. The effectiveness
(f) Battery voltage
of the proposed control strategy is validated by comparing with the
Fig. 14. Simulation results for Power management for variable wind (High wind conventional vector control strategy using MATLAB/SIMULINK
velocity) and variable load conditions. environment. From the results, it is seen that, the proposed battery
Please cite this article in press as: D.K.V. Sagiraju et al., Dynamic performance improvement of standalone battery integrated PMSG wind energy system
using proportional resonant controller, Eng. Sci. Tech., Int. J. (2017), http://dx.doi.org/10.1016/j.jestch.2017.03.010
D.K.V. Sagiraju et al. / Engineering Science and Technology, an International Journal xxx (2017) xxxxxx 13
energy control scheme also ensures the power management [12] N.K. Jena, K.B. Mohanty, H. Pradhan, S.K. Sanyal, A decoupled control strategy
for a grid connected direct-drive PMSG based variable speed wind turbine
between battery and wind to meet the load demand under variable
system, in: International Conference on Energy, Power and Environment:
wind and load conditions. Towards Sustainable Growth (ICEPE), Shillong, 2015, pp. 16.
[13] H. Nian, Y. Song, Optimized parameter design of proportional integral and
Acknowledgement resonant current regulator for doubly fed induction generator during grid
voltage distortion, IET Renewable Power Gener. 8 (2014) 299313.
[14] M. Kassem, S.A. Zaid, Load parameter waveforms improvement of a stand-
The authors gratefully acknowledge the support provided by alone wind-based energy storage system and Takagi-Sugeno fuzzy logic
Shri Vishnu Engineering College for Women, Bhimavaram. algorithm, IET Renewable Power Gener. 8 (2014) 775785.
[15] P. Krause, O. Wasynczuk, S. Sudhoff, S. Pekarek, Analysis of Electric Machinery
and Drive Systems, 3rd ed., IEEE Press, Wiley Hoboken, NJ, USA, 2013.
Appendix A [16] C. Liu, K.T. Chau, X. Zhang, An efficient windphotovoltaic hybrid generation
system using doubly excited permanent-magnet brushless machine, IEEE
Trans. Ind. Electron. 57 (2010) 831839.
[17] N. Lachguer, M.T. Lamchich, Control strategy of permanent magnet
synchronous generator for standalone wind power generation system, in:
International Aegean Conference on Electrical Machines and Power Electronics
Simulation parameters Values and Electro Motion, Istanbul, 2011, pp. 392397.
[18] C. Liu, F. Blaabjerg, W. Chen, D. Xu, Stator current harmonic control with
PMSG Rated Power 40 KW
resonant controller for doubly fed induction generator, IEEE Trans. Power
PMSG Rated Voltage 595 V Electron. 27 (2012) 32073220.
PMSG Stator Resistance Rs 1.8750 pu [19] M. Mahmud Hussein, S. Tomonobu, A. Orabi Mohamed, M. Hamada, Control of
Direct Inductance 0.085 (mh) a stand-alone variable speed wind energy supply system, J. Appl. Sci. 3 (2013)
437456.
Quadrature Inductance 0.085 (mh) [20] N. Mendis, K.M. Muttaqi, S. Sayeef, S. Perera, A control approach for voltage
Machine Inertia 0.3 (J kg-m2) and frequency regulation of a Wind-Diesel-battery based hybrid remote area
Number of pole pairs 4 power supply system, in: 36th Annual Conference of the IEEE Industrial
Electronics Society, 2010, pp. 30543060.
rotor speed 200 rpm [21] N. Mendis, K.M. Muttaqi, S. Sayee, S. Perera, Operation of wind turbine-based
DC link Voltage 1200 variable speed generators with maximum power extraction capability, IEEE
DC link capacitance 20 mF Trans. Energy Converse. 27 (2012) 822834.
[22] N. Mendis, K.M. Muttaqi, S. Sayeef, Management of battery-super capacitor
Operating Wind speed 12 m/s hybrid energy storage and synchronous condenser for isolated operation of
Battery Rated Capacity (amp-h) 160 PMSG based variable-speed wind turbine generating systems, IEEE Trans.
Rated voltage of battery (V) 360 Smart Grid 5 (2014) 944953.
[23] H. Nian, R. Zeng, Improved control strategy for stand-alone distributed
PI controller parameters Kp = 12, Ki = 0.1
generation system under unbalanced and non-linear loads, IET Renewable
PR controller parameters Kp = 1, Kri = 20 Power Gener. 5 (2011) 323331.
[24] O. Onur, M. Ismail, A. Hakk, Fuzzy logic control for a wind/battery renewable
energy production system, Turk. J. Elec. Eng. Comp. Sci. 20 (2012) 187205.
[25] R. Pena, R. Cardenas, E. Escobar, J. Clare, P. Wheeler, Control system for
unbalanced operation of stand-alone doubly fed induction generators, IEEE
References Trans. Energy Convers. 22 (2007) 544545.
[26] R. Pena, R. Cardenas, E. Escobar, J. Clare, P. Wheeler, Control strategy for a
[1] L. Barote, C. Marinescu, M.N. Cirstea, Control structure for single-phase stand- Doubly-Fed Induction Generator feeding an unbalanced grid or stand-alone
alone wind-based energy sources, IEEE Trans. Ind. Electron. 60 (2013) 764 load, Electric Power Systems Research 79 (2009) 355364.
772. [27] V.T. Phan, H. Lee, Elimination of voltage harmonics in a stand-alone DFIG using
[2] B. Bahrani, A. Karimi, B. Rey, A. Rufer, Decoupled dq-current control of grid-tied a PI-R controller in the fundamental reference frame, in: IEEE International
voltage source converters using nonparametric models, IEEE Trans. Ind. Conference on Sustainable Energy Technologies (ICSET), Kandy, December,
Electron. 60 (2013) 13561366. 2010.
[3] B. Bahrani, S. Kenzelmann, A. Rufer, Multivariable-PI-based dq current control [28] V.T. Phan, H. Lee, Control strategy for harmonic elimination in stand-alone
of voltage source converters with superior axis decoupling capability, IEEE DFIG applications with nonlinear loads, IEEE Trans. Power Electron. 26 (2011)
Trans. Ind. Electron. 58 (2011) 30163026. 26622675.
[4] J. Chen, W. Zhang, B. Chen, Y. Ma, Improved vector control of brushless doubly [29] V.T. Phan, H. Lee, Performance enhancement of stand-alone DFIG systems with
fed induction generator under unbalanced grid conditions for offshore wind control of rotor and load side converters using resonant controllers, IEEE Trans.
power generation, IEEE Trans. Energy Convers. 31 (2016) 293302. Ind. Appl. 48 (2012) 199210.
[5] J. Chen, C. Gong, On optimizing the aerodynamic load acting on the turbine [30] M. Rezkallah, A. Chandra, B. Singh, M. El Kahel, Vector control of squirrel-cage
shaft of PMSG-based direct-drive wind energy conversion system, IEEE Trans. induction generator for stand-alone wind power generation, in: 38th Annual
Ind. Electron. 61 (2013) 40224031. IEEE Industrial Electronics Society conference, Montreal, QC, October, 2012.
[6] Y. Errami, M. Maaroufi, M. Ouassaid, A MPPT vector control of electric network [31] S. Zhang, K. Tseng, B. Mahindra Vilathgamuwa, T. Nguyen, X. Wang, Design of a
connected Wind Energy Conversion System employing PM Synchronous robust grid interface system for PMSG-based wind turbine generators, IEEE
Generator, in: International Renewable and Sustainable Energy Conference Trans. Ind. Electron. 58 (2011) 316328.
(IRSEC), Ouarzazate, 2013, pp. 228233. [32] R. Teodorescu, F. Blaabjerg, U. Borup, M.A. Liserre, New control structure for
[7] Y. Errami, M. Maaroufi, C. Maaroufi, M. Maaroufi, Variable structure sliding grid-connected LCL PV inverters with zero steady-state error and selective
mode control and direct torque control of wind power generation system harmonic compensation, in: Nineteenth Annual IEEE Applied Power
based on the PM synchronous generator, J. Electr. Eng. 66 (2015) 121131. Electronics Conference and Exposition, vol. 1, 2004, pp. 580586.
[8] A.E. Fitzgerald, C. Kingsley, S.D. Umans, Electric machinery, sixth ed., McGraw- [33] F. Wei, D.M. Vilathgamuwa, S. Choi, X. Zhang, Improved control of rotor- and
Hill, Boston, 2003. load-side converters of stand-alone DFIGs under nonlinear loads conditions,
[9] Lijun He, Yongdong Li, R.G. Harley, Adaptive multi-mode power control of a in: IEEE ECCE Asia Conference, Melbourne, June 2013.
direct-drive PM wind generation system in a micro grid, IEEE J. Emerg. Sel. Top. [34] H. Zeng, Y. Nian, J. Quan, J. Liu, Improved load-adaptive control strategy for
Power Electron. 1 (2013) 217225. PMSG based stand-alone wind energy generation system, in: IEEE
[10] M.E. Haque, K.M. Muttaqi, M. Negnevitsky, Control of a standalone variable International Conference on Electrical Machines and Systems, Tokyo,
speed wind turbine with a permanent magnet synchronous generator, in: IEEE November 2009.
Power and Energy Society General Meeting - Conversion and Delivery of [35] D.N. Zmood, D.G. Holmes, Stationary frame current regulation of PWM
Electrical Energy in the 21st Century, Pittsburgh, PA, July, 2008. inverters with zero steady-state error, IEEE Trans. Power Electron. 18 (2003)
[11] M.E. Haque, M.K. Negnevitsky, M.A. Muttaqi, Novel control strategy for a 814822.
variable-speed wind turbine with a permanent-magnet synchronous
generator, IEEE Trans. Ind. Electron. 46 (2010) 331339.
Please cite this article in press as: D.K.V. Sagiraju et al., Dynamic performance improvement of standalone battery integrated PMSG wind energy system
using proportional resonant controller, Eng. Sci. Tech., Int. J. (2017), http://dx.doi.org/10.1016/j.jestch.2017.03.010