Veeder-Root shall not be liable for errors contained herein or for incidental or consequential damages in connection with the
furnishing, performance, or use of this publication.
Veeder-Root reserves the right to change system options or features, or the information contained in this publication.
This publication contains proprietary information which is protected by copyright. All rights reserved. No part of this publication
may be photocopied, reproduced, or translated to another language without the prior written consent of Veeder-Root.
Contact TLS Systems Technical Support for additional troubleshooting information at 800-323-1799.
RETURN SHIPPING
For the parts return procedure, please follow the appropriate instructions in the "General Returned Goods Policy pages in the
"Policies and Literature" section of the Veeder-Root North American Environmental Products price list. Veeder-Root will not
accept any return product without a Return Goods Authorization (RGA) number clearly printed on the outside of the package.
Introduction
Contractor Certification Requirements .................................................................... 1
Related Manuals ..................................................................................................... 1
Safety Symbols ....................................................................................................... 2
Safety Warnings ...................................................................................................... 2
Regulatory Compliance and Approvals ................................................................... 3
Console ................................................................................................................... 3
Monitoring Functions ............................................................................................ 3
Output Relay......................................................................................................... 3
Communications Functions .................................................................................. 3
Alarm Message Quick Reference Index .................................................................. 4
iii
Contents
Reports
System Reports ..................................................................................................... 49
Inventory Reports .................................................................................................. 50
Example Report Printout - Inventory Report with TC volume ............................. 50
Example Report Printout - Timed Shift Inventory Report with TC volume .......... 50
Example Report Printout - Snapshot Shift Inventory Report .............................. 51
Inventory Report Notes ....................................................................................... 51
Example Report Printout - Inventory Log Report ................................................ 51
Inventory Log Report Notes ................................................................................ 51
Active Alarm Status Screen ................................................................................... 52
Alarm Reports ....................................................................................................... 52
Important Alarm Notes........................................................................................ 53
Information on Alarm States .................................................................................. 54
Active Alarm........................................................................................................ 54
Acknowledging an Active Alarm ......................................................................... 54
Returning to Normal State .................................................................................. 54
In-Tank Alarm Information ..................................................................................... 54
Max Product Alarm ............................................................................................. 54
Overfill Alarm ...................................................................................................... 54
Low Product Alarm ............................................................................................. 54
High Water Alarm ............................................................................................... 54
Probe Out Alarm ................................................................................................. 55
Invalid Fuel Height .............................................................................................. 55
Probe Low Temperature Warning....................................................................... 55
Delivery Needed Alarm ....................................................................................... 55
Leak Test Alarm.................................................................................................. 55
Diagnostic Screens
Function Test Menu Screen .................................................................................. 56
LCD Touch Test Screen ........................................................................................ 57
Probe Diagnostic Screen ....................................................................................... 58
Example Report Printout - Probe Diagnostic Report .......................................... 58
Availability of Probe Data.................................................................................... 58
iv
Contents
Tables
Table 1: Alarm Message Table ................................................................................... 4
Table 2: U.S. and Metric Thermal Coefficients ......................................................... 39
Table 3: Calculating Tank Tilt ................................................................................... 40
Table 4: System Reports .......................................................................................... 49
Table 5: Alarm Reports ............................................................................................. 52
Table 6: Tank Setup Label Codes ............................................................................ 59
Table 7: System Setup Label Codes ........................................................................ 60
v
Introduction
This manual describes setup and operating procedures for the following Touch-Screen consoles:
Veeder-Root TLS2
Gilbarco EMC2
TLS2 Underground Storage Tank (UST) Console. It assumes that your system has already been set up by a
Certified Contractor. This manual assumes that the console is installed and has successfully completed the Cold
Boot procedure. You should begin the setup procedure with the System Setup Screens and finish with the Tank
Setup Screens.
After entering the System and Tank Setup parameters the console should be operational. Consult the Reports
Section for instructions on viewing system and alarm reports. The Diagnostic Section contains some simple
console test procedures and access to Probe Diagnostic data.
Veeder-Root requires the following minimum training certifications for contractors who will install and setup the
equipment discussed in this manual:
Level 1 Contractors holding valid Level 1 Certification are approved to perform wiring and conduit routing,
equipment mounting, probe and sensor installation, tank and line preparation, and line leak detector installation.
Level 2/3 Contractors holding valid Level 2 or 3 Certifications are approved to perform installation checkout,
startup, programming and operations training, troubleshooting and servicing for all Veeder-Root Tank Monitoring
Systems, including Line Leak Detection and associated accessories.
Related Manuals
1
TLS2 Setup
Safety Symbols
The following safety symbols are used in this manual to alert you to important safety hazards and precautions.
EXPLOSIVE FLAMMABLE
Fuels and their vapors are extremely Fuels and their vapors are extremely
explosive if ignited. flammable.
Safety Warnings
WARNING
This system operates near highly combustible fuel storage tanks.
Leaking tanks can create serious environmental and health hazards. Improper
programming and operation may also result in equipment self-test failures
and submersible pump shutdowns.
2
TLS2 Setup
Plan your leak detection program to comply with local, state, and federal regulations governing underground
storage tanks. Save all inventory and leak test records provided by the system as part of a regulatory compliance
program.
The system, when equipped with magnestrictive 0.2 gallon-per-hour (gph) (0.76 lph) (Mag 2) probes , is classified
as an Automatic Tank Gauge System and has been third-party tested by Midwest Research Institute. This system
can detect a 0.2 gph leak exceeding a 95% probability of detection [P(D)] and less than a 5% probability of false
alarm [P(FA)]. It meets federal U.S. E.P.A. performance standards (0.2 gph at [P(D)] of 95% and [P(FA)] of 5%)
and the federal performance standard of measuring water in the bottom of a tank to the nearest 1/8 inch (3.2 mm).
The system, when equipped with magnestrictive 0.1 gph (0.38 lph) (Mag 1) probes, meets Volumetric Tank
Tightness Testing Method standards and has been third-party tested by Midwest Research Institute. This system
can detect a 0.1 gph leak exceeding a 95% probability of detection [P(D)] and less than a 1% probability of false
alarm [P(FA)]. This system meet U.S. E.P.A. federal performance standards (0.1 gph at [P(D)] of 95% and [P(FA)]
of 5%).
Console
The TLS2 Console features a front panel touch screen display, a dual-purpose Alarm/Normal LED, and an audible
beeper for alarm and warning notification. Serial and parallel printer ports are available for connection to a remote
printer. The TLS2 Console can monitor up to six magnetostrictive probes.
Monitoring Functions
Output Relay
An output relay is provided that can trigger external alarm devices when an alarm condition is sensed by the
system.
Communications Functions
RS-422
3
TLS2 Setup Alarm Message Quick Reference Index
Annual Test Fail Tank In-tank annual leak test failed Rerun in-tank leak test. If second test
fails, call for service.
Autodial Fail Comm System failed to connect to a remote Check remote receiver.
receiver after programmed number
of tries.
Delivery Needed Tank Product level dropped below preset Call for delivery.
limit.
Gross Test Fail Tank In-tank leak test failed. Rerun in-tank leak test. If second test
fails, call for service.
High Water Tank Water detected in tank exceeds pre- Remove water from the tank.
set limit.
Invalid Fuel Height Tank Fuel level dropped to a point below Call for delivery.
the minimum detectable level or only
one float is present.
Low Product Tank Tank level dropped below preset Call for delivery.
limit.
Low Temperature Tank Probe temperature dropped below - Probe returns to normal operation after
4F (-20C). For Low Temperature probe temperature rises above 0F
probes, below -40F (-40C). (-17.7C). For Low Temperature probes,
above -36F (-38C)
Max Product Tank Product level rose above preset limit. Stop delivery.
Overfill Tank Potential overflow of tank may occur. Stop delivery. Check for spillage.
Periodic Test Fail Tank In-tank leak test failed. Rerun in-tank leak test. If second test
fails, call for service.
Probe Out Tank Hardware failure - probe or intercon- Call for service.
necting wiring to console.
4
System Setup Screens
This section describes all of the TLS2 System Setup Screens along with setup choices and explanations that you will need
for data entry. Because the TLS2 Setup Displays have only English labels, Screen Label codes have been placed in brackets
beneath every English label to let you quickly find a translation of the label and the page number(s) of the Screen in which
the label is used. Tank Setup Screens are covered in a separate section.
Entering data, confirming selections, etc. is done through one of several Data Entry Screens which display when you touch
any button to the right of a data entry window. These screens are described where they are first discussed in this section.
1 2 3 4
11
5
10
12
9 8 7 6
1 Date/time window - displays current date and time 6 Environmental Report button - touch to display tank
2 Message window - displays All Functions Normal or leak test results (page 49).
active alarms. 7 Alarm Report button - touch to display the Active
3 Alarm button - touch to acknowledge alarm and Alarm Status (and History) Screen (page 52).
silence alarm beeper. Note: touching this button does 8 Delivery Report button - touch to display the Delivery
not clear the alarm - the problem that caused the Report Screen (page 49).
alarm must be repaired. 9 Inventory Report button - touch to display the
4 Print button - For menu screens, touch this button Inventory Report Screen (page 50).
and all items available through the menu are printed 10 Tank buttons - touch any tank button to display the
to a connected printer. For non-menu screens only, a current inventory report for that tank.
print dialog box appears when the print button is
touched. The user also has the option to cancel the 11 Screen title window.
print. 12 Manual Shift Close button - touch to manually close
5 Main Menu button - touch to display the Main Menu the shift. (visible only if Snapshot is selected in Shift
Screen (page 6) for access to system/tank setup and Time (System Setup) as the Shift Close Method.
manual tank testing.
5
TLS2 Setup Main Menu Screen
1 4
2 5
II
3 6
ABOUT
consoles/tls2/menuscrn.eps
6
TLS2 Setup System Setup Screen
2 3 4
1
6 7
5
8
10 11 12
1 Language button - touch to display the Language and 7 Dialing Setup button - touch to display the System
Units Setup Screen (page 8) Setup Dial Out Setup Screen (page 19).
2 Current Time button - touch to display the Time/Date 8 Temp button - touch to display the Temperature
Setup Screen (page 13). Setup Screen (page 32).
3 Comm button - touch to display the Comm Setup 9 Security button - touch to display the System Security
Screen (page 24). Setup Screen (page 12).
4 Alarm Relay button - touch to display the Alarm Relay 10 Daylight Savings button - touch to display the
Setup Screen (page 31). Daylight Savings Setup Screen (page 18).
5 Header button - touch to display the Station Header 11 Autodial Alarms button - touch to display the Autodial
Setup Screen (page 9). Alarms Setup Screen (page 20).
6 Shift Time button - touch to select the Setup Shift 12 EuroProtocol button - touch to display the
Times Screen (page 17) or Manual Shift Close. EuroProtocol and Stick Offset Setup Screen (page
33). This screen also lets you select a leak test report
format.
7
TLS2 Setup [201-203, 240] System Language and Units Setup Screen
1
[201]
2
[202]
3
[203]
8
TLS2 Setup [204 - 207] Station Header Setup Screen
1
[204]
2
[205]
3
[206]
4
[207]
9
TLS2 Setup Alpha Keypad Screen
10
4 SAVE
5 6 7 8 9
1 Displays Title of data to be entered. 6 Cursor left button - touch to move the cursor one
2 Data Entered Window displays data entered. position left in the Data Entered Window (2).
3 Alpha keypad buttons - touch a character button to 7 Cursor right button - touch to move the cursor one
place that character in the data entered window (2). position right in the Data Entered Window (2).
4 Save button - touch to accept entered data and close 8 Backspace delete button - touch to delete character
Screen. in cursor.
5 Cancel button - touch to cancel any entry and close 9 Number keypad button - touch to display the Numeric
Screen. Keypad Screen.
10 Clear button - touch to clear contents of Data Entered
Window (2).
10
TLS2 Setup Numeric Keypad Screen
10
4 SAVE 9
5 6 7 8
1 Displays title of data to be entered. 7 Cursor right button - touch to move the cursor one
2 Data Entered Window displays data entered. position right in the Data Entered Window (2).
3 Numeric Keypad buttons - touch a character button to 8 Backspace delete button - touch to delete character
place that character in the Data Entered Window (2). above cursor.
4 Save button - touch to accept entered data entered 9 Alpha keypad button - touch to display the Alpha
and close Screen. Keypad Screen.
5 Cancel button - touch to cancel any entry and close 10 Clear button - touch to clear contents of Data Entered
Screen. Window (2).
6 Cursor left button - touch to move the cursor one
position left in the Data Entered Window (2).
11
TLS2 Setup [208-211] System Security Setup Screen
1 COMM 1 PASSWORD
[208]
2 COMM 1 PASSWORD
[209]
3 COMM 2 PASSWORD
[210]
4 COMM 2 PASSWORD
[211]
12
TLS2 Setup [212-214] System Time/Date Setup Screen
1 10-04-01
[212]
2
[213] 13-54
13
TLS2 Setup Current Date Entry Screen
1 2001 3
14
TLS2 Setup Current Time Entry Screen
1 3
15
TLS2 Setup [500-503] System Setup Close Times Screen
This screen allows you to select Auto (Timed) or Manual Inventory Log.
(Snapshot) Shift Close times. The default setting is Default is 00:00 (midnight).
Timed (close by time). 4 Inventory Log Interval [503] - Inventory Log records
1 Shift Close Method [500] - touch the Select button to will be recorded by the system automatically at the
the right of the window and select Timed (Auto) or intervals you select in this field. Touch the down
Snapshot (Manual) shift close method. Default is arrow button to the right of the window and select the
Timed. interval.
2 Shift Close Timeout [501] - Enabled only if the Allowable intervals: 1 hour, 2 hours, 3 hours, 4 hours,
Snapshot shift close method is chosen. Touch the 6 hours, 8 hours, 12 hours, 24 hours, 5 minutes, 10
number button to the right of the window and enter minutes, 15 minutes, 20 minutes or 30 minutes.
the Timeout. Default is 1 hour.
When the timeout period starting from the last closed
tank shift expires, any unopened tank shifts will For example, you select an Inventory Log Time (item
automatically be closed. 3) of 00:00 (midnight) and you select a 30 minute
For example, Shift Close Timeout is set to 30. You Inventory log interval (item 4), then the system will
select manual shift close on tank 3. 30 minutes later record inventory snapshots at 00:00 (midnight), 12:30
the shift is closed for the remaining tanks, the shift am, 1:00 am, 1:30 am, etc.. The maximum number or
number increments and a shift report is created. If the records in the Inventory Log is 72. The Inventory Log
system is setup to autodial on Shift Close Event, the is a rolling (first in, first out) log of 72 maximum
autodial assigned receiver will be sent the records.
notification.
Allowable Timeout selections: 30 to 60 minutes.
Default is 30 minutes.
3 Inventory Log Time [502] - Touch the clock button to
select the start time in a 24-hour period you want to
record the first inventory that will be placed in the
16
TLS2 Setup [215-218] Shift Times Setup Screen
1
[215]
2
[216]
3
[217]
4
[218]
Shift Times Setup Screen is only visible if Timed is 8 Shift 4 [218] - touch the time button to the right of the
selected as the Shift Close Method in the System Setup window and enter the Shift 4 start time and AM or
Close Times screen (page 16). At each shift start time PM.
selected below, the system automatically saves a
complete inventory report in memory. The default setting
is disabled for all shifts.
NOTE: At least one shift start time must be entered to
activate the Last Shift Inventory feature.
5 Shift 1 [215] - touch the time button to the right of the
window and enter the Shift 1 start time and AM or
PM.
6 Shift 2 [216] - touch the time button to the right of the
window and enter the Shift 2 start time and AM or
PM.
7 Shift 3 [217] - touch the time button to the right of the
window and enter the Shift 3 start time and AM or
PM.
17
TLS2 Setup [219-223] Daylight Savings Time Setup Screen
1 ENABLE
[219]
2 MAR WEEK 2 SUN
[220]
3
[221] 2:00 AM
This feature allows you to enter Daylight Savings Start 4 End Date [222] - touch the Date button to the right of
and End Dates/Times. Once enabled, the system will the window and enter the enter the end date (default
automatically adjust for daylight savings time at the dates is OCT WEEK 6 SUN).
and times you enter. 5 End Time [223] - touch the Time button to the right of
1 Daylight Savings [219] - touch the Arrow button to the the window and enter the end time [and AM or PM]
right of the window and select Enable or Disable (default is 02:00 AM).
(default is Disable).
2 Start Date [220] - touch the Date button to the right of
the window and enter the start date (default is APR
WEEK 1 SUN).
3 Start Time [221] - touch the Time button to the right
of the window and enter the start time [and AM or
PM] (default is 02:00 AM).
18
TLS2 Setup [224-226, 321] Auto-Dialout Setup Screen
1 PHONE
[224]
2 RETRIES
[225]
3 RETRY DELAY
[226]
This feature requires that Modem be selected as the 4 Autodial Confirm [321] - touch the Down Arrow button
Comm Type. to select On or Off.
1 Phone [224] - touch the Numeric button to the right of
the window and enter one phone number to which
you want the system to dial.
2 Retries [225] - touch the Numeric button to the right
of the window and enter the number of times (1-99)
you want the system to redial the phone number if
there is a busy signal, no answer, or an incomplete
connection (default is 3 retries).
3 Retry Delay [226] - touch the Numeric button to the
right of the window and enter the number of minutes
(1-99) you want the computer to delay before
redialing the phone number if there is a busy signal,
no answer, or an incomplete connection (default is 3
minutes).
19
TLS2 Setup [227-230] Autodial Alarm Setup Screen 1
1
[227]
2
[228]
3
[229]
4
[230]
5
1 2 3 4 5 6
20
TLS2 Setup [231-234] Autodial Alarm Setup Screen 2
1
[231]
2 6
[232]
3
[233] 7
4
[234] 8
11 22 33 4
4 5
5 6
6
21
TLS2 Setup [235-237, 320] Autodial Alarm Setup Screen 3
1
[235]
2
[236]
3
[237]
4 DELIVERY COMPLETED OFF
[320]
11 22 33 4
4 5
5 6
6
22
TLS2 Setup [550] Autodial Alarm Setup Screen 4
11 22 33 4
4 5
5 6
6
23
TLS2 Setup [238-239] Comm Port 1 and 2 Serial Setup Screen 1
1
[238]
2
[239]
3 4 5 6
This screen is similar for Comm 1 and Comm 2 port 5 PARALLEL button - touch to display the Parallel Port
setup. Setup Screen (page 30).
1 Comm Type [238] - touch the Down Arrow button to 6 Down button - touch to display Comm Port Setup
the right of the window and select: Screen 2 (page 27).
If Comm 1 -
Serial, Modem, Printer, or None (default)
If Comm 2 -
Serial or None (default)
2 Handshaking [239] - touch the Down Arrow button to
the right of the window and select None, XON/XOFF,
or Hardware (default). This parameter is identical for
Comm 1 and Comm 2.
3 COMM 1 button - touch to display the Comm 1 Setup
Screen (shown above).
4 COMM 2 button - touch to display the Comm 2 Setup
Screen.
24
TLS2 Setup [241] Comm Port 1 Printer Setup Screen
[238]
1
[241] 9
[239]
2 PRINTER LANG EPSON ESC/P
[253] 3
25
TLS2 Setup [244-246] Comm Port 1 Modem Setup Screen 1
[238]
2
[244]
3
[245]
4 5
[246]
26
TLS2 Setup [249-252] Comm Port Setup Screen 2
1 9600
[249]
2 ODD
[250]
3 7
[251]
4
[252]
27
TLS2 Setup [247-248] Advanced Communications Setup Screen
1 DIAL IN AT&B1
[247]
2 AT&B1
[248]
CAUTION!
Entering the wrong number strings in this screen may
disable the modem.
28
TLS2 Setup Data Entry Screen
1
[249]
2 SAVE 3
The Data Entry screens are similar and display when you
touch the arrow next to a setup parameter. In this example,
Baud Rate offers multiple choices, so you touch the arrow
button to choose one of the options.
1 Baud Rate [249]- touch the Down Arrow button to the
right of the window and select a desired baud rate: 300,
600, 1200, 2400, 4800, or 9600 (default).
2 Save and Cancel buttons - touch the Save button to
accept the choice shown and close the screen or touch
the Cancel button to abort and close the screen.
29
TLS2 Setup Parallel Port Setup Screen
1 COMM TYPE
[238]
2 PAGE EJECT
[238]
9
3 PRINTER LANG EPSON ESC/P
[253]
30
TLS2 Setup [256] Alarm Relay Setup Screen
1
[256]
31
TLS2 Setup [257-258] Temperature Setup Screen
1 59 F
[257]
2
[258]
32
TLS2 Setup [259-262] EuroProtocol and Stick Offset Setup Screen
1
[259]
2
[260]
3
[261]
4
[262]
33
TLS2 Setup About TLS2 Screen
ABOUT
SYSTEM FEATURES
STATIC TANK LEAK DETECT
This screen lists information about the TLS2 Consoles installed software and features:
System Software Revision Level
Software Version number
Software Part Number
Software Creation Date
System Features: Static Tank Leak Detect
34
Tank Setup Screens
1 2
35
TLS2 Setup [119-121] Tank Setup Screen 1
TANK 1
1 CONFIGURED
[119]
2
[120]
3
[121]
1 2 3 4 5 6
36
TLS2 Setup [122-124] Tank Setup Screen 2
TANK 1
1
[122]
2
[123]
3
[124]
1 2 3 4 5 6
37
TLS2 Setup [125-128] Tank Setup Screen 3
TANK 1
1
[125] 0.00070
2
[126] 0 IN
3
[127]
4
[128]
1 2 3 4 5 6
This screen concludes Tank Setup. 3 Float Size [127] - Touch the Down Arrow button to the
1 Thermal Coefficient [125] - Touch the Down Arrow right of the window and from the float sizes presented,
button to the right of the window and enter the diameter enter the Mag probe float size that you installed on
of the tank. the tanks probe
To ensure accurate temperature compensated volume 4 Stick Offset [128] - Touch the Down Arrow button to
conversions the products thermal coefficient of the right of the window and enter a Stick Offset value.
expansion must be correctly entered. An incorrect value The allowable range is -144 to +144 inches (-365.76
will adversely affect leak detection testing and to +365.76 cm) and the default is 0.
temperature compensated inventory values. Note: To enter a Stick Offset value, the Stick Offset
Table 2 lists the U.S. and Metric coefficients for option must have been enabled (page 33), and you
approved fuels and liquids. Enter the coefficient in U.S. must have calculated and entered the tank tilt (if
or Metric units, depending on the units specified in necessary). A Stick Offset can be entered so that the
System Setup (page 8). Be careful to add the correct probe (product) height appears to be equal to a stick
number of zeros to the right of the decimal point. gauge reading of the product height - This entry is for
Incorrect entry can cause test failures and other operator convenience only, and as such it has no
problems. bearing on product volume calculations.
2 Tank Tilt [126] - Touch the Down Arrow button to the To determine the value to enter for Stick Offset, record
right of the window and enter the tank tilt. The allowable the probe height reading and record a stick height
range is -144 to +144 inches (-365.76 to +365.76 cm) reading from the tank. If the probe's fuel height
and the default is 0. reading is lower than the stick reading, enter the
positive difference between the two. If the probe's
Tank Tilt allows you to adjust for a difference between reading is higher than the stick reading, enter the
fuel height at the probe location and fuel height at the negative difference between the two. For example, if
center of the tank caused by a tilt in the tank. You must stick height = 52 and probe height = 48, you enter +4;
enter a minus (-) if the Tank Tilt is a negative value. A if stick height = 52 and probe height = 54, you enter -
Tank Tilt value is not required if the probe is located in 2.
the center of the tank. If the probe is located in the
center of the tank, the value entered is 000.00 U.S units
or 0000.0 Metric units. If the probe is not in the center
of the tank, calculate the tanks tilt using the directions
in Table 3. Enter the value from Column G in the
worksheet as the Tank Tilt.
38
TLS2 Setup [125-128] Tank Setup Screen 3
Thermal Thermal
Coefficient Coefficient
Product (U.S. Units) (Metric Units)
39
TLS2 Setup [125-128] Tank Setup Screen 3
Use the worksheet below to record measurements and perform Tank Tilt calculations for each of the tanks.
1. Stick the tank at the fill riser opening at least three times. Record the average reading in column A of the chart.
2. Before beginning this step, make sure the Tank Tilt [126] on the screen = 0. Record the probes Fuel Height (In-Tank
Inventory Function) reading in column B of the chart.
3. Subtract the value entered in column B from the value entered in column A. Record the result in column C.
4. Measure the distance in inches (or millimeters if you use Metric Units) between the probe and fill risers. Record the
measurement in column D.
5. Divide the value in column C by column D to determine the pitch. Record the results in column E.
6. Measure the distance in inches or millimetres from the probe riser to the center of the tank. Record the distance in
column F.
7. Multiply column E by column F to determine Tank Tilt (E X F = Tank Tilt Value). Record the value in column G.
A B C D E F G
6
*Tank Tilt may be a positive (+) or negative (-) value. If it is a negative value, BE SURE to change the value symbol to minus
(-) when entering a negative Tank Tilt value.
40
TLS2 Setup [101-104] Tank Limits Setup Screen 1
1
[101]
2
[102]
3
[103]
4
[104]
1 2 3 4 5 6
This screen begins Tank Alarm Limits setup. Allowable range is 0-26000 gallons (0-98420 L).
1 Max Product [101] - Alarms when the level of fluid in Default is 0 (which disables the alarm). An active
the tank exceeds the volume you enter here. Allowable Probe Low Temperature Warning will disable this
range is 0-26000 gallons (0-98420 L). Default is 0. If alarm. Touch the Down Arrow button to the right of the
the value entered is 0 or full volume, this alarm is window and enter this value at a volume lower than
disabled. An active Probe Low Temperature Warning that of the Delivery Needed alarm.
will disable this alarm. Touch the Down Arrow button to NOTE: Typically this alarm is set to the lowest level
the right of the window and enter the max product for before the pump runs dry. All dispensing should stop
the tank. when this alarm is active.
2 Overfill [102] - Overfill Limit warns of a potential overfill The Tank Alarm Limit Setup continues on next page.
during a delivery. When the volume reaches this limit,
the system can activate an overfill alarm. The overfill
alarm threshold is referenced to the Max Product value.
If the Max Product value is 0, the Overfill Alarm
threshold is referenced to the Full Volume capacity.
Allowable range is 0 to 100%. Default is 0 (disabled).
An active Probe Low Temperature Warning will disable
this alarm.
3 Delivery Needed [103] - Delivery Needed warns when
the level of fluid in the tank drops to a level at which the
operator calls for a delivery. This value is a percentage
of Full Volume with an allowable range of 0 to 100%.
Default is 0% (which disables the alarm).Touch the
Down Arrow button to the right of the window and enter
a volume higher than that of the Low Product alarm.
4 Low Product [104] - Low Product warns when volume in
the tank pumps down to the level you enter here.
41
TLS2 Setup [105-108] Tank Limits Setup Screen 2
1
[105]
2
[106]
3
[107]
4
[108]
1 2 3 4 5 6
This screen continues Tank Alarm Limits setup. 4 Per Leak Test Min [108] - This value sets the minimum
1 High Water [105] - Alarms when the level of water in the tank volume required to record a passed periodic leak
tank exceeds the height you enter here. Set this value test. The value reflects federal, state, and local
at a level lower than the pickup for the submersible requirements. This value is a percentage of Full
pump or suction line. Allowable range is 0-9 inches (0- Volume with an allowable range of 1.0 to 100%.
228.6 mm). Default is 0 (which disables the alarm). Default is 0 (which disables the alarm). Touch the
Touch the Down Arrow button to the right of the window Down Arrow button to the right of the window and
and enter the desired high water limit. enter a volume.
The Tank Alarm Limit Setup continues on next page.
2 Delivery Delay [106] - Use this display to set a delay
time between the completion of a bulk delivery and the
Delivery Increase Report. This feature prevents
generation of multiple reports during the intervals
between multi-compartment drops to one tank. The
feature also allows fuel to settle out after a delivery,
which is especially important in manifolded tank groups.
Allowable delay is 1 to 60 minutes. Default is 1. Touch
the Down Arrow button to the right of the window and
enter a desired delay.
3 Ann Leak Test Min [107] - This value sets the minimum
tank volume required to record a passed annual leak
test. The value reflects federal, state, and local
requirements. This value is a percentage of Full Volume
with an allowable range of 1.0 to 100%. Default is 0
(which disables the alarm). Touch the Down Arrow
button to the right of the window and enter a volume.
42
TLS2 Setup [109-111] Tank Limits Setup Screen 3
1
[109]
2
[110]
3
[111]
1 2 3 4 5 6
43
TLS2 Setup [112-114] Tank Leak Test Setup Screen 1
1 0.2 GPH
[112]
2 EARLY STOP
[113]
3
[114]
1 2 3 4 5 6
The Tank Leak Test Setup allows you to establish and enter There is too little fuel in tank.
the method, timing, and duration of automatic leak tests. Touch the Down Arrow button to the right of the
You must have a Mag 1 or 2 probe installed to perform leak window and enter the desired choice.
tests.
3 Test Duration [114] - The maximum duration is 24
If you are using the In-Tank Leak Test feature for hours. There is a minimum duration of two hours for
underground storage tank regulatory compliance, be sure 0.2 gph (0.76 lph) tests and three hours for 0.1 gph
the leak test limits you establish and enter comply with the (0.38 lph) tests.
test type, accuracy, and frequency requirements as defined
by local, county, state, federal and any other regulatory Note: If you have Early Stop enabled and the console
authority governing your site. determines that an Tank Leak Test has passed the
test is completed before the duration times out.
In addition, set the test time for a period when no fueling Default duration is 2 hours. Touch the Down Arrow
from or bulk delivery to the tank will occur. Such activity button to the right of the window and enter the desired
during a leak test procedure will result in inaccurate leak choice.
test results.
4 Same All Tanks button - Touch this button to transfer
1 Test Rate [112] - You can set the leak test rate at 0.2 identical selections made on this screen for Tank 1 to
gph (0.76 lph) (default) or 0.1 gph (0.38 lph). Selecting All Tanks (opens the confirm Same All Tanks Screen
0.1 gph (0.38 lph) requires a Mag 1 probe. Touch the on page 45).
Down Arrow button to the right of the window and enter
the desired choice. The Tank Leak Test setup concludes on page 46.
2 Early Stop [113] - Disabled is the default setting. When
enabled this feature will prevent an In-Tank Leak Test
from starting under the following conditions:
Tank volume is less than Leak Min Periodic vlaue or
Leak Min Annual value.
It is less than 8 hours from a delivery.
The product temperature is less than 0F (-17.6C)
or more than +100F (+37.4C).
44
TLS2 Setup [115] Same All Tanks Screen
1
[115]
2 SAVE 3
45
TLS2 Setup [116-118] Tank Leak Test Setup Screen 2
TANK 1
1
[116]
2 DATE/DAY
[117]
3
[118]
1 2 3 4 5 6
46
Manually Closing a Shift
TANK VOLUME HEIGHT WATER WVOL TANK VOLUME HEIGHT WATER WVOL
1 17508 1229 25 500 1 17508 1229 25 500
2 14993 966 0 0
3 9843 771 0 0
4 10844 801 0 0
5 4844 900 0 0
6 9843 775 0 0
OK CANCEL OK CANCEL
3 4 3 4
1 You can manually close the shift for any tank by NOTES:
touching the desired tanks graphic on the screen, or Pressing a tank that is already closed will not display the
2 You can manually close the shift for all tanks by confirmation close screen.
touching the All Tanks button. Once all tanks are closed, you can not close another shift
3 For either Single or All Tank shift closure, touch the OK until 2 hours after the last tank was closed.
button to confirm the closing. From midnight to 11:59 pm, you can manually close a
4 For either Single or All Tank shift closure, touch the maximum of four shifts.
Cancel button to abort the closing.
47
Manually Starting/Stopping Tank Leak Tests
1
[129]
2 5
[130]
3 0.76 LPH 6
[112]
4
[114]
1 2 3 4 5 6
5 Test Method [129] - Select Single Tank or All Tanks. Arrow button to the right of the window and
Touch the Down Arrow button to the right of the enter the desired choice.
window and enter the desired choice. 9 Test Start button - Touch this button to begin
6 Test Control [130] - Select Timed Duration or Manual the test.
Stop (test runs until you stop it, or for 24 hours, 10 Test Stop button - Touch this button to stop a
whichever comes first). Touch the Down Arrow button tank leak test.
to the right of the window and enter the desired
choice.
7 Test Rate [112] - Select a leak test rate of 0.2 gph
(0.76 lph) (default) or 0.1 gph (0.38 lph). The 0.1 gph
(0.38 lph) rate requires a Mag 1 Probe. Touch the
Down Arrow button to the right of the window and
enter the desired choice.
8 Test Duration [114] - Select a test duration of from 0 to
24 hours. There is a minimum duration of two hours for
0.2 gph (0.76 lph) tests and three hours for 0.1 gph
(0.38 lph) tests. Default is 2 hours.
Note: this window only appears if you selected Timed
Duration in the Test Control window. Touch the Down
48
Reports
System Reports
System reports are accessed from the System Status (Home) Screen (see page 5) by touching one of the
four report buttons at the bottom of the screen. Table 4 describes the available System reports.
CURRENT TEST
RESULTS CURRENT TEST RESULTS
Test Type, Start Date/Time, Test Result, Hours
Touch the Current Test Results but- Run, %Volume in Tank at Time of Test
ton to display the results of the last
passed Annual, Periodic, and Gross
tests. You can touch the Print button
on the display to print the report to a
connected printer.
Touch to display
the Environmental
Reports Screen.
When this screen
displays you can
select one of two
test reports. FULLEST LAST PASS REPORT
Touch the Fullest Last Pass button Test Type, Start Date/Time, Hours Run, %Vol-
to display the results of the last 12 ume in Tank at Time of Test
Periodic (1 for each month) tests
and Last Annual test in which the
tank had the most volume.You can
touch the Print button on the display
to print the report to a connected
printer.
49
TLS2 Setup Inventory Reports
Inventory Reports
37.3 F
1
5329 GAL
(5413 GAL TC)
2
72 IN
3
WATER 0.0 IN
1 2 3 4 5 6
To view the inventory report for a tank, touch the inventory report button for the desired tank at the bottom of the
screen. To view the Shift Inventory report for the selected tank, touch the Shift Inventory button (item 1 in the screen
above). To view the stick height (if enabled) for the selected tank, touch the Delta Stick button (item 2 in the screen
above). To view the Inventory Log report for the selected tank, touch the Inventory Log Report button (item 3 in the
screen above).
T 1:REGULAR UNLEADED
TANK VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP
1 5329 5413 4500 48.8 0.0 37.3
2 5329 5413 4500 48.8 0.0 37.3
T 1:REGULAR UNLEADED
TANK PRODUCT
1 REGULAR UNLEADED VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP
SHIFT 1 STARTING VALUES 8518 8492 1482 76.26 0.0 64.7
ENDING VALUES 8518 8492 1482 76.26 0.0 64.7
DELIVERY VALUE 0
TOTALS 0
SHIFT 2 STARTING VALUES 8518 8492 1482 76.26 0.0 64.7
ENDING VALUES 8518 8492 1482 76.26 0.0 64.7
DELIVERY VALUE 0
TOTALS 0
50
TLS2 Setup Inventory Reports
TC Volume and temperature columns are printed only for the probes in the system that have temperature measurement
capability.
If system setup parameter Print TC Volumes is set to NO, the TC Volume and temperature columns are not printed.
The water column is printed only for probes in the system that have water measurement capability.
51
TLS2 Setup Active Alarm Status Screen
Alarm Reports
Alarm reports are accessed from the Active Alarm Reports Screen above by touching the report buttons
across the bottom of the screen. Table 5 describes the available reports.
52
TLS2 Setup Alarm Reports
Touching the Alarm Ack button (item 3 on page 5) turns off the beeper even if the alarm is still active.
The Alarm Status Screen displays the alarm until it is cleared. When an alarm condition returns to the
normal state, the alarm will be removed from the list of active alarms.
When no alarms are active, the front panel LED is in the Normal state (continuous green) and the
System Status (Home) Screen Message Window reads All Functions Normal (Item 2 on page 5).
An active Probe Out or Low Temperature Warning will inhibit all level alarms (Max Product, Overfill, Low
Product, Delivery Needed, and High Water).
53
TLS2 Setup Alarm Reports
Active Alarm
When an alarm goes active, the consoles internal beeper activates, the alarm relay activates (if enabled), the front
panel LED flashes red, and the Screens Message Window (item 2 on page 5) displays an alarm message. In the
case of multiple alarms, the Message Window will automatically scroll through the active alarms . In the case of an
alarm assigned to autodial, the console dials out and establishes a connection with the remote host. The host can
then send requests to the console to determine the reason for the call.
When an alarm is active, the user can turn the beeper off and deactivate the alarm relay by touching the ALARM
Button (Item 3 on page 5). The front panel LED will stay in the ALARM state and the alarm will remain in the
active alarm list until the alarm returns to normal state. If the alarm is inactive but not acknowledged, it will remain
in the alarm list and the beeper and alarm relay (if enabled) will remain active until it is acknowledged.
With any alarm when an out-of-limit condition(s) is corrected, or a faulty device is replaced with a properly
operating one, the alarm is automatically cleared. To clear a failed leak test alarm, a passing leak test must be run.
If the product level volume exceeds the Max Product value, the Max Product Alarm will activate. If the alarm is
active and the product level volume is lower than the Max Product value by at least 0.005 times the full volume
capacity or 10 gallons [37.8 L] (whichever is greater), the alarm will deactivate. The Max Product value is entered
as a volume with the default value equal to 0. If the Max Product value is equal to 0 or the full tank volume
capacity, the alarm is disabled. An active Probe Low Temperature Warning will disable the alarm.
Overfill Alarm
If the product level volume exceeds the Overfill Alarm threshold and there is a delivery in progress, the Overfill
Alarm will activate. When the delivery stops, the alarm will deactivate. The Overfill alarm value is entered as a
percentage with the default value equal to 0%. An overfill threshold value of 0% disables the alarm. The overfill
alarm threshold is referenced to the Max Product value. If the Max Product value is 0, the overfill value is
referenced to the Full volume capacity. An active Probe Low Temperature Warning will disable the alarm.
If the product level volume is less than the Low Product threshold, the Low Product Alarm will activate. If the
alarm is active and the product level volume is higher than the threshold by at least 0.005 times the full volume
capacity or 10 gallons [37.8 L] (whichever is greater), the alarm will deactivate. The Low Product value is entered
as a volume with the default value equal to 0. If the value is equal to 0, the alarm is disabled. An active Probe Low
Temperature Warning will disable the alarm.
If the water level height continuously exceeds the High Water threshold for a period exceeding 3 minutes, the High
Water Warning will activate. The high water alarm will not activate if there is a delivery in progress. If the alarm is
active and the water level height is lower than the threshold by at least 0.2 inches (5 mm), the alarm will
54
TLS2 Setup Alarm Reports
deactivate. The High Water value is entered as a height with the default value equal to 0. If the value is equal to 0,
the alarm is disabled. An active Probe Low Temperature Warning will disable the alarm.
If the console is not reliably communicating with the probe, the Probe Out alarm will activate.
If the water float and the product float are too close together to provide reliable height data, the Invalid Fuel Height
alarm will activate.
Standard Probe: If the Probe is reporting a temperature lower than -4F (-20C), the Low Temperature warning
will activate. If the alarm is active and the temperature rises above 0F (-17.7C) the alarm will deactivate.
Low Temperature Probe: Alarm -40F (-40C), Clear -36F (-37.7). When the low temperature warning is
active the High Water, Low Product, Max Product, Delivery Needed, and Overfill alarms are disabled.
When the tanks product level drops below the preset limit, the Delivery Needed alarm will activate.
When a Gross, Periodic, or Annual leak test fails a Gross, Periodic, or Annual Leak Test Alarm will activate. To
clear a failed leak test alarm, a passing leak test must be run.
55
Diagnostic Screens
1 2 3
4 5 6
RED LED GREEN LED LCD OFF
7 8
56
TLS2 Setup LCD Touch Test Screen
Description
57
TLS2 Setup Probe Diagnostic Screen
TANK : 1
PROBE TYPE : MAG 01
SERIAL NUMBER : 123001
PROBE ID : C000
PROBE LENGTH : 96.0
GRADIENT : 360.000
NUMBER SAMPLES: 20
1 2 3 4 5 66
To view another tanks probe diagnostics, touch the desired tanks Diagnostic button at the bottom of the screen.
Diagnostic probe data for configured tanks or for active tanks will be available in the Probe Diagnostic
Screen above, in printed reports, and in serial commands. An active tank is defined as a tank that has a
probe that is communicating with the system. If the tank is configured but not active, all data will be
zero and the probe type will be unknown.
When the software identifies probes that do not have temperature measurement capability, it will
inhibit temperature related data. For probes that do not have water measurement capability, it will
inhibit water related data.
58
Label Code Index
Table 6 and Table 7 are included to help non-English speaking users find translations of all English labels used in
the TLS2 Setup screens. Beneath each label is a unique code in brackets, e.g., [101]. This code is listed in the
tables below and points to every Setup Screen in this manual where the label is used.
59
TLS2 Setup Probe Diagnostic Screen
60
TLS2 Setup Probe Diagnostic Screen
61
TLS2 Setup Probe Diagnostic Screen
62
Warranty Conditions and Limitations of Liability
Limitations Of Liability
We warrant that this product will be free from defects in materials and workmanship for a period of 1
year from the date of installation or 24 months from the date of invoice, whichever occurs first. During
the warranty period, we or our representative will repair or replace the product, if determined by us to
be defective, at the location where the product is in use and at no charge to the purchaser.
We shall not be responsible for any expenses incurred by the user.
This warranty applies only when the product is installed in accordance with Veeder-Root's
specifications, and a Warranty Registration and Checkout Form has been filed with Veeder-Root by an
Authorized Veeder-Root Distributor. This warranty will not apply to any product which has been
subjected to misuse, negligence or accident; or misapplied; or used in violation of product manuals,
instructions or warnings; or modified or repaired by unauthorized persons; or improperly installed.
Inspection
You shall inspect the product promptly after receipt and shall notify us at our Simsbury office in
writing of any claims, including claims of breach of warranty, within 30 days after you discover or
should have discovered the facts upon which the claim is based. Your failure to give written notice of a
claim within the time period shall be deemed to be a waiver of such claim.
The provisions of Limitations Of Liability above are our sole obligation and exclude all other
remedies or warranties, express or implied, including warranties of MERCHANTABILITY and
FITNESS FOR A PARTICULAR PURPOSE, whether or not purposes or specifications are described
herein. We further disclaim any responsibility whatsoever to you or to any other person for injury to
person or damage to or loss of property or value caused by any product which has been subjected to
misuse, negligence, or accident; or misapplied; or used in violation of product manuals, instructions or
warnings; or modified or repaired by unauthorized persons; or improperly installed.
Limitation of Damages
Under no circumstances shall we be liable for any incidental, consequential or specific damages, losses
or expenses arising from this contract or its performance or in connection with the use of, or inability
to use, our product for any purpose whatsoever.
Limitation of Actions
No action regardless of form arising out of this contract may be commenced more than 1 year after the
cause of action has accrued, except an action for nonpayment.
63
TLS2 Setup
Collateral Promises
Interpretation
Rights and liabilities arising out of any contract with us shall be determined under the Uniform
Commercial Code as enacted in Connecticut.
64
CHINESE
....................................................................................................... 1
.................................................................................................................. 1
.................................................................................................................. 2
.................................................................................................................. 2
....................................................................................................... 3
..................................................................................................................... 3
............................................................................................................... 3
............................................................................................................... 3
............................................................................................................... 3
............................................................................................ 4
........................................................................................... 5
.............................................................................................................. 6
........................................................................................................... 7
[201-203] ......................................................................... 8
[204 - 207] ................................................................................. 9
......................................................................................................... 10
......................................................................................................... 11
[208 -211] ................................................................................ 12
[212 -214] / ...................................................................... 13
................................................................................................. 14
................................................................................................. 15
[215 -218] ................................................................................ 16
[219-223] .......................................................................... 17
[224-226] ................................................................................. 18
[227-230] 1 ....................................................................... 19
[231-234] 2 ....................................................................... 20
[235-237] 3 ....................................................................... 21
[238-239] 1 2 1 ............................................................ 22
[241] 1 .......................................................................... 23
[244-246] 1 1 ......................................................... 24
[249-252] 2 .............................................................................. 25
[247 -248] ................................................................................ 26
......................................................................................................... 27
................................................................................................. 28
[256] ......................................................................................... 29
[257-258] ......................................................................................... 30
[259-262] ............................................................ 31
TLS2 ..................................................................................................... 32
................................................................................................. 33
[119-121] 1 ...................................................................................... 34
[122-124] 2 ...................................................................................... 35
[125-128] 3 ...................................................................................... 36
[101-104] 1 .............................................................................. 39
[105-108] 2 .............................................................................. 40
[109-111] 3 .............................................................................. 41
[112-114] 1 ....................................................................... 42
[115] ......................................................................................... 43
[116-118] 2 ....................................................................... 44
/
/ ........................................................................................ 45
................................................................................................................ 46
............................................................................................................ 47
-TC .......................................................... 47
- TC .......................................... 47
................................................................................................... 48
.................................................................................................. 48
................................................................................................................ 48
...................................................................................................... 49
.............................................................................................. 50
............................................................................................................. 50
...................................................................................................... 50
................................................................................................... 50
......................................................................................................... 50
...................................................................................................... 50
............................................................................................................. 50
.......................................................................................................... 50
.......................................................................................................... 50
...................................................................................................... 50
................................................................................................... 51
...................................................................................................... 51
...................................................................................................... 51
...................................................................................................... 51
.................................................................................................. 52
LCD ................................................................................................. 53
......................................................................................................... 54
- ...................................................................... 54
............................................................................................... 54
................................................................................................................ 59
....................................................................................................................... 59
..................................................................................................... 59
................................................................................................................ 59
................................................................................................................ 59
................................................................................................................ 60
....................................................................................................................... 60
............................................................................................................ 62
..................................................................................................................... 62
..................................................................................................................... 62
..................................................................................................................... 62
..................................................................................................................... 62
..................................................................................................................... 62
ii
................................................................................................................. 62
................................................................................................................. 62
................................................................................................................. 62
1: 4
2: 37
3: 38
4: 46
5: 48
6: 55
7: 56
iii
iv
TLS2
1: 4
2: 37
3: 38
4: 46
5: 48
6: 55
7: 56
1
TLS
TLS2 (UST)
Veeder-Root
1 1
2 3 2/3 Veeder-Root
577013-756 TLS2
1
TLS2
1.
2.
/
3.
4.
5.
6. Veeder-Root
2
TLS2
/
0.2 (gph) 0.76 (Mag 2)
0.2
95%[P(D)] 5% [P(FA)] U.S. E.P.A. 0.2 gph
95% [P(D)] 5% [P(FA)] 1/8 3.2
TLS2 / LED
TLS2
TLS2
RS-232
RS-422
RS-485 2- 4-
3
TLS2
-4 - 0 -
20 -40 17.7
-40 -36 -38
TLS2 TLS2
(Data Entry
Screen)
1 2 3 4
11
5
10
9 8 7 6
1 / - 8 - 46
2 - 9 - 47
3 -
- 10 -
11
4 -
5 - 6
/
6 - 46
7 -
48
5
TLS2
1 2
6 3
II
5 4
/2/ .
1 (System Setup) -
(System Setup) 7
2 (Tank Setup)- Tank
Setup Menu 33
3 (Diagnostics) - Probe
Diagnostic 54
4 - About 32
TLS2
5 (Function Test) -
Function Test Menu 52
6 (Manual Test) - /
Manual Tank Test Start/Stop 45
6
TLS2
2 3 4
1
6 7
5
8
10 11 12
7
TLS2 [201-203]
[201-203]
1
[201]
2
[202]
3
[203]
1 [201]- English
Chinese (French)
(Portuguese) (Spanish)
2 [202]- Metric (U.S)
3 [203]- English
(French) (Portuguese)
(Spanish)
8
TLS2 [204 - 207]
[204 - 207]
1
[204]
2
[205]
3
[206]
4
[207]
1 1 [204]-
20
2 2 [205]-
20
3 3 [206]-
20
4 4 [207]-
20
9
TLS2
10
4 SAVE
5 6 7 8 9
1 7 -(2)
2
3 - 8 -
(2) 9 -
4 (Save) - 10 - (2)
5 (Cancel) -
6 -(2)
10
TLS2
10
4 SAVE 9
5 6 7 8
1 8 -
2 9 -
3 - 10 - (2)
(2)
4 (Save) -
5 (Cancel) -
6 -(2)
7 -(2)
11
TLS2 [208 -211]
[208 -211]
1 COMM 1 PASSWORD
[208]
2 COMM 1 PASSWORD
[209]
3 COMM 2 PASSWORD
[210]
4 COMM 2 PASSWORD
[211]
12
TLS2 [212 -214] /
[212 -214] /
1 10-04-01
[212]
2
[213] 13-54
1 (Date)[212]-
2 (Time)[213]-
3 / (TM/Date Format)[214]-
DD-MM-YY-HH1-MM
YY-MM-DD-HH1-MM
MM-DD-YY-HH2-MM-xM
DD = 01-31
MM = 01-12
YY = 2 01
HH1 = 01 - 24
HH2 = 01 -12
MM = 00-59
xM = AM PM
13
TLS2
1 2001 3
1 (Month) - 01 - 12
2 (Day) - 01 -31
3 (Year) - 2001
11
14
TLS2
1 3
1 (Hours) - 00-23 01 - 12
2 (Minutes) - 01 -59
3 / (AM/PM) 1 - AM PM
4 PM1
5 AM1
11
15
TLS2 [215 -218]
[215 -218]
1
[215]
2
[216]
3
[217]
4
[218]
6 1 Shift 1 [215]-
1 AM PM
7 2 Shift 2 [216]-
2 AM PM
8 3 Shift 3 [217]-
3 AM PM
9 4 Shift 4 [218]-
4 AM PM
16
TLS2 [219-223]
[219-223]
1 ENABLE
[219]
2 APR WEEK 1 SUN
[220]
3
[221] 2:00 AM
17
TLS2 [224-226]
[224-226]
1 PHONE
[224]
2 RETRIES
[225]
3 RETRY DELAY
[226]
1 (Phone) [224]-
2 (Retries) [225]-
(1-99)
3 (Retry Delay) [226]-
(1-99)
18
TLS2 [227-230] 1
[227-230] 1
1
[227]
2
[228]
3
[229]
4
[230]
5
1 2 3 4 5 6
1 (Max Product) [227]-
(On) (Off)
2 (Overfill Limit) [228]-
(On) (Off)
3 (Delivery Needed) [228]-
(On) (Off)
4 (Low Product) [230]-
(On) (Off)
5
1-3
19
TLS2 [231-234] 2
[231-234] 2
1
[231]
2 6
[232]
3
[233] 7
4
[234] 8
11 22 33 4
4 5
5 6
6
1 (High Water) [231]-
(On) (Off)
2 (Gross Test Fail) [232]-
(On) (Off)
3 (Periodic Test Fail) [233]-
(On) (Off)
4 (Annual Test Fail) [234]-
(On) (Off)
20
TLS2 [235-237] 3
[235-237] 3
1
[235]
2
[236]
3
[237]
11 22 33 4
4 5
5 6
6
21
TLS2 [238-239] 1 2 1
[238-239] 1 2 1
1
[238]
2
[239]
3 4 5 6
1 2 6 - 2 ( 25 )
1 (Comm Type) [238]-
1 -
Serial Modem
Printer None
2 -
Serial None
2 (Handshaking) [239]-
(None) XON/XOFF
(Hardware) 1 2
3 1 (COMM 1) - 1
4 2 (COMM 2) - 2 (Comm 2
Setup)
5 (PARALLEL) -
Parallel Port Setup ( 28 )
22
TLS2 [241] 1
[241] 1
[238]
1
[241] 9
[239]
2 PRINTER LANG EPSON ESC/P
[253] 3
23
TLS2 [244-246] 1 1
[244-246] 1 1
[238]
2
[244]
3
[245]
4 5
[246]
1 (Comm
Type) (Modem) ( 22
)
1 -
(Advanced Communications Setup) ( 26 )
2 (Modem Type) [244]-
3 (Dial Type) [245]-
Pulse (Tone)
4 (Answer On) [246]-
0-9 1
5 - 2( 25 )
24
TLS2 [249-252] 2
[249-252] 2
1 9600
[249]
2 ODD
[250]
3 7
[251]
4
[252]
25
TLS2 [247 -248]
[247 -248]
1 DIAL IN AT&B1
[247]
2 AT&B1
[248]
26
TLS2
1
[249]
2 SAVE 3
(Baud Rate)
1 (Baud Rate) [249]-
300 600 1200 2400 4800
9600
2 (Save) Cancel) - (Save)
(Cancel)
27
TLS2
1 COMM TYPE
[238]
2 PAGE EJECT
[238]
9
3 PRINTER LANG EPSON ESC/P
[253]
28
TLS2 [256]
[256]
1
[256]
29
TLS2 [257-258]
[257-258]
1 59 F
[257]
2
[258]
1 (TC Reference) [257]-
-49 +120 -45 +48.9 59
15
2 (Print TC Volume) [258]-
(Yes) (No)
(NO) (TC Volumes)
30
TLS2 [259-262]
[259-262]
1
[259]
2
[260]
3
[261]
4
[262]
1 (H-Protocol Format) [259]-
(Height)
(Volume)
2 (Euro Protocol Prefix) [260]-
S d
3 (Stick Height Offset) [261]-
(Enabled)
(Disabled)
4 (Leak Test Format) [262] -
(Enhanced)
(Normal)
(Enhanced)
31
TLS2 TLS2
TLS2
SYSTEM FEATURES
STATIC TANK LEAK DETECT
TLS2
32
1 2
1 (Tank Setup) - (Tank
Setup) ( 34 )
2 (Tank Alarm Limit)-
Tank Alarm Limits Setup ( 39
)
3 (Tank Test Setup)-
Tank Test Setup ( 44 )
33
TLS2 [119-121] 1
[119-121] 1
TANK 1
1 CONFIGURED
[119]
2
[120]
3
[121]
1 2 3 4 5 6
1 (Configured) [119]-
(Enabled) (Disabled)
2 (Prod Label) [120]-
20 0-9
3 (Manifold Status) [121]-
34
TLS2 [122-124] 2
[122-124] 2
TANK 1
1
[122]
2
[123]
3
[124]
1 2 3 4 5 6
1 (Diameter) [122]-
2 (Full Volume) [123]-
3 (Tank Profile) [124]-
-
1 - 4-
20 -
4 (Tank Chart)-420
4
20
4 20
0
35
TLS2 [125-128] 3
[125-128] 3
TANK 1
1
[125] 0.00070
2
[126] 0 IN
3
[127]
4
[128]
1 2 3 4 5 6
1 (Thermal Coefficient) [125]-
-
2
= 52 =
( 8 ) 48 +4 = 52 =
54 -2
2 (Tank Tilt) [126]-
-144 +144 -
365.76 +365.76 0
(-)
000.00 0000.0
3
G
3 (Float Size) [127]-
Mag
4 (Stick Offset) [128]-
-144 +144
-365.76 +365.76 0
Stick Offset
( 31 )
36
TLS2 [125-128] 3
0.00063 0.00114
0.00075 0.00135
2 0.00045 0.00081
0.00037 0.00067
4 0.00047 0.00085
0.00069 0.00125
0.00047 0.00085
0.00047 0.00085
1 0.00050 0.00090
0.00070 0.00126
0.00047 0.00085
0.00070 0.00126
0.00070 0.00126
0.00047 0.00085
0.00047 0.00085
0.00012 0.00022
0.00047 0.00085
0.00044 0.00079
37
TLS2 [125-128] 3
1. A
2. (Tank Tilt)[126] = 0
B
3. A B C
4. D
5. C D E
6. F
7. E F E X F = G
A B C D E F G
*
(A - B = C) (C / D = E) (E x F = G)
6
*
38
TLS2 [101-104] 1
[101-104] 1
1
[101]
2
[102]
3
[103]
4
[104]
1 2 3 4 5 6
39
TLS2 [105-108] 2
[105-108] 2
1
[105]
2
[106]
3
[107]
4
[108]
1 2 3 4 5 6
40
TLS2 [109-111] 3
[109-111] 3
1
[109]
2
[110]
3
[111]
1 2 3 4 5 6
41
TLS2 [112-114] 1
[112-114] 1
1 0.2 GPH
[112]
2 EARLY STOP
[113]
3
[114]
1 2 3 4 5 6
42
TLS2 [115]
[115]
1
[115]
2 SAVE 3
(SAME ALL TANKS)
1 (Confirm) [115]- (Yes)
1
(No) 1
(No)
2 (Save) -
3 (Cancel) -
43
TLS2 [116-118] 2
[116-118] 2
TANK 1
1
[116]
2 DATE/DAY
[117]
3
[118]
1 2 3 4 5 6
1 (Frequency) [116]-
On Date
Annually
Monthly
Weekly
Daily
2 / (Date/Day) [117]-
3 (Time) [118]-
44
/
1
[129]
2 5
[130]
3 0.76 LPH 6
[112]
4
[114]
1 2 3 4 5 6
45
4 5 4
TC
47
9 TC
TC
TC
CURRENT TEST
RESULTS
/
(Current Test
Results)
/
Fullest Last
Pass 12
T = C =
48
46
TLS2
37.3 F
1
5329 GAL
(5413 GAL TC)
2
72 IN
WATER 0.0 IN
1 2 3 4 5 6
Shift Inventory Delta
-TC
T 1:REGULAR UNLEADED
TANK VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP
1 5329 5413 4500 48.8 0.0 37.3
2 5329 5413 4500 48.8 0.0 37.3
- TC
T 1:REGULAR UNLEADED
TANK PRODUCT
1 REGULAR UNLEADED VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP
SHIFT 1 STARTING VALUES 8518 8492 1482 76.26 0.0 64.7
ENDING VALUES 8518 8492 1482 76.26 0.0 64.7
DELIVERY VALUE 0
TOTALS 0
SHIFT 2 STARTING VALUES 8518 8492 1482 76.26 0.0 64.7
ENDING VALUES 8518 8492 1482 76.26 0.0 64.7
DELIVERY VALUE 0
TOTALS 0
47
TLS2
TC
TC Print TC Volumes NO TC
/
/
/
/
48
TLS2
T = C =
50
4
(Count)
-
T = C =
50
Alarm Ack 5
LED
All Functions Normal 5
49
TLS2
LED
5
ALARM 5
LED
0.005 10 [37.8 ]
0 0
0% 0%
0
0.005 10 [37.8 ]
0 0
3
0.2 5
0 0
50
TLS2
-4 -20
0 -17.7 )
-40 -40 -36 (-37.7)
51
1 2 3
4 5 6
RED LED GREEN LED LCD OFF
7 8
1 TEST ALARM -
2 TEST RELAY - 5
3 -
4 LED RED LED - LED
5 LED GREEN LED - LED
6 LCD LCD OFF -
7 LCD LCD TEST -
8 TOUCH - LCD ( 53
)
52
TLS2 LCD
LCD
5 1
x/y 5
53
TLS2
TANK : 1
PROBE TYPE : MAG 01
SERIAL NUMBER : 123001
PROBE ID : C000
PROBE LENGTH : 96.0
GRADIENT : 360.000
NUMBER SAMPLES: 20
1 2 3 4 5 66
54
6 7 TLS2
[101]
101 (Max Product) 39
102 (Overfill) 39
107 (Ann 40
Leak Test Min)
108 (Per 40
Leak Test Min)
115 (Confirm) 43
116 (Frequency) 44
117 / (Date/Day) 44
118 (Time) 44
119 (Configured) 34
122 (Diameter) 35
55
TLS2
123 (Full Volume) 35
201 (System Language) 8
202 (Units) 8
204 1(Header 1) 9
205 2(Header 2) 9
206 3(Header 3) 9
207 4(Header 4) 9
208 1 (Comm 1 12
Password Enable)
209 1 (Comm 1 12
Password)
210 2 (Comm 2 12
Password Enable)
211 2 (Comm 2 12
Password)
212 (Date) 13
213 (Time) 13
214 / (Time/Date 13
Format)
56
TLS2
215 1(Shift 1) 16
216 2(Shift 2) 16
217 3(Shift 3) 16
218 4(Shift 4) 16
225 (Retries) 18
239 (Handshaking) 22 ,
23
57
TLS2
241 (Page Eject) 23 ,
28
244 (Modem 24
Type)
250 (Parity) 25
258 TC (Print TC 30
Volume)
259 (H-Protocol 31
Format)
58
FRENCH
Table des matires
Avis
Tableaux
Introduction
Exigences de certification de lentreprise contractante ........................................... 1
Manuel concerns ................................................................................................... 1
Symboles de scurit .............................................................................................. 2
Avertissements de scurit ..................................................................................... 2
Conformit aux rglements et approbations ........................................................... 3
Console ................................................................................................................... 3
Fonctions de contrle ........................................................................................... 3
Relais de sortie..................................................................................................... 3
Fonctions de communication ................................................................................ 3
Index des rfrences rapides des messages d'alarme ........................................... 4
i
Table des matires
Rapports
Rapports du systme ............................................................................................ 46
Rapports d'inventaire ............................................................................................. 47
Exemple de rapport imprim - Rapport d'inventaire avec volume TC ................ 47
ii
Table des matires
Ecrans de diagnostic
Ecran Menu de test de fonction (Function Test Menu) ......................................... 52
Ecran Test touche de dclenchement LCD (LCD Touch Test) ............................. 53
Ecran de dtection de sonde ................................................................................ 54
Exemple de rapport imprim - Rapport de dtection de sonde .......................... 54
Disponibilit des donnes de sonde................................................................... 54
iii
Table des matires
iv
Configuration du TLS2
1
Configuration du TLS2
2
Introduction
Ce manuel dcrit les procdures de configuration et d'utilisation de la console pour rservoirs de stockage souter-
rains (UST) TLS2. Il considre que votre systme a dj t configur par une entreprise agre. Il considre
galement que la console est installe et que la procdure de dmarrage froid a t correctement effectue.
Il convient de dmarrer la procdure de configuration avec les crans de configuration du systme et de la terminer
avec les crans de configuration des rservoirs.
La console est oprationnelle lorsque les paramtres du systme et de configuration des rservoirs ont t
introduits. Se reporter la section Rapports pour les instructions sr le systme de visualisation et les rapports
d'alarme. La section Diagnostic contient quelques procdures simples de test de la console et des donnes de
diagnostic des sondes.
Veeder-Root exige que l'entreprise qui ralise l'installation et la configuration de l'quipement concern par ce
manuel dispose au moins des certifications de formation suivantes:
Niveau 1 Les entreprises contractantes qui possdent une certification de niveau 1 valable sont autorises
effectuer des oprations de cblage et d'acheminement de conduits, de montage d'quipements, d'installation de
sondes et de capteurs, de prparation des rservoirs et des canalisations, ainsi que d'installation de dtecteurs de
fuite sr les canalisations.
Niveau 2/3 Les entreprises contractantes qui possdent des certifications de niveau 2 ou 3 valables sont
autorises effectuer des oprations de vrification de l'installation, de mise en service, de formation la
programmation et au fonctionnement, de dpannage et d'entretien de tous les systmes de contrle
des rservoirs Veeder-Root, y compris la dtection des fuites sr les canalisations et les accessoires associs.
Les contrats de garantie ne peuvent tre proposs que par des distributeurs slectionns.
Manuel concerns
1
Configuration du TLS2
Symboles de scurit
Ce manuel utilise les symboles de scurit suivants pour attirer l'attention sr les risques importants en
matire de scurit et les prcautions prendre.
EXPLOSIF INFLAMMABLE
Les carburants et leurs vapeurs Les carburants et leurs vapeurs sont
sont extrmement explosifs s'ils extrmement inflammables.
s'enflamment.
Avertissements de scurit
AVERTISSEMENT
Ce systme fonctionne proximit de rservoirs de stockage de carburants
extrmement combustibles.
Les fuites dans les rservoirs peuvent entraner des dangers graves pour
l'environnement et la sant. Une programmation et une utilisation incor-
rectes peuvent galement provoquer des pannes du systme d'autotest de
l'quipement et des arrts de la pompe immerge.
2
Configuration du TLS2
Le programme de dtection de fuites doit tre planifi suivant les rglementations locales, dpartementales ou
rgionales applicables aux rservoirs de stockage souterrains. Il convient de conserver tous les relevs d'inventaire
et de tests d'tanchit fournis par le systme comme faisant partie d'un programme de conformit aux rglements.
Lorsqu'il est muni de sondes magntostrictives de 0,2 gallon par heure (gph) (0,76 lph) (Mag 2), le systme est
class comme un systme jaugeur de rservoir automatique et a t test par un organisme tiers, le Midwest
Research Institute. Ce systme peut dtecter une fuite de 0,2 gph avec une probabilit de dtection [P(D)]
de plus de 95% et une probabilit de fausse alarme [P(FA)] de moins de 5%. Il rpond aux normes de performance
fdrales E.P.A. des Etats-Unis (0,2 gph [P(D)] de 95% et [P(FA)] de 5%) ainsi qu'aux normes de performance
fdrales en ce qui concerne la mesre de l'eau au fond des rservoirs avec une prcision de 1/8" (3,2 mm).
Lorsqu'il est muni de sondes magntostrictives de 0,1 gph (0,38 lph) (Mag 1), le systme rpond aux normes
de la mthode de test d'tanchit des rservoirs volumtriques et a t test par un organisme tiers, le Midwest
Research Institute. Ce systme peut dtecter une fuite de 0,1 gph avec une probabilit de dtection [P(D)] de plus
de 95% et une probabilit de fausse alarme [P(FA)] de moins de 1%. Ce systme rpond aux normes de perfor-
mance fdrales E.P.A. des Etats-Unis (0,1 gph [P(D)] de 95% et [P(FA)] de 5%).
Console
La console TLS2 dispose d'un cran de visualisation tactile situ sr le panneau avant, d'une DEL Alarme/Normal
double usage et d'un avertisseur sonore pour les alarmes et la notification d'avertissements. Des ports d'impri-
mante srie et parallle permettent de connecter une imprimante distance. La console TLS2 peut contrler
jusqu' six sondes magntostrictives.
Fonctions de contrle
Relais de sortie
Un relais de sortie permet de dclencher des dispositifs d'alarme externes lorsque le systme dtecte
une condition d'alarme.
Fonctions de communication
RS-422
3
Configuration du TLS2 Index des rfrences rapides des messages d'alarme
Echec du Rservoir Le test d'tanchit annuel dans Procder un nouveau test d'tanchit
test annuel le rservoir a chou. dans le rservoir. Si le second test
choue, appeler le service de
rparation.
Echec du test brut Rservoir Le test d'tanchit dans le Procder un nouveau test d'tanchit
rservoir a chou. dans le rservoir. Si le second test
choue, appeler le service de
rparation.
Eau haute Rservoir L'eau dtecte dans le rservoir Retirer de l'eau du rservoir.
dpasse la limite prdfinie.
Produit bas Rservoir Le niveau du rservoir est descendu Demander une livraison.
sous la limite prdfinie.
Basse temprature Rservoir La temprature mesre par la Le fonctionnement normal est rtabli
sonde est infrieure -4F (-20C). lorsque la temprature de la sonde
Pour les sondes basses temp- remonte au-dessus de 0F (-17.7C).
ratures, infrieure -40F (-40C). Pour les sondes basses tempratures,
au-dessus de -36F (-38C).
Dbordement Rservoir Le rservoir est peut-tre trop rempli. Interrompre la livraison. Rechercher les
dversements ventuels.
Echec du test Rservoir Le test d'tanchit dans le rservoir Procder un nouveau test d'tanchit
priodique a chou. dans le rservoir. Si le second test
choue, appeler le service de
rparation.
Sonde sortie Rservoir Panne matrielle - sonde ou cblage Appeler le service de rparation.
reliant la sonde la console.
4
Ecrans Configuration du systme (System Setup)
Cette section dcrit tous les crans de configuration du systme TLS2; elle contient galement les options de configuration et
les explications ncessaires lentre de donnes. Etant donn que les crans de configuration du TLS2 contiennent uni-
quement des tiquettes en anglais, des codes d'tiquettes ont t placs entre parenthses en dessous de chaque tiquette
anglaise pour permettre d'obtenir rapidement la traduction de l'tiquette et le(s) numro(s) de page de l'cran dans lequel
l'tiquette est utilise. Les crans de configuration des rservoirs sont abords dans une autre section.
On peut entrer des donnes, confirmer des slections, etc., partir d'un des crans dentre de donnes qui s'affichent
lorsqu'on touche un des boutons situs droite des fentres dentre de donnes. Ces crans sont dcrits dans cette section,
lors de leur premire apparition.
11
5
10
9 8 7 6
5
Configuration du TLS2 Ecran Menu principal (Main Menu)
1 2
6 3
II
5 4
consoles/tls2/menuscrn.eps
6
Configuration du TLS2 Ecran Configuration du systme (System Setup)
2 3 4
1
6 7
5
8
10 11 12
1 Touche Langue (Language) - Appuyez pour afficher 8 Touche Temprature (Temp) - Appuyez pour afficher
l'cran Configuration de la langue et des units l'cran Configuration de la temprature (Temp Setup)
(Language and Units Setup) (page 8). (page 30).
2 Touche Heure actuelle (Current Time) - Appuyez pour 9 Touche Scurit (Security) - Appuyez pour afficher
afficher l'cran Configuration de l'heure/la date (Time/ l'cran Configuration de la scurit du systme
Date Setup) (page 13). (System Security Setup) (page 12).
3 Touche Communications (Comm) - Appuyez pour 10 Touche Economies d'clairage (Daylight Savings) -
afficher l'cran Configuration des communications Appuyez pour afficher l'cran Configuration des
(Comm Setup) (page 22). conomies d'clairage (Daylight Savings Setup)
4 Touche Relais d'alarme (Alarm Relay) - Appuyez (page 17).
pour afficher l'cran Configuration du relais d'alarme 11 Touche Alarmes composition automatique (Autodial
(Alarm Relay Setup) (page 29). Alarms) - Appuyez pour afficher l'cran Configuration
5 Touche En-tte (Header) - Appuyez pour afficher des alarmes composition automatique (Autodial
l'cran Configuration de l'en-tte de station (Station Alarms Setup) (page 19).
Header Setup) (page 9). 12 Touche protocole euro (EuroProtocol) - Appuyez pour
6 Touche Heure de mouvement (Shift Time) - Appuyez afficher l'cran Configuration du protocole euro et de
pour afficher l'cran Configuration de l'heure de l'cart de tige (EuroProtocol and Stick Offset Setup)
mouvement (Setup Shift Times) (page 16). (page 31). Cet cran vous permet aussi de
slectionner un format de rapport de test
7 Touche Configuration de la composition (Dialing d'tanchit.
Setup) - Appuyez pour afficher l'cran Configuration
de la composition automatique de la configuration du
systme (System Setup Dial Out Setup) (page 18).
7
Configuration du TLS2 [201-203] Ecran Configuration de la langue et des units du systme (System Language and Units Setup)
1
[201]
2
[202]
3
[203]
8
Configuration du TLS2 [204-207] Ecran Configuration de l'en-tte de station (Station Header Setup)
1
[204]
2
[205]
3
[206]
4
[207]
9
Configuration du TLS2 Ecran Clavier alphabtique (Alpha Keypad)
10
4 SAVE
5 6 7 8 9
1 Affiche le titre des donnes entrer. 7 Touche Curseur vers la droite - Appuyez pour
2 La fentre des Donnes entres (Data Entered) dplacer le curseur d'un espace vers la droite dans la
affiche les donnes entres. fentre Donnes entres (Data Entered) (2).
3 Touches de clavier alphabtique - Appuyez sr une 8 Touche de retour arrire (suppression) - Appuyez
touche de caractre pour insrer ce caractre pour supprimer le caractre au niveau du curseur.
dans la fentre de donnes entres (2). 9 Touche de clavier numrique - Appuyez pour afficher
4 Touche Enregistrer (Save) - Appuyez pour accepter l'cran Clavier numrique (Numeric Keypad).
les donnes entres et fermer l'cran. 10 Touche d'effacement - Appuyez pour effacer le
5 Touche Annuler (Cancel) - Appuyez pour annuler contenu de la fentre Donnes entres (Data
toute donne entres et fermer l'cran. Entered) (2).
10
Configuration du TLS2 Ecran Clavier numrique (Numeric Keypad)
10
4 SAVE 9
5 6 7 8
1 Affiche le titre des donnes entrer. 7 Touche Curseur vers la droite - Appuyez sr dplacer
2 La fentre des Donnes entres (Data Entered) le curseur d'un espace vers la droite dans la fentre
affiche les donnes entres. Donnes entres (Data Entered) (2).
3 Touches de clavier numrique - Appuyez sr une 8 Touche de retour arrire (suppression) - Appuyez sr
touche de caractre pour insrer ce caractre dans la supprimer le caractre au-dessus du curseur.
fentre de donnes entres (2). 9 Touche de clavier alphabtique - Appuyez sr
4 Touche Enregistrer (Save) - Appuyez sr accepter les afficher l'cran Clavier alphabtique (Alpha Keypad).
donnes saisies et fermer l'cran. 10 Touche d'effacement - Appuyez sr effacer le
5 Touche Annuler (Cancel) - Appuyez sr annuler toute contenu de la fentre Donnes entres (Data
donne entres et fermer l'cran. Entered) (2).
11
Configuration du TLS2 [208-211] Ecran Configuration de la scurit du systme (System Security Setup)
1 COMM 1 PASSWORD
[208]
2 COMM 1 PASSWORD
[209]
3 COMM 2 PASSWORD
[210]
4 COMM 2 PASSWORD
[211]
12
Configuration du TLS2 [212-214] Ecran Configuration de l'heure/la date du systme (System Time/Date Setup)
1 10-04-01
[212]
2
[213] 13-54
13
Configuration du TLS2 Ecran entre de la date actuelle (Current Date Entry)
1 2001 3
14
Configuration du TLS2 Ecran entre de l'heure actuelle (Current Time Entry)
1 3
15
Configuration du TLS2 [215-218] Ecran Configuration de lheure de mouvement (Shift Times Setup)
1
[215]
2
[216]
3
[217]
4
[218]
A chaque heure de dbut de mouvement slectionne 7 Mouvement 2 (Shift 2) [216] - Appuyez sr la touche
ci-dessous, le systme enregistre automatiquement un Heure droite de la fentre et entrez l'heure de
rapport d'inventaire complet dans la mmoire. La valeur dbut du Mouvement 2 (Shift 2) et AM ou PM.
par dfaut est 'dsactiv' pour tous les mouvements. 8 Mouvement 3 (Shift 3) [217] - Appuyez sr la touche
REMARQUE: Il faut entrer au moins une heure de dbut Heure droite de la fentre et entrez l'heure de
de mouvement pour activer la fonction "Inventaire du dbut du Mouvement 3 (Shift 3) et AM ou PM.
dernier mouvement" (Last Shift Inventory).
9 Mouvement 4 (Shift 4) [218] - Appuyez sr la touche
6 Mouvement 1 (Shift 1) [215] - Appuyez sr la touche Heure droite de la fentre et entrez l'heure de
Heure droite de la fentre et entrez l'heure de dbut dbut du Mouvement 4 (Shift 4) et AM ou PM.
du Mouvement 1 (Shift 1) et AM ou PM.
16
Configuration du TLS2 [219-223] Ecran Configuration de l'heure pour les conomies d'clairage (Daylight Savings Time Setup)
1 ENABLE
[219]
2 APR WEEK 1 SUN
[220]
3
[221] 2:00 AM
Cette fonction permet dentrer des dates/heures de 3 Heure de dbut (Start Time) [221] - Appuyez sr la
dbut et de fin d'conomies d'clairage. Lorsque cette touche Heure droite de la fentre et entrez l'heure
fonction est active, le systme rgle automatiquement de dbut [et AM ou PM] (l'heure par dfaut est
l'heure des conomies d'clairage aux dates et aux 02:00 AM).
heures entres. 4 Date de fin (End Date) [222] - Appuyez sr la touche
1 Economies d'clairage (Daylight Savings) [219] - Date droite de la fentre et entrez la date de fin
Appuyez sr la touche Flche droite de la fentre (la date par dfaut est OCT SEMAINE 6 DIM (OCT
et slectionnez Activ (Enable) ou Dsactiv WEEK 1 SUN)).
(Disable) (la slection par dfaut est Dsactiv). 5 Heure de fin (End Time) [223] - Appuyez sr la
2 Date de dbut (Start Date) [220] - Appuyez sr la touche Heure droite de la fentre et entrez l'heure
touche Date droite de la fentre et entrez la date de fin [et AM ou PM] (l'heure par dfaut est
de dbut (la date par dfaut est AVR SEMAINE 1 02:00 AM).
DIM (APR WEEK 1 SUN)).
17
Configuration du TLS2 [224-226] Ecran Configuration de la composition automatique (Auto-Dialout Setup)
1 PHONE
[224]
2 RETRIES
[225]
3 RETRY DELAY
[226]
Pour cette fonction, il faut slectionner Modem dans Type 3 Dlai de recomposition (Retry Delay) [226] - Appuyez
de communication (Comm Type). sr la touche Numrique (Numeric) droite de la
fentre et entrez le nombre de minutes (1-99) que le
1 Tlphone (Phone) [224] - Appuyez sr la touche systme doit attendre pour recomposer le numro de
Numrique (Numeric) droite de la fentre et entrez tlphone en cas de tonalit d'occupation, d'absence
un numro de tlphone composer par le systme. de rponse ou de connexion incomplte (la valeur
2 Recompositions (Retries) [225] - Appuyez sr la par dfaut est 3 minutes).
touche Numrique (Numeric) droite de la fentre et
entrez le nombre de fois (1-99) que le systme doit
recomposer le numro de tlphone en cas de
tonalit d'occupation, d'absence de rponse ou de
connexion incomplte (la valeur par dfaut est 3
recompositions).
18
Configuration du TLS2[227-230] Configuration des alarmes composition automatique - Ecran 1 (Autodial Alarm Setup Screen 1)
1
[227]
2
[228]
3
[229]
4
[230]
5
1 2 3 4 5 6
19
Configuration du TLS2 [231-234] Configuration des alarmes composition automatique - Ecran 2 (Autodial Alarm Setup Screen 2)
1
[231]
2 6
[232]
3
[233] 7
4
[234] 8
11 22 33 4
4 5
5 6
6
20
Configuration du TLS2[235-237] Configuration des alarmes composition automatique - Ecran 3 (Autodial Alarm Setup Screen 3)
1
[235]
2
[236]
3
[237]
11 22 33 4
4 5
5 6
6
21
Configuration du TLS2 [238-239] Configuration srie des ports de communication 1 et 2 - Ecran 1 (Comm Port 1 and 2 Serial Setup Screen 1)
1
[238]
2
[239]
3 4 5 6
Cet cran est valable pour la configuration des ports de 3 Touche Communications 1 (COMM 1) - Appuyez pour
communication 1 et 2. afficher l'cran Configuration du port de communication
1 Type de communication (Comm Type) [238] - 1 (Comm 1 Setup) (illustr ci-dessus).
Appuyez sr la touche Flche vers le bas droite de 4 Touche Communications 2 (COMM 2) - Appuyez pour
la fentre et slectionnez: afficher l'cran Configuration du port de communication
Si port de communication 1 - 2 (Comm 2 Setup).
Srie (Serial), Modem, Imprimante (Printer) ou Aucun 5 Touche PARALLLE (PARALLEL) - Appuyez pour
(None) (par dfaut) afficher l'cran Configuration du port parallle (Parallel
Port Setup) (page 28).
Si port de communication 2 -
Srie (Serial) ou Aucun (None) (par dfaut) 6 Touche Flche vers le bas - Appuyez pour afficher
Configuration du port de communication - Ecran 2
2 Etablissement de liaison (Handshaking) [239] - (Comm Port Setup Screen 2) (page 25).
Appuyez sr la touche Flche vers le bas droite de
la fentre et slectionnez Aucune (None), XON/XOFF
ou Matriel (Hardware) (par dfaut). Ce paramtre
est identique pour les ports de communication 1 et 2.
22
Configuration du TLS2 [241] Ecran Configuration dimprimante du port de communication 1 (Comm Port 1 Printer Setup)
[238]
1
[241] 9
[239]
2 PRINTER LANG EPSON ESC/P
[253] 3
23
Configuration du TLS2 [244-246] Configuration de modem du port de communication 1 - Ecran 1 (Comm Port 1 Modem Setup Screen 1)
[238]
2
[244]
3
[245]
4 5
[246]
24
Configuration du TLS2 [249-252] Configuration du port de communication - Ecran 2 (Comm Port Setup Screen 2)
1 9600
[249]
2 ODD
[250]
3 7
[251]
4
[252]
25
Configuration du TLS2 [247-248] Ecran Configuration avance des communications (Advanced Communications Setup)
1 DIAL IN AT&B1
[247]
2 AT&B1
[248]
ATTENTION!
Le modem peut sarrter si l'on saisit un nombre
erron de chanes dans cet cran.
26
Configuration du TLS2 Ecran entre de donnes (Data Entry)
1
[249]
2 SAVE 3
27
Configuration du TLS2 Ecran Configuration du port parallle (Parallel Port Setup)
1 COMM TYPE
[238]
2 PAGE EJECT
[238]
9
3 PRINTER LANG EPSON ESC/P
[253]
28
Configuration du TLS2 [256] Ecran Configuration du relais dalarme (Alarm Relay Setup)
1
[256]
29
Configuration du TLS2 [257-258] Ecran Configuration de la temprature (Temperature Setup)
1 59 F
[257]
2
[258]
30
Configuration du TLS2[259-262] Ecran Configuration du protocole euro et de l'cart de tige (EuroProtocol and Stick Offset Setup)
1
[259]
2
[260]
3
[261]
4
[262]
31
Configuration du TLS2 Ecran A propos du TLS2 (About TLS2)
SYSTEM FEATURES
STATIC TANK LEAK DETECT
Cet cran prsente les informations relatives au logiciel install sr la console TLS2 et ses fonctions:
Niveau de rvision du systme du logiciel (System Software Revision Level)
Numro de version du logiciel
Numro de rfrence du logiciel
Date de cration du logiciel
Caractristiques du systme: Dtection de fuite au rservoir statique
32
Ecrans Configuration des rservoirs (Tank Setup)
1 2
33
Configuration du TLS2 [119-121] Configuration des rservoirs (Tank Setup) - Ecran 1
TANK 1
1 CONFIGURED
[119]
2
[120]
3
[121]
1 2 3 4 5 6
34
Configuration du TLS2 [122-124] Configuration des rservoirs (Tank Setup) - Ecran 2
TANK 1
1
[122]
2
[123]
3
[124]
1 2 3 4 5 6
La configuration des rservoirs continue sr cet cran. Le systme calculera les hauteurs pour chaque
1 Diamtre (Diameter) [122] - Appuyez sr la touche point (4 ou 20) suivant le profil slectionn et le
Flche vers le bas droite de la fentre et entrez le diamtre du rservoir, et les affichera ct des
diamtre du rservoir. fentres dans lesquelles doit tre introduit le
volume correspondant. Trouvez dans le
2 Volume plein (Full Volume) [123] - Appuyez sr la diagramme du rservoir le volume pour les
touche Flche vers le bas droite de la fentre et hauteurs affiches, et entrez ce volume dans la
entrez le volume 100% du rservoir. fentre.
3 Profil du rservoir (Tank Profile) [124] - Appuyez sr la S'assrer que l'on entre bien la valeur exacte
touche Flche vers le bas droite de la fentre et fournie par le diagramme pour la hauteur
slectionnez un profil de rservoir: Linaire (Linear) - spcifie. Les valeurs hors limites ne seront
pour les rservoirs rectangulaires ou les rservoirs pas acceptes.
cylindriques reposant sr une extrmit, 1 point - pour
les rservoirs en acier extrmits plates (par dfaut), Si le profil 4 points ou 20 points a t slectionn,
4 points - pour les rservoirs en fibre de verre, ou 20 il faut entrer un volume pour chaque point. A
points - pour tous les rservoirs. dfaut, le systme calculera un volume gal 0
pour toutes les hauteurs.
4 Touche Diagramme rservoir (Tank Chart) - Cette
Suite des paramtres de configuration des rservoirs la
touche n'apparat que si vous avez slectionn le profil
page suivante.
4 points ou 20 points.
35
Configuration du TLS2 [125-128] Configuration des rservoirs (Tank Setup) - Ecran 3
TANK 1
1
[125] 0.00070
2
[126] 0 IN
3
[127]
4
[128]
1 2 3 4 5 6
Ceci est le dernier cran de configuration des rservoirs. d'inclinaison du rservoir la valeur qui figure dans la
1 Coefficient thermique (Thermal Coefficient) [125] - colonne G du tableau.
Appuyez sr la touche Flche vers le bas droite de la 3 Taille du flotteur (Float Size) [127] - Appuyez sr la
fentre et entrez le coefficient thermique du rservoir. touche Flche vers le bas droite de la fentre et
Pour permettre une conversion prcise du volume entrez, parmi les tailles de flotteur affiches, la taille
thermocompens, le coefficient de dilatation thermique du flotteur de sonde Mag install sr la sonde du
du produit doit tre correctement entr. Une valeur rservoir.
incorrecte nuirait au bon fonctionnement des essais 4 Ecart de tige (Stick Offset) [128] - Appuyez sr la
d'tanchit et des valeurs d'inventaire de volume touche Flche vers le bas droite de la fentre et
thermocompens. entrez une valeur pour l'cart de tige. Les valeurs
Le Tableau 2 indique les coefficients pour les combus- admises vont de -144 +144 pouces (-365,76
tibles et autres liquides approuvs, selon le systme +365,76 cm) et la valeur par dfaut est 0.
amricain (E.-U.) et mtrique Entrez le coefficient en Remarque: Pour pouvoir entrer une valeur d'cart de
units amricaines ou mtriques, suivant les units tige, l'option Ecart de tige doit avoir t active (page
spcifies dans la configuration du systme (page 8). 31) et si ncessaire, l'inclinaison du rservoir doit
Veillez entrer le nombre correct de zros avoir t calcule et entre. Il peut tre utile dentrer
droite du point dcimal. Une entre incorrecte une valeur d'cart de tige afin que la hauteur de
peut provoquer l'chec des essais ou sonde (de produit) "semble" quivalente la hau-teur
d'autres problmes. de produit fournie par la tige de niveau - Cette valeur
2 Inclinaison du rservoir (Tank Tilt) [126] - Appuyez sr sert uniquement faciliter le travail de l'oprateur et
la touche Flche vers le bas droite de la fentre et n'influence pas le calcul du volume
entrez l'inclinaison du rservoir. Les valeurs admises de produit.
vont de -144 +144 pouces (-365,76 +365,76 cm) et Pour dterminer la valeur d'cart de tige qui doit tre
la valeur par dfaut est 0. entre, enregistrez la hauteur de sonde qui s'affiche
La valeur d'inclinaison permet de corriger une diff- ainsi que la hauteur fournie par la tige de niveau.
rence entre la hauteur du combustible l'emplacement Si la hauteur de combustible indique par la sonde
de la sonde et la hauteur du combustible au centre du est infrieure la hauteur de la tige de niveau, entrez
rservoir, due une inclinaison du rservoir. Entrez le la diffrence positive entre ces deux valeurs. Si la
signe moins (-) si l'inclinaison du rservoir est une hauteur de combustible indique par la sonde est
valeur ngative. Il n'est pas ncessaire dentrer une suprieure la hauteur de la tige de niveau, entrez
valeur d'inclinaison si la sonde se trouve au centre du la diffrence ngative entre ces deux valeurs. Par
rservoir. Si la sonde se trouve au centre du rservoir, exemple, si la hauteur de tige = 52 et la hauteur de
la valeur entre est 000.00 (units E.-U.) ou 0000.0 sonde = 48, entrez +4; si la hauteur de tige = 52
(units mtriques). Si la sonde n'est pas au centre du et la hauteur de sonde = 54, entrez -2.
rservoir, calculer l'inclinaison du rservoir en utilisant
les indications du Tableau 3. Entrez comme valeur
36
Configuration du TLS2 [125-128] Configuration des rservoirs (Tank Setup) - Ecran 3
Coefficient
Coefficient
thermique
thermique
(units
(units E.-U.)
Produit mtriques)
37
Configuration du TLS2 [125-128] Configuration des rservoirs (Tank Setup) - Ecran 3
Utilisez le tableau ci-dessous pour enregistrer les mesres et effectuez les calculs d'inclinaison de rservoir pour chacun
des rservoirs.
1. Jaugez le rservoir l'ouverture de la colonne de remplissage trois reprises au moins. Inscrivez la valeur moyenne
dans la colonne A du tableau.
2. Avant d'entamer cette tape, il faut vous assrer que l'inclinaison du rservoir (Tank Tilt [126]) l'cran est gale 0.
Inscrivez la hauteur de carburant de la sonde (Fonction d'inventaire dans le rservoir) dans la colonne B du tableau.
3. Soustrayez la valeur inscrite dans la colonne B de la valeur inscrite dans la colonne A. Notez le rsultat de ce calcul
dans la colonne C.
4. Mesrez la distance en pouces (ou en millimtres si vous utilisez le systme mtrique) entre la sonde et la colonne
de remplissage. Inscrivez cette valeur dans la colonne D.
5. Divisez la valeur de la colonne C par celle de la colonne D pour dterminer la pente. Inscrivez les rsultats dans
la colonne E.
6. Mesrez la distance en pouces ou en millimtres entre la colonne de la sonde et le centre du rservoir. Inscrivez
cette distance dans la colonne F.
7. Multipliez la colonne E par la colonne F pour dterminer l'inclinaison du rservoir (E x F = valeur d'inclinaison du
rservoir). Inscrivez cette valeur dans la colonne G.
A B C D E F G
6
* L'inclinaison du rservoir peut tre une valeur positive (+) ou ngative (-). S'il s'agit d'une valeur ngative, VEILLEZ
BIEN placer un signe moins ( - ) devant la valeur d'inclinaison.
38
Configuration du TLS2 [101-104] Configuration des limites des rservoirs (Tank Limits Setup) - Ecran 1
1
[101]
2
[102]
3
[103]
4
[104]
1 2 3 4 5 6
Ceci est le premier cran de configuration des limites valeur est un pourcentage du volume plein, les
d'alarme des rservoirs. valeurs admises tant comprises entre 0 et 100%. La
1 Produit max (Max Product [101]) - Dclenche une valeur par dfaut est 0% (ce qui dsactive l'alarme).
alarme lorsque le niveau du liquide dans le rservoir Appuyez sr la touche Flche vers le bas droite de
dpasse la valeur entre. Les valeurs admises vont de la fentre et entrez une valeur suprieure celle
0 98420 litres (0-26000 gallons). La valeur par dfaut entre pour l'alarme Produit bas.
est 0. Si la valeur entre est 0 ou volume plein, cette 4 Produit bas (Low Product [104]) - Ce paramtre
alarme est dsactive. Si un avertissement de basse dclenche une alarme lorsque le volume du rservoir
temprature de sonde est actif, il dsactivera cette devient infrieur la valeur entre. Les valeurs
alarme. Appuyez sr la touche Flche vers le bas admises vont de 0 98420 litres (0-26000 gallons).
droite de la fentre et entrez le produit max pour le La valeur par dfaut est 0 (ce qui dsactive l'alarme).
rservoir. Si un avertissement de basse temprature de sonde
2 Dbordement (Overfill [102]) - La limite de dborde- est actif, il dsactivera cette alarme. Appuyez sr la
ment signale un risque de dbordement durant une touche Flche vers le bas droite de la fentre et
livraison. Lorsque le volume atteint cette limite, le entrez cette valeur, qui doit tre infrieure celle
systme peut activer une alarme de dbordement. Le entre pour l'alarme Livraison ncessaire.
seuil d'alarme de dbordement est fond sr la valeur REMARQUE: En gnral, cette alarme est rgle au
de Produit max. Si la valeur de Produit max est gale niveau le plus bas avant que la pompe tourne sec.
0, le seuil d'alarme de dbordement est fond sr le Toute distribution doit tre interrompue lorsque cette
Volume plein. Les valeurs admises sont comprises alarme est active.
entre 0 et 100%. La valeur par dfaut est 0 (dsactiv). La configuration des limites d'alarme des rservoirs
Si un avertissement de basse temprature de sonde continue la page suivante.
est actif, il dsactivera cette alarme.
3 Livraison ncessaire (Delivery Needed [103]) - Ce
paramtre dclenche une alarme lorsque le niveau
de liquide dans le rservoir diminue jusqu' un niveau
auquel l'oprateur doit demander une livraison. Cette
39
Configuration du TLS2 [105-108] Configuration des limites des rservoirs (Tank Limits Setup) - Ecran 2
1
[105]
2
[106]
3
[107]
4
[108]
1 2 3 4 5 6
Cet cran poursuit la configuration des limites d'alarme 3 Min test d'tanchit annuel (Ann Leak Test Min
des rservoirs. [107]) - Cette valeur tablit le volume minimal du
1 Eau haute (High Water [105]) - Dclenche une alarme rservoir requis pour enregistrer un test d'tanchit
lorsque le niveau d'eau dans le rservoir dpasse la annuel russi. Cette valeur reflte les exigences des
hauteur entre. Entrez une valeur infrieure la autorits locales et fdrales et de l'Etat. Cette valeur
hauteur de la prise de la pompe submersible ou de est un pourcentage du volume plein, les valeurs
la conduite d'aspiration . Les valeurs admises sont permises tant comprises entre 1.0 et 100%. La
comprises entre 0 et 228,6 mm (0 et 9 pouces). La valeur par dfaut est 0 (ce qui dsactive l'alarme).
valeur par dfaut est 0 (ce qui dsactive l'alarme). Appuyez sr la touche Flche vers le bas droite de
Appuyez sr la touche Flche vers le bas droite de la fentre et entrez un chiffre de volume.
la fentre et entrez la limite Eau haute souhaite. 4 Min test d'tanchit priodique (Per Leak Test Min
2 Dlai de livraison (Delivery Delay [106]) - Utilisez cet [108]) - Cette valeur dfinit le volume minimal du
affichage pour dfinir un temps d'attente entre rservoir requis pour enregistrer un test d'tanchit
l'achvement d'une livraison brute et le rapport priodique russi. Cette valeur correspond aux
d'augmentation de livraison. Cette fonction permet exigences des autorits locales et fdrales et de
d'viter la cration de plusieurs rapports durant les l'Etat. Cette valeur est un pourcentage du volume
intervalles qui sparent les livraisons multicomparti- plein, les valeurs permises tant comprises entre
ments dans un rservoir. Elle permet galement au 1.0 et 100%. La valeur par dfaut est 0 (ce qui
carburant de "se dposer" aprs une livraison, ce qui dsactive l'alarme). Appuyez sr la touche Flche
est particulirement important avec les groupes de vers le bas droite de la fentre et entrez une valeur.
rservoirs raccords via un collecteur. Le dlai admis La configuration des limites d'alarme des rservoirs
est compris entre 1 et 60 minutes. La valeur par dfaut continue la page suivante.
est 1. Appuyez sr la touche Flche vers le bas
droite de la fentre et entrez le dlai souhait.
40
Configuration du TLS2 [109-111] Configuration des limites des rservoirs (Tank Limits Setup) - Ecran 3
1
[109]
2
[110]
3
[111]
1 2 3 4 5 6
41
Configuration du TLS2 [112-114] Configuration des tests d'tanchit des rservoirs (Tank Leak Test Setup) - Ecran 1
1 0.2 GPH
[112]
2 EARLY STOP
[113]
3
[114]
1 2 3 4 5 6
42
Configuration du TLS2 [115] Ecran Identique pour tous les rservoirs (Same All Tanks)
[115] Ecran Identique pour tous les rservoirs (Same All Tanks)
1
[115]
2 SAVE 3
43
Configuration du TLS2 [116-118] Configuration des tests d'tanchit des rservoirs (Tank Leak Test Setup) - Ecran 2
TANK 1
1
[116]
2 DATE/DAY
[117]
3
[118]
1 2 3 4 5 6
44
Marche/arrt manuel des tests d'tanchit des rservoirs
1
[129]
2 5
[130]
3 0.76 LPH 6
[112]
4
[114]
1 2 3 4 5 6
1 Mthode de test (Test Method [129]) - Slectionnez Remarque: cette fentre n'apparat que si
Rservoir unique (Single Tank) ou Tous les rservoirs l'on a slectionn Dure temporise (Timed
(All Tanks). Appuyez sr la touche Flche vers le bas Duration) dans la fentre de contrle de
droite de la fentre et entrez l'option choisie. test. Appuyez sr la touche Flche vers le
2 Contrle de test (Test Control [130]) - Slectionnez bas droite de la fentre et entrez l'option
Dure temporise (Timed Duration) ou Arrt manuel choisie.
(Manual Stop) (le test se poursuit jusqu' ce qu'on 5 Touche Lancement du test (Test Start) -
l'arrte ou durant 24 heures, selon l'vnement qui Appuyez sr cette touche pour lancer le
arrive en premier). Appuyez sr la touche Flche vers test.
le bas droite de la fentre et entrez l'option choisie. 6 Touche Arrt du test (Test Stop) - Appuyez
3 Dbit de test (Test Rate [112]) - Choisissez un dbit de sr cette touche pour arrter un test
test d'tanchit de 0,2 gph (0.76 lph) (par dfaut) ou d'tanchit de rservoir.
0,1 gph (0.38 lph). Un dbit de 0,1 gph (0.38 lph)
requiert une sonde Mag 1. Appuyez sr la touche
Flche vers le bas droite de la fentre et entrez
l'option choisie.
4 Dure de test (Test Duration [114]) - Choisissez une
dure de test comprise entre 0 et 24 heures. La dure
minimale est de deux heures pour les tests 0,2 gph
(0.76 lph) et de trois heures pour les tests 0,1 gph
(0.38 lph). La dure par dfaut est 2 heures.
45
Rapports
Rapports du systme
On accde aux rapports du systme partir de l'cran Etat du systme (Home) (voir page 5) en
appuyant sr une des quatre touches de rapport dans le bas de l'cran. Le Tableau 4 dcrit les rapports
du systme disponibles.
Touche de
rapport Rapport Paramtres de rapport
46
Configuration du TLS2 Rapports dinventaire
Rapports dinventaire
37.3 F
1
5329 GAL
(5413 GAL TC)
2
72 IN
WATER 0.0 IN
1 2 3 4 5 6
Pour consulter le(s) rapport(s) d'inventaire d'un autre rservoir, appuyez sr la touche de rapport d'inventaire pour ce
rservoir dans le bas de l'cran. Pour visualiser le rapport d'inventaire de mouvement du rservoir, appuyez sr la
touche Inventaire de mouvement (Shift Inventory) (lment 1 sr l'cran ci-dessus). Pour visualiser la hauteur de tige
(si active), appuyez sr la touche Tige Delta (Delta Stick) (lment 2 sr l'cran ci-dessus).
T 1:REGULAR UNLEADED
TANK VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP
1 5329 5413 4500 48.8 0.0 37.3
2 5329 5413 4500 48.8 0.0 37.3
T 1:REGULAR UNLEADED
TANK PRODUCT
1 REGULAR UNLEADED VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP
SHIFT 1 STARTING VALUES 8518 8492 1482 76.26 0.0 64.7
ENDING VALUES 8518 8492 1482 76.26 0.0 64.7
DELIVERY VALUE 0
TOTALS 0
SHIFT 2 STARTING VALUES 8518 8492 1482 76.26 0.0 64.7
ENDING VALUES 8518 8492 1482 76.26 0.0 64.7
DELIVERY VALUE 0
TOTALS 0
47
Configuration du TLS2 Ecran Etat dalarme active (Active Alarm Status)
Rapports dalarme
On accde aux rapports d'alarme partir de l'cran Rapports d'alarme active illustr ci-dessus en
appuyant sr les touches de rapports dans le bas de l'cran. Le Tableau 5 dcrit les rapports disponibles.
48
Configuration du TLS2 Rapports dalarme
Si l'on effleure la touche Validation d'alarme (Alarm Ack) (lment 3 la page 5), l'avertisseur sonore
s'teint, mme si l'alarme est toujours active. L'cran Etat de l'alarme affiche l'alarme jusqu' ce qu'elle
soit efface. Lorsqu'une condition d'alarme retourne l'tat normal, l'alarme est retire de la liste des
alarmes actives.
Si aucune alarme n'est active, la DEL du panneau est l'tat Normal (vert continu) et la fentre de
message de l'cran Etat du systme (Home) affiche Toutes les fonctions normales (All Functions
Normal) (lment 2 sr la page 5).
Un avertissement actif Sonde sortie ou Temprature basse empchera tous les niveaux d'alarme
(Produit Max, Dbordement, Produit bas, Livraison ncessaire et Eau haute).
49
Configuration du TLS2 Rapports dalarme
Alarme active
Lorsqu'une alarme devient active, l'avertisseur interne de la console est activ, le relais d'alarme est dclench (si
valid), la DEL du panneau avant est rouge et clignote, et la fentre de message de l'cran (lment 2 sr la page 5)
affiche un message d'alarme. En cas d'alarmes multiples, la fentre de message fera automatiquement dfiler les
alarmes actives. Dans le cas d'une alarme assigne la composition automatique, la console compose le numro et
tablit une connexion avec l'hte distant. L'hte peut alors envoyer des demandes la console afin de dterminer la
raison de l'appel.
Lorsqu'une alarme est active, l'utilisateur peut arrter l'avertisseur sonore et le relais d'alarme en appuyant sr la
touche Alarme (ALARME) (Element 3 la page 5). La DEL du panneau avant restera en tat d'Alarme et l'alarme
restera dans la liste des alarmes actives jusqu' ce que l'alarme retourne l'tat normal. Si l'alarme est inactive mais
non valide, elle restera dans la liste des alarmes et l'avertisseur sonore et le relais d'alarme (si valid) resteront
actifs jusqu' ce qu'elle soit valide.
Pour toutes les alarmes, lorsqu'une situation de dpassement des limites est corrige ou qu'un dispositif dfectueux
est remplac par un dispositif en bon tat, l'alarme est annule automatiquement. Pour annuler une alarme d'chec
de test d'tanchit, un test d'tanchit russi doit tre ralis.
Si la valeur de niveau de produit dpasse la valeur de Produit max, l'alarme de produit max se dclenche. Si
l'alarme est active et que le niveau de produit est infrieur la valeur de Produit max d'au moins 0,005 fois la
capacit du rservoir plein ou 37,8 l [10 gallons] (selon la valeur la plus leve), l'alarme est arrte. Le valeur de
Produit max est exprime en units de volume, la valeur par dfaut tant 0. Si la valeur de Produit max est gale
0 ou la capacit du rservoir plein, l'alarme est arrte. Si un avertissement Temprature de sonde basse est actif,
il stoppe l'alarme.
Alarme de dbordement
Si la valeur du niveau de produit dpasse le seuil d'alarme de dbordement, et si une livraison est en cours,
l'alarme de dbordement se dclench. Lorsque la livraison s'arrte, l'alarme est arrte. La valeur d'alarme
de dbordement est entre sous la forme d'un pourcentage, la valeur par dfaut tant 0%. Une valeur de seuil de
dbordement gale 0% arrte l'alarme. Le seuil d'alarme de dbordement est fond sr la valeur de Produit max.
Si la valeur de Produit max est gale 0, la valeur de dbordement est fonde sr la capacit de volume du
rservoir plein. Si un avertissement Temprature de sonde basse est actif, il arrte l'alarme.
Si la valeur du niveau de produit est infrieure au seuil de produit bas, l'alarme Produit bas se dclenche. Si
l'alarme est active et si le niveau de produit est suprieur au seuil d'au moins 0,005 fois la capacit du rservoir
plein ou 37,8 l [10 gallons] (selon la valeur la plus leve), l'alarme est arrte. La valeur de produit bas est
exprime en units de volume, la valeur par dfaut tant 0. Si la valeur est gale 0, l'alarme est stoppe.
Si un avertissement Temprature de sonde basse est actif, il arrte l'alarme.
50
Configuration du TLS2 Rapports dalarme
Si la hauteur de niveau d'eau dpasse de manire continue le seuil d'Eau haute pendant plus de 3 minutes,
l'avertissement Eau haute est dclench . L'alarme Eau haute ne se dclenchra pas si une livraison est en cours. Si
l'alarme est active et si la hauteur du niveau d'eau est infrieure au seuil d'au moins 5 mm (0,2 pouces), l'alarme
est arrte. La valeur d'eau haute est entre sous la forme d'une hauteur, la valeur par dfaut tant 0. Si cette valeur
est gale 0, l'alarme est arrte. Si un avertissement Temprature de sonde basse est actif, il
stoppe l'alarme.
Si la console n'tablit pas une communication solide avec la sonde, l'alarme Sonde sortie est dclenche.
Si le flotteur d'eau et le flotteur de produit sont trop prs l'un de l'autre pour fournir des donnes de hauteur fiables,
l'alarme de hauteur de carburant invalide se dclenche.
Sonde standard: si la sonde indique une temprature infrieure -20C (-4F), l'avertissement de basse temp-
rature sera dclenche. Si l'alarme est active et si la temprature passe au-dessus de -17,7C (0F), l'alarme
est arrte.
Sonde basse temprature: Alarme -40C (-40F), Annulation -37,7C (-36F). Lorsque l'avertissement de basse
temprature est actif, les alarmes Eau haute, Produit Bas, Produit max, Livraison ncessaire et Dbordement
sont arrtes.
Lorsque le niveau de produit du rservoir descend sous la limite prergle, l'alarme de livraison ncessaire
est dclenche.
Lorsqu'un test d'tanchit brut, priodique ou annuel choue, une alarme de test d'tanchit brut, priodique
ou annuel est dclenche. Pour annuler une alarme d'chec de test d'tanchit, Il faut russir un test dtanchit.
51
Ecrans de diagnostic
1 2 3
4 5 6
RED LED GREEN LED LCD OFF
7 8
52
Configuration du TLS2 Ecran Test touche de dclenchement LCD (LCD Touch Test)
Description
53
Configuration du TLS2 Ecran de dtection de sonde
TANK 1
MAG 01
C000
360.000
1 2 3 4 5 66
Pour consulter les dtections de la sonde d'un autre rservoir, appuyez sr la touche de dtection du rservoir
souhait dans le bas de l'cran.
Les donnes de diagnostic de sonde pour les rservoirs configurs ou pour les rservoirs actifs
sont disponibles sr l'cran de dtection de sonde ci-dessus, dans les rapports imprims, et dans les
commandes de srie. Un rservoir actif se dfinit comme un rservoir qui dispose d'une sonde en
communication avec le systme. Si le rservoir est configur mais non actif, toutes les donnes
vaudront zro et le type sonde ne sera pas reconnu.
Si le logiciel identifie des sondes qui ne peuvent pas mesrer la temprature, les donnes relatives la
temprature seront empches. Pour les sondes qui ne peuvent pas mesrer le niveau de l'eau, les
donnes relatives l'eau seront empches.
54
Index des codes d'tiquette
Le Tableau 6 et le Tableau 7 permettent aux utilisateurs qui ne parlent pas langlais de trouver les traductions
de toutes les tiquettes en anglais utilises dans les crans de configuration du TLS2. Sous chaque tiquette
se trouve un code unique entre crochets, p.ex. [101]. Ces codes sont repris dans les tableaux ci-dessous, avec
mention des crans de configuration de ce manuel qui utilisent cette tiquette.
Code
d'tiquette Etiquette Utilis
55
Configuration du TLS2 Ecran de dtection de sonde
Code
d'tiquette Etiquette Utilis
Code
d'tiquette Etiquette Utilis
56
Configuration du TLS2 Ecran de dtection de sonde
Code
d'tiquette Etiquette Utilis
57
Configuration du TLS2 Ecran de dtection de sonde
Code
d'tiquette Etiquette Utilis
58
ITALIAN
Avviso
Veeder-Root non fornisce alcuna garanzia rispetto alla presente pubblicazione, comprese, ma non in maniera esclusiva, le garanzie
implicite di commerciabilit e di idoneit ad uno scopo particolare.
Veeder-Root non responsabile di eventuali errori presenti o danni accidentali o indiretti derivanti dalla fornitura, dalle prestazioni o
dall'utilizzo della presente pubblicazione.
Veeder-Root si riserva il diritto di modificare le opzioni o le caratteristiche di sistema o le informazioni contenute nella presente
pubblicazione.
Questa pubblicazione contiene informazioni protette da copyright. Tutti i diritti riservati. Nessuna parte della presente pubblicazione pu
essere fotocopiata, riprodotta o tradotta senza il preventivo consenso scritto di Veeder-Root.
Contattare TLS Systems Technical Support per informazioni supplementari relative alla risoluzione dei problemi al numero 055
3094.230.
Introduzione
Requisiti di certificazione delle ditte incaricate dell'installazione ............................. 1
Manuali correlati ...................................................................................................... 1
Simboli relativi alla sicurezza .................................................................................. 2
Avvertimenti relativi di sicurezza ............................................................................. 2
Rispetto delle norme e certificazioni ....................................................................... 3
Console ................................................................................................................... 3
Funzioni di monitoraggio ...................................................................................... 3
Rel di output ....................................................................................................... 3
Funzioni di comunicazione ................................................................................... 3
Indice di riferimento rapido messaggi di allarme ..................................................... 4
iii
Indice
Report
Report di sistema .................................................................................................. 49
Report giacenze .................................................................................................... 50
Esempio di report - Report giacenza con volume TC ......................................... 50
Esempio di report - Report giacenza turno Timed con volume TC ..................... 50
Esempio di report - Report giacenza turno Snapshot ......................................... 51
Note report giacenze .......................................................................................... 51
Esempio di report - Report log giacenza ............................................................ 51
Note report log giacenze..................................................................................... 51
Schermata stato allarmi attivi ................................................................................ 52
Report allarmi ........................................................................................................ 52
Note importanti sugli allarmi ............................................................................... 53
Informazioni sugli Stati Allarme ............................................................................. 54
Allarme attivo ...................................................................................................... 54
Presa d'atto di allarme attivo............................................................................... 54
Ritorno allo stato Normale .................................................................................. 54
Informazioni allarmi in cisterna .............................................................................. 54
Allarme Max Product .......................................................................................... 54
Allarme Overfill ................................................................................................... 54
Allarme Low Product........................................................................................... 54
Allarme High Water............................................................................................. 55
Allarme Probe Out .............................................................................................. 55
Invalid Fuel Height .............................................................................................. 55
Avvertimento Probe Low Temperature ............................................................... 55
Allarme Delivery Needed .................................................................................... 55
Allarme Leak Test ............................................................................................... 55
Schermate diagnostica
Schermata menu test funzionali ............................................................................ 56
Schermata Test LCD Touch Screen ..................................................................... 57
Schermate diagnostica sonda ............................................................................... 58
Esempio di report - Report diagnostica sonda.................................................... 58
Disponibilit di dati sonda ................................................................................... 58
iv
Indice
Tabelle
Tabella 1: Tabella messaggi di allarme ....................................................................... 4
Tabella 2: Coefficienti termici U.S. e Metrici .............................................................. 39
Tabella 3: Calcolo dell'inclinazione della cisterna...................................................... 40
Tabella 4: Report di sistema ...................................................................................... 49
Tabella 5: Report allarmi............................................................................................ 52
Tabella 6: Codici etichette setup cisterna .................................................................. 59
Tabella 7: Codici etichette setup sistema .................................................................. 60
v
Introduzione
Questo manuale descrive il setup e le procedure operative per le seguenti console Touch-Screen:
Veeder-Root TLS2
Gilbarco EMC2
Console TLS2 Underground Storage Tank (UST). Prevede che il vostro sistema sia gi stato installato da un
Certified Contractor. Questo manuale prevede che la console sia stata installata e che sia stata completata con
successo la procedura di Cold Boot. La procedura di setup inizia con le schermate di setup del sistema e termina
con le schermate di setup della cisterna.
Dopo aver immesso i parametri di setup del sistema e della cisterna, la console dovrebbe essere operativa.
Consultare la sezione Report per istruzioni sulla visualizzazione dei report sul sistema e sugli allarmi. La sezione
Diagnostica contiene alcune semplici procedure di test della console e di accesso ai dati di diagnostica della sonda.
Veeder-Root richiede almeno le seguenti certificazioni di addestramento per le ditte che installeranno e
eseguiranno il setup delle apparecchiature descritte nel manuale:
Livello 1 Le ditte che detengono la certificazione di Livello 1 hanno l'approvazione per eseguire la posa dei
condotti, il montaggio delle apparecchiature, l'installazione delle sonde e dei sensori, la preparazione delle
tubazioni e delle cisterne e l'installazione di rilevatori di perdite sulle linee.
Livello 2/3 Le ditte che detengono la certificazione di Livello 2 o 3 hanno lapprovazione per eseguire la verifica,
l'avvio, la programmazione e l'addestramento operativo relativo all'installazione, la ricerca guasti e la
manutenzione per tutti i Sistemi di monitoraggio cisterne di Veeder-Root, inclusi il rilevamento delle perdite sulle
tubazioni e i relativi accessori.
Manuali correlati
1
Setup TLS2
In questo manuale sono utilizzati i seguenti simboli per indicare gravi pericoli e importanti precauzioni di
sicurezza.
ESPLOSIVO INFIAMMABILE
I carburanti e i loro vapori sono I carburanti e i loro vapori sono
estremamente esplosivi se vengono estremamente infiammabili.
sottoposti all'azione del fuoco.
ATTENZIONE
Questo sistema opera vicino a cisterne di carburante estremamente
infiammabile.
Cisterne con perdite possono creare gravi pericoli all'ambiente e alla salute.
Anche una programmazione e un utilizzo non corretto possono provocare il
mancato superamento delle procedure di auto-test delle apparecchiature e
l'arresto delle pompe sommergibili.
2
Setup TLS2
Pianificare il programma di rilevamento delle perdite in modo da rispettare le norme applicabili relative alle
cisterne interrate. Nell'ambito del programma di rispetto delle norme, conservare tutti i report relativi alle giacenze
e ai test di tenuta forniti dal sistema.
Il sistema, quando munito di sonde magnestrittive (Mag 2) da 0,2 galloni all'ora (gph) (0,76 lph), classificato
come Automatic Tank Gauge System ed stato testato dal Midwest Research Institute. Questo sistema pu
rilevare una perdita di 0,2 gph con una precisione superiore al 95% e con una probabilit di falso allarme inferiore
al 5%. Soddisfa gli standard prestazionali federali statunitensi E.P.A. (0,2 gph con precisione del 95% e probabilit
di errore del 5%) e gli standard prestazionali federali di misurazione dell'acqua sul fondo di una cisterna al pi
vicino 1/8 di pollice (3,2 mm).
Il sistema, quando munito di sonde magnestrittive (Mag 1) da 0,1 galloni all'ora (gph) (0,38 lph), soddisfa gli
standard Volumetric Tank Tightness Testing Method ed stato testato dal Midwest Research Institute. Questo
sistema pu rilevare una perdita di 0.1 gph con una precisione superiore al 95% e con una probabilit di falso
allarme inferiore al 1%. Questo sistema soddisfa gli standard U.S. E.P.A. (0,1 gph con una precisione del 95% e
con una probabilit di falso allarme del 5%).
Console
La console TLS2 munita di display touch screen sul pannello frontale, un LED a doppia funzione Allarme/
Normale, ed un segnale acustico in caso di allarmi. Sono disponibili porte per stampanti seriale e parallele. La
console TLS2 pu monitorare sino a sei sonde magnetostrittive.
Funzioni di monitoraggio
Rel di output
Viene fornito un rel di output in grado di attivare sistemi di allarme esterni quando il sistema rileva una situazione
di allarme.
Funzioni di comunicazione
RS-422
RS-485, 2 o 4 fili
3
Setup TLS2 Indice di riferimento rapido messaggi di allarme
Annual Test Fail Cisterna Test annuale tenuta cisterna non Eseguire nuovamente il test di tenuta
superato cisterna. Se anche il secondo test non
viene superato, chiamare l'assistenza.
Autodial Fail Comm Il sistema non stato in grado di Controllare il ricevitore remoto.
collegarsi ad un ricevitore remoto
dopo il numero programmato di
tentativi.
Delivery Needed Cisterna Il livello del prodotto sceso sotto al Chiedere erogazione.
limite impostato.
Gross Test Fail Cisterna Test tenuta cisterna non superato Eseguire nuovamente il test di tenuta
cisterna. Se anche il secondo test non
viene superato, chiamare l'assistenza.
High Water Cisterna Il livello dell'acqua rilevato nella Rimuovere l'acqua dalla cisterna.
cisterna supera il limite impostato.
Invalid Fuel Height Cisterna Il livello del carburante sceso sotto Chiedere erogazione.
al livello minimo rilevabile o
presente un solo galleggiante.
Low Product Cisterna Il livello del prodotto nella cisterna Chiedere erogazione.
sceso sotto al limite impostato.
Low Temperature Cisterna La temperatura della sonda scesa La sonda ritorna alla normale operativit
sotto i -4F (-20C). Per sonde Low dopo che la temperatura della sonda
Temperature, sotto a -40F (-40C). supera 0F.
(-17,7C). Per sonde Low Temperature,
sotto a -36F (-38C).
Max Product Cisterna Il livello del prodotto salito sopra al Arrestare l'erogazione.
limite impostato.
Periodic Test Fail Cisterna Test tenuta cisterna non superato Eseguire nuovamente il test di tenuta
cisterna. Se anche il secondo test non
viene superato, chiamare l'assistenza.
4
Schermate setup sistema
Questa sezione descrive tutte le schermate di setup del sistema TLS2 oltre alle opzioni e alle spiegazioni necessarie per
l'immissione dei dati. Poich le etichette delle schermate di setup della TLS2 dispongono di etichette solo in inglese, sono
state inserite tra parentesi dei codici sotto ogni etichetta in modo che possiate trovare velocemente una traduzione
dell'etichetta e il numero di pagina della schermata in cui l'etichetta viene usata. Le schermate di setup della cisterna sono
trattate in una sezione separata.
L'immissione dei dati, la conferma delle selezioni, ecc. viene effettuata attraverso diverse schermate di immissione dati che
appaiono quanto vengono premuti i pulsanti a destra della casella di immissione dati. Queste schermate sono descritte dove
vengono trattate per la prima volta in questa sezione.
1 2 3 4
11
5
10
12
9 8 7 6
1
Legenda box numerati 6 Pulsante Environmental Report - premere per
1 Finestra data/ora - visualizza la data/ora corrente visualizzare i risultati del test di tenuta cisterna (pagina
2 Finestra messaggi - visualizza All Functions Normal o gli 49).
allarmi attivi. 7 Pulsante Alarm Report - premere per visualizzare le
3 Pulsante Alarm - premere per prendere atto dell'allarme schermate Active Alarm Status (e History) (pagina 52).
e arrestare il segnale acustico di allarme. Nota: 8 Pulsante Delivery Report - premere per visualizzare la
premendo questo pulsante l'allarme non viene schermata Report erogazione (pagina 49).
cancellato - il problema che ha causato l'allarme deve 9 Pulsante Inventory Report - premere per visualizzare la
essere risolto. schermata Report Giacenze (pagina 50).
4 Pulsante Print - Per le schermate dei menu, premere 10 Pulsanti Tank - premere per visualizzare il report relativo
questo pulsante e tutte le voci presenti nel menu alla giacenza corrente per la specifica cisterna.
verranno stampate sulla stampante collegata. Solo per 11 Finestra titolo schermata.
schermate che non contengono menu, quando si preme 12 Pulsante Manual Shift Close - premere per chiudere
il pulsante di stampa appare una finestra di dialogo manualmente il turno. (visibile solo se selezionato
relativa alla stampa. L'utente ha la possibilit di Snapshot in Shift Time (System Setup) come Shift
annullare la stampa. Close Method.
5 Pulsante Main Menu - premere per visualizzare la
schermata Menu principale (pagina 6) per l'accesso al
setup del sistema/cisterna e al test manuale delle
cisterne.
5
Setup TLS2 Schermata Menu principale
1 4
2 5
II
3 6
ABOUT
consoles/tls2/menuscrn.eps
6
Setup TLS2 Schermata setup sistema
2 3 4
1
6 7
5
8
10 11 12
1 Pulsante Language - premere per visualizzare la 7 Pulsante Dialing Setup - premere per visualizzare la
schermata Setup Lingua e Unit (pagina 8) schermata Setup Dial Out Sistema (pagina 19).
2 Pulsante Current Time - premere per visualizzare la 8 Pulsante Temp - premere per visualizzare la
schermata Setup Ora/Data (pagina 13). schermata Setup Temperatura (pagina 32).
3 Pulsante Comm - premere per visualizzare la 9 Pulsante Security - premere per visualizzare la
schermata Setup Comm (pagina 24). schermata Setup Sicurezza Sistema (pagina 12).
4 Pulsante Alarm Relay - premere per visualizzare la 10 Pulsante Daylight Savings - premere per visualizzare
schermata Setup Rel Allarme (pagina 31). la schermata Setup Date Ora Legale (pagina 18).
5 Pulsante Header - premere per visualizzare la 11 Pulsante Autodial Alarms - premere per visualizzare
schermata Setup Testata Stazione (pagina 9). la schermata Setup Allarmi Autodial (pagina 20).
6 Pulsante Shift Time - premere per selezionare la 12 Pulsante EuroProtocol - premere per visualizzare la
schermata Setup Orari Turni (pagina 17) o Manual schermata Setup Europrotocollo e Stick Offset
Shift Close. (pagina 33). Questa schermata consente inoltre di
selezionare un formato di report test tenuta.
7
Setup TLS2 Schermata Setup Lingua e Unit Sistema [201-203, 240]
1
[201]
2
[202]
3
[203]
8
Setup TLS2 Schermata Setup Testata Stazione [204 - 207]
1
[204]
2
[205]
3
[206]
4
[207]
9
Setup TLS2 Schermata Tastierino Alfabetico
10
4 SAVE
5 6 7 8 9
1 Visualizza il titolo dei dati da inserire. 6 Pulsante Cursore a sinistra - premere per spostare il
2 La casella Dati immessi visualizza i dati immessi. cursore a sinistra di una posizione nella Casella dati
immessi (2).
3 Pulsanti tastierino alfabetico - premere il pulsante
relativo ad un carattere per posizionare tale carattere 7 Pulsante Cursore a destra - premere per spostare il
nella casella dati immessi (2). cursore a destra di una posizione nella Casella dati
immessi (2).
4 Pulsante Save - premere per accettare i dati immessi
e chiudere la schermata. 8 Pulsante di cancellazione Backspace - premere per
cancellare il carattere sopra al cursore.
5 Pulsante Cancel - premere per annullare qualsiasi
immissione effettuata e chiudere la schermata. 9 Pulsante tastierino numerico - premere per
visualizzare la schermata Tastierino Numerico.
10 Pulsante Clear - premere per cancellare il contenuto
della casella Dati immessi (2).
10
Setup TLS2 Schermata Tastierino Numerico
10
4 SAVE 9
5 6 7 8
1 Visualizza il titolo dei dati da inserire. 7 Pulsante Cursore a destra - premere per spostare il
2 La casella Dati immessi visualizza i dati immessi. cursore a destra di una posizione nella Casella dati
immessi (2).
3 Pulsante tastierino numerico - premere il pulsante
relativo ad un numero o carattere per posizionarlo nella 8 Pulsante di cancellazione Backspace - premere per
casella dati immessi (2). cancellare il carattere sopra al cursore.
4 Pulsante Save - premere per accettare i dati immessi e 9 Pulsante tastierino alfabetico - premere per visualizzare
chiudere la schermata. la schermata Tastierino Alfabetico.
5 Pulsante Cancel - premere per annullare qualsiasi 10 Pulsante Clear - premere per cancellare il contenuto
immissione effettuata e chiudere la schermata. della casella Dati immessi (2).
6 Pulsante Cursore a sinistra - premere per spostare il
cursore a sinistra di una posizione nella Casella dati
immessi (2).
11
Setup TLS2 Schermata Setup Sicurezza Sistema [208-211]
1 COMM 1 PASSWORD
[208]
2 COMM 1 PASSWORD
[209]
3 COMM 2 PASSWORD
[210]
4 COMM 2 PASSWORD
[211]
12
Setup TLS2 Schermata Setup Data/Ora Sistema [212-214]
1 10-04-01
[212]
2
[213] 13-54
13
Setup TLS2 Schermata Immissione Data Corrente
1 2001 3
14
Setup TLS2 Schermata Immissione Ora Corrente
1 3
15
Setup TLS2 Schermata Setup Sistema Orari di chiusura [500-503]
Questa schermata consente di selezionare orari giacenza che verr inserita nell'Inventory Log.
Chiusura Turno Auto (Timed) o Manuale (Snapshot). Il valore predefinito 00:00 (mezzanotte).
L'impostazione di default Timed (chiusura a tempo). 4 Inventory Log Interval [503] - Le registrazioni di
1 Shift Close Method [500] - premere il pulsante Select Inventory Log verranno automaticamente effettuate
a destra della casella e selezionare il metodo di dal sistema agli intervalli selezionati in questo campo.
chiusura del turno Timed (Auto) o Snapshot Premere il pulsante freccia gi a destra della casella
(Manual). Il valore di default Timed. e selezionare l'intervallo.
2 Shift Close Timeout [501] - Abilitato solo se stato Intervalli consentiti: 1 ora, 2 ore, 3 ore, 4 ore, 6 ore, 8
selezionato il metodo chiusura turno Snapshot. ore, 12 ore, 24 ore, 5 minuti, 10 minuti, 15 minuti, 20
Premere il pulsante numerico a destra della casella minuti o 30 minuti.
ed immettere il Timeout. Il valore predefinito 1 ora.
Quando scade il periodo di timeout iniziato dall'ultimo
turno cisterna chiuso, qualsiasi turno cisterna non Ad esempio, selezionando un Inventory Log Time
aperto verr automaticamente chiuso. (voce 3) di 00:00 (mezzanotte) ed un intervallo
Ad esempio, Shift Close Timeout impostato a 30. Si Inventory Log di 30 minuti (voce 4), il sistema
seleziona chiusura manuale turno su cisterna 3. 30 effettuer delle istantanee della giacenza alle 00.00
minuti dopo, il turno viene chiuso per le rimanenti (mezzanotte), 00.30, 1.00, 1.30, ecc.. Il numero
cisterne, il numero dei turni viene incrementato e massimo di registrazioni nell'Inventory Log 72.
viene creato un report dei turni. Se il sistema Inventory Log un log a rotazione (il primo ad
impostato su autodial su Shift Close Event, al entrare il primo ad uscire) di un massimo di 72
ricevitore autodial assegnato verr inviata la notifica. registrazioni.
Selezioni consentite di Timeout: da 30 a 60 minuti.
L'impostazione predefinita 30 minuti.
3 Inventory Log Time [502] - Premere il pulsante
orologio per selezionare l'orario di inizio in un periodo
di 24 ore in cui desiderate registrare la prima
16
Setup TLS2 Schermata Setup Orari Turni [215-218]
1
[215]
2
[216]
3
[217]
4
[218]
La schermata Shift Times Setup visibile solo se 8 Shift 4 [218] - premere il pulsante a destra della
selezionato Timed come Shift Close Method nella casella e immettere l'orario di inizio Shift 4 e AM o
schermata System Setup Close Times (pagina 16). Ad PM.
ogni orario di cambio turno selezionato, il sistema
automaticamente salva in memoria un report completo di
giacenza. L'impostazione predefinita disabilitato per
tutti i turni.
NOTA: deve essere immesso almeno un orario di inizio
turno per attivare la funzione "Last Shift Inventory".
5 Shift 1 [215] - premere il pulsante a destra della
casella e immettere l'orario di inizio Shift 1 e AM o
PM.
6 Shift 2 [216] - premere il pulsante a destra della
casella e immettere l'orario di inizio Shift 2 e AM o
PM.
7 Shift 3 [217] - premere il pulsante a destra della
casella e immettere l'orario di inizio Shift 3 e AM o
PM.
17
Setup TLS2 Schermata Setup Ora Legale [219-223]
1 ENABLE
[219]
2 MAR WEEK 2 SUN
[220]
3
[221] 2:00 AM
Questa funzione consente di immettere la data e l'ora di 3 Start Time [221] - premere il pulsante Time a destra
inizio e termine del periodo in cui in vigore l'ora legale. della casella e immettere l'orario di inizio [e AM o PM]
Una volta abilitato, il sistema si adeguer (valore predefinito: 02:00 AM).
automaticamente all'ora legale alle date ed orari 4 End Date [222] - premere il pulsante Date a destra
immessi. della casella e immettere la data finale (data
1 Daylight Savings [219] - premere il pulsante freccia a predefinita: OCT WEEK 6 SUN).
destra della casella e selezionare Enable o Disable 5 End Time [223] - premere il pulsante Time a destra
(valore predefinito: Disable). della casella e immettere l'orario di termine [e AM o
2 Start Date [220] - premere il pulsante Date a destra PM] (valore predefinito: 02:00 AM).
della casella e immettere la data iniziale (data
predefinita: APR WEEK 1 SUN).
18
Setup TLS2 Schermata Setup Auto-Dialout [224-226, 321]
1 PHONE
[224]
2 RETRIES
[225]
3 RETRY DELAY
[226]
Questa funzione richiede che sia selezionato Modem 4 Autodial Confirm [321] - premere il pulsante Freccia
come Comm Type. Gi per selezionare On o Off.
1 Phone [224] - premere il pulsante Numerico a destra
della casella e immettere un numero di telefono che
verr composto dal sistema.
2 Retries [225] - premere il pulsante Numerico a destra
della casella e immettere il numero di volte (1-99) che
il sistema prover a comporre il numero di telefono in
caso di occupato, nessuna risposta, o connessione
incompleta (valore predefinito: 3 tentativi).
3 Retry Delay [226] - premere il pulsante Numerico a
destra della casella e immettere il numero di minuti
(1-99) che il sistema attender prima di ricomporre il
numero di telefono in caso di occupato, nessuna
risposta, o connessione incompleta (valore
predefinito: 3 minuti).
19
Setup TLS2 Schermata 1 Setup Autodial Allarme [227-230]
1
[227]
2
[228]
3
[229]
4
[230]
5
1 2 3 4 5 6
20
Setup TLS2 Schermata 2 Setup Autodial Allarme [231-234]
1
[231]
2 6
[232]
3
[233] 7
4
[234] 8
11 22 33 4
4 5
5 6
6
21
Setup TLS2 Schermata 3 Setup Autodial Allarme [235-237, 320]
1
[235]
2
[236]
3
[237]
4 DELIVERY COMPLETED OFF
[320]
11 22 33 4
4 5
5 6
6
22
Setup TLS2 Schermata 4 Setup Autodial Allarme [550]
11 22 33 4
4 5
5 6
6
23
Setup TLS2 Schermata 1 Setup Comm Port 1 e 2 Seriale [238-239]
1
[238]
2
[239]
3 4 5 6
Questa schermata simile per il setup delle porte Comm 5 Pulsante PARALLEL - premere per visualizzare la
1 e Comm 2. schermata Setup porta parallela (pagina 30).
1 Comm Type [238] - premere il pulsante Freccia Gi a 6 Pulsante Gi - premere per visualizzare la schermata
destra della casella e selezionare: 2 Setup Porta Comm (pagina 27).
Se Comm 1 -
Serial, Modem, Printer, o None (valore predefinito)
Se Comm 2 -
Serial o None (valore predefinito)
2 Handshaking [239] - premere il pulsante Freccia Gi
a destra della casella e selezionare None, XON/
XOFF, o Hardware (valore predefinito): Questo
parametro identico per Comm 1 e Comm 2.
3 Pulsante COMM 1 - premere per visualizzare la
schermata Setup Comm 1 (mostrata sopra).
4 Pulsante COMM 2 - premere per visualizzare la
schermata Setup Comm 2.
24
Setup TLS2 Schermata Setup Porta Comm 1 Stampante [241]
[238]
1
[241] 9
[239]
2 PRINTER LANG EPSON ESC/P
[253] 3
25
Setup TLS2 Schermata Setup Porta Comm 1 Modem [244-246]
[238]
2
[244]
3
[245]
4 5
[246]
26
Setup TLS2 Schermata 2 Setup Porta Comm [249-252]
1 9600
[249]
2 ODD
[250]
3 7
[251]
4
[252]
27
Setup TLS2 Schermata Setup Avanzato Comunicazioni [247-248]
1 DIAL IN AT&B1
[247]
2 AT&B1
[248]
ATTENZIONE!
L'immissione di una stringa con numeri errati
potrebbe disabilitare il modem.
28
Setup TLS2 Schermata Immissione Dati
1
[249]
2 SAVE 3
29
Setup TLS2 Schermata Setup Porta Parallela
1 COMM TYPE
[238]
2 PAGE EJECT
[238]
9
3 PRINTER LANG EPSON ESC/P
[253]
30
Setup TLS2 Schermata Setup Rel Allarme [256]
1
[256]
31
Setup TLS2 Schermata Setup Temperatura [257-258]
1 59 F
[257]
2
[258]
32
Setup TLS2 Schermata EuroProtocollo e Stick Offset [259-262]
1
[259]
2
[260]
3
[261]
4
[262]
33
Setup TLS2 Schermata Informazioni su TLS2
ABOUT
SYSTEM FEATURES
STATIC TANK LEAK DETECT
Questa schermata elenca le informazioni sul software e le funzionalit della Console TLS2:
Livello revisione software di sistema
Numero versione software
Numero parte del software
Data di creazione del software
Funzionalit del sistema: Rilevamento tenuta statica cisterna
34
Schermate setup cisterna
1 2
35
Setup TLS2 Schermata 1 Setup Cisterna [119-121]
TANK 1
1 CONFIGURED
[119]
2
[120]
3
[121]
1 2 3 4 5 6
36
Setup TLS2 Schermata 2 Setup Cisterna [122-124]
TANK 1
1
[122]
2
[123]
3
[124]
1 2 3 4 5 6
37
Setup TLS2 Schermata 3 Setup Cisterna [125-128]
TANK 1
1
[125] 0.00070
2
[126] 0 IN
3
[127]
4
[128]
1 2 3 4 5 6
Questa schermata conclude il setup delle cisterne presentate, immettere la dimensione del galleggiante
1 Thermal Coefficient [125] - premere il pulsante Freccia Gi della sonda Mag installato sulla sonda della cisterna.
a destra della casella e immettere il diametro della 4 Stick Offset [128] - premere il pulsante Freccia Gi a
cisterna. destra della casella e selezionare un valore per Stick
Per assicurare conversioni accurate del volume Offset. L'intervallo consentito da -144 a +144 pollici (da
compensate per temperatura, il coefficiente termico di -365,76 a +365,76 cm) e il valore predefinito 0.
espansione del prodotto deve essere immesso Note: Per immettere un valore di Stick Offset, l'opzione
correttamente. Un valore errato avrebbe un effetto Stick Offset deve essere stata abilitata (pagina 33), e
negativo sui test di rilevazione della tenuta e sui valori di deve essere stato calcolata e immessa l'inclinazione
giacenza compensati per temperatura. della cisterna (se necessaria). possibile immettere uno
Tabella 2 elenca i coefficienti U.S. e Metrici per i carburanti Stick Offset in modo che l'altezza della sonda (prodotto)
e i liquidi approvati. Immettere il coefficiente in unit U.S. o "appaia" essere uguale a una lettura tramite indicatore di
Metriche, a seconda delle unit specificate in Setup livello dell'altezza del prodotto - Questa voce presente
Sistema (pagina 8). Fare attenzione ad aggiungere il solo per comodit dell'operatore, e non ha effetti sui
numero corretto di zeri a destra del punto decimale. calcoli del volume del prodotto.
Un immissione non corretta pu causare errori nel test Per determinare il valore da immettere per Stick Offset,
e altri problemi. annotare la lettura dell'altezza della sonda e annotare
2 Tank Tilt [126] - premere il pulsante Freccia Gi a destra una lettura tramite indicatore di livello della cisterna. Se
della casella e immettere l'inclinazione della cisterna. la lettura dell'altezza del carburante della sonda
L'intervallo consentito da -144 a +144 pollici (da -365,76 inferiore a quella dell'indicatore di livello, immettere la
a +365,76 cm) e il valore predefinito 0. differenza positiva tra i due. Se la lettura della sonda
superiore a quella dell'indicatore di livello, immettere la
Tank Tilt consente di compensare la differenza tra l'altezza differenza negativa tra i due. Ad esempio, se altezza
del carburante presso la posizione della sonda e l'altezza indicatore = 52 altezza sonda = 48, immettere +4; se
del carburante al centro della cisterna causata altezza indicatore = 52 e altezza sonda = 54, immettere -
dall'inclinazione della cisterna. Immettere un meno (-) se 2.
l'inclinazione della cisterna negativa. Un valore di Tank
Tilt non richiesto se la sonda si trova al centro della
cisterna. Se la sonda si trova al centro della cisterna, il
valore immesso 000,00 unit U.S o 0000,0 unit
Metriche. Se la sonda non al centro della cisterna,
calcolare l'inclinazione della cisterna usando le indicazioni
in Tabella 3. Immettere il valore presente nella Colonna G
in Tank Tilt.
3 Float Size [127] - premere il pulsante Freccia Gi a destra
della casella e dalle dimensioni del galleggiante
38
Setup TLS2 Schermata 3 Setup Cisterna [125-128]
Coefficiente
Coefficiente
termico
termico
(Unit
(Unit U.S.)
Prodotti metriche)
39
Setup TLS2 Schermata 3 Setup Cisterna [125-128]
Usare la tabella seguente per annotare le misure e calcolare l'inclinazione delle cisterne.
1. Misurare la cisterna all'apertura del montante di riempimento almeno tre volte. Annotare la lettura media nella
colonna A della tabella.
2. Prima di iniziare, accertarsi che Tank Tilt [126] sulla schermata sia = 0. Annotare l'altezza carburante misurata dalla
sonda (Funzione giacenza cisterna) nella colonna B della tabella.
3. Sottrarre il valore immesso in colonna B dal valore immesso in colonna A. Annotare il risultato in colonna C.
4. Misurare la distanza in pollici (o millimetri se usate unit Metriche) tra la sonda e i montanti di riempimento. Annotare
la misura in colonna D.
5. Dividere il valore in colonna C per colonna D per determinare l'inclinazione. Annotare i risultati in colonna E.
6. Misurare la distanza in pollici o millimetri dal montante della sonda al centro della cisterna. Annotare la distanza in
colonna F.
7. Moltiplicare la colonna E per la colonna F per determinare l'inclinazione della cisterna (E X F = valore inclinazione
cisterna). Annotare il valore in colonna G.
A B C D E F G
6
*L'inclinazione della cisterna pu essere un valore positivo (+) o negativo (-). Se un valore negativo, ACCERTARSI di
cambiare il simbolo in meno (-) immettendo il valore in Tank Tilt.
40
Setup TLS2 Schermata 1 Setup Limiti Cisterna [101-104]
1
[101]
2
[102]
3
[103]
4
[104]
1 2 3 4 5 6
Questa schermata inizia il setup dei limiti allarme cisterna. Freccia Gi a destra della casella e immettere un
1 Max Product [101] - Viene generato un allarme quando volume superiore a quello dell'allarme Low Product.
il livello del fluido nella cisterna supera il volume 4 Low Product [104] - Low Product avverte quando il
immesso qui. L'intervallo consentito da 0 a 26000 volume nella cisterna si abbassa al livello inserito qui.
galloni (0-98420 L). Il valore predefinito 0. Se il valore L'intervallo consentito da 0 a 26000 galloni (0-98420
immesso 0 o volume intero, questo allarme L). L'impostazione predefinita 0 (che disabilita
disabilitato. Un Avvertimento Bassa Temperatura l'allarme). Un Avvertimento Bassa Temperatura
Sonda attivo disabilita questo allarme. Premere il Sonda attivo disabilita questo allarme. Premere il
pulsante Freccia Gi a destra della casella e immettere pulsante Freccia Gi a destra della casella e
la quantit massima di prodotto per la cisterna. immettere questo valore ad un volume inferiore a
2 Overfill [102] - Il limite di riempimento eccessivo avverte quello dell'allarme Delivery Needed.
di un potenziale riempimento eccessivo durante NOTA: Tipicamente questo allarme impostato al
l'erogazione. Quando il volume raggiunge questo limite, livello pi basso prima che la pompa rimanga a secco.
il sistema pu attivare un allarme di riempimento Qualsiasi erogazione deve interrompersi quando
eccessivo. La soglia di allarme riempimento eccessivo questo allarme attivo.
fa riferimento al valore di Max Product. Se il valore di Il setup Limite Allarme Cisterna continua alla pagina
Max Product 0, la soglia di Overfill Alarm fa successiva.
riferimento alla capacit Full Volume. L'intervallo di
valori consentito va da 0 a 100%. L'impostazione
predefinita 0 (disabilitato). Un Avvertimento Bassa
Temperatura Sonda attivo disabilita questo allarme.
3 Delivery Needed [103] - Delivery Needed avverte
quando il livello di fluido nella cisterna scende ad un
livello per cui l'operatore richiede una erogazione.
Questo valore una percentuale di Full Volume con un
intervallo consentito da 0 a 100%. Il valore predefinito
0% (che disabilita l'allarme). Premere il pulsante
41
Setup TLS2 Schermata 2 Setup Limiti Cisterna [105-108]
1
[105]
2
[106]
3
[107]
4
[108]
1 2 3 4 5 6
Questa schermata continua il setup dei limiti allarme L'impostazione predefinita 0 (che disabilita
cisterna. l'allarme). Premere il pulsante Freccia Gi a destra
1 High Water [105] - Viene generato un allarme quando il della casella e immettere un volume.
livello dell'acqua nella cisterna supera l'altezza 4 Per Leak Test Min [108] - Questo valore imposta il
immessa qui. Impostare questo valore ad un livello volume minimo della cisterna richiesto per superare
inferiore a quello di aspirazione per la pompa un test periodico di tenuta. Il valore riflette le norme
sommergibile o linea di aspirazione. L'intervallo di valori applicabili. Questo valore una percentuale di Full
consentito va da 0 a 228,6 mm. (da 0 a 9 pollici). Volume con un intervallo consentito da 1,0 a 100%.
L'impostazione predefinita 0 (che disabilita l'allarme). L'impostazione predefinita 0 (che disabilita
Premere il pulsante Freccia Gi a destra della casella e l'allarme). Premere il pulsante Freccia Gi a destra
immettere il limite massimo di High Water desiderato. della casella e immettere un volume.
2 Delivery Delay [106] - Consente di impostare un ritardo Il setup Limite Allarme Cisterna continua alla pagina
tra il completamento di una erogazione e il Delivery successiva.
Increase Report. Questa funzione evita la generazione
di molteplici report durante gli intervalli tra erogazioni
multi-compartimento in una cisterna. Questa funzione
consente inoltre l'assestamento dopo un'erogazione,
particolarmente importante in gruppi di cisterne
collegate. Il ritardo consentito tra 1 e 60 minuti. Il
valore predefinito 1. Premere il pulsante Freccia Gi a
destra della casella e immettere il ritardo desiderato.
3 Per Leak Test Min [107] - Questo valore imposta il
volume minimo della cisterna richiesto per superare un
test annuale di tenuta. Il valore riflette le norme
applicabili. Questo valore una percentuale di Full
Volume con un intervallo consentito da 1,0 a 100%.
42
Setup TLS2 Schermata 3 Setup Limiti Cisterna [109-111]
1
[109]
2
[110]
3
[111]
1 2 3 4 5 6
43
Setup TLS2 Schermata 1 Setup Test Tenuta Cisterna [112-114]
1 0.2 GPH
[112]
2 EARLY STOP
[113]
3
[114]
1 2 3 4 5 6
Setup test tenuta cisterna consente di stabilire e immettere Premere il pulsante Freccia Gi a destra della casella
il metodo, i tempi, e la durata dei test automatici di tenuta. e selezionare il valore desiderato.
Per effettuare i test di tenuta deve essere installata una 3 Test Duration [114] - La durata massima 24 ore. La
sonda Mag 1 o 2. durata minima per test 0,2 gph (0,76 lph) di 2 ore e
Se si usa la funzione In-Tank Leak Test per il rispetto delle per test 0,1 gph (0,38 lph) di 3 ore.
norme relative alle cisterne, accertarsi che i limiti dei test di Nota: Se Early Stop abilitato e la console determina
tenuta stabiliti e immessi soddisfino i requisiti in termini di che un Test Tenuta Cisterna stato superato, il test
tipo, precisione e frequenza dei test definiti dalle norme viene completato prima che la durata sia trascorsa. La
applicabili. durata predefinita di 2 ore. Premere il pulsante
Inoltre, impostare l'orario del test quando non sono previste Freccia Gi a destra della casella e selezionare il
erogazioni. Tale attivit renderebbe inaffidabili i risultati del valore desiderato.
test.
4 Pulsante Same All Tank - Premere questo pulsante
1 Test Rate [112] - possibile impostare Test Rate a 0.2 per trasferire selezioni identiche effettuate in questa
gph (0,76 lph) (valore predefinito) o 0.1 gph (0,38 lph). schermata in relazione alla cisterna 1 a tutte le
La selezione di 0.1 gph (0,38 lph) richiede una sonda cisterne (apre la schermata di conferma Same All
Mag 1. Premere il pulsante Freccia Gi a destra della Tanks a pagina 45).
casella e selezionare il valore desiderato. Il setup di Test Tenuta Cisterna si conclude a pagina 46.
2 Early Stop [113] - L'impostazione predefinita
Disabled. Quando questa funzione abilitata, un Test
Tenuta Cisterna non si avvier nei seguenti casi:
Il volume della cisterna inferiore al valore di Leak
Min Periodic o di Leak Min Annual.
Sono passate meno di 8 ore da un'erogazione.
La temperatura del prodotto inferiore a 0F (-
17,6C) o superiore a +100F (+37,4C).
Il carburante nella cisterna insufficiente.
44
Setup TLS2 Schermata Same All Tanks [115]
1
[115]
2 SAVE 3
45
Setup TLS2 Schermata 2 Setup Test Tenuta Cisterna [116-118]
TANK 1
1
[116]
2 DATE/DAY
[117]
3
[118]
1 2 3 4 5 6
46
Chiusura manuale di un turno
TANK VOLUME HEIGHT WATER WVOL TANK VOLUME HEIGHT WATER WVOL
1 17508 1229 25 500 1 17508 1229 25 500
2 14993 966 0 0
3 9843 771 0 0
4 10844 801 0 0
5 4844 900 0 0
6 9843 775 0 0
OK CANCEL OK CANCEL
3 4 3 4
47
Avvio/arresto manuale dei test di tenuta cisterna
Usare questa schermata per avviare o arrestare manualmente un test tenuta cisterna.
1
[129]
2 5
[130]
3 0.76 LPH 6
[112]
4
[114]
1 2 3 4 5 6
5 Test Method [129] - Selezionare Single Tank o All Freccia Gi a destra della casella e
Tanks. Premere il pulsante Freccia Gi a destra della selezionare il valore desiderato.
casella e selezionare il valore desiderato. 9 Pulsante Test Start - premere questo
6 Test Control [130] - Selezionare Timed Duration o pulsante per iniziare il test.
Manual Stop (il test continua fino a quando viene 10 Pulsante Test Stop - Premere questo
arrestato, o per 24 ore, se non viene arrestato prima). pulsante per arrestare un test tenuta
Premere il pulsante Freccia Gi a destra della casella cisterna.
e selezionare il valore desiderato.
7 Test Rate [112] - Selezionare 0.2 gph (0,76 lph)
(valore predefinito) o 0.1 gph (0,38 lph). La selezione
di 0.1 gph (0,38 lph) richiede una sonda Mag 1.
Premere il pulsante Freccia Gi a destra della casella
e selezionare il valore desiderato.
8 Test Duration [114] - Selezionare una durata massima
da 0 a 24 ore. La durata minima per test 0,2 gph (0,76
lph) di 2 ore e per test 0,1 gph (0,38 lph) di 3 ore.
L'impostazione predefinita 2 ore.
Nota: questa finestra appare solo se si seleziona
Timed Duration in Test Control. Premere il pulsante
48
Report
Report di sistema
possibile accedere ai report di sistema dalla schermata Stato Sistema (Home) (vedere pagina 5)
premendo uno dei 4 pulsanti relativi ai report nella parte inferiore della schermata. Tabella 4 descrive i
report di sistema disponibili.
CURRENT TEST
RESULTS RISULTATI TEST CORRENTE
Test Type, Start Date/Time, Test Result, Hours
Premere il pulsante Risultati Test Run, %Volume in Tank at Time of Test
Corrente per visualizzare i risultati
degli ultimi test Annual, Periodic, e
Gross superati. Premere il pulsante
Print sul display per stampare il report
su una stampante collegata.
Premere per
visualizzare la
schermata Report
Ambientali. Quando
viene visualizzata
questa schermata
possibile
selezionare uno tra REPORT ULTIMO SUPERATO PIU' PIENO
due report test. Premere il pulsante Fullest Last Pass Test Type, Start Date/Time, Hours Run, %Volume
per visualizzare i risultati degli ultimi in Tank at Time of Test
12 test periodici (1 per ogni mese) e
dell'ultimo test annuale in cui la
cisterna aveva il volume maggiore.
Premere il pulsante Print sul display
per stampare il report su una
stampante collegata.
49
Setup TLS2 Report giacenze
Report giacenze
37.3 F
1
5329 GAL
(5413 GAL TC)
2
72 IN
3
WATER 0.0 IN
1 2 3 4 5 6
Per visualizzare il report giacenza per una cisterna, premere il tasto inventory report per la cisterna desiderata nella
parte inferiore della schermata. Per visualizzare il report giacenze turno per la cisterna selezionata, premere il tasto
Shift Inventory (elemento 1 della schermata sopra). Per visualizzare l'altezza indicatore (se abilitata) per la cisterna
selezionata, premere il pulsante Delta Stick (elemento 2 della schermata sopra). Per visualizzare il report log
giacenza per la cisterna selezionata, premere il tasto Inventory Log Report (elemento 3 della schermata sopra).
T 1:REGULAR UNLEADED
TANK VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP
1 5329 5413 4500 48.8 0.0 37.3
2 5329 5413 4500 48.8 0.0 37.3
T 1:REGULAR UNLEADED
TANK PRODUCT
1 REGULAR UNLEADED VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP
SHIFT 1 STARTING VALUES 8518 8492 1482 76.26 0.0 64.7
ENDING VALUES 8518 8492 1482 76.26 0.0 64.7
DELIVERY VALUE 0
TOTALS 0
SHIFT 2 STARTING VALUES 8518 8492 1482 76.26 0.0 64.7
ENDING VALUES 8518 8492 1482 76.26 0.0 64.7
DELIVERY VALUE 0
TOTALS 0
50
Setup TLS2 Report giacenze
Le colonne TC Volume e Temperature vengono stampate solo per sonde nel sistema che dispongono di capacit di misurazione
temperatura.
Se il parametro di setup sistema Print TC Volumes impostato su NO, le colonne TC Volume e Temperature non vengono
stampate.
La colonna Water viene stampata solo per sonde nel sistema che dispongono di capacit di misurazione dell'acqua.
51
Setup TLS2 Schermata stato allarmi attivi
Report allarmi
possibile accedere ai report allarmi dalla schermata Report allarmi attivi premendo uno dei pulsanti
relativi ai report nella parte inferiore della schermata. Tabella 5 descrive i report disponibili.
52
Setup TLS2 Report allarmi
Premendo il tasto Alarm Ack (voce 3 a pagina 5) il segnale acustico viene disattivato anche se l'allarme
ancora attivo. La schermata Stato Allarmi visualizza l'allarme sino a che non viene cancellato. Quando
una condizione di allarme ritorna allo stato normale, l'allarme viene rimosso dall'elenco degli allarmi
attivi.
Quando non attivo nessun allarme, il LED del pannello anteriore in stato Normale (verde fisso) e il
riquadro 2 della schermata a pagina 5 mostra All Functions Normal.
Un avvertimento Probe Out o Low Temperature attivo disabilita tutti gli allarmi livello (Max Product,
Overfill, Low Product, Delivery Needed, e High Water).
53
Setup TLS2 Report allarmi
Allarme attivo
Quando si attiva un allarme, si attivano anche il segnale acustico della console e il rel allarme (se abilitato), il
LED rosso del pannello anteriore lampeggia, e il riquadro 2 della schermata a pagina 5 visualizza un messaggio di
allarme. In caso di molteplici allarmi, nel riquadro scorrono automaticamente gli allarmi attivi. In caso di allarme
assegnato ad autodial, la console stabilisce una connessione con l'host remoto. L'host pu quindi inviare alla
console le richieste per determinare la ragione della chiamata.
Quando un allarme attivo, l'utente pu disattivare il segnale acustico e il rel allarme premendo il pulsante
ALARM (elemento 3 a pagina 5). Il LED del pannello anteriore rimane in stato di allarme e l'allarme rimane
nell'elenco degli allarmi attivi sino a che non ritorna allo stato normale. Se l'allarme inattivo ma non
riconosciuto, rimane nell'elenco degli allarmi e il segnale acustico e il rel allarme (se abilitato) rimangono attivi
sino a che viene riconosciuto.
Quando le condizioni di allarme vengono corrette, o un dispositivo guasto viene sostituito, l'allarme viene
automaticamente cancellato. Per cancellare un allarme test tenuta non superato, deve essere eseguito e superato un
nuovo test tenuta.
Se il volume livello prodotto supera il volume Max Product, si attiva l'allarme Max Product. Se l'allarme attivo e
il volume livello prodotto inferiore al valore di Max Product di almeno 0,005 volte la capacit volume completa
o di 10 galloni [37,8 L] (a seconda di quale dei due valori maggiore), l'allarme si disattiva. Il valore di Max
Product viene immesso come volume con valore predefinito pari a 0. Se il valore di Max Product uguale a 0 o
alla capacit volume cisterna completa, l'allarme viene disabilitato. Un Avvertimento Bassa Temperatura Sonda
attivo disabilita l'allarme.
Allarme Overfill
Se il volume livello prodotto supera la soglia di allarme Overfill ed una erogazione in corso, si attiva l'allarme
Overfill. Qualsiasi l'erogazione si interrompe, l'allarme si disattiva. Il valore allarme Overfill si immette come
percentuale e il valore predefinito 0%. Un valore soglia Overfill di 0% disabilita l'allarme. La soglia di allarme
riempimento eccessivo fa riferimento al valore di Max Product. Se il valore di Max Product 0, il valore di
Overfill fa riferimento alla capacit Full Volume. Un Avvertimento Bassa Temperatura Sonda attivo disabilita
l'allarme.
Se il volume livello prodotto inferiore alla soglia Low Product, si attiva l'allarme Low Product. Se l'allarme
attivo e il volume livello prodotto superiore alla soglia di almeno 0,005 volte la capacit volume completa o di
10 galloni [37,8 L] (a seconda di quale dei due valori maggiore), l'allarme si disattiva. Il valore di Max Product
viene immesso come volume con valore predefinito pari a 0. Se il valore uguale a 0, l'allarme viene disabilitato.
Un Avvertimento Bassa Temperatura Sonda attivo disabilita l'allarme.
54
Setup TLS2 Report allarmi
Se l'altezza livello acqua supera continuamente la soglia High Water per un periodo superiore a 3 minuti, si attiva
l'avvertimento High Water. L'allarme High Water non si attiva se in corso un'erogazione. Se l'allarme attivo e
l'altezza livello acqua inferiore alla soglia di almeno 0,2 pollici (5 mm), l'allarme si disattiva. Il valore di High
Water viene immesso come altezza con valore predefinito pari a 0. Se il valore uguale a 0, l'allarme viene
disabilitato. Un Avvertimento Bassa Temperatura Sonda attivo disabilita l'allarme.
Se la console non comunica in modo affidabile con la sonda, si attiva l'allarme Probe Out.
Se il galleggiante dell'acqua e quello del prodotto sono troppo vicini per fornire dati affidabili sull'altezza, si attiva
l'allarme Invalid Fuel Height.
Sonda Standard: Se la sonda riporta una temperatura inferiore a -4F (-20C), si attiva l'avvertimento Low
Temperature. Se l'allarme attivo e la temperatura supera 0F (-17,7C), l'allarme si disattiva.
Bassa Temperatura Sonda: Allarme -40F (-40C), Annullamento -36F (-37.7). Quando l'avvertimento Low
Temperature attivo, gli allarmi High Water, Low Product, Max Product, Delivery Needed, e Overfill sono
disabilitati.
Se il livello prodotto della cisterna scende sotto al limite prefissato, si attiva l'allarme Delivery Needed.
Quando non viene superato un test perdita Gross, Periodic, o Annual, si attiva un allarme test perdita Gross,
Periodic, o Annual. Per cancellare un allarme test tenuta non superato, deve essere eseguito e superato un nuovo
test tenuta.
55
Schermate diagnostica
1 2 3
4 5 6
RED LED GREEN LED LCD OFF
7 8
56
Setup TLS2 Schermata Test LCD Touch Screen
Descrizione
57
Setup TLS2 Schermate diagnostica sonda
TANK : 1
PROBE TYPE : MAG 01
SERIAL NUMBER : 123001
PROBE ID : C000
PROBE LENGTH : 96.0
GRADIENT : 360.000
NUMBER SAMPLES: 20
1 2 3 4 5 66
Per visualizzare la diagnostica della sonda di un'altra cisterna, premere il pulsante Diagnostica relativo alla cisterna
desiderata nella parte inferiore dello schermo.
58
Indice codici etichetta
La Tabella 6 e la Tabella 7 aiutano gli utenti delle lingue supportate diverse dall'inglese ad identificare le etichette
usate nelle schermate di Setup TLS2. Nella parentesi accanto a ciascuna etichetta si trova un codice univoco, ad
esempio [101]. Questo codice viene elencato nelle tabelle seguenti e fa riferimento alle schermate di setup
presenti nel manuale dove viene usata l'etichetta.
Codice
etichetta Etichetta Usata in
59
Setup TLS2 Schermate diagnostica sonda
Codice
etichetta Etichetta Usata in
Codice
etichetta Etichetta Usata in
60
Setup TLS2 Schermate diagnostica sonda
Codice
etichetta Etichetta Usata in
61
Setup TLS2 Schermate diagnostica sonda
Codice
etichetta Etichetta Usata in
62
Condizioni di garanzia e limitazioni di responsabilit
Limitazioni di responsabilit
Garantiamo che questo prodotto sar privo di difetti in termini di materiali e costruzione per un periodo
di 1 anno dalla data di installazione o di 24 mesi dalla data della fattura, a seconda di quale delle due
date occorra per prima. Durante il periodo di garanzia, noi o un nostro rappresentante ripareremo o
sostituiremo il prodotto, se lo riterremo difettoso, presso la sede dove viene utilizzato il prodotto, senza
alcun costo per l'acquirente.
Non saremo responsabili di eventuali spese sostenute dall'utente.
Questa garanzia valida solo quando il prodotto viene installato conformemente alle specifiche di
Veeder-Root, e il modulo di Registrazione della Garanzia e Collaudo stato fatto pervenire a Veeder-
Root da parte di un Distributore Autorizzato Veeder-Root. Questa garanzia non valida in caso di
prodotto soggetto ad uso improprio, negligenza o incidente; o applicato non correttamente; o usato in
violazione di manuali, istruzioni o avvertenze relative al prodotto; o modificato o riparato da personale
non autorizzato; o installato in modo non corretto.
Ispezione
Il cliente dovr ispezionare il prodotto immediatamente dopo la ricezione e comunicare in forma scritta
al nostro ufficio di Simsbury eventuali reclami, compresi quelli relativi alla garanzia, entro 30 giorni
dalla rilevazione dell'eventuale problema. In caso di mancato invio di reclamo scritto entro il periodo
indicato, il reclamo stesso non sar valido.
I termini della Limitazioni di responsabilit sopra riportati costituiscono il nostro unico obbligo ed
escludono qualsiasi altra azione correttiva o garanzia, esplicita o implicita, comprese le garanzie di
COMMERCIABILITA' e ADEGUATEZZA AD UNO SCOPO SPECIFICO, indipendentemente dalla
descrizione o meno in questo documento degli scopi o delle specifiche. In nessun caso saremo
responsabili verso il cliente o qualsiasi altra persona per danni alle persone o alle cose causati da
qualsiasi prodotto soggetto ad uso errato, negligenza, o incidente; o applicato non correttamente; o
usato in violazione di manuali, istruzioni o avvertenze relative al prodotto; o modificato o riparato da
personale non autorizzato; o installato in modo non corretto.
In nessun caso saremo responsabili per danni, perdite o spese incidentali, consequenziali o specifici,
derivanti da questo contratto o dalla sua attuazione o in relazione con l'utilizzo o l'impossibilit di
utilizzo del nostro prodotto per qualsiasi scopo.
Nessuna azione legale, indipendentemente dalla sua forma, derivante da questo contratto pu essere
promossa dopo 1 anno dal manifestarsi della causa dell'azione stessa, eccetto in caso di mancato
pagamento.
63
Setup TLS2
Garanzie collaterali
Non esistono garanzie o condizioni, esplicite o implicite, obbligatorie o di altro tipo, eccetto quelle qui
contenute, e nessun accordo o atto di rinuncia collaterale a questo sar vincolante per le parti, eccetto
che in forma scritta e firmato dal cliente e accettato da noi presso il nostro ufficio di Simsbury.
Interpretazione
I diritti e le responsabilit derivanti da qualsiasi contratto con noi saranno determinati in base
all'Uniform Commercial Code in vigore nel Connecticut.
64
PORTUGUESE
Contedo
Introduo
Requisitos de certificao do fornecedor ................................................................ 1
Manuais relacionados .............................................................................................. 1
Smbolos de segurana .......................................................................................... 2
Avisos de segurana ............................................................................................... 2
Aprovaes e acordos reguladores ........................................................................ 3
Console ................................................................................................................... 3
Funes de monitoramento .................................................................................. 3
Sada do rel ........................................................................................................ 3
Funes de comunicaes ................................................................................... 3
ndice de referncia rpida de mensagens de alarme ............................................ 4
i
Contedo
Relatrios
Relatrios do sistema ............................................................................................ 46
Relatrios de inventrio ......................................................................................... 47
Impresso do relatrio de exemplo - Relatrio de inventrio com Volume CT... 47
Impresso do relatrio de exemplo - Relatrio de inventrio de
mudana com Volume CT ........................................................................... 47
Notas sobre o relatrio de inventrio .................................................................. 47
Tela Status do alarme ativo ................................................................................... 48
Relatrios de alarmes ........................................................................................... 48
Notas importantes sobre o alarme...................................................................... 49
Informaes sobre os estados do alarme ............................................................. 50
Alarme ativo........................................................................................................ 50
Reconhecendo um alarme ativo ......................................................................... 50
Retornando ao estado normal ............................................................................ 50
Informaes sobre o alarme no tanque ................................................................. 50
Alarme de nvel mximo ..................................................................................... 50
Alarme de transbordamento ............................................................................... 50
Alarme de nvel mnimo ...................................................................................... 50
Alarme de gua alta............................................................................................ 51
Alarme de sonda fora ......................................................................................... 51
Nvel de combustvel invlido ............................................................................. 51
Aviso de baixa temperatura da sonda ................................................................ 51
Alarme de abastecimento necessrio................................................................. 51
Alarme de teste de vazamento ........................................................................... 51
Telas de diagnstico
Tela Menu do teste de funo ............................................................................... 52
Tela Teste de toque do LCD ................................................................................. 53
Tela de diagnstico da sondas .............................................................................. 54
Impresso do relatrio de exemplo - Relatrio de diagnstico da sonda .......... 54
Disponibilidade dos dados da sonda .................................................................. 54
ii
Configurao do TLS2
iii
Configurao do TLS2
iv
Introduo
Depois de inserir os parmetros Configurao do sistema e do tanque, o console dever estar em operao.
Consulte a seo Relatrios para obter instrues sobre como exibir os relatrios de sistema e alarme. A seo
Diagnstico contm alguns procedimentos simples de teste do console e acesso aos dados de Diagnstico
das sondas.
O Veeder-Root requer as seguintes certificaes mnimas de treinamento para fornecedores que instalaro
e configuraro o equipamento abordado neste manual:
Nvel 1 Os fornecedores que possuem a Certificao de nvel 1 tm aprovao para executar o roteamento de
fiao e tubulao, a montagem de equipamento, a instalao da sonda e do sensor, a preparao do tanque
e da linha e a instalao do detector de vazamento da linha.
Manuais relacionados
1
Configurao do TLS2
Smbolos de segurana
Os seguintes smbolos de segurana so usados neste manual para alert-lo sobre os perigos e as
precaues da segurana.
EXPLOSIVO INFLAMVEL
Os combustveis e seus vapores Os combustveis e seus vapores so
so extremamente explosivos, se extremamente inflamveis.
inflamados.
Avisos de segurana
AVISO
Este sistema opera prximo aos tanques de armazenamento de combustvel
altamente inflamveis.
2
Configurao do TLS2
Planeje seu programa de deteco de vazamento para estar de acordo com as normas locais, estaduais e federais
que controlam os tanques de armazenamento subterrneos. Guarde todos os registros de testes de vazamento
e inventrios fornecidos pelo sistema, como parte de um programa de acordo regulador.
O sistema, quando equipado com as sondas magnetorestritivas 0,2 galo por hora (gph) (0,76 lph) (Mag 2),
est classificado como um Sistema de indicador de nvel automtico e foi testado por terceiros pelo Midwest
Research Institute. Este sistema pode detectar um vazamento de 0,2 gph excedendo uma probabilidade de 95% de
deteco [P(D)] e uma probabilidade menor que 5% de alarme falso [P(FA)]. Isto corresponde aos padres de
desempenho federais EPA dos Estados Unidos (0,2 gph em [P(D)] de 95% e [P(FA)] de 5%) e o padro
de desempenho federal de medio de gua na parte inferior de um tanque para aproximadamente
1/8 polegadas (3,2 mm).
O sistema, quando equipado com sondas magnetorestritivas 0,1 gph (0,38 lph) (Mag 1), corresponde aos padres
do Mtodo de impermeabilidade de tanque volumtrico e foi testado por terceiros, pelo Midwest Research
Institute. Este sistema pode detectar um vazamento de 0,1 gph excedendo uma probabilidade de 95% de deteco
[P(D)] e uma probabilidade menor que 1% de alarme falso [P(FA)]. Este sistema corresponde aos padres de
desempenho federais EPA dos Estados Unidos (0,1 gph em [P(D)] de 95% e [P(FA)] de 5%).
Console
O Console TLS2 est equipado com uma tela de exibio de toque no painel frontal, um LED Alarme/Normal
de dupla finalidade e um bipe para notificao de alarme e aviso. Portas de impressora paralelas e seriais esto
disponveis para conexo a uma impressora remota. O Console TLS2 pode monitorar at seis sondas
magnetorestritivas.
Funes de monitoramento
Sada do rel
Uma sada do rel existe desde que possa disparar dispositivos de alarme externos quando uma condio de alarme
detectada pelo sistema.
Funes de comunicaes
RS-422
3
Configurao do TLS2 ndice de referncia rpida das mensagem de alarme
Falha no teste Tanque Falha no teste anual de vazamento Execute novamente o teste de vaza-
anual no tanque. mento no tanque. Se o segundo teste
falhar, ligue para o servio de
assistncia tcnica.
Falha no teste Tanque Falha no teste de vazamento Execute novamente o teste de vaza-
bruto no tanque. mento no tanque. Se o segundo teste
falhar, ligue para o servio de
assistncia tcnica.
gua alta Tanque A gua detectada no tanque excede Retire a gua do tanque.
o limite predefinido.
Baixa temperatura Tanque A temperatura da sonda caiu abaixo A sonda retorna operao normal
de -4F (-20C). Para sondas de aps a temperatura da sonda subir
baixa temperatura, abaixo de acima de 0F (-17,7C). Para sondas
-40F (-40C). de baixa temperatura, abaixo de
-36F (-38C).
Sonda fora Tanque Falha no hardware - sonda ou fiao Ligue para o servio de assistncia
de interconexo ao console. tcnica.
4
Telas de configurao do sistema
Esta seo descreve todas as telas de configurao do sistema TLS2, juntamente com as opes de configurao e as expli-
caes necessrias para a entrada de dados. Uma vez que as telas de configurao do TLS2 possuem rtulos somente em
ingls, os cdigos de Rtulo de tela foram colocados entre colchetes abaixo de cada rtulo em ingls, para permitir que voc
encontre rapidamente uma traduo do rtulo e o(s) nmero(s) de pgina da tela em que o rtulo foi usado. As Telas de
configurao do tanque so abordadas em uma seo separada.
Entrada de dados, confirmao de selees, etc. so feitas por uma das vrias telas de entrada de dados exibidas quando voc
toca em qualquer boto direita de uma janela de entrada de dados. Essas telas foram descritas onde foram abordadas pela
primeira vez nesta seo.
11
5
10
9 8 7 6
1 Janela de data e hora (Date/Time) - exibe a data e 6 Boto Relatrio do ambiente (Environment Report) -
hora atuais toque para exibir os resultados do teste de vaza-
2 Janela de mensagens (Message) - exibe Todas as mento do tanque (pgina 46).
funes normais ou os alarmes ativos. 7 Boto Relatrio do alarme (Alarm Report) - toque
3 Boto de alarme (Alarm) - toque para conhecer o para exibir a tela Status de alarme ativo (e histrico)
alarme e silenciar o bipe. Nota: tocar neste boto no (pgina 48).
elimina o alarme - o problema que causou o alarme 8 Boto Relatrio de abastecimento (Delivery Report) -
deve ser corrigido. toque para exibir a tela Relatrio de abastecimento
4 Boto Imprimir (Print) - Para telas de menu, toque (pgina 46).
nesse boto e todos os itens disponveis no menu 9 Boto Relatrio de inventrio (Inventory Report) -
sero impressos em uma impressora conectada. toque par exibir a tela Relatrio de inventrio
Somente para telas fora do menu, aparecer uma (pgina 47).
caixa de dilogo de impresso quando o boto de 10 Botes do tanque - toque em qualquer boto do
impresso for tocado. O usurio tambm tem a tanque para exibir o relatrio de inventrio atual
opo de cancelar a impresso. desse tanque.
5 Boto Menu principal (Main Menu) - toque para exibir 11 Janela de ttulo da tela.
a tela Menu principal (pgina 6) para obter acesso
configurao do sistema ou tanque e ao teste
manual do tanque.
5
Configurao do TLS2 Tela Menu principal
1 2
6 3
II
5 4
consoles/tls2/menuscrn.eps
6
Configurao do TLS2 Tela Configurao do sistema
2 3 4
1
6 7
5
8
10 11 12
1 Boto Idioma (Language) - toque para exibir a tela 8 Boto Temperatura (Temp) - toque para exibir a tecla
Configurao de idioma e unidades (Language and Con-figurao da temperatura (Temperature Setup)
Units) (pgina 8). (pgina 30).
2 Boto Hora atual (Current Time) - toque para exibir a 9 Boto Segurana (Security) - toque para exibir a tela
tela Configurao de hora e data (Time/Date Setup) Configurao de segurana do sistema (System
(pgina 13). Security Setup) (pgina 12).
3 Boto Comunicao (Comm) - toque para exibir a 10 Boto Horrio de vero (Daylight Savings) - toque
tela Configurao da comunicao (Comm Setup) para exibir a tela Configurao dos Horrio de vero
(pgina 22). (Daylite Savings Setup) (pgina 17).
4 Boto Rel de alarme (Alarm Relay) - toque para 11 Boto Alarmes de discagem automtica (Autodial
exibir a tela Configurao do rel de alarme Alarms) - toque para exibir a tela Configurao dos
(Alarm Relay Setup) (pgina 29). alarmes de discagem automtica (Auto Dial Alarms
5 Boto Cabealho (Header) - toque para exibir a tela Setup) (pgina 19).
Configurao do cabealho da estao (Station 12 Boto EuroProtocol (Europrotocol) - toque para exibir
Header Setup) (pgina 9). a tela Con-figurao de EuroProtocol e Deslocamen-
6 Boto Hora de mudana (Shift Time) - toque para to da vareta (Europrotocol and Stick Offset Setup)
exibir a tela Configurar horas de mudana (pgina 31). Esta tela tambm permite selecionar
(Setup Shift Times) (pgina 16). um formato de relatrio de teste de vazamento.
7
Configurao do TLS2 [201-203] Tela Configurao de idioma e unidades do sistema
1
[201]
2
[202]
3
[203]
8
Configurao do TLS2 [204-207] Tela Configurao do cabealho da estao
1
[204]
2
[205]
3
[206]
4
[207]
9
Configurao do TLS2 Tela Teclado alfanumrico
10
4 SAVE
5 6 7 8 9
1 Exibe o ttulo dos dados a serem inseridos. 7 Boto Cursor direita (Cursor Right) - toque para
2 A janela Dados inseridos exibe os dados inseridos. mover o cursor uma posio direita na janela
Dados inseridos (2) (Data Entered).
3 Botes do teclado alfanumrico - toque em um boto
de caractere para colocar esse caractere na janela 8 Boto Excluir com Backspace (Backspace Delete) -
de dados inseridos (2) (Data Entered). toque para excluir caractere no cursor.
4 Boto Salvar (Save) - toque para aceitar os dados 9 Boto Teclado numrico (Number Keypad) - toque
inseridos e fechar a tela. para exibir a tela Teclado numrico.
5 Boto Cancelar (Cancel) - toque para cancelar 10 Boto Limpar (Clear) - toque para limpar o contedo
qualquer entrada e fechar a tela. da janela Dados inseridos (2 )(Data Entered).
10
Configurao do TLS2 Tela Teclado numrico
10
4 SAVE 9
5 6 7 8
1 Exibe o ttulo dos dados a serem inseridos. 6 Boto Cursor esquerda (Cursor Left) - toque para
2 A janela Dados inseridos (Data Entered) exibe os mover o cursor uma posio esquerda na janela
dados inseridos. Dados inseridos (2) (Data Entered).
3 Botes do Teclado numrico (Numeric Keypad) - 7 Boto Cursor direita (Cursor Right) - toque para
toque em um boto de caractere para colocar mover o cursor uma posio direita na janela
esse caractere na janela Dados inseridos Dados inseridos (2) (Data Entered).
(2) (Data Entered). 8 Boto Excluir com Backspace (Backspace Delete) -
4 Boto Salvar (Save) - toque para aceitar os dados toque para excluir caractere acima do cursor.
inseridos e fechar a tela. 9 Boto Teclado alfanumrico (Alpha Keypad) -
5 Boto Cancelar (Cancel) - toque para cancelar toque para exibir a tela Teclado alfanumrico
qualquer entrada e fechar a tela. (Alpha Keypad).
10 Boto Limpar (Clear) - toque para limpar o contedo
da janela Dados inseridos (2) (Data Entered).
11
Configurao do TLS2 [208-211] Tela Configurao de segurana do sistema
1 COMM 1 PASSWORD
[208]
2 COMM 1 PASSWORD
[209]
3 COMM 2 PASSWORD
[210]
4 COMM 2 PASSWORD
[211]
12
Configurao do TLS2 [212-214] Tela Configurao de data e hora do sistema
1 10-04-01
[212]
2
[213] 13-54
13
Configurao do TLS2 Tela de entrada de data atual
1 2001 3
14
Configurao do TLS2 Tela Entrada de hora atual
1 3
15
Configurao do TLS2 [215-218] Tela Configurao de horas de mudana
1
[215]
2
[216]
3
[217]
4
[218]
Em cada hora de incio de mudana selecionada a 7 Mudana 2 (Shift 2) [216] - toque no boto de hora
seguir, o sistema salva automaticamente um relatrio de direita da janela e digite a hora de incio da Mudana
inventrio completo na memria. A definio-padro 2 e AM ou PM.
desativado para todas as mudanas. 8 Mudana 3 (Shift 3) [217] - toque no boto de hora
NOTA: Pelo menos uma hora de incio de mudana deve direita da janela e digite a hora de incio da Mudana
ser digitada para ativar o recurso ltimo inventrio 3 e AM ou PM.
de mudana.
9 Mudana 4 (Shift 4) [218] - toque no boto de hora
6 Mudana 1 (Shift 1) [215] - toque no boto de hora direita da janela e digite a hora de incio da Mudana
direita da janela e digite a hora de incio da Mudana 4 e AM ou PM.
1 e AM ou PM.
16
Configurao do TLS2 [219-223] Tela Configurao de hora de salvamentos diurnos
1 ENABLE
[219]
2 APR WEEK 1 SUN
[220]
3
[221] 2:00 AM
Este recurso permite digitar datas e horas de incio e 3 Hora de incio (Start Time) [221] - toque no boto
trmino de horrio de vero. Quando ativado, o sistema Hora direita da janela e digite a hora de incio
ser ajustado automaticamente para hora de horrio de [e AM ou PM] (o padro 02:00 AM).
vero nas datas e horas digitadas.
4 Data de trmino (End Date) [222] - toque no boto
1 Horrio de vero (Daylight Savings) [219] - toque no Data direita da janela e digite a data de trmino
boto de seta para a direita da janela e selecione (o padro OCT WEEK 6 SUN).
Ativar ou Desativar (o padro Ativar).
5 Hora de trmino (End Time) [223] - toque no boto
2 Data de incio (Start Date) [220] - toque no boto Hora direita da janela e digite a hora de trmino
Data direita da janela e digite a data de incio [e AM ou PM] (o padro 02:00 AM).
(o padro APR WEEK 1 SUN).
17
Configurao do TLS2 [224-226] Tela Configurao de discagem automtica
1 PHONE
[224]
2 RETRIES
[225]
3 RETRY DELAY
[226]
18
Configurao do TLS2 [227-230] Tela 1 Configurao do alarme de discagem automtica
1
[227]
2
[228]
3
[229]
4
[230]
5
1 2 3 4 5 6
Este recurso permite que o sistema seja programado 3 Abastecimento necessrio (Delivery Needed) [229] -
para discar nas seguintes condies de alarme. toque no boto de seta para baixo para selecionar
Nota: Os alarmes de discagem automtica continuam Ligado ou Desligado.
nas duas pginas seguintes. 4 Nvel mnimo (Low Product) [230] - toque no boto de
1 Nvel mximo (Max. Product) [227] - toque no boto seta para baixo para selecionar Ligado ou Desligado.
de seta para baixo para selecionar Ligado 5 Toque no boto Alarme de discagem automtica para
(discagem) ou Desligado (no discar). o tanque que voc deseja configurar e selecione os
2 Limite de transbordamento (Overfill Limit) [228] - alarmes desejados nas telas 1 a 3 de Alarmes de
toque no boto de seta para baixo para selecionar discagem automtica. Voc deve repetir este pro-
Ligado ou Desligado. cesso para cada tanque.
19
Configurao do TLS2 [231-234] Tela 2 Configurao do alarme de discagem automtica
1
[231]
2 6
[232]
3
[233] 7
4
[234] 8
11 22 33 4
4 5
5 6
6
20
Configurao do TLS2 [235-237] Tela 3 Configurao do alarme de discagem automtica
1
[235]
2
[236]
3
[237]
11 22 33 4
4 5
5 6
6
21
Configurao do TLS2 [238-239] Tela 1 Configurao da porta de comunicao serial 1 e 2
1
[238]
2
[239]
3 4 5 6
Essa tela semelhante configurao da porta de 3 Boto COMUNICAO 1 (Comm 1) - toque para
comunicao 1 e 2. exibir a tela Configurao da comunicao 1
1 Tipo de comunicao (Comm Type) [238] - toque (mostrado a seguir).
no boto de seta para baixo direita da janela 4 Boto COMUNICAO 2 (Comm 2) - toque para
e selecione: exibir a tela Configurao da comunicao 2.
Se Comunicao 1 - 5 Boto PARALELO (Parallel)- toque para exibir a tela
Serial, Modem, Impressora ou Nenhum (padro) Con-figurao da porta paralela (pgina 28).
Se Comunicao 2 - 6 Boto Para baixo (Down) - toque para exibir a tela 2
Serial ou Nenhum (padro) Con-figurao da porta de comunicao (pgina 25).
22
Configurao do TLS2 [241] Tela Configurao da porta de comunicao 1 da impressora
[238]
1
[241] 9
[239]
2 PRINTER LANG EPSON ESC/P
[253] 3
23
Configurao do TLS2 [244-246] Tela 1 Configurao da porta de comunicao 1 do modem
[238]
2
[244]
3
[245]
4 5
[246]
24
Configurao do TLS2 [249-252] Tela 2 Configurao da porta de comunicao
1 9600
[249]
2 ODD
[250]
3 7
[251]
4
[252]
25
Configurao do TLS2 [247-248] Tela Configurao das comunicaes avanadas
1 DIAL IN AT&B1
[247]
2 AT&B1
[248]
CUIDADO!
Digitar as seqncias numricas incorretas nesta tela
pode desativar o modem.
26
Configurao do TLS2 Tela de entrada de dados
1
[249]
2 SAVE 3
27
Configurao do TLS2 Tela Configurao da porta paralela
1 COMM TYPE
[238]
2 PAGE EJECT
[238]
9
3 PRINTER LANG EPSON ESC/P
[253]
28
Configurao do TLS2 [256] Tela Configurao do rel de alarme
1
[256]
29
Configurao do TLS2 [257-258] Tela Configurao da temperatura
1 59 F
[257]
2
[258]
30
Configurao do TLS2 [259-262] Tela Configurao de EuroProtocol e deslocamento da vareta
1
[259]
2
[260]
3
[261]
4
[262]
31
Configurao do TLS2 Sobre a tela do TLS2
SYSTEM FEATURES
STATIC TANK LEAK DETECT
Essa tela lista informaes sobre o software e os recursos instalados do Console TLS2:
Nvel de reviso de software do sistema
Nmero de verso do software
Nmero de pea do software
Data de criao do software
Recursos do sistema: Deteco de vazamento do tanque esttico
32
Telas de configurao do tanque
1 2
33
Configurao do TLS2 [119-121] Tela 1 Configurao do tanque
TANK 1
1 CONFIGURED
[119]
2
[120]
3
[121]
1 2 3 4 5 6
34
Configurao do TLS2 [122-124] Tela 2 Configurao do tanque
TANK 1
1
[122]
2
[123]
3
[124]
1 2 3 4 5 6
Essa tela continua a Configurao do tanque. O sistema calcular o nvel para cada ponto (4 ou
1 Dimetro (Diameter) [122] - toque no boto de seta 20) com base no perfil selecionado e no dimetro
para baixo direita da janela e digite o dimetro do tanque e os exibir ao lado das janelas nas
do tanque. quais deve ser digitado o volume correspondente.
A partir do grfico do tanque, obtenha o volume
2 Volume completo (Full Volume) [123] - toque no boto dos nveis exibidos e digite esse volume na janela.
de seta para baixo direita da janela e digite o Volume
completo do tanque. Tenha cuidado para digitar o valor exato do grfico
do tanque para o nvel rotulado. Entradas fora da
3 Perfil do tanque (Tank Profile) [124] - toque no boto de faixa no sero aceitas.
seta para baixo direita da janela e selecione o perfil
do tanque: Linear - para montagem de tanques retan- Se o perfil de 4 pontos ou 20 pontos for seleci-
gulares ou tanques cilndricos na extremidade; onado, voc dever digitar um volume para cada
1 ponto - para tanques de ao com extremidade plana ponto ou o sistema calcular um volume 0 para
(padro); 4 pontos - para tanques de fibra de vidro ou qualquer nvel.
20 pontos - para todos os tanques. Os parmetros de configurao do tanque continuam na
prxima pgina.
4 Boto Grfico do tanque (CHRT) - Este boto s
aparece se voc selecionou o perfil de tanque de 4
pontos ou de 20 pontos.
35
Configurao do TLS2 [125-128] Tela 3 Configurao do tanque
TANK 1
1
[125] 0.00070
2
[126] 0 IN
3
[127]
4
[128]
1 2 3 4 5 6
Esta tela conclui a Configurao do tanque. 3 Tamanho da bia (Float Size) [127] - Toque no boto
1 Coeficiente trmico (Thermal Coeff) [125] - Toque no de seta para baixo direita da janela e a partir dos
boto de seta para baixo direita da janela e digite o tamanhos de bias apresentados, digite o tamanho
dimetro do tanque. da bia da sonda Mag que foi instalada na sonda do
tanque
Para assegurar a exatido das converses de volumes
compensados de temperatura, o coeficiente de expan- 4 Deslocamento da vareta (Stick Offset) [128] - Toque
so trmico do produto deve ser inserido corretamente. no boto de seta para baixo direita da janela
Um valor incorreto afetar de forma adversa o teste de e digite um valor de deslocamento da vareta.
deteco de vazamento e os valores de inventrio O intervalo permitido -144 a +144 polegadas (-
compensados de temperatura. 365,76 a +365,76 cm) e o padro 0.
Tabela 2 lista os coeficientes mtricos e dos Estados Nota: Para digitar um valor de deslocamento da
Unidos para combustveis e lquidos aprovados. Digite vareta, a opo Deslocamento da vareta deve estar
o coeficiente em unidades mtricas ou dos Estados ativada (pgina 31) e deve ter sido calculada e
Unidos, dependendo das unidades especificadas na inserida a inclinao do tanque (se necessrio).
Configurao do sistema (pgina 8). Tenha cuidado Um deslocamento da vareta pode ser inserido para
ao adicionar a quantidade de zeros correta direita que o nvel da sonda (produto) parea ser igual
da casa decimal. A entrada incorreta pode causar a uma leitura de indicador da vareta do nvel do
falhas no teste e outros problemas. produto- Essa entrada apenas para comodidade
do operador e, dessa forma, no tem qualquer
2 Inclinao do tanque (Tank Tilt) [126] - Toque no boto influncia sobre os clculos do volume do produto.
de seta para baixo direita da janela e digite a incli-
nao do tanque. O intervalo permitido -144 a +144 Para determinar o valor a ser inserido para Desloca-
polegadas (-365,76 a +365,76 cm) e o padro 0. mento da vareta, registre a leitura do nvel da sonda e
registre uma leitura do nvel da vareta do tanque. Se
A inclinao do tanque permite ajustar a diferena a leitura do nvel do combustvel do tanque for menor
entre o nvel do combustvel no local da sonda e o nvel que a leitura da vareta, digite a diferena positiva
do combustvel no centro do tanque causado por uma entre os dois. Se a leitura da sonda for maior que a
inclinao no tanque. Voc deve digitar um sinal de leitura da vareta, digite a diferena negativa entre os
menos (-) se a inclinao do tanque for um valor dois. Por exemplo, se o nvel da vareta for = 52 e o
negativo. Um valor de inclinao do tanque no nvel da sonda for = 48, digite +4; se o nvel da vareta
requerido se a sonda estiver localizada no centro do for = 52 e o nvel da sonda for = 54, digite -2.
tanque. Se a sonda estiver localizada no centro do
tanque, o valor digitado ser 000,00 unidades dos
Estados Unidos ou 0000,0 unidades mtricas.
Se a sonda no estiver no centro do tanque, calc-
ule a inclinao do tanque, usando as direes
contidas na Tabela 3. Digite o valor da Coluna
G da planilha conforme a inclinao do tanque.
36
Configurao do TLS2 [125-128] Tela 3 Configurao do tanque
Coeficiente
Coeficiente
trmico
trmico
(Unidades
(Unidades
dos Estados
mtricas)
Produto Unidos)
37
Configurao do TLS2 [125-128] Tela 3 Configurao do tanque
Use a planilha a seguir para registrar medidas e executar clculos de inclinao de tanque para cada tanque.
1. Mea o nvel do tanque com a vareta na abertura de abastecimento, pelo menos 3 vezes. Registre a leitura mdia
na coluna A do grfico.
2. Antes de comear esta etapa, certifique-se de que a Inclinao do tanque [126] na tela seja = 0. Registre a leitura
do nvel de combustvel da sonda (Funo do inventrio no tanque) na coluna B do grfico.
3. Subtraia o valor digitado na coluna B do valor digitado na coluna A. Registre o resultado na coluna C.
4. Mea a distncia em polegadas (ou milmetros se usar unidades mtricas) entre a sonda e as aberturas de
abastecimento. Registre a medida na coluna D.
5. Divida o valor na coluna C pela coluna D para determinar o ngulo. Registre os resultados na coluna E.
6. Mea a distncia em polegadas ou milmetros na abertura da sonda at o centro do tanque. Registre a distncia
na coluna F.
7. Multiplique a coluna E pela coluna F para determinar a Inclinao do tanque (E X F = Valor da inclinao do
tanque). Registre o valor na coluna G.
A B C D E F G
6
* A inclinao do tanque pode ser um valor positivo (+) ou negativo (-). Se for um valor negativo, CERTIFIQUE-SE de
alterar o smbolo do valor para menos (-), quando inserir um valor de inclinao do tanque negativo.
38
Configurao do TLS2 [101-104] Tela 1 Configurao dos limites do tanque
1
[101]
2
[102]
3
[103]
4
[104]
1 2 3 4 5 6
Essa tela inicia a configurao dos limites do alarme 4 Nvel mnimo (Low Product) [104] - Avisos de Nvel
do tanque. mnimo quando o volume nas bombas do tanque
1 Nvel mximo (Max Product) [101] - Avisa quando o caem para o nvel digitado aqui. O intervalo permitido
nvel de fluido no tanque excede o volume digitado 0 a 26.000 gales (0 a 98.420 L). O padro 0 (o
aqui. O intervalo permitido 0 a 26.000 gales (0 a qual desativa o alarme). Um Aviso de baixa tempera-
98.420 L). O padro 0. Se o valor digitado for 0 ou o tura da sonda ativo desativar esse alarme. Toque no
volume completo, esse alarme desativado. Um Aviso boto de seta para baixo direita da janela e digite
de baixa tempera-tura da sonda ativo desativar esse esse valor em um volume menor que o do alarme de
alarme. Toque no boto de seta para baixo direita da Abastecimento necessrio.
janela e digite o nvel mximo para o tanque. NOTA: Normalmente esse alarme definido
para o nvel mais baixo antes da bomba secar.
2 Transbordamento (Overfill) [102] - Avisos de Limite de
Toda distribuio dever ser interrompida quando
abaste-cimento de um transbordamento potencial
esse alarme estiver ativo.
durante um abastecimento. Quando o volume atinge
esse limite, o sistema pode ativar um alarme de trans- A Configurao de limite do alarme do tanque continua
bordamento. O alarme de transbordamento refere-se na prxima pgina.
ao valor do Nvel mximo. Se o valor de Nvel mximo
for 0, o limite do Alarme de transbordamento referese
capa-cidade do Volume completo. O intervalo permitido
0 a 100%. O padro 0 (desativado). Um Aviso
de baixa temperatura da sonda ativo desativar
esse alarme.
3 Abastecimento necessrio (Delivery Needed) [103] -
Avisos de Abaste-cimento necessrio quando o nvel
de fluido no tanque cai para um nvel em que o ope-
rador solicita um abas-tecimento. Esse valor uma
porcentagem de Volume completo com um intervalo
permitido de 0 a 100%. O padro 0% (o qual desativa
o alarme). Toque no boto de seta para baixo direita
da janela e digite um volume maior que o alarme de
Nvel mnimo.
39
Configurao do TLS2 [105-108] Tela 2 Configurao dos limites do tanque
1
[105]
2
[106]
3
[107]
4
[108]
1 2 3 4 5 6
Essa tela continua a configurao dos Limites de alarme 3 Teste de vazamento mnimo anual (Ann Leak Test
do tanque. Min) [107] - Este valor define o volume mnimo do
1 gua alta (High Water) [105] - Avisa quando o nvel de tanque necessrio para registrar um teste de
gua no tanque excede o nvel digitado aqui. Defina vazamento anual que passou. O valor reflete os
este valor em um nvel menor que o obtido para a requisitos federais, estaduais e locais. Esse valor
bomba sub-mersa ou a linha de suco. O intervalo uma porcentagem de Volume completo com um
permitido 0 a 9 polegadas (0 a 228,6 mm). O padro intervalo permitido de 1,0 a 100%. O padro 0 (o
0 (o qual desativa o alarme). Toque no boto de seta qual desativa o alarme). Toque no boto de seta para
para baixo direita da janela e digite o limite de nvel baixo direita da janela e digite um volume.
de gua desejado. 4 Teste de vazamento mnimo peridico (Per Leak
2 Tempo de espera para abastecimento (Delivery Delay) Test Min) [108] - Este valor define o volume mnimo
[106] - Use esta tela para definir um tempo de espera do tanque necessrio para registrar um teste de
entre o trmino de uma operao de abastecimento e o vazamento peridico que passou. O valor reflete os
Relatrio de aumento de abastecimento. Este recurso requisitos federais, esta-duais e locais. Esse valor
evita a gera-o de vrios relatrios durante os uma porcentagem de Volume completo com um
intervalos entre as quedas de vrios compartimentos intervalo permitido de 1,0 a 100%. O padro
em um tanque. O recurso tambm permite que o 0 (o qual desativa o alarme). Toque no boto de
combustvel seja assentado aps um abastecimento, seta para baixo direita da janela e digite um volume.
o que especi-almente importante em grupos de A Configurao de limite do alarme do tanque continua
tanques conectados por tubulao. O tempo de espera na prxima pgina.
permitido 1 a 60 minutos. O padro 1. Toque no
boto de seta para baixo direita da janela e digite um
tempo de espera desejado.
40
Configurao do TLS2 [109-111] Tela 3 Configurao dos limites do tanque
1
[109]
2
[110]
3
[111]
1 2 3 4 5 6
41
Configurao do TLS2 [112-114] Tela 1 Configurao do teste de vazamento do tanque
1 0.2 GPH
[112]
2 EARLY STOP
[113]
3
[114]
1 2 3 4 5 6
A Configurao do teste de vazamento do tanque permite O volume do tanque for menor que o valor de
estabelecer e inserir o mtodo, a hora e a durao dos Vazamento mnimo peridico ou de Vazamento
testes de vazamento automticos. necessrio ter uma mnimo anual.
sonda Mag 1 ou 2 instalada para executar os testes For menor que 8 horas desde o abastecimento.
de vazamento.
A temperatura do produto for menor que
Se voc estiver usando o recurso Teste de vazamento no
0F (-17,6C) ou maior que +100F (+37,4C).
tanque para obter a conformidade com as normas para o
tanque de armazenamento subterrneo, certifique-se de H muito pouco combustvel no tanque.
que os limites de teste de vazamento que voc estabelecer Toque no boto de seta para baixo direita da janela
ou inserir estejam de acordo com os requisitos de tipo de e digite a opo desejada.
teste, exatido e freqncia, conforme estabelecido pelas
autoridades normativas locais, estaduais, federais ou 3 Durao do teste (Test Duration) [114] - A durao
quaisquer outras autoridades normativas vigentes mxima 24 horas. H uma durao mnima de duas
em seu local. horas para testes de 0,2 gph (0,76 lph) e trs horas
para testes de 0,1 gph (0,38 lph).
Alm disso, defina a hora do teste para um perodo em
que no ocorrer abastecimento de combustvel ou uma Nota: Se a Parada antecipada estiver ativada e o
operao de abastecimento do tanque. Tal atividade console determinar que um Teste de vazamento do
durante um procedimento de teste de vazamento causar tanque passou, o teste concludo antes de atingir a
resultados de teste de vazamento inexatos. hora de durao. A durao padro 2 horas. Toque
no boto de seta para baixo direita da janela e
1 Taxa de teste (Test Rate) [112] - Pode-se definir a taxa digite a opo desejada.
de teste de vazamento para 0,2 gph (0,76 lph) (padro)
ou 0,1 gph (0,38 lph). Selecionar 0,1 gph (0,38 lph) 4 Boto Todos os tanques iguais (Save All Tanks) -
requer uma sonda Mag 1. Toque no boto de seta para Toque neste boto para transferir as selees
baixo direita da janela e digite a opo desejada. idnticas feitas nesta tela do Tanque 1 para
Todos os tanques (abre a tela de confirmao
2 Parada antecipada (Early Stop) [113] - Desativado a Todos os tanques iguais na pgina 43).
definio padro. Quando este recurso for ativado,
A configurao do Teste de vazamento do tanque
evitar que um Teste de vazamento no tanque seja
concluda na pgina 44.
iniciado sob as seguintes condies:
42
Configurao do TLS2 [115] Tela Todos os tanques iguais
1
[115]
2 SAVE 3
43
Configurao do TLS2 [116-118] Tela 2 Configurao do teste de vazamento do tanque
TANK 1
1
[116]
2 DATE/DAY
[117]
3
[118]
1 2 3 4 5 6
44
Iniciar ou parar manualmente os testes de vazamento do tanque
Use esta tela para iniciar ou parar manualmente um teste de vazamento do tanque.
1
[129]
2 5
[130]
3 0.76 LPH 6
[112]
4
[114]
1 2 3 4 5 6
1 Mtodo de teste (Test Method) [129] - Selecione Nota: esta janela s aparece se voc seleci-
Tanque nico ou Todos os tanques. Toque no onou Durao de tempo limite esgotado na
boto de seta para baixo direita da janela e janela Controle de Teste. Toque no boto de
digite a opo desejada. seta para baixo direita da janela e digite a
2 Controle de teste (Test Control) [130] - Selecione opo desejada.
Durao de tempo limite esgotado ou Parada manual 5 Boto Iniciar teste (Start) - Toque neste
(o teste executa-do at que voc o pare, ou por 24 boto para iniciar o teste.
horas, qualquer que seja que ocorra primeiro). Toque 6 Boto Parar teste (Stop) - Toque neste
no boto de seta para baixo direita da janela e digite boto para parar o teste de vazamento de
a opo desejada. um tanque.
3 Taxa de teste (Test Rate) [112] - Selecione uma taxa
de teste de 0,2 gph (0,76 lph) (padro) ou de 0,1 gph
(0,38 lph). A taxa 0,1 gph (0,38 lph) requer uma sonda
Mag 1. Toque no boto de seta para baixo direita da
janela e digite a opo desejada.
4 Durao do teste (Test Duration) [114] - Selecione
uma durao de teste de 0 a 24 horas. H uma
durao mnima de duas horas para testes
de 0,2 gph (0,76 lph) e trs horas para testes
de 0,1 gph (0,38 lph). O padro 2 horas.
45
Relatrios
Relatrios do sistema
Os relatrios do sistema so acessados da Tela de status do sistema (local) (consulte pgina 5), tocando
em um dos quatro botes de relatrio, na parte inferior da tela. A Tabela 4 descreve os relatrios do
sistema disponveis.
CURRENT TEST
RESULTS RESULTADOS DO TESTE ATUAL
Tipo de teste, Data e hora de incio, Resultado
Toque no boto Resultados do teste do teste, Horas de execuo, % de volume no
atual para exibir os resultados dos tanque na hora do teste
ltimos testes Anual, Peridico e
Bruto que passaram. Toque no bo-
to Imprimir, na tela, para imprimir
o relatrio em uma impressora
Toque para exibir conectada.
a tela de
Relatrios
ambientais.
Quando essa tela
exibida,
possvel
selecionar um dos RELATRIO DO LTIMO TESTE MAIS
dois relatrios de Toque no boto ltimo teste mais COMPLETO QUE PASSOU
teste. completo que passou para exibir os Tipo de teste, Data e hora de incio, Horas de
resultados dos ltimos 12 testes execuo, % de volume no tanque na hora
peridicos (1 para cada ms) e do do teste
ltimo teste anual em que o tanque
possua maior volume. Toque no
boto Imprimir, na tela, para impri-
mir o relatrio em uma impressora
conectada.
46
Configurao do TLS2 Relatrios de inventrio
Relatrios de inventrio
37.3 F
1
5329 GAL
(5413 GAL TC)
2
72 IN
WATER 0.0 IN
1 2 3 4 5 6
Para ver o(s) relatrio(s) de inventrio de qualquer outro tanque, toque no boto Relatrio de inventrio do tanque,
na parte inferior da tela. Para exibir o relatrio de inventrio de mudana do tanque, toque no boto Inventrio de
mudana (item 1 na tela acima). Para exibir o nvel da vareta (se ativada), toque no boto Vareta delta (item 2 na
tela acima).
T 1:REGULAR UNLEDED
TANK VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP
1 5329 5413 4500 48.8 0.0 37.3
2 5329 5413 4500 48.8 0.0 37.3
T 1:REGULAR UNLEADED
TANK PRODUCT
1 REGULAR UNLEADED VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP
SHIFT1 STARTING VALUES 8518 8492 1482 76,26 0,0 64,7
ENDING VALUES 8518 8492 1482 76,26 0,0 64,7
DELIVERY VALUE 0
TOTALS 0
SHIFT 2 STARTING VALUES 8518 8492 1482 76,26 0,0 64,7
ENDING VALUES 8518 8492 1482 76,26 0,0 64,7
DELIVERY VALUE 0
TOTALS 0
47
Configurao do TLS2 Tela Status do alarme ativo
Relatrios de alarmes
48
Configurao do TLS2 Relatrios de alarmes
RELATRIO DE ALARME DE
PRIORIDADE ALTA
Exibe nmero do Dispositivo (T = Tanque,
C = Comunicao), Tipo de alarme, Data, Hora
e status dos ltimos 50 alarmes de prioridade
4 alta: Nvel mximo, Transbordamento, Nvel
Toque para exibir o Relatrio de mnimo, gua alta, Falha no teste bruto, Falha
alarme de prioridade alta. Toque no teste peridico, Falha no teste anual, Sonda
no boto Imprimir, na tela, para fora e Falha na discagem automtica. Somente
imprimir o relatrio em uma para Sondas fora, a verso impressa tambm
impressora conectada. inclui uma coluna Contagem, a qual lista o
Toque para exibir a nmero de vezes que o alarme foi repetido
tela Relatrios de desde a Data de incio.
alarmes Histrico
do alarme. Nessa
tela, voc pode
escolher se deseja RELATRIO DE ALARME DE
exibir o histrico dos PRIORIDADE BAIXA
Alarmes de prioridade
alta ou baixa. Exibe nmero do Dispositivo (T = Tanque,
C = Comunicao), Tipo de alarme, Data, Hora
Toque para exibir o Relatrio de e status dos ltimos 50 alarmes de prioridade
alarme de prioridade baixa. Toque baixa: Abastecimento necessrio, Nvel de
no boto Imprimir, na tela, para combustvel invlido e Baixa temperatura,
imprimir o relatrio em uma
impressora conectada.
Tocar no boto Reconhecimento do alarme (item 3 na pgina 5) desativa o bipe se o alarme ainda
estiver ativo. A tela Status do Alarme exibe o alarme at que ele seja limpo. Quando uma condio de
alarme retorna para o estado normal, o alarme ser removido da lista de alarmes ativos.
Quando nenhum alarme est ativado, o LED do painel frontal fica no estado Normal (continua verde) e
a janela de mensagem da tela Tela de status do sistema (local) l Todas as funes normais (Item 2 na
pgina 5).
Um aviso de Baixa temperatura ou Sonda fora ativo inibir todos os alarmes de nvel (Nvel mximo,
Transbordamento, Nvel mnimo, Abastecimento necessrio e gua alta).
49
Configurao do TLS2 Relatrios de alarmes
Alarme ativo
Quando um alarme est ativado, o bipe interno do console ativado, o rel de alarme ativado (se permitido),
a luz vermelha do LED do painel frontal pisca e a Janela de mensagem da tela (item 2 na pgina 5) exibe uma
mensagem de alarme. No caso de vrios alarmes, a Janela de mensagem rolar automaticamente pelos alarmes
ativos. No caso de um alarme atribudo discagem automtica, o console disca e estabelece uma conexo com
o host remoto. O host pode, ento, enviar pedidos ao console para determinar o motivo da chamada.
Quando um alarme ativado, o usurio pode desligar o bipe e desativar o rel de alarme, tocando no boto
ALARME (Item 3 na pgina 5). O LED do painel frontal permanecer no estado ALARME e o alarme
permanecer na lista de alarmes ativos at que ele retorne ao estado normal. Se o alarme estivar inativo
mas no for reconhecido, ele permanecer na lista de alarmes e o bipe e o rel de alarme (se permitido)
permanecero ativos at serem reconhecidos.
Com qualquer alarme, quando uma condio fora de limite for corrigida, ou um dispositivo com falha for
substitudo por um que esteja operando adequadamente, o alarme automaticamente limpo. Para
limpar um alarme de teste de vazamento com falha, um teste de vazamento passado deve ser retornado.
Se o volume do nvel de produto exceder o valor de Nvel mximo, o Alarme de nvel mximo ser ativado. Se o
alarme for ativado e o volume do nvel de produto for menor que o valor do Nvel mximo por pelo menos 0,005
vezes a capacidade do volume completo ou 10 gales [37,8 L] (o que for maior), o alarme ser desativado. O valor
do Nvel mximo inserido como um volume com o valor padro igual a 0. Se o valor do Nvel mximo for igual
a 0 ou igual a capacidade do volume completo do tanque, o alarme ser desativado. Um Aviso de baixa tem-
peratura da sonda ativo desativar esse alarme.
Alarme de transbordamento
Se o volume do nvel de produto for menor que o limite do Nvel mnimo, o Alarme de nvel mnimo ser ativado.
Se o alarme for ativado e o volume do nvel de produto for maior que o limite por pelo menos 0,005 vezes a
capacidade do volume completo ou 10 gales [37,8 L] (o que for maior), o alarme ser desativado. O valor do
Nvel mnimo inserido como um volume com o valor padro igual a 0. Se o valor for igual a 0, o alarme ser
desativado. Um Aviso de baixa temperatura da sonda ativo desativar esse alarme.
50
Configurao do TLS2 Relatrios de alarmes
Se a altura do nvel de gua exceder continuamente o limite de gua alta por um perodo excedente a 3 minutos,
o Aviso de gua alta ser ativado. O alarme de gua alta no ser ativado se houver um abastecimento em anda-
mento. Se o alarme estiver ativado e a altura do nvel de gua for menor que o limite por pelo menos 0,2 polegadas
(5 mm), o alarme ser desativado. O valor de gua alta inserido como um nvel com o valor padro igual a 0.
Se o valor for igual a 0, o alarme ser desativado. Um Aviso de baixa temperatura da sonda ativo desativar
esse alarme.
Se o console no estiver comunicando com a sonda de forma confiante, o alarme de Sonda fora ser ativado.
Se a bia de gua e a bia do produto estiverem muito prximas uma da outra para fornecer dados de nvel
confiveis, o alarme de Nvel de combustvel invlido ser ativado.
Sonda padro: Se a sonda estiver relatando uma temperatura menor que -4F (-20C), o aviso de Baixa
temperatura ser ativado. Se o alarme estiver ativado e a temperatura subir acima de 0F (-17,7C),
o alarme ser desativado.
Sonda com baixa temperatura: Alarme -40F (-40C), Limpar -36F (-37,7). Quando o aviso de baixa tempe-
ratura estiver ativado, os alarmes de gua alta, Nvel mximo, Nvel mnimo, Abastecimento necessrio
e Transbordamento sero desativados.
Quando o nvel de produto do tanque cai abaixo do limite atual, o alarme de Abastecimento necessrio
ser ativado.
Quando um teste de vazamento Bruto, Peridico ou Anual falhar, um alarme de teste de vazamento Bruto,
Peridico e Anual ser ativado. Para limpar um alarme de teste de vazamento com falha, um teste de vazamento
passado deve ser executado.
51
Telas de diagnstico
1 2 3
4 5 6
RED LED GREEN LED LCD OFF
7 8
52
Configurao do TLS2 Tela Teste de toque do LCD
Descrio
53
Configurao do TLS2 Tela de diagnstico da sonda
TANK 1
MAG 01
C000
360.000
1 2 3 4 5 66
Para exibir outro diagnstico das sondas do tanque, toque no boto Diagnstico do tanque desejado, na parte
inferior na tela.
Os dados da sonda de diagnstico para tanques configurados ou para tanques ativos ficaro disponveis
na Tela de diagnstico das sondas acima, em relatrios impressos e em comandos de srie. Um tanque
ativo definido como um tanque que possui uma sonda que esteja comunicando com o sistema.
Se o tanque for configurado mas no estiver ativo, todos os dados sero zero e o tipo de sonda
ser desconhecido.
Quando o software identifica as sondas que no possuem a capacidade de medio de temperatura, ele
inibir os dados relacionados temperatura. Para sondas que no possuem a capacidade de medio de
gua, ele inibir os dados relacionados gua.
54
ndice de cdigos de rtulos
Tabela 6 e Tabela 7 so includos para ajudar os usurios que no falam ingls a localizarem tradues de todos
os rtulos em ingls usados nas telas de configurao do TLS2. Abaixo de cada rtulo h um nico cdigo entre
colchetes, por exemplo, [101]. Esse cdigo listado nas tabelas a seguir e aponta para cada Tela de
configurao deste manual onde o rtulo usado.
Cdigo do
rtulo Rtulo Onde usado
55
Configurao do TLS2 Tela de diagnstico da sonda
Cdigo do
rtulo Rtulo Onde usado
Cdigo do
rtulo Rtulo Onde usado
56
Configurao do TLS2 Tela de diagnstico da sonda
Cdigo do
rtulo Rtulo Onde usado
57
Configurao do TLS2 Tela de diagnstico da sonda
Cdigo do
rtulo Rtulo Onde usado
58
SPANISH
Contenido
Introduccin
Requisitos de la certificacin del contratista ........................................................... 1
Manuales que se relacionan con ste ..................................................................... 1
Smbolos de seguridad ........................................................................................... 2
Advertencias de seguridad ...................................................................................... 2
Cumplimiento y aprobacin reglamentaria .............................................................. 3
Consola ................................................................................................................... 3
Funciones de monitoreo ....................................................................................... 3
Rel de salida....................................................................................................... 3
Funciones de comunicaciones ............................................................................. 3
ndice de referencia rpida para los mensajes de alarma ...................................... 4
i
Contenido
Informes
Informes del sistema ............................................................................................. 46
Informes de inventario (Inventory) ......................................................................... 47
Impresin de informe de ejemplo - Informe de inventario
con volumen de CT (Inventory with TC volume) ......................................... 47
Impresin de informe de ejemplo Informe de rotacin de inventario
con volumen de CT (Shift Inventory with TC volume) ................................. 47
Notas del informe de inventario (Inventory) ........................................................ 47
Pantalla de Estado de alarma activa (Active Alarm Status) .................................. 48
Informes de alarmas (Alarm) ................................................................................. 48
Notas importantes sobre las alarmas ................................................................. 49
Informacin sobre los estados de alarmas ............................................................ 50
Alarma activa ...................................................................................................... 50
Reconocimiento de una alarma activa................................................................ 50
Retorno al estado normal ................................................................................... 50
Informacin sobre la alarma en tanque ................................................................. 50
Alarma de producto mximo............................................................................... 50
Alarma de sobrecarga ........................................................................................ 50
Alarma de poco producto.................................................................................... 50
Alarma de agua alta............................................................................................ 51
Alarma de sonda fuera ....................................................................................... 51
Altura de combustible invlida ............................................................................ 51
Advertencia de temperatura baja en la sonda .................................................... 51
Alarma de suministro necesario ......................................................................... 51
Alarma de prueba de fugas ................................................................................ 51
ii
Contenido
Tablas
Tabla 1. Tabla de mensajes de alarma ............................................................... 4
Tabla 2. Coeficientes trmicos de los sistemas de EE. UU. y mtrico.............. 37
Tabla 3. Clculo de inclinacin del tanque ........................................................ 38
Tabla 4. Informes del sistema ........................................................................... 46
Tabla 5. Informes del sistema ........................................................................... 48
Tabla 6. Cdigos de etiqueta de configuracin del tanque ............................... 55
Tabla 7. Cdigos de etiqueta de configuracin del sistema .............................. 56
iii
Contenido
iv
Configuracin de TLS2
1
Configuracin de TLS2
2
Introduccin
Este manual describe los procedimientos de configuracin y operacin de la Consola del tanque de almacena-
miento subterrneo TLS2 (UST). Asumimos que un contratista autorizado ya configur su sistema. Este manual
supone que la consola ya est instalada y que se complet satisfactoriamente el procedimiento de calentamiento.
Debe comenzar el procedimiento de configuracin con las pantallas de configuracin del sistema (System Setup)
y finalizarlo con las pantallas de configuracin del tanque (Tank Setup).
Despus de introducir los parmetros de configuracin del sistema y del tanque, la consola podr comenzar a
funcionar. Consulte la seccin Informes para obtener las instrucciones que le ayudarn a ver los informes del
sistema y de alarma. En la seccin Diagnstico encontrar algunos procedimientos simples de prueba
de la consola y podr obtener acceso a los datos del diagnstico de sonda.
Es necesario que los contratistas que instalarn y configurarn el equipo que se menciona en este manual cuenten
con las siguientes certificaciones mnimas de capacitacin:
Nivel 1 Los contratistas que cuenten con la certificacin vlida del Nivel 1 podrn llevar a cabo el enrutamiento
del cableado y del conducto, el montaje del equipo, la instalacin de la sonda y el sensor, la preparacin del tanque
y de la lnea y la instalacin del detector de fugas de la lnea.
Nivel 2 y 3 Los contratistas que cuenten con las certificaciones vlidas de los niveles 2 3 podrn llevar a cabo la
revisin de la instalacin, el arranque, la capacitacin de programacin y operaciones, la solucin de problemas y
el servicio de todos los Sistemas de monitoreo del tanque Veeder-Root, entre los que se incluyen la deteccin de
fugas de lnea y los accesorios relacionados con sta.
1
Configuracin de TLS2
Smbolos de seguridad
Los smbolos de seguridad que se presentan a continuacin, se utilizan en este manual para advertirle acerca de los
peligros y las precauciones de seguridad ms importantes.
EXPLOSIVO INFLAMABLE
Los combustibles y sus vapores son Los combustibles y sus vapores son
extremadamente explosivos si se muy inflamables.
exponen al fuego.
Advertencias de seguridad
ADVERTENCIA
Este sistema funciona cerca de los tanques de almacenamiento de combus-
tible muy inflamable.
Los tanques que tienen fugas pueden ocasionar severos peligros ambientales
y para la salud. La programacin y la operacin incorrecta tambin pueden
ocasionar fallas en la prueba automtica del equipo, as como que la bomba
sumergible se apague.
2
Configuracin de TLS2
Disee su programa de deteccin de fugas de acuerdo con los reglamentos locales, estatales y federales que rigen
los tanques de almacenamiento subterrneo. Guarde todos los registros de inventario y de prueba de fugas que
proporcion el sistema como parte de un programa de aprobacin reglamentario.
Cuando el sistema est equipado con sondas magnetoestrictivas de 0.2 galones por hora (gph) (0.76 lph) (Mag 2),
est clasificado como un Sistema automtico de manmetro del tanque y ha sido probado por terceras personas en
el Instituto de Investigacin del Medio Oeste (Midwest Reseach Institute). Este sistema puede detectar una
fuga de 0.2 gph que excede una probabilidad de deteccin [P(D)] de 95% y que es inferior a una probabilidad de
falsa alarma [P(FA)] de 5%. El sistema cumple con los estndares federales de rendimiento de U.S.E.P.A.
(0.2 gph en [P(D)] de 95% y [P(FA)] de 5%) y con el estndar federal de rendimiento de la medicin de agua
en la parte inferior de un tanque que se aproxima a 1/8 inch (3.2 mm)
Cuando el sistema est equipado con sondas magnetoestrictivas de 0.1 gph (0.38 lph) (Mag 1), cumple con los
estndares del Mtodo de ensayo de la tensin volumtrica del tanque y ha sido probado por terceras personas en
el Instituto de Investigacin del Medio Oeste (Midwest Research Institute). Este sistema puede detectar una fuga
de 0.1 gph que excede una probabilidad de deteccin [P(D)] de 95% y que es inferior a una probabilidad de falsa
alarma [P(FA)] de 1%. Adems, cumple con los estndares federales de rendimiento U.S.E.P.A. (0.1 gph a [P(D)]
de 95% y [P(FA)] de 5%).
Consola
La consola TLS2 presenta una pantalla tctil del panel delantero, una alarma de doble uso/LED normal y un
zumbador audible para la notificacin de la alarma y de la advertencia. Los puertos en serie y paralelos de la
impresora se pueden conectar a una impresora remota. La consola TLS2 puede monitorear un mximo de seis
sondas magnetoestrictivas.
Funciones de monitoreo
Rel de salida
Es posible que un rel de salida pueda disparar los dispositivos externos de la alarma cuando el sistema detecta una
condicin de la misma.
Funciones de comunicaciones
RS-422
RS-485 de 2 4 cables
3
Configuracin de TLS2 ndice de referencia rpida para los mensajes de alarma
Reprobacin de Tanque Prueba anual de fugas en tanque Prueba de fugas en tanque repetida. Si
prueba anual reprobada. la segunda prueba falla, solicite servicio.
Suministro Tanque El nivel del producto est por debajo Solicite suministro.
necesario del lmite predefinido.
Agua alta Tanque Se detect que el agua del tanque Saque agua del tanque.
sobrepasa los lmites predefinidos.
Poco producto Tanque El nivel del tanque est por debajo Solicite suministro.
del lmite predefinido.
4
Pantallas de configuracin del sistema (System Setup)
Esta seccin describe todas las pantallas de configuracin del sistema TLS2 (TLS2 System Setup) y sus opciones de
configuracin, as como las explicaciones que necesitar para la entrada de datos. Debido a que las pantallas de confi-
guracin TLS2 slo tienen etiquetas en ingls, debajo de cada una de estas etiquetas se colocaron los cdigos de la etiqueta
de la pantalla entre corchetes para que pueda encontrar rpidamente una traduccin de la etiqueta y los nmeros de pgina de
la pantalla en donde se utilizar dicha etiqueta. Las pantallas de configuracin del tanque (Tank Setup) se describen en una
seccin separada.
La entrada de datos, la confirmacin de selecciones, etc. se realiza a travs de una de las diversas pantallas de entrada de
datos (Data Entry), las cuales aparecen cuando pulsa cualquier tecla que se encuentra a la derecha de una ventana de entrada
de datos. Estas pantallas ya se describieron en esta seccin.
11
5
5
Configuracin de TLS2 Pantalla del men principal (Main Menu)
1 2
6 3
II
5 4
consoles/tls2/menuscrn.eps
6
Configuracin de TLS2 Pantalla de Configuracin del sistema (System Setup)
2 3 4
1
6 7
5
8
10 11 12
1 Tecla Idioma (Language) - pulse para mostrar la 8 Tecla Temperatura (Temp) - pulse para mostrar la
pantalla de Configuracin de idioma y unidades pantalla de Configuracin de la temperatura
(Language and Units) (pgina 8). (Temperature Setup) (pgina 30).
2 Tecla Tiempo actual (Current Time) - pulse para 9 Tecla Seguridad (Security) - pulse para mostrar la
mostrar la pantalla de Configuracin de fecha pantalla de Configuracin de seguridad del sistema
y hora (Time/Date Setup) (pgina 13). (System Security Setup) (pgina 12).
3 Tecla Comunicaciones (Comm) - pulse para mostrar 10 Tecla Ahorro diurno de energa (Daylight Savings) -
la pantalla de Configuracin de comunicaciones pulse para mostrar la pantalla de Configuracin de
(Comm Setup) (pgina 22). ahorro diurno de energa (Daylight Savings Setup)
4 Tecla Rel de alarma (Alarm Relay) - pulse para (pgina 17).
mostrar la pantalla de Configuracin del rel de 11 Tecla Alarmas de marcacin automtica (Autodial
alarma (Alarm Relay Setup) (pgina 29). Alarms) - pulse para mostrar la pantalla de Confi-
5 Tecla Encabezado (Header) - pulse para mostrar la guracin de alarmas de marcacin automtica
pantalla de Configuracin del encabezado de la (Autodial Alarms Setup) (pgina 19).
estacin (Station Header Setup) (pgina 9). 12 Tecla Protocolo europeo (EuroProtocol) - pulse para
6 Tecla Tiempo de rotacin (Shift Time) - pulse para mostrar la pantalla de Configuracin de compen-
mostrar la pantalla de Configuracin de los tiempos sacin de la varilla y de EuroProtocol (EuroProtocol
de rotacin (Setup Shift Times) (pgina 16). and Stick Offset Setup) (pgina 31). Esta pantalla
tambin le permite seleccionar un formato de informe
7 Tecla Configuracin de marcacin (Dialing Setup) - de prueba de fugas.
pulse para mostrar la pantalla de Configuracin de
marcacin saliente de configuracin del sistema
(System Setup Dial Out Setup) (pgina 18).
7
Configuracin de TLS2 [201-203] Pantalla de Configuracin de idioma y unidades del sistema (System Language and Units Setup)
1
[201]
2
[202]
3
[203]
8
Configuracin de TLS2 [204-207] Pantalla de Configuracin del encabezado de la estacin (Station Header Setup)
1
[204]
2
[205]
3
[206]
4
[207]
9
Configuracin de TLS2 Pantalla de Teclado alfabtico (Alpha Keypad)
10
4 SAVE
5 6 7 8 9
1 Muestra el ttulo de los datos que se van a introducir. 7 Tecla derecha del cursor (Cursor right) - pulse para
2 La ventana de datos introducidos (Data Entered) mover el cursor una posicin hacia la derecha en la
muestra los datos que ya se introdujeron. ventana de datos introducidos (2) (Data Entered).
3 Teclas del teclado alfabtico - pulse una tecla de un 8 Tecla de retroceso para eliminar (Backspace delete) -
carcter para colocar ese carcter en la ventana de pulse para eliminar los caracteres que aparecen en
datos introducidos (2) (Data Entered). el cursor.
4 Tecla Guardar (Save) - pulse para aceptar los datos 9 Tecla Teclado numrico (Number keypad) - pulse
que se introdujeron y cerrar la pantalla. para mostrar la pantalla de Teclado numrico.
5 Tecla Cancelar (Cancel) - pulse para cancelar 10 Tecla Borrar (Clear) - pulse para borrar el contenido
cualquier entrada y cerrar la pantalla. de la ventana de datos introducidos (2) (Data
Entered).
6 Tecla izquierda del cursor (Cursor left) - pulse para
mover el cursor una posicin hacia la izquierda en
la ventana de datos introducidos (2) (Data Entered).
10
Configuracin de TLS2 Pantalla de Teclado numrico (Numeric Keypad)
10
4 SAVE 9
5 6 7 8
1 Muestra el ttulo de los datos que se van a introducir. 7 Tecla derecha del cursor (Cursor right) - pulse para
2 La ventana de datos introducidos (Data Entered) mover el cursor una posicin hacia la derecha en la
muestra los datos que ya se introdujeron. Ventana de datos introducidos (2) (Data Entered).
3 Teclas del teclado numrico (Numeric Keypad) - 8 Tecla de retroceso para eliminar (Backspace delete) -
pulse una tecla de un carcter para colocar ese pulse para eliminar los caracteres que aparecen
carcter en la ventana de datos introducidos el cursor.
(Data Entered) (2). 9 Tecla del teclado alfabtico (Alpha keypad) - pulse
4 Tecla Guardar (Save) - pulse para aceptar los datos para mostrar la pantalla de Teclado alfabtico
que se introdujeron y cerrar la pantalla. (Alpha Keypad).
5 Tecla Cancelar (Cancel) - pulse para cancelar 10 Tecla Borrar (Clear) - pulse para borrar el contenido
cualquier entrada y cerrar la pantalla. de la ventana de datos introducidos (2)
(Data Entered).
6 Tecla izquierda del cursor (Cursor left) - pulse para
mover el cursor una posicin hacia la izquierda en
la ventana de datos introducidos (2) (Data Entered).
11
Configuracin de TLS2 [208-211] Pantalla de Configuracin de seguridad del sistema (System Security Setup)
1 COMM 1 PASSWORD
[208]
2 COMM 1 PASSWORD
[209]
3 COMM 2 PASSWORD
[210]
4 COMM 2 PASSWORD
[211]
12
Configuracin de TLS2 [212-214] Pantalla de Configuracin de fecha y hora del sistema (System Time/Date Setup)
1 10-04-01
[212]
2
[213] 13-54
13
Configuracin de TLS2 Pantalla de Entrada de fecha actual (Current Date Entry)
1 2001 3
14
Configuracin de TLS2 Pantalla de Entrada de hora actual (Current Time Entry)
1 3
15
Configuracin de TLS2 [215-218] Pantalla de Configuracin de tiempos de rotacin (Shift Times Setup)
1
[215]
2
[216]
3
[217]
4
[218]
En cada hora inicial de rotacin que seleccione a 7 Rotacin 2 [216] - pulse la tecla Hora (Time) que se
continuacin, el sistema automticamente guarda encuentra a la derecha de la ventana e introduzca
un informe completo del inventario en la memoria. la hora inicial de rotacin 2 y AM o PM.
La configuracin predeterminada se desactiva para 8 Rotacin 3 [217] - pulse la tecla Hora (Time) que se
todas las rotaciones. encuentra a la derecha de la ventana e introduzca
NOTA: Se debe introducir por lo menos un tiempo inicial la hora inicial de rotacin 3 y AM o PM.
de rotacin para activar la funcin ltimo inventario
9 Rotacin 4 [218] - pulse la tecla Hora (Time) que se
de rotacin.
encuentra a la derecha de la ventana e introduzca
6 Rotacin 1 [215] - pulse la tecla Hora (Time) que se la hora inicial de rotacin 4 y AM o PM.
encuentra a la derecha de la ventana e introduzca
la hora inicial de rotacin 1 y AM o PM.
16
Configuracin de TLS2 [219-223] Pantalla de Configuracin del tiempo de ahorro diurno de energa (Daylight Savings Time Setup)
1 ENABLE
[219]
2 APR WEEK 1 SUN
[220]
3
[221] 2:00 AM
Esta funcin le permite introducir las fechas y las horas 3 Fecha inicial [221] - pulse la tecla Hora (Time) que se
iniciales y finales del ahorro de energa diurno. Una vez encuentra a la derecha de la ventana e introduzca
se activan, el sistema ajustar automticamente el la hora inicial [y AM o PM] (el valor predeterminado
tiempo del ahorro de energa diurno en las fechas y es 02:00 AM).
horas que usted introduzca. 4 Fecha final [222] - pulse la tecla Fecha (Date) que se
1 Ahorro de energa diurno [219] - pulse la tecla Flecha encuentra a la derecha de la ventana e introduzca la
hacia abajo (Down Arrow) que se encuentra a la fecha final (el valor predeterminado es OCT
derecha de la ventana y seleccione Activar o Desac- SEMANA 6 DOMINGO (OCT WEEK 6 SUN).
tivar (el valor predeterminado es Desactivar). 5 Fecha final [223] - pulse la tecla Hora (Time) que se
2 Fecha inicial [220] - pulse la tecla Fecha (Date) que encuentra a la derecha de la ventana e introduzca
se encuentra a la derecha de la ventana e introduzca la hora final [y AM o PM] (el valor predeterminado
la fecha inicial (el valor predeterminado es ABR es 02:00 AM).
SEMANA 1 DOMINGO (APR WEEK 1 SUN).
17
Configuracin de TLS2 [224-226] Pantalla de Configuracin de marcacin saliente automtica (Auto-Dialout Setup)
1 PHONE
[224]
2 RETRIES
[225]
3 RETRY DELAY
[226]
Para esta funcin es necesario que el mdem est 3 Demora de reintento [226] - pulse la tecla Numrico
seleccionado como el tipo de comunicacin. (Numeric) que se encuentra a la derecha de la ven-
tana e introduzca el nmero de minutos (entre 1 y
1 Telfono [224] - pulse la tecla Numrica (Numeric) 99) que desea que la computadora se demore antes
que se encuentra a la derecha de la ventana e de marcar de nuevo el nmero de telfono si hay
introduzca el nmero de telfono que desea que seal de ocupado, si no hay respuesta o si hay
marque el sistema. una conexin incompleta (el valor predeterminado
2 Reintentos [225] - pulse la tecla Numrica que se es 3 reintentos).
encuentra a la derecha de la ventana e introduzca
el nmero de veces (entre 1 y 99) que desea que el
sistema marque el nmero de telfono si hay seal
de ocupado, si no hay respuesta o si hay una co-
nexin incompleta (el valor predeterminado es
3 reintentos).
18
Configuracin de TLS2 [227-230] Pantalla de Configuracin de alarma de marcacin automtica 1 (Autodial Alarm Setup 1)
1
[227]
2
[228]
3
[229]
4
[230]
5
1 2 3 4 5 6
19
Configuracin de TLS2 [231-234] Pantalla de Configuracin de alarma de marcacin automtica 2 (Autodial Alarm Setup 2)
1
[231]
2 6
[232]
3
[233] 7
4
[234] 8
11 22 33 4
4 5
5 6
6
20
Configuracin de TLS2 [235-237] Pantalla de Configuracin de alarma de marcacin automtica 3 (Autodial Alarm Setup 3)
1
[235]
2
[236]
3
[237]
11 22 33 4
4 5
5 6
6
21
Configuracin de TLS2 [238-239] Pantalla de Configuracin en serie 1 del puerto de comunicaciones 1 y 2 (Comm Port 1 and 2 Serial Setup 1)
1
[238]
2
[239]
3 4 5 6
Esta pantalla es parecida a la configuracin del puerto 3 Tecla Comunicaciones 1 (COMM 1) - pulse para
de comunicaciones 1 y 2. mostrar la pantalla de Configuracin de comuni-
1 Tipo de comunicaciones [238] - pulse la tecla Flecha caciones 1 (Comm 1 Setup) (que aparece
hacia abajo (Down Arrow) que se encuentra a la anteriormente).
derecha de la ventana y seleccione lo siguiente: 4 Tecla Comunicaciones 2 (COMM 2) - pulse para
Si es el puerto de comunicaciones 1: mostrar la pantalla de Configuracin de comuni-
caciones 2 (Comm 2 Setup).
En serie, mdem, impresora o ninguno
(predeterminado) 5 Tecla Paralelo (PARALLEL) - pulse para mostrar
la pantalla de Configuracin del puerto paralelo
Si es el puerto de comunicaciones 2:
(Parallel Port Setup) (pgina 28).
En serie o ninguno (predeterminado)
6 Tecla Hacia abajo (Down) - pulse para mostrar la
2 Enlace [239] - pulse la tecla Flecha hacia abajo pantalla de Configuracin del puerto de comuni-
(Down Arrow) que se encuentra a la derecha de caciones 2 (Comm Port Setup 2) (pgina 25).
la ventana y seleccione Ninguno, XON/XOFF o
hardware (predeterminado). Este parmetro es
idntico para el puerto de comunicaciones 1 y 2.
22
Configuracin de TLS2 [241] Pantalla de Configuracin de la impresora del puerto de comunicaciones 1 (Comm Port 1 Printer Setup)
[238]
1
[241] 9
[239]
2 PRINTER LANG EPSON ESC/P
[253] 3
23
Configuracin de TLS2 [244-246] Pantalla de Configuracin del mdem 1 del puerto de comunicaciones 1 (Comm Port 1 Modem Setup 1)
[238]
2
[244]
3
[245]
4 5
[246]
24
Configuracin de TLS2 [249-252] Pantalla de Configuracin del puerto de comunicaciones 2 (Comm Port Setup 2)
1 9600
[249]
2 ODD
[250]
3 7
[251]
4
[252]
25
Configuracin de TLS2 [247-248] Pantalla de Configuracin de comunicaciones avanzadas (Advanced Communications Setup)
1 DIAL IN AT&B1
[247]
2 AT&B1
[248]
PRECAUCIN!
Si introduce las cadenas con los nmeros equivo-
cados en esta pantalla puede desactivar el mdem.
26
Configuracin de TLS2 Pantalla de Entrada de datos (Data Entry)
1
[249]
2 SAVE 3
27
Configuracin de TLS2 Pantalla de Configuracin de puerto paralelo (Parallel Port Setup)
1 COMM TYPE
[238]
2 PAGE EJECT
[238]
9
3 PRINTER LANG EPSON ESC/P
[253]
28
Configuracin de TLS2 [256] Pantalla de Configuracin de rel de alarma (Alarm Relay Setup)
1
[256]
29
Configuracin de TLS2 [257-258] Pantalla de Configuracin de temperatura (Temperature Setup)
1 59 F
[257]
2
[258]
30
Configuracin de TLS2 [259-262] Pantalla de Configuracin de protocolo europeo y de compensacin de la varilla (EuroProtocol and Stick Offset Setup)
1
[259]
2
[260]
3
[261]
4
[262]
31
Configuracin de TLS2 Pantalla Acerca de TLS2 (About TLS2)
SYSTEM FEATURES
STATIC TANK LEAK DETECT
Esta pantalla contiene informacin sobre el software y las funciones que se instalaron en la consola de TLS2:
Nivel de revisin del software del sistema
Nmero de versin del software
Nmero de repuesto del software
Fecha de creacin del software
Funciones del sistema: Deteccin de fugas del tanque esttico
32
Pantallas de Configuracin del tanque (Tank Setup)
1 2
33
Configuracin de TLS2 [119-121] Pantalla de Configuracin del tanque 1 (Tank Setup)
TANK 1
1 CONFIGURED
[119]
2
[120]
3
[121]
1 2 3 4 5 6
34
Configuracin de TLS2 [122-124] Pantalla de Configuracin del tanque 2 (Tank Setup)
TANK 1
1
[122]
2
[123]
3
[124]
1 2 3 4 5 6
En esta pantalla contina la configuracin del tanque. Tenga cuidado de introducir el valor exacto del
1 Dimetro [122] - pulse la tecla Flecha hacia abajo cuadro del tanque para la altura etiquetada.
(Down Arrow) que se encuentra a la derecha de la No se aceptan las entradas fuera de intervalo.
ventana e introduzca el dimetro del tanque. Si selecciona el perfil de 4 puntos o el de 20
2 Volumen completo [123] - pulse la tecla Flecha hacia puntos, debe introducir un volumen para cada
abajo (Down Arrow) que se encuentra a la derecha punto o el sistema calcular un volumen de
de la ventana e introduzca el volumen completo 0 para cualquier altura.
del tanque. Parmetros de configuracin del tanque contina en la
pgina siguiente.
3 Perfil del tanque [124] - pulse la tecla Flecha hacia
abajo (Down Arrow) que se encuentra a la derecha de
la ventana y seleccione un perfil del tanque: Lineal
para tanques rectangulares o tanques cilndricos que
se apoyan en un extremo, 1 punto para tanques de
acero de extremo plano (predeterminado), 4 puntos
para tanques de fibra de vidrio o 20 puntos para todos
los tanques.
4 Tecla Cuadro del tanque (Tank Chart) - Esta tecla
slo aparece cuando selecciona el perfil del tanque
de 4 puntos o el de 20 puntos.
El sistema calcular las Alturas para cada punto
(4 20) con base en el perfil seleccionado y en el
dimetro del tanque y los mostrar junto a las
ventanas en las que debe introducir el volumen
correspondiente. Busque el volumen para las
alturas que se muestran en el cuadro del tanque
e introdzcalo en la ventana.
35
Configuracin de TLS2 [125-128] Pantalla de Configuracin del tanque 3 (Tank Setup)
TANK 1
1
[125] 0.00070
2
[126] 0 IN
3
[127]
4
[128]
1 2 3 4 5 6
Con esta pantalla concluye la configuracin del tanque. valor de la columna G de la hoja de clculo como la
1 Coeficiente trmico [125] - pulse la tecla Flecha hacia inclinacin del tanque.
abajo (Down Arrow) que se encuentra a la derecha 3 Tamao del flotador [127] - pulse la tecla Flecha hacia
de la ventana e introduzca el dimetro del tanque. abajo (Down Arrow) que se encuentra a la derecha de
Para asegurar el clculo correcto de volumen compen- la ventana y de los tamaos de flotador que se pre-
sado por temperatura, debe introducir correctamente sentan, introduzca el tamao del flotador de la sonda
el coeficiente de expansin trmica. Un valor incorrecto magnetoestrictiva que instal en la sonda del tanque.
afectar de manera adversa las pruebas de deteccin 4 Compensacin de la varilla [128] - pulse la tecla
de fugas y los valores del inventario de temperatura Flecha hacia abajo (Down Arrow) que se encuentra
compensada. a la derecha de la ventana e introduzca un valor de
Tabla 2 enumera los coeficientes para combustibles compensacin de la varilla. El intervalo permitido es
y lquidos aprobados en el sistema de los E.E.U.U. de -144 a +144 pulgadas (de -365.76 a +365.76 cm)
y mtrico. Introduzca el coeficiente en unidades del y el valor predeterminado es 0.
sistema de los E.E.U.U. y mtrico, dependiendo de las Nota: Para introducir un valor de compensacin de la
unidades que especifique la configuracin del sistema varilla, la opcin de compensacin de la varilla debe
(pgina 8). Tenga cuidado de agregar el nmero estar activada (pgina 31) y debe calcular e introducir
correcto de ceros a la derecha del punto decimal. la inclinacin del tanque (si fuera necesario). Puede
Una entrada incorrecta puede ocasionar fallas en introducir la compensacin de la varilla para que la
las pruebas y otros problemas. altura (producto) de la sonda parezca igual a la
2 Inclinacin del tanque [126] - pulse la tecla Flecha lectura del calibre de la varilla de la altura del pro-
hacia abajo (Down Arrow) que se encuentra a la ducto - Esta entrada es nicamente para convenien-
derecha de la ventana e introduzca la inclinacin cia del operador y por lo tanto no tiene ninguna
del tanque. El intervalo permitido es de -144 a +144 relacin con los clculos de volumen del producto.
pulgadas (de -365.76 a +365.76 cm) y el valor Para determinar el valor que debe introducir para la
predeterminado es 0. compensacin de la varilla, registre la lectura de la
La inclinacin del tanque le permite realizar ajustes altura de la sonda en el tanque. Si la lectura de la
para la diferencia entre la altura del combustible en la altura del combustible en la sonda es menor que la
ubicacin de la sonda y el centro del tanque causada lectura de la varilla, introduzca la diferencia positiva
por la inclinacin del tanque. Debe introducir un signo que hay entre las dos. Si la lectura de la sonda es
menos (-) si la inclinacin del tanque es un valor nega- mayor que la lectura de la varilla, introduzca la
tivo. No se requiere un valor de inclinacin del tanque diferencia negativa que hay entre las dos. Por
si la sonda se encuentra en el centro del tanque. Si la ejemplo, si la altura de la varilla es igual a 52 y la
sonda est instalada en el centro del tanque, el valor altura de la sonda es igual a 48, debe introducir
que debe introducir es 000.00 en unidades del sistema +4; si la altura de la varilla es igual a 52 y la altura
de E.E.U.U. o 0000.0 en unidades del sistema mtrico. de la sonda es igual a 54, debe introducir -2.
Si la sonda no se encuentra al centro del tanque,
calcule la inclinacin del tanque utilizando las instruc-
ciones que se encuentran en la Tabla 3. Introduzca el
36
Configuracin de TLS2 [125-128] Pantalla de Configuracin del tanque 3 (Tank Setup)
Coeficiente Coeficiente
trmico trmico
(Unidades del (Unidades del
sistema de sistema
Producto los E.E:U.U.) mtrico)
37
Configuracin de TLS2 [125-128] Pantalla de Configuracin del tanque 3 (Tank Setup)
A B C D E F G
Calibre de la Lectura de la
varilla altura del
Promedio. combustible de Distancia Distancia desde
Altura la sonda Llenar hasta el Cuello de la Paso del
No. de @ cuello (Cuello de cuello de la Paso sonda al centro tanque*
tanque de llenado la sonda) (A - B = C) sonda (C / D = E) del tanque (E x F = G)
6
* La inclinacin del tanque puede ser un valor positivo (+) o negativo (-). Si es un valor negativo, ASEGRESE de cambiar
el signo del valor a menos (-) cuando introduzca un valor negativo de inclinacin del tanque.
38
Configuracin de TLS2 [101-104] Pantalla de Configuracin de lmites del tanque 1 (Tank Limits Setup)
1
[101]
2
[102]
3
[103]
4
[104]
1 2 3 4 5 6
En esta pantalla inicia la configuracin de lmites de Este valor es un porcentaje de volumen completo
alarma del tanque. con un intervalo permitido de 0 a 100%. El valor pre-
1 Producto mximo [101] - Produce una advertencia determinado es 0% (el cual desactiva la alarma).
cuando el nivel del fluido del tanque excede el volumen Pulse la tecla Flecha hacia abajo (Down Arrow) que
que se haya ingresado aqu. El intervalo permitido es se encuentra a la derecha de la ventana e introduzca
de 0 a 26000 galones (de 0 a 98420 litros). El valor un volumen ms alto que aquel de la alarma de
predeterminado es 0. Si el valor que introdujo es poco producto.
0 o volumen completo, la alarma se desactiva. Una 4 Poco producto [104] - Poco producto produce una
advertencia de temperatura baja en la sonda desac- advertencia cuando el nivel de flujo en el tanque
tivar la alarma. Pulse la tecla Flecha hacia abajo disminuye por debajo del volumen que se haya ingre-
(Down Arrow) que se encuentra a la derecha de sado aqu. El intervalo permitido es de 0 a 26000
la ventana e introduzca el producto mximo para galones (de 0 a 98420 litros). El valor predeterminado
el tanque. es 0 (el cual desactiva la alarma). Una advertencia
2 Sobrecarga [102] - Produce una advertencia de sobre- activa de temperatura baja de la sonda desactivar
carga potencial durante un suministro. Cuando el esta alarma. Pulse la tecla Flecha hacia abajo (Down
volumen alcanza este nivel el sistema puede activar Arrow) que se encuentra a la derecha de la ventana e
una alarma de sobrecarga. El umbral de la alarma de introduzca este valor en un volumen menor que el de
sobrecarga tiene relacin con el valor de producto la alarma de suministro necesario.
mximo. Si el valor de producto mximo es 0, el NOTA: Generalmente esta alarma se establece en el
umbral de alarma de sobrecarga tiene relacin con nivel ms bajo antes de que la bomba se quede sin
la capacidad de volumen completo. El intervalo per- lquido.Toda la distribucin se debe detener cuando
mitido es de 0 a 100%. El valor predeterminado es 0 se activa esta alarma.
(activado). Una advertencia activa de temperatura baja Configuracin de lmite de alarma del tanque contina en
en la sonda desactivar esta alarma. la pgina siguiente.
3 Suministro necesario [103] - Suministro necesario
advierte cuando el nivel de lquidos en el tanque cae
a un nivel en el que el operador necesita un suministro.
39
Configuracin de TLS2 [105-108] Pantalla de Configuracin de limites del tanque 2 (Tank Limits Setup)
1
[105]
2
[106]
3
[107]
4
[108]
1 2 3 4 5 6
En esta pantalla contina la configuracin de lmites de 3 Mnimo de prueba de fugas anual [107] - Este valor
alarma del tanque. establece el volumen mnimo del tanque que se
1 Agua alta [105] - Cuando el agua en el tanque sube necesita para registrar una prueba de fugas anual
hasta la altura que se haya ingresado aqu. Fije este l aprobada. El valor refleja los requisitos federales,
nivel a una altura inferior al de la altura de captacin de estatales y locales. Este valor es un porcentaje de
la bomba sumergible o la lnea de succin. El intervalo volumen completo con un intervalo permitido de 1.0 a
permitido es de 0 a 9 pulgadas (de 0 a 228.6 mm). 100%. El valor predeterminado es 0 (el cual desactiva
El valor predeterminado es 0 (el cual desactiva la la alarma). Pulse la tecla Flecha hacia abajo (Down
alarma). Pulse la tecla Flecha hacia abajo (Down Arrow) que se encuentra a la derecha de la ventana
Arrow) que se encuentra a la derecha de la ventana e introduzca un volumen.
e introduzca el lmite de agua alta que desea. 4 Mnimo de prueba de fugas peridicas [108] - Este
2 Demora en suministro [106] - utilice esta pantalla para valor establece el volumen mnimo del tanque, nece-
establecer un tiempo de demora entre la terminacin sario para registrar una prueba de fugas peridicas
de un suministro a granel y el de aumento de suminis- aprobada. El valor refleja los requisitos federales,
tro (Delivery Increase). Esta funcin evita la generacin estatales y locales. Este valor es un porcentaje de
de varios informes durante los intervalos entre disminu- volumen completo con un intervalo permitido de 1.0
ciones de multicompartimientos a un tanque. La fun- a 100%. El valor predeterminado es 0 (el cual desac-
cin tambin permite que el combustible se sedi- tiva la alarma). Pulse la tecla Flecha hacia abajo
mente despus de un suministro, lo que es especial- (Down Arrow) que se encuentra a la derecha de la
mente importante en grupos de tanques distribuidos. ventana e introduzca un volumen.
La demora permitida es de 1 a 60 minutos. El valor La configuracin de lmite de alarma del tanque contina
predeterminado es 1. Pulse la tecla Flecha hacia abajo en la pgina siguiente.
(Down Arrow) que se encuentra a la derecha de la
ventana e introduzca la demora que desee.
40
Configuracin de TLS2 [109-111] Pantalla de Configuracin de lmites del tanque 3 (Tank Limits Setup)
1
[109]
2
[110]
3
[111]
1 2 3 4 5 6
41
Configuracin de TLS2 [112-114] Pantalla de Configuracin de prueba de fugas del tanque 1 (Tank Leak Test Setup)
1 0.2 GPH
[112]
2 EARLY STOP
[113]
3
[114]
1 2 3 4 5 6
La configuracin de prueba de fugas del tanque le permite Han pasado menos de 8 horas desde el
establecer e introducir el mtodo, el tiempo y la duracin ltimo suministro.
de las pruebas de fugas automticas. Debe tener instalada La temperatura del producto es menor que
una sonda magnetoestrictiva 1 2 para realizar las 0F (-17.6C) o mayor que +100F (+37.4C).
pruebas de fugas.
Hay muy poco combustible en el tanque.
Si utiliza la funcin prueba de fugas en tanque de confor-
midad con las normas de almacenamiento subterrneo, Pulse la tecla Flecha hacia abajo (Down Arrow) que
asegrese de que los lmites de prueba de fugas que se encuentra a la derecha de la ventana e introduzca
establece e introduce cumplen con los requisitos de tipo de la eleccin deseada.
prueba, exactitud y frecuencia que definen las autoridades 3 Duracin de la prueba [114] - La duracin mxima
reguladoras del condado, estatales o federales que es de 24 horas. Existe una duracin mnima de dos
gobiernan su localidad. horas para pruebas de 0.2 gph (0.76 lph) y de tres
Adems, establezca el momento de la prueba para un horas para pruebas de 0.1 gph (0.38 lph).
perodo donde no ocurra carga de gasolina o suministro Nota: Si tiene activada Detencin anticipada y la
a granel al tanque. Dichas actividades durante un proce- consola determina que aprob la prueba de fugas del
dimiento de prueba de fugas puede ocasionar resultados tanque, la misma termina antes de que se cumpla la
incorrectos de prueba de fugas. duracin de la prueba. La duracin predeterminada
1 Prueba de tasa [112] - Puede establecer la tasa de es de 2 horas. Pulse la tecla Flecha hacia abajo
prueba de fugas en 0.2 gph (0.76 lph) (predeter- (Down Arrow) que se encuentra a la derecha de
minado) 0.1 gph (0.38 lph). Si selecciona 0.1 gph la ventana e introduzca la eleccin deseada.
(0.38 lph) necesita una sonda magnetoestrictiva 1. 4 Tecla Igual en todos los tanques (Same All Tanks) -
Pulse la tecla Flecha hacia abajo (Down Arrow) que pulse esta tecla para transferir las selecciones idnti-
se encuentra a la derecha de la ventana e introduzca cas que realiz en esta pantalla del Tanque (Tank)
la opcin que desea. 1 a todos los tanques (abre la pantalla Igual en todos
2 Detencin anticipada [113] - La configuracin predeter- los tanques (Same All Tanks) que se encuentra en
minada es Desactivada. Si esta funcin est activada la pgina 43).
evitar que empiece una prueba de fugas en tanque Configuracin de prueba de fugas del tanque concluye en
bajo las siguientes condiciones: pgina 44.
El volumen del tanque es menor que el valor
peridico mnimo de fugas o que el valor anual
mnimo de fugas.
42
Configuracin de TLS2 [115] Pantalla Igual en todos los tanques (Same All Tanks)
1
[115]
2 SAVE 3
43
Configuracin de TLS2 [116-118] Pantalla de Configuracin de prueba de fugas del tanque 2 (Tank Leak Test Setup)
TANK 1
1
[116]
2 DATE/DAY
[117]
3
[118]
1 2 3 4 5 6
44
Inicio e interrupcin manual de pruebas de fugas del tanque
Utilice esta pantalla para iniciar o interrumpir de forma manual la prueba de fugas del tanque.
1
[129]
2 5
[130]
3 0.76 LPH 6
[112]
4
[114]
1 2 3 4 5 6
1 Mtodo de prueba [129] - Seleccione un tanque nico 4 Duracin de la prueba [114] - Seleccione
o todos los tanques. Pulse la tecla Flecha hacia abajo una duracin de prueba de 0 a 24 horas.
(Down Arrow) que se encuentra a la derecha de la Existe una duracin mnima de dos horas
ventana e introduzca la opcin que desee. para pruebas de 0.2 gph (0.76 lph) y de tres
2 Control de prueba [130] - Seleccione la duracin horas para pruebas de 0.1gph (0.38 lph).
temporizada o la interrupcin manual (la prueba se El valor predeterminado son dos horas.
ejecuta hasta que la interrumpe o al transcurrir 24 Nota: esta ventana slo aparece si seleccio-
horas, cualquier condicin que se presente primero). n la duracin temporizada en la ventana
Pulse la tecla Flecha hacia abajo (Down Arrow) que de control de prueba (Test Control). Pulse la
se encuentra a la derecha de la ventana e introduzca tecla Flecha hacia abajo (Down Arrow) que
la opcin que desee. se encuentra a la derecha de la ventana
e introduzca la opcin que desee.
3 Velocidad de prueba [112] - Seleccione una velocidad
de prueba de fugas de 0.2 gph (0.76 lph) (predeter- 5 Tecla Inicio de prueba (Test Start) - pulse
minado) o de 0.1 gph (0.38 lph). La velocidad de esta tecla para iniciar la prueba.
0.1 gph (0.38 lph) necesita una sonda magnetoes- 6 Tecla Interrupcin de prueba (Test Stop) -
trictiva 1. Pulse la tecla Flecha hacia abajo (Down pulse esta tecla para interrumpir una
Arrow) que se encuentra a la derecha de la ventana prueba de fugas del tanque.
e introduzca la opcin que desee.
45
Informes
Se obtiene acceso a los informes del sistema desde la pantalla de Estado del sistema (local)
(System Status) (consulte la pgina 5) al pulsar una de las cuatro teclas de informe que se
encuentran en la parte inferior de la pantalla. La Tabla 4 describe los informes del sistema que se
encuentran disponibles.
Tecla Informe
(Report) Informe Parmetros del informe
CURRENT TEST
RESULTADOS DE PRUEBA ACTUAL
RESULTS
Tipo de prueba, fecha y hora inicial, resultado de la
Pulse la tecla Resultados de prueba prueba, horas transcurridas, % de volumen en el tan-
actual (Current Test Results) para que en el momento de la prueba.
mostrar los resultados de las prue-bas
anuales, peridicas y generales ms
recientes. Puede pulsar la tecla Imprimir
(Print) en la pantalla para imprimir el
informe en una impresora conectada.
Pulse para mostrar
la pantalla de
Informes
ambientales
(Environmental).
Cuando se muestra
esta pantalla puede
seleccionar uno de INFORME DE LTIMA APROBACIN COMPLETA
estos dos informes (FULLEST LAST PASS)
de prueba. Pulse la tecla ltima aprobacin com-
pleta (Fullest Last Pass) para mostrar Tipo de prueba, fecha y hora inicial, horas transcu-
los resultados de las lti-mas 12 rridas, % de volumen en el tanque en el momento
pruebas peridicas (1 por cada mes) de la prueba.
y de la ltima prueba anual en la cual
el tanque tena el volumen ms alto.
Puede pulsar la tecla Imprimir (Print) en
la pantalla para imprimir el informe en
una impresora conectada.
46
Configuracin de TLS2 Informes de inventario (Inventory)
37.3 F
1
5329 GAL
(5413 GAL TC)
2
72 IN
WATER 0.0 IN
1 2 3 4 5 6
Para consultar los informes de inventario (inventory) de cualquier otro tanque pulse la tecla Informe de inventario
(Inventory) que corresponda a ese tanque, la cual se encuentra en la parte inferior de la pantalla. Para ver el informe
de rotacin de inventario (shift inventory) del tanque, pulse la tecla Rotacin de inventario (Shift Inventory) (ele-
mento 1 de la pantalla anterior). Para ver la altura de la varilla (si est activada), pulse la tecla Varilla delta (Delta
Stick) (elemento 2 de la pantalla anterior).
Impresin de informe de ejemplo - Informe de inventario con volumen de CT (Inventory with TC volume)
T1:REGULAR UNLEADED
TANK VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP
1 5329 5413 4500 48.8 0.0 37.3
2 5329 5413 4500 48.8 0.0 37.3
T1:REGULAR UNLEADED
TANK PRODUCT
1 REGULAR UNLEADED VOLUME TC VOLUMEN ULLAGE HEIGHT WATER TEMP
SHIFT 1 STARTING VALUES 8518 8492 1482 76.26 0.0 64.7
ENDING VALUES 8518 8492 1482 76.26 0.0 64.7
DELIVERY VALUE 0
TOTALS 0
SHIFT 2 STARTING VALUES 8518 8492 1482 76.26 0.0 64.7
ENDING VALUES 8518 8492 1482 76.26 0.0 64.7
DELIVERY VALUE 0
TOTALS 0
47
Configuracin de TLS2 Pantalla de Estado de alarma activa (Active Alarm Status)
Se obtiene acceso a los informes de alarmas (Active Alarm) desde la pantalla de Informes de alarmas
activas (Active Alarm) mencionada anteriormente al pulsar las teclas de informe que se encuentran
en la parte inferior de la pantalla. La Tabla 5 describe los informes que se encuentran disponibles.
48
Configuracin de TLS2 Informes de alarmas (Alarm)
Cuando ninguna alarma se encuentra activa, el LED del panel delantero se encuentra en estado
Normal (verde continuamente encendido) y en la ventana de mensajes de la pantalla de Estado del
sistema (local) (System Status) se lee: Todas las funciones normales (elemento 2 en la pgina 5).
Una advertencia activa de sonda fuera o de temperatura baja suprimir las alarmas de todos los
niveles (producto mximo, sobrecarga, poco producto, suministro necesario y agua alta).
49
Configuracin de TLS2 Informes de alarmas (Alarm)
Alarma activa
Al activarse una alarma, se activa el zumbador interno de la consola y el rel de la alarma (si est activado), el
LED del panel delantero destallar en color rojo y la ventana de mensajes de la pantalla (elemento 2 en la pgina
5) muestra un mensaje de alarma. Si se producen mltiples alarmas, la ventana de mensajes pasar automtica-
mente por las alarmas activas. En el caso de que una alarma est asignada a marcacin automtica, la consola
realiza una marcacin saliente y establece una conexin con el host remoto. Luego el host puede enviar solicitudes
a la consola para determinar la razn de la llamada.
Cuando una alarma est activa, el usuario puede desactivar el zumbador as como el rel de la alarma al pulsar la
tecla ALARMA (ALARM) (elemento 3 en la pgina 5). El LED del panel delantero se mantendr en el estado
ALARMA y la alarma permanecer en la lista de alarmas activas hasta que la alarma regrese a su estado normal.
Si la alarma no est activa y no se ha reconocido, sta permanecer en la lista de alarmas y el zumbador y el rel
de la alarma (si est habilitado) continuarn activos hasta que se reconozca.
Con cualquier alarma cuando se corrige una o varias condiciones fuera del lmite, o bien se cambia un dispositivo
daado por uno que funcione correctamente, la alarma se desactiva automticamente. Para desactivar una alarma
de prueba de fugas que fue reprobada, se debe realizar una prueba de fugas que sea aprobada.
Si el volumen del nivel de producto excede el valor de producto mximo, se activar la alarma de producto
mximo. Si la alarma est activa y el volumen del nivel de producto es menor que el valor de producto mximo en
una relacin de por lo menos 0.005 veces la capacidad del volumen completo o 10 galones [37.8 L] (cualquiera
que sea mayor), se desactivar la alarma. El valor de producto mximo se introduce como un volumen con un valor
predeterminado igual a 0. Si el valor de producto mximo es igual a 0 o a la capacidad de volumen completo del
tanque, se desactiva la alarma. Una advertencia activa de temperatura baja en la sonda desactivar la alarma.
Alarma de sobrecarga
Si el volumen del nivel de producto excede el umbral de la alarma de sobrecarga y existe un suministro en proceso,
se activar la alarma de sobrecarga. Cuando se interrumpe el suministro, la alarma se desactivar. El valor de
la alarma de sobrecarga se introduce como un porcentaje con un valor predeterminado igual a 0%. Un valor de
umbral de sobrecarga de 0% desactiva la alarma. El umbral de la alarma de sobrecarga tiene relacin con el
valor del producto mximo. Si el valor de producto mximo es 0, el valor de sobrecarga est relacionado con la
capacidad del volumen completo. Una advertencia activa de temperatura baja en la sonda desactivar la alarma.
Si el volumen del nivel de producto es menor que el umbral de poco producto, se activar la alarma de poco
producto. Si la alarma est activa y el volumen del nivel de producto es mayor que el umbral en una relacin de
por lo menos 0.005 veces la capacidad del volumen completo o 10 galones [37.8 L] (cualquiera que sea mayor),
se desactivar la alarma. El valor de poco producto se introduce como un volumen con un valor predeterminado
igual a 0. Si el valor es igual a 0, la alarma se desactivar. Una advertencia activa de temperatura baja en la
sonda desactivar la alarma.
50
Configuracin de TLS2 Informes de alarmas (Alarm)
Si la altura del nivel de agua excede continuamente el umbral de agua alta por ms de tres minutos, se activar la
advertencia de agua alta. La alarma de agua alta no se activar si hay un suministro en proceso. Si la alarma est
activa y la altura del nivel de agua es menor que el umbral en una relacin de por lo menos 0.2 pulgadas (5 mm), la
alarma se desactivar. El valor de agua alta se introduce como una altura con un valor predeterminado igual a 0. Si
el valor es igual a 0, la alarma se desactivar. Una advertencia activa de temperatura baja en la sonda desactivar
la alarma
Si la consola no se puede comunicar confiablemente con la sonda, se activar la alarma de sonda fuera.
Si el flotador del agua y del producto estn muy juntos para proporcionar datos confiables de la altura, se activar
la alarma de altura de combustible invlida.
Cuando el nivel del producto del tanque se encuentre por debajo del lmite predefinido, se activar la alarma de
suministro necesario.
Cuando se repruebe una prueba de fugas general, peridica o anual, se activar una alarma de prueba de fugas
general, peridica o anual. Para desactivar una alarma de prueba de fugas que fue reprobada, se debe realizar
una prueba de fugas que sea aprobada.
51
Pantallas de Diagnstico (Diagnostic)
1 2 3
4 5 6
RED LED GREEN LED LCD OFF
7 8
52
Configuracin de TLS2 Pantalla de Prueba tctil LCD (LCD Touch Test)
Descripcin
53
Configuracin de TLS2 Pantalla de Diagnstico de sonda (Probe Diagnostic)
TANK 1
MAG 01
C000
360.000
1 2 3 4 5 66
Para ver los diagnsticos de la sonda de otro tanque, pulse la tecla Diagnstico (Diagnostic) del tanque
que desea, la cual se encuentra en la parte inferior de la pantalla.
Los datos de diagnstico de la sonda correspondientes a los tanques configurados o activos estarn dis-
ponibles en la pantalla de Diagnstico de la sonda (Probe Diagnostic) que aparece anteriormente,
en los informes impresos y en los comandos en serie. Un tanque activo se define como aqul que tiene
una sonda que se comunica con el sistema. Si el tanque est configurado pero no activo, todos los datos
sern cero y no se conocer el tipo de sonda.
Cuando el software identifica las sondas que no tienen la capacidad de medicin de temperatura, ste
suprime todos los datos relacionados con la temperatura. Para las sondas que no tienen la capacidad de
medicin del agua, ste suprimir los datos relacionados con el agua.
54
ndice de cdigos de etiqueta
La Tabla 6 y la Tabla 7 se incluyen para ayudar a que los usuarios que no hablan ingls, encuentren traduccio-
nes para todas las etiquetas en ingls que se utilizan en las pantallas de Configuracin de TLS2 (TLS2 Setup).
Debajo de cada etiqueta aparece un cdigo nico entre corchetes, P. Ej., [101]. Este cdigo aparece en las
tablas siguientes e identifica a cada pantalla de Configuracin (Setup) de este manual, en la que se utiliz
la etiqueta.
Cdigo de la Destino de
etiqueta Etiqueta uso
55
Configuracin de TLS2 Pantalla de Diagnstico de sonda (Probe Diagnostic)
Cdigo de la Destino de
etiqueta Etiqueta uso
Cdigo de la
etiqueta Etiqueta Destino de uso
56
Configuracin de TLS2 Pantalla de Diagnstico de sonda (Probe Diagnostic)
Cdigo de la
etiqueta Etiqueta Destino de uso
57
Configuracin de TLS2 Pantalla de Diagnstico de sonda (Probe Diagnostic)
Cdigo de la
etiqueta Etiqueta Destino de uso
58
For technical support, sales or
other assistance, please visit:
www.veeder.com