Anda di halaman 1dari 9

Energy and Buildings 39 (2007) 212220

www.elsevier.com/locate/enbuild

Energy simulation in the variable refrigerant flow


air-conditioning system under cooling conditions
Y.P. Zhou a, J.Y. Wu a,*, R.Z. Wang a, S. Shiochi b
a
Institute of Refrigeration and Cryogenics, Shanghai Jiao Tong University, Shanghai 200030, China
b
Daikin Air-conditioning and Enviromental Lab., Ltd Osaka, Japan
Received 29 April 2006; received in revised form 10 June 2006; accepted 20 June 2006

Abstract
As a high-efficiency air-conditioning scheme, the variable refrigerant flow (VRF) air-conditioning system is finding its way in office buildings.
However, there is no well-known energy simulation software available so far which can be used for the energy analysis of VRF. Based on the
generic dynamic building energy simulation environment, EnergyPlus, a new VRF module is developed and the energy usage of the VRF system is
investigated. This paper compares the energy consumption of the VRF system with that of two conventional air-conditioning systems, namely,
variable air volume (VAV) system as well as fan-coil plus fresh air (FPFA) system. A generic office building is used to accommodate the different
types of heating, ventilating, and air-conditioning (HVAC) systems. The work focuses on the energy consumption of the VRF system in the office
buildings and helps the designers evaluation and decision-making on the HVAC systems in the early stages of building design. Simulation results
show that the energy-saving potentials of the VRF system are expected to achieve 22.2% and 11.7%, compared with the VAV system and the FPFA
system, respectively. Energy-usage breakdown for the end-users in various systems is also presented.
# 2006 Elsevier B.V. All rights reserved.

Keywords: Energy simulation; Office buildings; HVAC systems; Variable refrigerant flow air-conditioning system; Energy usage

1. Introduction air-conditioning (VRF) system, which is being popular in


commercial buildings such as small offices, shopping centers,
As the worlds second largest energy consumer, only after hotels, and of course, domestic occasions in China.
the United States, China is now also one of the largest oil At present, researchers in the VRF field focus their interests
importers in the world [1]. Data about total energy consumption mainly on features of the equipment itself, e.g. the simulation or
and building energy consumption show that the proportion of experiment of the control logic of the variable speed
building energy consumption to the total energy consumption compressor, refrigerant distribution, and the control method
in China will be, inevitably, 35% in the near future [2]. of electric expansion valve (EEV), or modeling of novel
Furthermore, recent work on computer energy simulation algorithm for various types of system part [1114].
studies and field surveys reveals that air conditioning represent For decision-makers and practitioners in the HVAC industry,
3760% of total electricity use in office buildings, in especially for those who are interested in high-efficiency
accordance with buildings functions [3,4]. Consequently, systems like VRF, it is important, in the early stage of building
studies on the effects of heating, ventilating, and air- design, to compare the VRF with other systems and evaluate
conditioning (HVAC) system, along with building envelope, VRFs performance.
novel technologies of the utilization of natural energy and So far, there is no well-known energy simulation software
occupant behaviors, on energy efficiency by simulation is available yet which can be used for the energy analysis of VRF.
becoming concerns for professionals in this field [510]. This This paper investigates energy features of the VRF system and
paper addresses the simulation of the variable refrigerant flow develops a new model in EnergyPlus that is a new-generation
building energy simulation program (BESP) [15,16], to
evaluate the energy-use level of the VRF air-conditioning
* Corresponding author. Tel.: +86 21 62933250; fax: +86 21 62933250. system and hence to make above comparison. The examination
E-mail address: jywu@mail.sjtu.edu.cn (J.Y. Wu). of various air-conditioning strategies for the medium-sized
0378-7788/$ see front matter # 2006 Elsevier B.V. All rights reserved.
doi:10.1016/j.enbuild.2006.06.005
Y.P. Zhou et al. / Energy and Buildings 39 (2007) 212220 213

office building helps the owners and energy researchers to make 2. Modeling and programming
decision. The knowledge of how to choose the HVAC system
affects the building performance and can serve as a powerful 2.1. Schematic flowchart of the VRF system modeling in
tool for building designers and owners at last. Computer EnergyPlus
simulations of different systems is able to, in advance, provide
insights in balancing various types of system plans and Hourly cooling loads for the building are calculated in this
justifying the most appropriate system, and the differences can study by the building simulation program, EnergyPlus, which
be quantified [1719]. employs the heat balance engine with HVAC system integrated
The first part of this investigation will focus on verification of into the building simulation. More accurate than the weighting
the newly developed VRF model by comparing simulation factor method used in its predecessors such as DOE-2, the heat
outcomes with the experimental results in a literature [20]. balance method permits better simulation of a buildings
The new model in EnergyPlus is testified to be able to response to its heating and cooling system by allowing
simulate the VRF systems energy characteristics at part-load feedback between two main simulation components [21,22].
operating conditions. As covered in this study, the second part of The well-organized modular structure in the software allows
the investigation is concerned with application of EnergyPlus users adding specific modules according to their own needs
with the validated model. A generic office building in Shanghai is [23,24]. The EnergyPlus program has been extensively
used for the simulation study. Through graphical analysis, the validated through analytical, comparative, sensitivity, range,
energy consumptions of three popular systems, namely, the and empirical tests. The simulation results to date show good
variable air volume (VAV) system, the VRF system, the fan-coil agreement with well-established simulation tools such as DOE-
plus fresh air (FPFA) system, are presented and discussed. 2.1E, BLAST, and ESP [25,26].

Fig. 1. Flowchart of the new VRF model embedded into EnergyPlus.


214 Y.P. Zhou et al. / Energy and Buildings 39 (2007) 212220

EnergyPlus utilizes the performance-curve-oriented way to Fig. 1 shows the schematic process of modeling in source
calculate the energy performance of HVAC systems. Detailed codes of EnergyPlus. The new specific input parameters for VRF
performance data and parameters, along with their applicability are defined first in the InputProcessor module, which thereby gets
conditions usually shipped in the manufacture catalogue, the required information to simulate a VRF system. The energy
therefore, are requirements. consumption calculation of VRF is then embedded in the

Fig. 2. Flowchart of the main program for energy-use computation of the VRF system.
Y.P. Zhou et al. / Energy and Buildings 39 (2007) 212220 215

so-called ManageHVAC module. As the kernel program in the RHXYQ10MAY1 for the outdoor unit and FXFQ100KML for
source codes of EnergyPlus, ManageHVAC conducts the whole the indoor unit separately.
HVAC systems energy simulation, including air loops, zone There exist three categories of space internal gains for each
equipments, plant supply and demand sides, and condenser zone, people, lights, and office electric equipments. Four
supply and demand sides. After the simulation is finished occupants stay in each zone, where space lighting of 1400 W is
successfully, electricity usage of the VRF system, as well as other installed. The design level of the electric equipments is 2160 W
abundant calculation results in CSV format, can be supplied to for zones 14, and 3240 W for zones 5 and 6.
users for further research and analysis.
3.2. Simulation results under the conditions of different
2.2. Description of the main VRF calculation program amount of operating indoor units

Based on aforementioned modeling considerations, the One summer-design-day simulation running is used in this
coding work for calculation of the energy consumption of the investigation. All the space gains are supposed to happen during
VRF system is established at right place in the EnergyPlus 8:0017:00.
source code and in the EnergyPlus coding style. Taking the VRF-1 system as an instance, Fig. 4 denotes
Fig. 2 shows the schematic flowchart of the main energy power-use curves of the VRF system, under a group of indoor-
computation program for the VRF system. temperature set points, namely 22 8C, 24 8C, 26 8C, and 28 8C,
Being consistent with the original open characteristics in when all three indoor units are operating. The electricity usage
EnergyPlus, the newly developed module allows necessary of the VRF-1 system increases gradually, with the outdoor air
expansibility. For example, in these codes, the number of indoor dry bulb temperature going up. The outdoor air temperature
units is limited in eight currently. They are able to be extended achieves its daily top 32.6 8C on 15:00. By contrast, the power
to any desired amounts according to user needs. use gets to its highest value on 16:00, due to the delay of cooling
load. Simulation results for different set points in the figure (and
3. Validation different amount of operating indoor units) show good
consistency on trend with the experimental outcomes in the
3.1. Building and system description literature [20].
It is noticed that there are some cooling loads when outdoor
As shown in Fig. 3, a single-floor multi-zone building is used air temperature is lower than the indoor air temperature during
to testify the simulation effect of the VRF energy-calculation 8:0011:30 in the morning. Compared with the recommended
module embedded in EnergyPlus. The building is divided into value 16.15 W/m2 in the literature [27], the design density of
six thermal zones, in which there is a conditioned area of office equipment 32.40 W/m2 is found much higher; at the same
66.67 m2 for zones 14, and of 100 m2 for each of other two time well-insulated building envelops (i.e. adiabatic ground and
zones. The ground-to-ceiling height is 4 m. no fenestration at all for some zones) contribute to prevent
The six thermal zones are split to two groups, namely, Group larger internal heat gains escaping from the building shell, thus
1 consisting of zones 13, and Group 2 consisting of other three corresponding cooling amount from air-conditioning indoor
zones. Each group is served by a VRF outdoor unit of nominal units is required to meet the set point of the thermostat. To some
cooling capacity 28.0 kW, called VRF-1 or VRF-2. The cooling extent, the zones behave essentially like an interior zone being
load in each thermal zone is satisfied by an indoor unit of
nominal cooling capacity 11.2 kW. The product types are

Fig. 3. A multi-zone building for validation of the new VRF model. Fig. 4. Power use of the VRF-1 system with three indoor units on.
216 Y.P. Zhou et al. / Energy and Buildings 39 (2007) 212220

Fig. 5. Energy use of VRF-1 when two units on while the left one turns off.

affected little by the outside weather in large commercial


buildings. Fig. 7. Correlations between COP and PLR.
Xue et al. [20] also tested the energy use by the VRF system
when parts of indoor units turn off. For a purpose of
comparison, the evolution features of the VRF-1 systems 0.4 to 0.6, the COP values attain their maximums in the day;
energy use is studied in this paper when two indoor units or only when PLRs get their value from 0.81 to 0.87, the COPs fall to
one indoor unit run in this Group 1 zones. Simulation results for their lowest points. It is shown that COP reaches its diurnal
parts of running indoor units reveal similar characteristics with maximum values when PLR ranges from 0.4 to 0.6 in this
the situation under all indoor unit running, as shown in Figs. 5 simulation. This simulation result is in accordance with the
and 6, which is accordant to the experimental results recorded conclusion of the experiment [20].
in Xues research. In order to make a comparison between VRF and traditional
As far as the overlapped curves in Fig. 6 in late afternoon are window air-conditioners (windAC), a simulation run with one-
concerned, it is found that the indoor air temperature has not windAC-per-zone scheme is established. That means each zone
been kept at the set point in the case of the set point 22 8C, is served by one window air-conditioner. With all the indoor
24 8C, and 26 8C, respectively. The largest deviation can get to units or windACs working in the simulation, Fig. 8 shows the
2.98 8C. On account of aforementioned well-insulated shell and daily absolute changes of the COP value for the VRF-1 system
non-infiltration for each zone, rooms surrounding the air- and corresponding alternative window air-conditioners in the
conditioned zone reach an indoor air temperature of above Group 1 zones. It can be shown that COPs in both systems
40 8C. In this case, the indoor air-conditioning unit is at full achieve their highest point one after the other between 8:00 and
capacity, and interlaced curves reflect that the cooling capacity 10:00, and their lowest points during 13:0015:00. The diurnal
of the indoor unit fails to meet the cooling demand. variation between maximum and minimum COP gets up to 1.12
for the VRF system, compared to 0.5 for window air-
3.3. Relationship between coefficient of performance and conditioners. In other words, it denotes that the VRF system
part-load ratio has a more flexible and sensitive response to the cooling loads
in the whole-day running, compared with the window air-
Fig. 7 describes the relationship between coefficient of conditioners. It reflects the ability of VRF on tracking cooling
performance (COP) and part-load ratio (PLR) for the two load duly at a higher operational efficiency. Meanwhile, the
outdoor VRF units. The evolution patterns for both outdoor COP value of the VRF system keeps much higher than those of
units are rather similar. The COP values for the units decrease the window air-conditioners. This result indicates the superior
with increment of PLR. When PLR locates in the range from performance at part load for the VRF system.

4. Case studies: building and system descriptions

As an application of the VRF energy-calculation module in


EnergyPlus, a comparative energy studies is conducted among
three popular HVAC systems in China, namely, VAV, FPFA,
and VRF. In this study, various systems are examined so that
their applicability and features can be identified from the
energy uses point view by simulation analysis.
A general 10-storey office building is developed to serve as a
platform which can accommodate different air-conditioning
systems for the purpose of comparison research. How to select
Fig. 6. Energy use of VRF-1 when only one indoor unit turns on. the building type and materials for evaluation of different kinds
Y.P. Zhou et al. / Energy and Buildings 39 (2007) 212220 217

shown in Fig. 9. In this investigation, the following assumptions


are made.

 All the floor plans in the sample building are the same. There
are not basement spaces underneath the building.
 Only one type of HVAC system is installed to serve the
building in each case.
 The indoor air set points are identical everywhere in the
building.
 A single chiller serves the whole building, while a VRV
system per floor supplies needed cooling.

The water-cooled type chiller and the VRF equipments from


the same manufacturer are chosen to meet the cooling demand.
There are not shading devices associated with the building enve-
Fig. 8. Comparison on the daily amplitude of COPs between the VRF-1 system
lope, nor are there any adjacent tall buildings that would bring on
and the window air-conditioners. daytime shading. There is no roof glazing or skylights in the
sample building. The geographical and weather file, infiltration,
thermostat, and other parameters related to building load
of HVAC systems is based on the commercial building studied calculations are the same for all the HVAC systems simulated.
by Li et al. [3], Miyazaki et al. [28], and Ardehali and Smith
[29]. However, in this study, some of the building envelope 5. Results and discussion
features are modified to meet the present research conditions.
Each floor of the building is divided into six conditioned A series of simulation are implemented for the performance
thermal zones, corresponding to four outside exposures (north, comparison of the HVAC systems in this section. The results of
east, south, and west), the interior zones, and the centre core. the simulations for evaluating systems are presented in
The typical floor in the simulation incorporates a floor- categories that describe the energy consumption shares of
multiplier of 8 to account for the actual number of middle floors the electricity end-users in systems such as VAV, FPFA, and
in the building. A summary of the key parameters of the VRF. Results show the differences among systems, as reported
building is given in Table 1, construction material properties is in Fig. 10. The breakdown of the total electrical energy
listed in Table 2, and the typical floor plan and section are consumption into various parts include system fans, chillers,

Table 1
Brief descriptions of the sample building and HVAC systems
Items Description
General information
Location Shanghai, China
Building type and stories Office building, 10 stories above ground
Air-conditioned area 7840 m 2
Floor area and height 28 m  28 m; floor-to-floor height = 3.5 m
Windows and shading Low-e double pane glazing. Window height = 1.5 m; sill height = 0.80 m;
WWR = 30%. No shading device
Operation hours ON during weekdays: 7:0017:00; OFF during all other days
Design values of internal heat gains, ventilation, and infiltration
Occupancy density 5 m2/person (perimeter and interior zones), 25 m2/person (center core)
Lighting density 25 W/m2 (perimeter and interior zones), 15 W/m2 (center core)
Plug equipments load 20 W/m2 (perimeter and interior zones), 0 W/m2 (center core)
Space design temperature 25.0 8C
Infiltration 0.1, air change per hour for each zone
Ventilation 4.0 m3/(m2 h) (perimeter and interior zones), 0.6 m3/(m2 h) (center core)
Night setup 37 8C
Running period June 1August 31, typical summer days in Shanghai (Ref. Weather file CTYW.STAT)
HVAC system and plant information
HVAC systems (with same cooling capacities) VAV no-reheat; fan-coil plus fresh air (FPFA); VRF
Chiller types Water-cooled screw chiller
Cooling source nominal COP (kW/kW) Screw chillers for VAV and FPFA: 4.6; VRF units: 3.02
Fans and pumps Variable speed drive (VSD) for the central fan and chilled water loop pumps in the VAV
system; VSD for chilled water supply pumps in the FPFA system
218 Y.P. Zhou et al. / Energy and Buildings 39 (2007) 212220

Table 2
Construction thermal properties
Layers (outer to inner) Thickness (mm) Conductivity (W/(m K)) Density (kg/m3) Specific heat (J/(kg K))
Exterior wall
Cast concrete 150 1.13 2000 1000
XPS extruded polystyrene 20 0.034 35 1400
Air gap Thermal resistance R = 0.18 m2 K/m2
Plasterboard 15 0.25 2800 896
Interior wall
Plaster (lightweight) 13 0.16 600 1000
Cast concrete 100 1.13 2000 1000
Plaster (lightweight) 13 0.16 600 1000
Ceiling/floor (the order of floor materials is the reverse of that of ceiling materials)
Cast concrete 150 1.13 2000 1000
Air gap Thermal resistance R = 0.18 m2 K/m2
Plasterboard 10 0.16 950 840
Slate tiles 10 2.00 2700 753

pumps, space lighting, plug equipment, and VRF system. Energy 7%, and heat rejection keeps the left 3%; for the FPFA system,
usage of drink-water pumping, lifts, and other non-HVAC- lighting and plug load share a part of 52% together, chillers
related power facilities is disregarded in electricity-usage 32%, indoor fans, system water pumps, and heat rejection hold
breakdown of end-users in the study. In this figure, system 6%, 7% and 3%, respectively; for the VRF system, lighting and
fans means the central supply fan in VAV, or the aggregate of plug load own a part of 58%, the VRF system and indoor fans
individual fans in FPFA, or the aggregate of indoor unit fans in take the residual part 42%.
VRF; chillers denotes energy consumption of chillers; As the second largest energy consumer in the VAV system,
pumps refers to the chilled water and cooling water pumps; the main air supply fan takes a remarkable larger part of
VRF systems stands for the energy input of VRF outdoor units electricity use than the indoor fans used in the FPFA and VRF
containing condenser fans, compressors, and control circuits; systems. This share by the VAV supply fan is still much less
while heat rejection is the tower fan electric consumption. than the survey data for a typical office building [4], whereas it
agrees well with the simulation result of 14.128.3% of the
5.1. Breakdown of electricity end-users in HVAC systems HVAC system consumption [30] comparatively. It can be
explained that unreasonable choices and operation strategies of
For the VAV system, lighting and plug load share a part of air transport facilities exist commonly in reality [31]. On-site
46%, chillers 33%, system main supply fan 11%, water pumps measured data do not mean rational data. In a sense, thus,
energy simulation of HVAC systems is able to put forward a gap
as reference between the ideal consumption and the actual
consumption of equipments. The indoor fan in the FPFA system
uses 6% of energy, and its absolute magnitude locates in the
middle of the fan energy in other two systems. It can be
understood that there is a strong relationship between the fan

Fig. 9. Typical floor plan of the sample building (unit in drawing: meters). Fig. 10. Comparison of energy usage among three systems.
Y.P. Zhou et al. / Energy and Buildings 39 (2007) 212220 219

account for 79.3%, 83.7%, and 81.9% in the overall 660


operation hours for the VRF units, the chiller in the FPFA
system and the chiller in the VAV system, respectively. It offers
the VRF system an occasion to perform within its favorable
energy-feature range in a significant part of working time. In
other words, the VRF system is provided with a high efficiency
at partial load condition and works at the condition in an
essential part of operation time, which may be considered as
one of reasons for its less energy usage. It may be established
the more the VRF system works in the favorable part-load
range, the more energy savings can be achieved. As the cooling
resources and the substantial energy consumers in other two
HVAC systems, the screw chillers take similar efficiency at part
load with that at full load [33]. Compared with the VRF system,
this feature makes the chiller less sensitive to changes of the
Fig. 11. Part-load range of the three kinds of systems. cooling load. Meanwhile, the refrigerant from nearby outdoor
units in the VRF system goes directly to conditioned zones to
energy and the type of cooling media. Specific enthalpy of exchange heat with air. By contrast, the chiller needs one or two
refrigerant in the VRF system is much greater than water and air secondary heat-transfer process to pipe the low-specific-
in the other systems, and phase change takes place in the indoor enthalpy cooling media, water or air, through a long way to
evaporator, which are both believed to bring out less fan energy. cool the zones in the building. It tends to result in large heat
For the VRF system, the indoor fans contribution to the exchange and transport loss and inevitably gives birth to added
whole VRF systems energy usage is 7%, according with the energy consumption.
experimental result 9.8% [32] on the whole, considering
diversity of application conditions and equipment series. 6. Conclusions

5.2. Summer electricity consumption of different systems Computer simulation is a convenient tool of assessing
building energy performance, air-conditioning system features,
HVAC systems can be categorized to the all-air system, the and system operational strategies. It allows users to test their
waterair system, and the refrigerant system in accordance with ideas and designs to see what the impact of their decisions
the kinds of cooling media. Fig. 10 depicts the electricity usage would be on energy consumption and other aspects. In this
for HVAC systems. The VRF system is the most energy- study, a new module is developed in the BESP program
efficient one among three sample cooling systems, followed by EnergyPlus, in order to evaluate the benefits of the VRF system
FPFA, while VAV ranks last, as shown in the figure. It denotes under cooling condition in terms of energy usage. A case study
that an all-air system like VAV consumes more energy than is then made to demonstrate the application of the new module
either a waterair system (FPFA in this case) or a refrigerant for the VRF air-conditioning system in a medium-sized office
system (VRF in this case), even though it is usually regarded as building.
a high-efficiency system. The superiority of a VAV system is Simulation results from the electricity-usage comparison
significant only if it is compared with a conventional constant among VAV, FPFA, and VRF systems implies that the VRF air-
air volume system [18,30]. conditioning system is the most energy efficient, compared
The VRF system uses 11.7% less electrical energy than the with other two conventional systems. The energy-saving
FPFA system with a variable speed drive (VSD) loop water potentials of the VRF system are expected to achieve 22.2%
pump, 22.2% less electrical energy than the VAV system and 11.7%, compared with the VAV system and the FPFA
outfitted with a VSD fan in this case. system, respectively. With the same nominal cooling capacity,
Owing to air-conditioning systems working usually off the the VRF system and VAV (or FPFA) plus chillers system
rated condition, the part-load performance of the refrigeration consume notably different electricity energy, due to various
equipments plays a significant role in final electricity usage of ways in transporting cooling media and diversity of part-load
the building. The number of working hours of the three systems performance. This study provides architects and engineers
based on different part-load ranges in this study is presented in some ideas to analyze the energy features of the VRF system
Fig. 11. The profiles of part load show some differences, which and to evaluate different systems by the view of energy
are believed to be induced by diverse humidity levels during the characteristics, especially during the primary conceptual design
simulation. Keeping the indoor air temperature at set point, the stage.
thermostat control makes the space humidity drift and results in It is pertinent to note that influencing factors of the energy
various latent load and then the various total load. It can be seen consumption of air-conditioning system is fairly complicated in
from this figure that a notable majority of operation hours of all real buildings. Building designs, constructions, operation
the VRF, FPFA, and VAV systems occurs between 30% and strategies, chillers configuration, maintenances, and other
90% part-load operating conditions. The accumulative totals unpredictable ingredients can impact on the eventual facility
220 Y.P. Zhou et al. / Energy and Buildings 39 (2007) 212220

bills for buildings. Simulations offer an ideal benchmark of [13] S.Q. Shao, W.X. Shi, X.T. Li, H.J. Chen, Performance representation
of variable-speed compressor for inverter air conditioners based on
energy usage of the integration of the building, air-conditioning
experimental data, International Journal of Refrigeration 27 (8) (2004)
systems and artificial interference under a certain condition, 805815.
rather than a predetermined augur. But this investigation still [14] C.P. Youn, C.K. Young, M.K. Min, Performance analysis on a multi-type
owns its sense in suggesting the VRF system may be an inverter air conditioner, Energy Conversion and Management 42 (13)
attractive option and a more efficient operation for a new (2001) 16071621.
installation or a changeover from an inefficient old system, by [15] D.B. Crawley, L.K. Lawrie, et al., EnergyPlus: creating a new-generation
building energy simulation program, Energy and Buildings 33 (4) (2001)
an energy use perspective. 319331.
The future work will include the economic evaluation and [16] D.B. Crawley, L.K. Lawrie, C.O. Pedersen, et al., EnergyPlus: new,
life-cycle cost analysis of various forms of HVAC systems. capable and linked, in: Proceedings of the World Renewable Energy
Also, electricity-usage field tests of the VRF system are Congress VIII, Denver, CO, 2004.
[17] M.M. Ardehali, T.F. Smith, Evaluation of variable volume and tempera-
underway, as a part of the extension of this research, so that the
ture HVAC system for commercial and residential buildings, Energy
results can be verified. Further, the VRF systems performance Conversion and Management 37 (9) (1996) 14691479.
in heating condition would be researched. [18] S.C. Sekhar, A critical evaluation of variable air volume system in hot and
humid climates, Energy and Buildings 26 (2) (1997) 223232.
Acknowledgements [19] S.C. Sekhar, J.Y. Chung, Energy simulation approach to air-conditioning
system evaluation, Building and Environment 33 (6) (1998) 397
408.
The authors would like to thank Richard A. Raustad for his
[20] W.H. Xue, P.L. Chen, C.J. Liu, The experimental study of the operating
generous assistance. characteristic and energy consumption of the VRV air-conditioning sys-
tem, Energy Conservation Technology 21 (119) (2003) 35 (in Chinese).
References [21] M.S. Al-Homoud, Computer-aided building energy analysis techniques,
Building and Environment 36 (4) (2001) 421433.
[1] P. Crompton, Y. Wu, Energy consumption in China: past trends and future [22] R.K. Strand, F. Winkelmann, F. Buhl, J. Huang, et al., Enhancing and
directions, Energy Economics 27 (1) (2005) 195208. extending the capabilities of the building heat balance simulation tech-
[2] Y.X. Zhu, B.R. Lin, Sustainable housing and urban construction in China, nique for use in EnergyPlus, in: Proceedings of the Buildings Simula-
Energy and Buildings 36 (12) (2004) 12871297. tion99, Kyoto, Japan, (1999), pp. 653660.
[3] D.H.W. Li, J.C. Lam, S.L. Wong, Daylighting and its implications to [23] R.K. Strand, K.T. Baumgartner, Modeling radiant heating and cooling
overall thermal transfer value (OTTV) determinations, Energy 27 (11) systems: integration with a whole-building simulation program, Energy
(2002) 9911008. and Buildings 37 (4) (2005) 389397.
[4] Z.F. Xue, Y. Jiang, Energy consumption and energy saving potential [24] P. Ihm, M. Krarti, G.P. Henze, Development of a thermal energy
analysis for large-scale public buildings in Beijing, HV & AC 34 (9) storage model for EnergyPlus, Energy and Buildings 36 (8) (2004)
(2004) 824 (in Chinese). 807814.
[5] P.G. Ellis, Development and validation of the unvented Trombe Wall [25] R.H. Henninger, M.J. Witte, D.B. Crawley, Analytical and comparative
Model in EnergyPlus, Master Thesis, University of Illinois at Urbana- testing of EnergyPlus using IEA HVAC BESTEST E100-E200 test suite,
Champaign, 2003. Energy and Buildings 36 (8) (2004) 855863.
[6] L. Jaewook, R.K. Strand, An analysis of the effect of the building envelope [26] M.J. Witte, R.H. Henninger, J. Glazer, D.B. Crawley, Testing and valida-
on thermal comfort using the EnergyPlus program, in: Proceedings of the tion of a new building energy simulation program, in: Proceedings of
ACSA Technology Conference, Austin, TX, (2001), pp. 96102. Building Simulation, 2001.
[7] Y.W. Jian, Y. Jiang, Calculation modes of heating and air conditioning [27] A.A.J. Bell, HVAC: Equations, Data, and Rules of Thumb, McGraw-Hill,
energy consumption of residential buildings, HV & AC 35 (2) (2005) 11 2000.
14 (in Chinese). [28] T. Miyazaki, A. Akisawa, T. Kashiwagi, Energy savings of office buildings
[8] R.K. Strand, D.E. Fisher, R.J. Liesen, C.O. Pedersen, Modular HVAC by the use of semi-transparent solar cells for windows, Renewable Energy
simulation and the future integration of alternative cooling system in a new 30 (3) (2005) 281304.
building energy simulation program, ASHRAE Transactions 108 (2) [29] M.M. Ardehali, T.F. Smith, Evaluation of HVAC system operational
(2002) 11071118. strategies for commercial buildings, Energy Conversion and Management
[9] F.C. Winkelmann, Modeling windows in EnergyPlus, in: Proceedings of 38 (3) (1997) 225236.
the Seventh International IBPSA Conference, Rio de Janeiro, Brazil, [30] H. Chen, G.B. Tu, T.H. Zou, Y. Francis, et al., Energy analysis of VAV air
(2001), pp. 457464. conditioning systems of office buildings in Hong Kong, HV & AC 34 (4)
[10] E.L. Olsen, Q. Chen, Energy consumption and comfort analysis for (2004) 7477 (in Chinese).
different low-energy cooling systems in a mild climate, Energy and [31] W.F. Zhu, Y. Jiang, Z.F. Xue, Analysis of common problems in refrig-
Buildings 35 (6) (2003) 560571. erating stations and air conditioning systems, HV & AC 30 (6) (2000) 4
[11] J.M. Choi, Y.C. Kim, Capacity modulation of an inverter-driven multi-air 11 (in Chinese).
conditioner using electronic expansion valves, Energy 28 (2) (2003) 141 [32] J.J. Xia, Research on optimizaiton control of the variable refrigerant flow
155. (VRF) air-conditioning system, Ph.D. Thesis, Department of Civil Engi-
[12] S.C. Hu, R.H. Yang, Development and testing of a multi-type air condi- neering, Tsinghua University, 2005 (in Chinese).
tioner without using AC inverters, Energy Conversion and Management [33] ASHRAE, ASHRAE Handbook of Refrigeration, American Society of
46 (3) (2005) 373383. Heating, Refrigerating and Air Conditioning Engineers, Inc., 1998.

Anda mungkin juga menyukai