Fans
Systemair | 1
Systemair worldwide
Hyderabad, India
Whenever higher requirements are needed, the new The results are impressive and will convince you as well
Multibox/T can play to its strength. For example, it can as your customers:
handle polluted and hot exhaust air up to 100 C in The exhaust direction can be modified on site by sim-
industrial areas or kitchens.
ply changing the side panel positions. The location of
This new fan sets standards for flexibility and functionali- the MUB/T can therefore be chosen freely and easily.
ty. During product development, great attention was paid The motor and impeller section can be removed as
to a fast and flexible installation on site as well as easy one section for maintenance. Practical handles allow
maintenance.
an easy extraction.
A condensate drain is pre-installed as standard.
Short time of delivery: MUB/T is available from stock.
Dimensions:
D
C
B
F
E
Technical data:
MUB/T 042 400DV 042 400E4 042 450D4-IE2 042 450E4 042 500D4-IE2 062 560D4-IE2 062 630D4-IE2
item no. 33655 33656 33657 33658 33622 33659 33660
Voltage/Frequency V/50Hz 400 230 400 230 400 400 400
Phase ~ 3 1 3 1 3 3 3
Shaft power W 370 370 750 750 1500 2200 4000
Current A 1,4 2,1 1,78 5,3 3,39 4,2 8,12
Max. air volume m/h 4082 3992 6188 6037 8042 11704 14843
RPM min
-1
1370 1370 1400 1430 1400 1445 1450
Max. medium temperature C 100 100 100 100 100 100 100
Sound pressure level at 1 m dB(A) 47 47 49 50 53 55 67
Weight kg 48 50 61 63 62 132 137
Motor isolation class F F F F F F F
Motor protection class IP 54 54 55 54 55 55 55
6 | Systemair
Accessories:
www.systemair.com
Systemair GmbH Dezember 2011 E3001