Customer : M/s. L&T
Client : UPPTCL
Date 24/01/2012
Revision Rev. 3
Page 1 of 9
3x63 MVAR BUS REACTOR PROTECTION
Reactor Differential Protection (87RA) - Main 1
Type of Relay used = P632
Reactor Capacity in MVAR = 189
Voltage level in kV = 765
Phase side - winding a
CT Ratio (Phase side) - Pri = 600
CT Ratio (Phase side) - Sec = 1
Neutal side - winding b:
CT Ratio (Neutral side) - Pri = 600
CT Ratio (Neutral side) - Sec = 1
= 189 * 10^3/ 3 * 765
Full load Current of the Reactor in Amps
= 142.64
= 6 times of rated current (assumed)
Charging current of the reactor
= 6 * 142.6
Charging current in Pri. in Amps = 855.86
= 856/600
Charging current in Secondary (If) in Amps
= 1.43
Supportive Calculations:
Amplitude matching factor for winding a and b:
Full load current of the reactor in Amps = 142.64
= 142.6/600
Eqv. Secondary current in Amps
= 0.24
= 1/0.2
Required ratio compensation
= 4.21
Biased Differential Settings:
Idiff> = 0.1 Iref
m1 = 0.2
m2 = 0.8
IR,m2 = 1.5 Iref
Idiff>> = 8 Iref
Idiff>>> = 10 Iref
Vector Group end a-b = 0
Op. mode rush restraining = Not Phase selective
Rush I(2f0)/I(f0) = 20%
Over Flux blocking enable = Yes
Ov I(5f0)/I(f0) = 20%
Zero Seq. Filter end a = No
Zero Seq. Filter end b = No
Stability Calculations:
Max. Fault current in kA = 40 kA
= 40kA/(600)
Eqv. Secondary current in Amps
= 66.67 A
= 66.67*4.21
Current in Iref at end a & end b
= 280.42
= 280.42-280.42
Differential Current Idiff> in Amps
= 0.00
= (280.42+280.42)/2
Restraining Current IR in Amps
= 280.42
Page 7 of 9
BUS REACTOR OVER CURRENT CURVE
10.00
1.00
0.10
0.01
Time (t)
0.00
Fault current (A)
OC AREVA T&D INDIA LIMITED,
For M/s. UPPTCL - Unnao SS Page 8 of 9 19/1, G.S.T.ROAD,
OC EF Coordination Curves for 1*63MVAR BUS REACTOR PALLAVARAM,
Rev 3. CHENNAI - 43.
EARTH FAULT CURVE
10.00
1.00
0.10
0.01
Time (t)
0.00
Fault current (A)
EF AREVA T&D INDIA LIMITED,
For M/s. UPPTCL - Unnao SS Page 9 of 9 19/1, G.S.T.ROAD,
OC EF Coordination Curves for 1MVA SST PALLAVARAM,
Rev 3 CHENNAI - 43.