Space Input Data

TALAL VILLA 09/12/2017


555 08:45PM

FF MASTERBED SIT

1. General Details:
Floor Area ............................................................... 64.0 m
Avg. Ceiling Height ................................................... 3.1 m
Building Weight .................................................... 341.8 kg/m
1.1. OA Ventilation Requirements:
Space Usage .......................................... User-Defined
OA Requirement 1 .................................................... 2.0 L/s/person
OA Requirement 2 .................................................. 0.00 L/(s-m)
Space Usage Defaults ........... ASHRAE Std 62.1-2004

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .............................. Recessed (Unvented) Occupancy ............................................................... 5.0 People
Wattage ................................................................ 40.00 W/m Activity Level ...................................... Sedentary Work
Ballast Multiplier ..................................................... 1.15 Sensible .................................................................. 82.1 W/person
Schedule ............................................................. 24 HR Latent ..................................................................... 79.1 W/person
Schedule ............................................................. 24 HR

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .................................................................. 0.00 W/m Sensible ....................................................................... 0 W
Schedule .............................................................. None Schedule ............................................................. 24 HR
Latent ........................................................................... 0 W
Schedule ............................................................. 24 HR
2.3. Electrical Equipment:
Wattage ................................................................ 320.0 Watts
Schedule ............................................................. 24 HR

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 25.5 18 0 0

3.1. Construction Types for Exposure E


Wall Type ........................................................ SINGLE WALL
1st Window Type ..................................................... WINDOW

4. Roofs, Skylights:

Exp. Roof Gross Area (m) Roof Slope (deg.) Skylight Qty.
H 64.0 0 0

4.1. Construction Types for Exposure H


Roof Type ..................................................................... ROOF

5. Infiltration:
Design Cooling ....................................................... 0.00 ACH
Design Heating ....................................................... 0.00 L/s
Energy Analysis ...................................................... 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ........................ Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ......................................... Wall Partition (No partition data)
Area ........................................................................ 10.0 m
U-Value ................................................................. 3.800 W/(m-K)
Uncondit. Space Max Temp ................................... 35.0 C
Ambient at Space Max Temp ................................. 46.0 C
Uncondit. Space Min Temp .................................... 24.0 C
Ambient at Space Min Temp .................................. 12.0 C
.
1. General Details:
Floor Area ............................................................... 83.0 m
FF MASTERBED+CHNGE Avg. Ceiling Height ................................................... 3.1 m
Building Weight .................................................... 341.8 kg/m

Hourly Analysis Program v4.50 Page 1 of 13


Space Input Data
TALAL VILLA 09/12/2017
555 08:45PM

1.1. OA Ventilation Requirements: 2.4. People:


Space Usage .................. PUBLIC ASSEMBLY: Lobby Occupancy ............................................................... 5.0 People
OA Requirement 1 .................................................... 2.5 L/s/person Activity Level ...................................... Sedentary Work
OA Requirement 2 .................................................. 0.30 L/(s-m) Sensible .................................................................. 82.1 W/person
Space Usage Defaults ........... ASHRAE Std 62.1-2004 Latent ..................................................................... 79.1 W/person
Schedule ............................................................. 24 HR
2. Internals:
2.1. Overhead Lighting:
Fixture Type .............................. Recessed (Unvented)
Wattage ................................................................ 45.00 W/m
Ballast Multiplier ..................................................... 1.15
Schedule ............................................................. 24 HR

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .................................................................. 0.00 W/m Sensible ....................................................................... 0 W
Schedule .............................................................. None Schedule ............................................................. 24 HR
Latent ........................................................................... 0 W
Schedule ............................................................. 24 HR
2.3. Electrical Equipment:
Wattage .................................................................. 5.00 W/m
Schedule ............................................................. 24 HR

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 21.0 9 0 0
E 15.0 0 0 0

3.1. Construction Types for Exposure N


Wall Type ........................................................ SINGLE WALL
1st Window Type ..................................................... WINDOW

3.2. Construction Types for Exposure E


Wall Type ........................................................ SINGLE WALL

4. Roofs, Skylights:

Exp. Roof Gross Area (m) Roof Slope (deg.) Skylight Qty.
H 83.0 0 0

4.1. Construction Types for Exposure H


Roof Type ..................................................................... ROOF

5. Infiltration:
Design Cooling ....................................................... 0.10 ACH
Design Heating ....................................................... 0.00 L/s
Energy Analysis ...................................................... 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ........................ Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ......................................... Wall Partition (No partition data)
Area ........................................................................ 50.0 m
U-Value ................................................................. 3.800 W/(m-K)
Uncondit. Space Max Temp ................................... 35.0 C
Ambient at Space Max Temp ................................. 46.0 C
Uncondit. Space Min Temp .................................... 24.0 C
Ambient at Space Min Temp .................................. 12.0 C
.
1.1. OA Ventilation Requirements:
Space Usage ......... MISCELLANEOUS: Photo studio
FF TV ROOM OA Requirement 1 .................................................... 2.5 L/s/person
OA Requirement 2 .................................................. 0.60 L/(s-m)
1. General Details: Space Usage Defaults ........... ASHRAE Std 62.1-2004
Floor Area ............................................................... 37.6 m
Avg. Ceiling Height ................................................... 3.1 m 2. Internals:
Building Weight .................................................... 341.8 kg/m 2.1. Overhead Lighting:

Hourly Analysis Program v4.50 Page 2 of 13


Space Input Data
TALAL VILLA 09/12/2017
555 08:45PM

Fixture Type .............................. Recessed (Unvented) 2.4. People:


Wattage ................................................................ 40.00 W/m Occupancy ............................................................... 5.0 People
Ballast Multiplier ..................................................... 1.15 Activity Level ...................................... Sedentary Work
Schedule ............................................................. 24 HR Sensible .................................................................. 82.1 W/person
Latent ..................................................................... 79.1 W/person
Schedule ............................................................. 24 HR

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .................................................................. 0.00 W/m Sensible ....................................................................... 0 W
Schedule .............................................................. None Schedule ............................................................. 24 HR
Latent ........................................................................... 0 W
Schedule ............................................................. 24 HR
2.3. Electrical Equipment:
Wattage ................................................................ 15.00 W/m
Schedule ............................................................. 24 HR

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 16.0 11 0 0
E 14.0 0 0 0

3.1. Construction Types for Exposure N


Wall Type ........................................................ SINGLE WALL
1st Window Type ..................................................... WINDOW

3.2. Construction Types for Exposure E


Wall Type ........................................................ SINGLE WALL

4. Roofs, Skylights:

Exp. Roof Gross Area (m) Roof Slope (deg.) Skylight Qty.
H 24.0 0 0

4.1. Construction Types for Exposure H


Roof Type ..................................................................... ROOF

5. Infiltration:
Design Cooling ....................................................... 0.00 ACH
Design Heating ....................................................... 0.00 L/s
Energy Analysis ...................................................... 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ........................ Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ......................................... Wall Partition (No partition data)
Area ........................................................................ 20.0 m
U-Value ................................................................. 3.800 W/(m-K)
Uncondit. Space Max Temp ................................... 35.0 C
Ambient at Space Max Temp ................................. 46.0 C
Uncondit. Space Min Temp .................................... 24.0 C
Ambient at Space Min Temp .................................. 12.0 C
.
2. Internals:
2.1. Overhead Lighting:
GF DINING Fixture Type .............................. Recessed (Unvented)
Wattage ................................................................ 45.00 W/m
1. General Details: Ballast Multiplier ..................................................... 1.15
Floor Area ............................................................... 31.0 m Schedule ............................................................. 24 HR
Avg. Ceiling Height ................................................... 3.1 m
Building Weight .................................................... 341.8 kg/m
1.1. OA Ventilation Requirements:
Space Usage FOOD SERVICE: Restaurant dining room
OA Requirement 1 .................................................... 3.8 L/s/person
OA Requirement 2 .................................................. 0.90 L/(s-m)
Space Usage Defaults ........... ASHRAE Std 62.1-2004

Hourly Analysis Program v4.50 Page 3 of 13


Space Input Data
TALAL VILLA 09/12/2017
555 08:45PM

2.4. People: Sensible .................................................................. 82.1 W/person


Occupancy ............................................................... 5.0 People Latent ..................................................................... 79.1 W/person
Activity Level ...................................... Sedentary Work Schedule ............................................................. 24 HR

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .................................................................. 0.00 W/m Sensible ................................................................... 200 W
Schedule .............................................................. None Schedule ............................................................. 24 HR
Latent ...................................................................... 200 W
Schedule ............................................................. 24 HR
2.3. Electrical Equipment:
Wattage ................................................................ 250.0 Watts
Schedule ............................................................. 24 HR

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 20.0 7 0 0
N 16.3 11 0 0

3.1. Construction Types for Exposure W


Wall Type ........................................................ SINGLE WALL
1st Window Type ..................................................... WINDOW

3.2. Construction Types for Exposure N


Wall Type ........................................................ SINGLE WALL
1st Window Type ..................................................... WINDOW

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ....................................................... 0.10 ACH
Design Heating ....................................................... 0.00 L/s
Energy Analysis ...................................................... 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ........................ Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ......................................... Wall Partition (No partition data)
Area ........................................................................ 35.0 m
U-Value ................................................................. 2.400 W/(m-K)
Uncondit. Space Max Temp ................................... 35.0 C
Ambient at Space Max Temp ................................. 46.0 C
Uncondit. Space Min Temp .................................... 24.0 C
Ambient at Space Min Temp .................................. 12.0 C
.
2.4. People:
Occupancy ............................................................... 5.0 People
GF GAMES ROOM Activity Level ...................................... Sedentary Work
Sensible .................................................................. 82.1 W/person
1. General Details: Latent ..................................................................... 79.1 W/person
Floor Area ............................................................... 31.0 m Schedule ............................................................. 24 HR
Avg. Ceiling Height ................................................... 3.1 m
Building Weight .................................................... 341.8 kg/m
1.1. OA Ventilation Requirements:
Space Usage ....................... SPORTS: Games arcade
OA Requirement 1 .................................................... 3.8 L/s/person
OA Requirement 2 .................................................. 0.90 L/(s-m)
Space Usage Defaults ........... ASHRAE Std 62.1-2004

2. Internals:
2.1. Overhead Lighting:
Fixture Type .............................. Recessed (Unvented)
Wattage ................................................................ 45.00 W/m
Ballast Multiplier ..................................................... 1.15
Schedule ............................................................. 24 HR

2.2. Task Lighting: Wattage .................................................................. 0.00 W/m

Hourly Analysis Program v4.50 Page 4 of 13


Space Input Data
TALAL VILLA 09/12/2017
555 08:45PM

Schedule .............................................................. None 2.5. Miscellaneous Loads:


Sensible ....................................................................... 0 W
Schedule ............................................................. 24 HR
Latent ........................................................................... 0 W
Schedule ............................................................. 24 HR
2.3. Electrical Equipment:
Wattage .................................................................. 5.00 W/m
Schedule ............................................................. 24 HR

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 15.0 8 0 0
E 20.0 3 0 0

3.1. Construction Types for Exposure S


Wall Type ........................................................ SINGLE WALL
1st Window Type ..................................................... WINDOW

3.2. Construction Types for Exposure E


Wall Type ........................................................ SINGLE WALL
1st Window Type ..................................................... WINDOW

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ....................................................... 0.10 ACH
Design Heating ....................................................... 0.00 L/s
Energy Analysis ...................................................... 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ........................ Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ......................................... Wall Partition (No partition data)
Area ........................................................................ 10.0 m
U-Value ................................................................. 3.500 W/(m-K)
Uncondit. Space Max Temp ................................... 35.0 C
Ambient at Space Max Temp ................................. 46.0 C
Uncondit. Space Min Temp .................................... 24.0 C
Ambient at Space Min Temp .................................. 12.0 C
.
2.4. People:
Occupancy ............................................................... 5.0 People
GF GUEST ROOM Activity Level ...................................... Sedentary Work
Sensible .................................................................. 82.1 W/person
1. General Details: Latent ..................................................................... 79.1 W/person
Floor Area ............................................................... 30.0 m Schedule ............................................................. 24 HR
Avg. Ceiling Height ................................................... 3.1 m
Building Weight .................................................... 341.8 kg/m
1.1. OA Ventilation Requirements:
Space Usage .............. HOTEL: Bedroom/living room
OA Requirement 1 .................................................... 2.5 L/s/person
OA Requirement 2 .................................................. 0.30 L/(s-m)
Space Usage Defaults ........... ASHRAE Std 62.1-2004

2. Internals:
2.1. Overhead Lighting:
Fixture Type .............................. Recessed (Unvented)
Wattage ................................................................ 45.00 W/m
Ballast Multiplier ..................................................... 1.15
Schedule ............................................................. 24 HR

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .................................................................. 0.00 W/m Sensible ....................................................................... 0 W
Schedule .............................................................. None Schedule ............................................................. 24 HR
Latent ........................................................................... 0 W
Schedule ............................................................. 24 HR

Hourly Analysis Program v4.50 Page 5 of 13


Space Input Data
TALAL VILLA 09/12/2017
555 08:45PM

2.3. Electrical Equipment:


Wattage .................................................................. 5.00 W/m
Schedule ............................................................. 24 HR

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 15.0 8 0 0
E 20.0 3 0 0

3.1. Construction Types for Exposure N


Wall Type ........................................................ SINGLE WALL
1st Window Type ..................................................... WINDOW

3.2. Construction Types for Exposure E


Wall Type ........................................................ SINGLE WALL
1st Window Type ..................................................... WINDOW

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ....................................................... 0.05 ACH
Design Heating ....................................................... 0.00 L/s
Energy Analysis ...................................................... 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ........................ Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ......................................... Wall Partition (No partition data)
Area ........................................................................ 10.0 m
U-Value ................................................................. 3.500 W/(m-K)
Uncondit. Space Max Temp ................................... 35.0 C
Ambient at Space Max Temp ................................. 46.0 C
Uncondit. Space Min Temp .................................... 24.0 C
Ambient at Space Min Temp .................................. 12.0 C
.
2.4. People:
Occupancy ............................................................... 3.0 People
GF INDOOR KIT Activity Level ...................................... Sedentary Work
Sensible .................................................................. 82.1 W/person
1. General Details: Latent ..................................................................... 79.1 W/person
Floor Area ............................................................... 21.4 m Schedule ............................................................. 24 HR
Avg. Ceiling Height ................................................... 3.1 m
Building Weight .................................................... 341.8 kg/m
1.1. OA Ventilation Requirements:
Space Usage .................. PUBLIC ASSEMBLY: Lobby
OA Requirement 1 .................................................... 2.5 L/s/person
OA Requirement 2 .................................................. 0.30 L/(s-m)
Space Usage Defaults ........... ASHRAE Std 62.1-2004

2. Internals:
2.1. Overhead Lighting:
Fixture Type .............................. Recessed (Unvented)
Wattage ................................................................ 35.00 W/m
Ballast Multiplier ..................................................... 1.15
Schedule ............................................................. 24 HR

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .................................................................. 0.00 W/m Sensible ....................................................................... 0 W
Schedule .............................................................. None Schedule ............................................................. 24 HR
Latent ........................................................................... 0 W
Schedule ............................................................. 24 HR
2.3. Electrical Equipment:
Wattage .............................................................. 150.00 W/m
Schedule ............................................................. 24 HR

3. Walls, Windows, Doors:

Hourly Analysis Program v4.50 Page 6 of 13


Space Input Data
TALAL VILLA 09/12/2017
555 08:45PM

Exp. Wall Gross Area (m) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 16.0 6 0 0

3.1. Construction Types for Exposure S


Wall Type ........................................................ SINGLE WALL
1st Window Type ..................................................... WINDOW

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ....................................................... 0.10 ACH
Design Heating ....................................................... 0.00 L/s
Energy Analysis ...................................................... 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ........................ Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ......................................... Wall Partition (No partition data)
Area ........................................................................ 40.0 m
U-Value ................................................................. 3.800 W/(m-K)
Uncondit. Space Max Temp ................................... 35.0 C
Ambient at Space Max Temp ................................. 46.0 C
Uncondit. Space Min Temp .................................... 24.0 C
Ambient at Space Min Temp .................................. 12.0 C
.
2.4. People:
Occupancy ............................................................... 5.0 People
GF LIVING Activity Level ............................................. Heavy Work
Sensible ................................................................ 153.9 W/person
1. General Details: Latent ................................................................... 271.1 W/person
Floor Area ............................................................... 54.0 m Schedule ............................................................. 24 HR
Avg. Ceiling Height ................................................... 3.1 m
Building Weight .................................................... 341.8 kg/m
1.1. OA Ventilation Requirements:
Space Usage FOOD SERVICE: Restaurant dining room
OA Requirement 1 .................................................... 3.8 L/s/person
OA Requirement 2 .................................................. 0.90 L/(s-m)
Space Usage Defaults ........... ASHRAE Std 62.1-2004

2. Internals:
2.1. Overhead Lighting:
Fixture Type .............................. Recessed (Unvented)
Wattage ................................................................ 55.00 W/m
Ballast Multiplier ..................................................... 1.15
Schedule ............................................................. 24 HR

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .................................................................. 0.00 W/m Sensible ................................................................... 200 W
Schedule .............................................................. None Schedule ............................................................. 24 HR
Latent ...................................................................... 200 W
Schedule ............................................................. 24 HR
2.3. Electrical Equipment:
Wattage .................................................................. 9.26 W/m
Schedule ............................................................. 24 HR

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 5.0 0 0 0
N 20.1 19 0 0
E 5.0 0 0 0

3.1. Construction Types for Exposure W


Wall Type ........................................................ SINGLE WALL

Hourly Analysis Program v4.50 Page 7 of 13


Space Input Data
TALAL VILLA 09/12/2017
555 08:45PM

3.2. Construction Types for Exposure N


Wall Type ........................................................ SINGLE WALL
1st Window Type ..................................................... WINDOW

3.3. Construction Types for Exposure E


Wall Type ........................................................ SINGLE WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ....................................................... 0.10 ACH
Design Heating ....................................................... 0.00 L/s
Energy Analysis ...................................................... 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ........................ Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ......................................... Wall Partition (No partition data)
Area ........................................................................ 13.0 m
U-Value ................................................................. 4.400 W/(m-K)
Uncondit. Space Max Temp ................................... 35.0 C
Ambient at Space Max Temp ................................. 46.0 C
Uncondit. Space Min Temp .................................... 24.0 C
Ambient at Space Min Temp .................................. 12.0 C
.
2.4. People:
Occupancy ............................................................... 3.0 People
GF OUTDOOR KIT Activity Level ...................................... Sedentary Work
Sensible .................................................................. 82.1 W/person
1. General Details: Latent ..................................................................... 79.1 W/person
Floor Area ............................................................... 16.2 m Schedule ............................................................. 24 HR
Avg. Ceiling Height ................................................... 3.1 m
Building Weight .................................................... 341.8 kg/m
1.1. OA Ventilation Requirements:
Space Usage .................. PUBLIC ASSEMBLY: Lobby
OA Requirement 1 .................................................... 2.5 L/s/person
OA Requirement 2 .................................................. 0.30 L/(s-m)
Space Usage Defaults ........... ASHRAE Std 62.1-2004

2. Internals:
2.1. Overhead Lighting:
Fixture Type .............................. Recessed (Unvented)
Wattage ................................................................ 35.00 W/m
Ballast Multiplier ..................................................... 1.15
Schedule ............................................................. 24 HR

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .................................................................. 0.00 W/m Sensible ....................................................................... 0 W
Schedule .............................................................. None Schedule ............................................................. 24 HR
Latent ........................................................................... 0 W
Schedule ............................................................. 24 HR
2.3. Electrical Equipment:
Wattage .............................................................. 150.00 W/m
Schedule ............................................................. 24 HR

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 16.0 0 0 0

3.1. Construction Types for Exposure W


Wall Type ........................................................ SINGLE WALL

4. Roofs, Skylights:

Exp. Roof Gross Area (m) Roof Slope (deg.) Skylight Qty.
H 16.2 0 0

Hourly Analysis Program v4.50 Page 8 of 13


Space Input Data
TALAL VILLA 09/12/2017
555 08:45PM

4.1. Construction Types for Exposure H


Roof Type ..................................................................... ROOF

5. Infiltration:
Design Cooling ....................................................... 0.10 ACH
Design Heating ....................................................... 0.00 L/s
Energy Analysis ...................................................... 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ........................ Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ......................................... Wall Partition (No partition data)
Area ........................................................................ 40.0 m
U-Value ................................................................. 3.800 W/(m-K)
Uncondit. Space Max Temp ................................... 35.0 C
Ambient at Space Max Temp ................................. 46.0 C
Uncondit. Space Min Temp .................................... 24.0 C
Ambient at Space Min Temp .................................. 12.0 C
.
2.4. People:
Occupancy ............................................................. 10.0 People
GF PASSAGE Activity Level ...................................... Sedentary Work
Sensible .................................................................. 82.1 W/person
1. General Details: Latent ..................................................................... 79.1 W/person
Floor Area ............................................................... 46.6 m Schedule ............................................................. 24 HR
Avg. Ceiling Height ................................................... 3.1 m
Building Weight .................................................... 341.8 kg/m
1.1. OA Ventilation Requirements:
Space Usage .................. PUBLIC ASSEMBLY: Lobby
OA Requirement 1 .................................................... 2.5 L/s/person
OA Requirement 2 .................................................. 0.30 L/(s-m)
Space Usage Defaults ........... ASHRAE Std 62.1-2004

2. Internals:
2.1. Overhead Lighting:
Fixture Type .............................. Recessed (Unvented)
Wattage ................................................................ 45.00 W/m
Ballast Multiplier ..................................................... 1.15
Schedule ............................................................. 24 HR

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .................................................................. 0.00 W/m Sensible ....................................................................... 0 W
Schedule .............................................................. None Schedule ............................................................. 24 HR
Latent ........................................................................... 0 W
Schedule ............................................................. 24 HR
2.3. Electrical Equipment:
Wattage .................................................................. 5.00 W/m
Schedule ............................................................. 24 HR

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 6.0 0 0 0
S 8.4 0 0 0

3.1. Construction Types for Exposure W


Wall Type ........................................................ SINGLE WALL

3.2. Construction Types for Exposure S


Wall Type ........................................................ SINGLE WALL

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ....................................................... 0.10 ACH
Design Heating ....................................................... 0.00 L/s

Hourly Analysis Program v4.50 Page 9 of 13


Space Input Data
TALAL VILLA 09/12/2017
555 08:45PM

Energy Analysis ...................................................... 0.00 L/s


Infiltration occurs only when the fan is off.

6. Floors:
Type ........................ Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ......................................... Wall Partition (No partition data)
Area ........................................................................ 70.0 m
U-Value ................................................................. 3.800 W/(m-K)
Uncondit. Space Max Temp ................................... 35.0 C
Ambient at Space Max Temp ................................. 46.0 C
Uncondit. Space Min Temp .................................... 24.0 C
Ambient at Space Min Temp .................................. 12.0 C
.
2.4. People:
Occupancy ............................................................... 5.0 People
PH BED 3 Activity Level ...................................... Sedentary Work
Sensible .................................................................. 82.1 W/person
1. General Details: Latent ..................................................................... 79.1 W/person
Floor Area ............................................................... 32.0 m Schedule ............................................................. 24 HR
Avg. Ceiling Height ................................................... 3.1 m
Building Weight .................................................... 341.8 kg/m
1.1. OA Ventilation Requirements:
Space Usage .............. HOTEL: Bedroom/living room
OA Requirement 1 .................................................... 2.5 L/s/person
OA Requirement 2 .................................................. 0.30 L/(s-m)
Space Usage Defaults ........... ASHRAE Std 62.1-2004

2. Internals:
2.1. Overhead Lighting:
Fixture Type .............................. Recessed (Unvented)
Wattage ................................................................ 40.00 W/m
Ballast Multiplier ..................................................... 1.15
Schedule ............................................................. 24 HR

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .................................................................. 0.00 W/m Sensible ....................................................................... 0 W
Schedule .............................................................. None Schedule ............................................................. 24 HR
Latent ........................................................................... 0 W
Schedule ............................................................. 24 HR
2.3. Electrical Equipment:
Wattage ................................................................ 190.0 Watts
Schedule ............................................................. 24 HR

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 16.5 6 0 0
E 17.3 0 0 0

3.1. Construction Types for Exposure S


Wall Type ........................................................ SINGLE WALL
1st Window Type ..................................................... WINDOW

3.2. Construction Types for Exposure E


Wall Type ........................................................ SINGLE WALL

4. Roofs, Skylights:

Exp. Roof Gross Area (m) Roof Slope (deg.) Skylight Qty.
H 32.0 0 0

4.1. Construction Types for Exposure H


Roof Type ..................................................................... ROOF

5. Infiltration:
Design Cooling ....................................................... 0.00 ACH
Design Heating ....................................................... 0.00 L/s

Hourly Analysis Program v4.50 Page 10 of 13


Space Input Data
TALAL VILLA 09/12/2017
555 08:45PM

Energy Analysis ...................................................... 0.00 L/s


Infiltration occurs only when the fan is off.

6. Floors:
Type ........................ Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ......................................... Wall Partition (No partition data)
Area ........................................................................ 20.0 m
U-Value ................................................................. 3.800 W/(m-K)
Uncondit. Space Max Temp ................................... 35.0 C
Ambient at Space Max Temp ................................. 46.0 C
Uncondit. Space Min Temp .................................... 24.0 C
Ambient at Space Min Temp .................................. 12.0 C
.
2.4. People:
Occupancy ............................................................... 9.0 People
PH GYM Activity Level ............................................. Heavy Work
Sensible ................................................................ 153.9 W/person
1. General Details: Latent ................................................................... 271.1 W/person
Floor Area ............................................................... 26.0 m Schedule ............................................................. 24 HR
Avg. Ceiling Height ................................................... 3.1 m
Building Weight .................................................... 341.8 kg/m
1.1. OA Ventilation Requirements:
Space Usage .... SPORTS: Gym, stadium (play area)
OA Requirement 1 .................................................... 0.0 L/s/person
OA Requirement 2 .................................................. 1.50 L/(s-m)
Space Usage Defaults ........... ASHRAE Std 62.1-2004

2. Internals:
2.1. Overhead Lighting:
Fixture Type .............................. Recessed (Unvented)
Wattage ................................................................ 40.00 W/m
Ballast Multiplier ..................................................... 1.15
Schedule ............................................................. 24 HR

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .................................................................. 0.00 W/m Sensible ....................................................................... 0 W
Schedule .............................................................. None Schedule ............................................................. 24 HR
Latent ........................................................................... 0 W
Schedule ............................................................. 24 HR
2.3. Electrical Equipment:
Wattage ................................................................ 600.0 Watts
Schedule ............................................................. 24 HR

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 17.6 0 0 0
E 13.3 0 0 0

3.1. Construction Types for Exposure N


Wall Type ........................................................ SINGLE WALL

3.2. Construction Types for Exposure E


Wall Type ........................................................ SINGLE WALL

4. Roofs, Skylights:

Exp. Roof Gross Area (m) Roof Slope (deg.) Skylight Qty.
H 26.0 0 0

4.1. Construction Types for Exposure H


Roof Type ..................................................................... ROOF

5. Infiltration:
Design Cooling ....................................................... 0.20 ACH
Design Heating ....................................................... 0.00 L/s
Energy Analysis ...................................................... 0.00 L/s

Hourly Analysis Program v4.50 Page 11 of 13


Space Input Data
TALAL VILLA 09/12/2017
555 08:45PM

Infiltration occurs only when the fan is off.

6. Floors:
Type ........................ Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ......................................... Wall Partition (No partition data)
Area ........................................................................ 20.0 m
U-Value ................................................................. 3.800 W/(m-K)
Uncondit. Space Max Temp ................................... 35.0 C
Ambient at Space Max Temp ................................. 46.0 C
Uncondit. Space Min Temp .................................... 24.0 C
Ambient at Space Min Temp .................................. 12.0 C
.
2.4. People:
Occupancy ............................................................... 3.0 People
PH STUDY Activity Level ...................................... Sedentary Work
Sensible .................................................................. 82.1 W/person
1. General Details: Latent ..................................................................... 79.1 W/person
Floor Area ............................................................... 16.3 m Schedule ............................................................. 24 HR
Avg. Ceiling Height ................................................... 3.1 m
Building Weight .................................................... 341.8 kg/m
1.1. OA Ventilation Requirements:
Space Usage ............................ OFFICE: Office space
OA Requirement 1 .................................................... 2.5 L/s/person
OA Requirement 2 .................................................. 0.30 L/(s-m)
Space Usage Defaults ........... ASHRAE Std 62.1-2004

2. Internals:
2.1. Overhead Lighting:
Fixture Type .............................. Recessed (Unvented)
Wattage ................................................................ 40.00 W/m
Ballast Multiplier ..................................................... 1.15
Schedule ............................................................. 24 HR

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .................................................................. 0.00 W/m Sensible ....................................................................... 0 W
Schedule .............................................................. None Schedule ............................................................. 24 HR
Latent ........................................................................... 0 W
Schedule ............................................................. 24 HR
2.3. Electrical Equipment:
Wattage .................................................................. 5.00 W/m
Schedule ............................................................. 24 HR

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 12.0 1 0 0
E 13.3 6 0 0

3.1. Construction Types for Exposure S


Wall Type ........................................................ SINGLE WALL
1st Window Type ..................................................... WINDOW

3.2. Construction Types for Exposure E


Wall Type ........................................................ SINGLE WALL
1st Window Type ..................................................... WINDOW

4. Roofs, Skylights:

Exp. Roof Gross Area (m) Roof Slope (deg.) Skylight Qty.
H 16.3 0 0

4.1. Construction Types for Exposure H


Roof Type ..................................................................... ROOF

5. Infiltration:
Design Cooling ....................................................... 0.20 ACH
Design Heating ....................................................... 0.00 L/s

Hourly Analysis Program v4.50 Page 12 of 13


Space Input Data
TALAL VILLA 09/12/2017
555 08:45PM

Energy Analysis ...................................................... 0.00 L/s


Infiltration occurs only when the fan is off.

6. Floors:
Type ........................ Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ......................................... Wall Partition (No partition data)
Area ........................................................................ 20.0 m
U-Value ................................................................. 3.800 W/(m-K)
Uncondit. Space Max Temp ................................... 35.0 C
Ambient at Space Max Temp ................................. 46.0 C
Uncondit. Space Min Temp .................................... 24.0 C
Ambient at Space Min Temp .................................. 12.0 C
.

Hourly Analysis Program v4.50 Page 13 of 13