Anda di halaman 1dari 2

Technical Data Bulletin

PESD 1012000

Photoelectric Smoke Detector


The Photoelectric Smoke Detector is supplied
with the following standard features:
C Stable operation under extreme environmental conditions
C Dual Bi-color LED status indication
C Low-Profile design attractive, unobtrusive
C Conforms to U.L. Standard 268, latest edition
C Designed in accordance with NFPA Standard 72E
C FMRC approved
C Backward compatibility to preceding detector and base designs

Description

% STATE-OF-THE-ART TECHNOLOGY % ARCHITECT/ENGINEER SPECIFICATIONS


The Chemetron Fire Systems Photoelectric Smoke Detector Early warning smoke detector shall be Chemetron Fire
features 2 bi-colored LEDs. In standby the LEDs flash green Systems detector stock number (see ordering information). It
once every second. If the detector sensitivity drifts outside the shall be of the photoelectric type and shall operate on the light
UL listed sensitivity window, the LEDs will flash red every 3 scatter principle.
seconds. Using the latest in photoelectric and surface mount Detectors shall be of low-profile design and shall protrude
technology, this detector reacts positively to smoldering and from ceiling not more than 2 inches.
flaming fires.
Each detector shall be adequately protected against radio
% SIMPLIFIED OPERATING PRECISION frequency interference and voltage transients. A labyrinth
It utilizes a labyrinth-style nondirectional smoke chamber. arrangement shall be used to protect the photo diode located
An infrared LED is mounted on one side and a silicone photo in the smoke chamber from stray light pulses caused by
diode receiver is mounted at an angle on the opposite side. camera flashes or other exterior high-energy light sources.
In normal standby condition, the receiver senses little or no Detector head shall be fitted with a locking pin that requires
light from the LED. When smoke enters the chamber, smoke an uncommon tool to allow for removal from its base.
particles reflect light from the LED onto the receiver. The light The head shall incorporate dual pulsing bi-color green LEDs
received is converted into an electric signal; signals are as an indication of power at the detector head and red when
measured and counted in a comparator. When two consecu- the detector is outside the UL window. The LED shall illuminate
tive signals exceed the basic level within a specified period of steadily to provide a positive indication when the detector is
time, the time delay circuit triggers the alarm signal. Both LEDs in the alarm condition. Wiring shall be accomplished by using
light continuously red during an alarm condition. screw terminals.
The detector head is fitted with an Allen head locking pin The base shall be capable of being used with both photo-
to help eliminate unauthorized removal and discourage electric and ionization detector heads. An optional relay base
vandalism. shall permit detectors to activate additional devices such as
% ADDITIONAL FUNCTIONS OPTIONAL remote alarms, door closers, etc.
An optional relay base is available to permit the smoke de-
tector to activate additional devices such as remote visual and
audible alarms, door closers, etc. The compact relay module
fits into the detector junction box.

Ordering Information

Shipping Weight
Stock Number Description lbs (kg)
70100906 Photoelectric Detector head with 43 mA Standard Base .5 (.23)
70100907 Photoelectric Detector head with 43 mA Relay Base 1 (.45)
70100908 Photoelectric Detector head with 93 mA Base .5 (.23)
70100909 Photoelectric Detector head, 135EF fixed temperature with 43 mA Std. Base 1 (.45)
70100910 Photoelectric Detector head, 135EF fixed temperature with 43 mA Relay Base 1 (.45)