Anda di halaman 1dari 1

Micrologic 2.2 / 2.

3-AB
Ratings (A) In at 40C (1) 100 160 240 400
Circuit breaker Compact NSX100 b - - -
Compact NSX160 b b - -
Compact NSX250 b b b -
Compact NSX400 - - - b
Compact NSX630 - - - b
L Long-time protection
Ii
Pick-up (A) Ir value depending on trip unit rating (In) and setting on dial
tripping between In = 100 A Ir = 40 40 50 60 70 80 90 100
1.05 and 1.20 Ir
In = 160 A Ir = 90 100 110 120 130 140 150 160
In = 240 A Ir = 140 150 160 170 180 200 220 240
In = 400 A Ir = 260 280 300 320 340 360 380 400
Time delay (s) tr non-adjustable
1.5 Ir 15
6 Ir 0.5
7.2 Ir 0.35
Thermal memory 20 minutes before and after tripping
S0 Short-time protection with fixed time delay
Pick-up (A) Isd = Ir x ... 1.5 2 3 4 5 6 7 8 10
accuracy 10 %
Time delay (ms) tsd non-adjustable: 20
Non-tripping time 20
Maximum break time 80
I Non-adjustable instantaneous protection
Pick-up (A) Ii non-adjustable 1500 1600 2880 4800
accuracy 15 %
Time delay (ms) Non-tripping time 10
Maximum break time 50
(1) If the trip units are used in high-temperature environments, the Micrologic setting must take into account the thermal limitations of the circuit breaker. See the
temperature derating table.

Technical details
DB115574

Utility Advantages of the AB trip unit


line AB or b Controls the power drawn with respect to contractual power levels. If the contractual level is
standard overrun, the circuit breaker opens and the consumer is not billed excess costs.
service- b If a short-circuit occurs, the circuit breaker opens and the upstream HRC fuses on utility lines
connection are not affected. No expensive utility servicing is billed to the consumer.
circuit breaker
Utility
property
limit

Coupling
enclosure Outgoing circuits

LV distribution switchboard

Consumer connection diagram.

A-49

Anda mungkin juga menyukai