General
Specifications UT35A/UT32A
Digital Indicating Controllers
GS 05P01D31-01EN [Style: S9]

n Overview
The UT35A/UT32A digital indicating controllers employ
an easy-to-read, 14-segment large color LCD display,
along with navigation keys, thus greatly increasing
the monitoring and operating capabilities. A ladder
sequence function is included as standard. The short
depth of the controller helps save instrument panel
space. The UT35A/UT32A also support open networks
such as Ethernet communication.

n Features
A 14-segment, active (PV display color changing
function) color LCD display is employed.
Two five-digit, high-resolution displays are possible.
Alphabet letters can be displayed in an easy-to-read
manner. The guide display shows parameter names.
Easy to operate
Navigation keys (SET/ENTER and Up/Down/Left/
Right arrow keys) are employed to facilitate making UT35A UT32A
settings.
65 mm depth
The small depth enables the mounting in a thin and
small instrumented panel.
*1: Excluding control output
Ladder sequence function is included as standard.
*2: In the case of cooling control output is analog output, it
This function allows for creating a simple sequence can not be used for transmission output.
control. Dedicated LL50A Parameter Setting Software *3: Excluding control output relays
(sold separatly) allows for performing programming
using a ladder language. n Control Computation Function
Various built-in open network functions such as Eth-
ernet are available. (1) Types of control
Easy connection with various vendors PLCs is possible. PID control
Quick setting function ON/OFF control (*4)
Setting only the minimum necessary parameters for Two-position two-level control (*5)
operation is possible. Heating and cooling control (*5)
Equipped with a multitude of functions *4: Not selectable for Position proportional type
Universal I/O are included as standard. PID control, *5: Selectable for heating and cooling control
heating/cooling control, etc. are available. (2) Control Computation Function
(a) Target setting point and the number of PID param-
n Functional Specifications eter groups
Control Specifications Respectively, four sets of target setpoints, alarm
setpoints, and PID parameters can be set.
(1) Control Mode (b) Selecting the PID parameter group
Single-loop control The following PID parameter groups can be selected.
(2) Control period Target setpoint number (SPNO) (The PID number
200 ms can be set arbitrarily.)
Measured input zone PID
Table of Number of Inputs and Outputs Target setpoint zone PID
Reached target setpoint zone PID
Model and Number Number Number Number of (c) Auto-tuning
suffix code of analog of analog of contact contact
Tuning results can be selected from two options,
(See the input output input output
model code) points points (*1) points points (*3) Normal or Stable.
UT35A Tuning output limit can be set. (It cannot be used in
-0 1 1 2 3 heating/cooling control.)
-1 1 1 4 5 (d) Super function: Overshoot-suppressing function
-2 1 1 (*2) 7 8
UT32A
(e) Super 2 function: Hunting-suppressing function
-0 1 1 2 3 (f) STOP preset output function
-1 1 1 2 3 (g) Input ERROR preset output function
-2 1 1 (*2) 4 5 (h) MANUAL preset output function

Yokogawa Electric Corporation GS 05P01D31-01EN


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan 1st Edition Nov.30, 2009 (KP)
Tel.: 81-422-52-7179 Fax.: 81-422-52-6619 5th Edition Jun. 28, 2013 (KP)
<<Contents>> <<Index>> 2
(3) Operation Mode Switching Contact I/O Function
Operation mode
AUTO/MANUAL and RUN/STOP switching This function allows for allocating the input error
REMOTE/LOCAL switching (only model with condition, operation condition, alarm condition or other
switching
communication option)
conditions to the contact input and contact output.
(4) Control Parameter Setting Range AUTO/MANUAL switching
Proportional band 0.1 to 999.9% REMOTE/LOCAL switching (only model with
Integral time 1 to 6000 sec. or OFF (using manual reset) communication option)
Derivative time 1 to 6000 sec. or OFF STOP/START switching
ON/OFF control Switching to AUTO
hysteresis (one or two 0.0 to 100.0% of measured input range width Switching to MANUAL
hysteresis points) Switching to REMOTE (only model with
Preset output -5.0 to 105.0% (however, 0 mA or less cannot communication option)
be output) Contact input
value Switching to LOCAL (only model with
High/low output -5.0 to 105.0% communication option)
limiter Low limit setpoint < high limit setpoint AUTO-TUNING START/STOP switching
When manual control is carried out with 4 to LCD backlight ON/OFF switching
Tight shut
20 mA output, control output can be reduced to Message interrupt displays 1 through 4
function
about 0 mA.
SP number specification
Rate-of-change
0.1 to 100.0%/sec., OFF PID number specification
limiter of output
Manual preset output number specification
Output For heating and cooling control: -100.0 to 50.0% Alarms 1 through 4
deadband For position proportional control: 1.0 to 10.0% Contact output
Status output

(5) Ladder computation period Ladder Sequence Function


Ladder computation period is the same as control period. (1) Number of I/O Points
UT35A UT32A
Alarm Functions Number of digital input points Up to 7 Up to 4
Types of Alarm Number of digital output points Up to 8 Up to 5

PV (measured value) high/low limit alarm This is limited by the number of contact I/O signal
Measured value Deviation high/low limit alarm points. (See the model code.)
alarm Deviation high and low limits alarm
Deviation alarm Deviation within high and low limits alarm (2) Types of Command
Rate-of-change Analog input PV high/low limit alarm Number of
alarm Feedback input high/low limit alarm Remark
commands
PV rate-of-change alarm Number of basic Load, AND, OR, Timer,
SP (setpoint) high/low limit alarm 13
command types Counter, etc.
Target SP high/low limit alarm
Comparison, reverse, addition/
Setpoint alarm Target SP deviation high/low limit alarm
Number of applica- subtraction/multiplication/
Target SP deviation high and low limits alarm 73
tion command types division, logic operation, high/
Target SP deviation within high and low limits alarm
low limiter, etc.
Control output high/low limit alarm
Output alarm
Cooling control output high/low limit alarm (3) Sequence Device
Heater disconnection alarm (for /HA option)
Other alarms Self-diagnosis alarm Types of device Number of points
FAIL Input relay 7 (max)
Digital I/O
Output relay 8 (max)
Alarm Functions M relay (bit data) 256
Alarm stand-by action DAT register (data) 28
Alarm output Alarm latch (forced reset) function Internal device
P register (parameter) 10
action Alarm hysteresis
Alarm ON/OFF delay timer K register (constant) 30
Number of alarm Special device Special relay (bit data) 12
4
settings Process data and process relay can be used besides
Number of alarm
Up to 8 (differs by model code) the above-mentioned.
output points
(4) Program capacity
Max Program capacity: 300 steps *
*: Available number of steps differs according to the
parameters and using command.
(5) Ladder computation period
Ladder computation period is the same as control
period.

All Rights Reserved. Copyright 2009-2013, Yokogawa Electric Corporation GS 05P01D31-01EN Jun. 28, 2013-00
<<Contents>> <<Index>> 3
Communication Function
Communication
Function Method Interface Targets Max connection
Data
Server Ethernet PLC and others 2 connections
RS-485:
Modbus/TCP UT55A/UT52A/
Ethernet
A standard industry protocol Gateway UT35A/UT32A/ 31 units
+RS-485
allowing communications UP55A/UP35A/
between the controller and UM33A (*1)
devices such as PCs, PLCs, PLC and others,
and DCSs. UT55A/UT52A/
Modbus
Slave RS-485 UT35A/UT32A/ 31 units
(RTU/ASCII) UP55A/UP35A/
UM33A (*2)
Number of nodes:
Slave RS-485 PLC and others 126
PROFIBUS-DP UT55A/UT52A/ 31 Units
Modbus master RS-485 UT35A/UT32A/ (Main Controller
function UP55A/UP35A is included.)
Number of nodes:
Used for communication Slave RS-485 PLC and others 42 (Remote device)
CC-Link between PLCs and UT55A/UT52A/ 31 Units
remote I/O, enabling high- Modbus master RS-485 UT35A/UT32A/ (Main Controller
speed data transmission. function PV, SP, OUT,
UP55A/UP35A is included.)
Number of nodes: ALM etc
Slave RS-485 PLC and others
64
DeviceNet UT55A/UT52A/ 31 Units
Modbus master
RS-485 UT35A/UT32A/ (Main Controller
function
UP55A/UP35A is included.)
A protocol allowing multiple Read/Write: 4
controllers to send and RS-485 UT55A/UT52A/ units
Peer to peer receive data between Multi-drop (2 wire UT35A/UT32A/ Read only : 28
one another. The Ladder only) UP55A/UP35A units
Program is used.
A protocol to coordinate the
Coordinated UT55A/UT52A/
operation of two or more Master : 1 unit
Master/Slave RS-485 UT35A/UT32A/
Communication instruments controlling the Slave : 31 units
UP55A/UP35A(*2)
same process.
The proprietary Yokogawa
protocol allowing PC and others,
PC link UT55A/UT52A /
communications to PCs,
PLCs and touch panels. Slave RS-485 UT35A/UT32A/ 31units
UP55A/UP35A/
A protocol to communicate UM33A(*2)
Ladder to PLCs.
*1: UT digital indicating controller, Signal conditioner JUXTA, Power monitor POWERCERT can be connected.
*2: UT digital indication controllers can be connected.
Physical interface
Ethernet Standard : IEEE802.3 (10BASE-T, 100BASE-TX)
Max segment length : 100m
Max. Connecting Configguration : Cascade Max. 4 level (10BASE-T), Max. 2 level (100BASE-TX)
RS-485 Standard : EIA RS-485
Communication method : Two-wire harf-duplex or four-wire harf-duplex, start-stop synchoronization,
and non-procedural
Baud rate : 600,1200,2400,4800,9600,19200 or 38400bps Peer to peer communication is only 19200bps
Maximum communication distance : 1200m
Terminating resistor : 220 (External)
PROFIBUS-DP Standard : Field bus (IEC61158)
Corresponding version : DP V0
Baud rate : 9.6k, 19.2k, 45.45k, 93.75k, 187.5k, 0.5M, 1.5M, 3M, 6M, 12M, AUTO (*3)
Communication distance : 1200m (9.6k to 93.75k) 1000m (187.5k)
400m (0.5M) 200m (1.5M)
100m (3M to 12M)
*3: AUTO automatically sets the baud rate to that of the host controller (PROFIBUS-DP master).
CC-Link Supported on version : Remote device (Ver.1.10, Ver.2.00)
Baud rate : 156k, 625k, 2.5M, 5M, 10M bps
Transmission distance : 1.2km (156k bps), 600m (625k bps), 200m (2.5M bps), 150m (5M bps),
100m (10M bps)
When used optical repeater : 7.6 km (156k) to 4.3 km (10M)
DeviceNet Field bus (IEC61158)
Baud rate 125k, 250k, 500k bps
Transmission distance 500m (125k bps), 250m (250k bps), 100m (500k bps)

All Rights Reserved. Copyright 2009-2013, Yokogawa Electric Corporation GS 05P01D31-01EN Jun. 28, 2013-00
<<Contents>> <<Index>> 4
n Hardware Specifications The accuracy is that in the standard operating condi-
tions: 23 2C, 55 10%RH, and power frequency at
Display Specifications 50/60 Hz.
PV display *1: 0.3C and 1 digit in the range between 0 and 100C
5-digit, 14-segment active color LCD (white/red) 0.5C 1 digit in the range between -100 and 200C
Character height: 21.5 mm for UT35A and 13.0 mm *2: W-5% Re/W-26% Re (Hoskins Mfg.Co.), ASTM E988
for UT32A Applicable standards: JIS, IEC and DIN (ITS-90) for ther-
Data display mocouples and resistance-temperature detectors (RTD)
5-digit, 11-segment color LCD (orange) Input sampling period: Synchronized to control period
Bar graph display Burnout detection
12-segment color LCD (orange) Upscale and downscale of function, and OFF can
be specified for the standard signal of thermocou-
Universal Input Specifications
ple and resistance-temperature detector (RTD).
Number of input points: 1 For integrated signal input, 0.1 V or 0.4 mA or less
Types of input, instrument range, and measurement is judged as a burnout.
accuracy (see the table below) Input bias current: 0.05 A (for thermocouple and
Instrument range resistance-temperature detector (RTD))
Types of input Accuracy
C F Resistance-temperature detector (RTD) measured
-270.0 to 1370.0C -450.0 to 2500.0F 0.1% of instrument
range 1 digit for 0C
current: About 0.16 mA
K -270.0 to 1000.0C -450.0 to 2300.0F
-200.0 to 500.0C -200.0 to 1000.0F or more Input resistance
J -200.0 to 1200.0C -300.0 to 2300.0F 0.2% of instrument 1 M or more for thermocouple/mV input
-270.0 to 400.0C -450.0 to 750.0F range 1 digit for less
than 0C About 1 M for voltage input
However, 2% of About 250 for current input (with built-in shunt
instrument range
1 digit for less than
resistance)
T
0.0 to 400.0C -200.0 to 750.0F -200C of thermocouple Allowable signal source resistance
K 1% of instrument
range 1 digit for less
250 or less for thermocouple/mV input
than -200C of thermo- Effect of signal source resistance: 0.1 V/ or less
couple T 2 k or less for DC voltage input
0.15% of instrument
range 1 digit for 400C Effect of signal source resistance: about
B 0.0 to 1800.0C 32 to 3300F
or more 0.01%/100
5% of instrument
range 1 digit for less
Allowable wiring resistance
than 400C Up to 150 per line for resistance-temperature
S 0.0 to 1700.0C 32 to 3100F 0.15% of instrument detector (RTD) input (conductor resistance
Thermocouple

R 0.0 to 1700.0C 32 to 3100F range 1 digit


0.1% of instrument between the three lines shall be equal)
range 1 digit Effect of wiring resistance: 0.1C/10
N -200.0 to 1300.0C -300.0 to 2400.0F 0.25% of instrument
range 1 digit for less
Allowable input voltage/current
than 0C 10 V DC for thermocouple/mV/mA or resistance-
E -270.0 to 1000.0C -450.0 to 1800.0F 0.1% of instrument
range 1 digit for 0C
temperature detector (RTD) input
L -200.0 to 900.0C -300.0 to 1600.0F
-200.0 to 400.0C -300.0 to 750.0F or more 20 V DC for V input
0.2% of instrument 40 mA DC for mA input
range 1 digit for less
than 0C Noise reduction ratio
U
0.0 to 400.0C -200.0 to 1000.0F However, 1.5% of 40 dB or more (at 50/60 Hz) in normal mode
instrument range 1 digit
for less than -200.0C of
120 dB or more (at 50/60 Hz) in common mode
thermocouple E Reference junction compensation error
W (*2) 0.0 to 2300.0C 32 to 4200F
0.2% of instrument 1.0C (15 to 35C)
range 1 digit
Platinel 0.1% of instrument 1.5C (-10 to 5C and 35 to 50C)
0.0 to 1390.0C 32.0 to 2500.0F
2 range 1 digit
0.5% of instrument
range 1 digit for 800C
PR20-40 0.0 to 1900.0C 32 to 3400F or more
Accuracy not guaran-
teed for less than 800C
W97
0.2% of instrument
Re3-W75 0.0 to 2000.0C 32 to 3600F
range 1 digit
Re25
0.1% of instrument
-200.0 to 500.0C -300.0 to 1000.0F
detector (RTD) 3-wire
Resistance-temperature

range 1 digit (*1)


JPt100
0.1% of instrument
-150.00 to 150.00C -200.0 to 300.0F
range 1 digit
-200.0 to 850.0C -300.0 to 1560.0F 0.1% of instrument
-200.0 to 500.0C -300.0 to 1000.0F range 1 digit (*1)

Pt100
0.1% of instrument
-150.00 to 150.00C -200.0 to 300.0F
range 1 digit

0.400 to 2.0000 V -
Standard
1.000 to 5.000 V -
signal
4.00 to 20.00 mA -
0.1% of instrument
0.000 to 2.000 V -
range 1 digit
DC voltage 0.00 to 10.00 V -
-10.00 to 20.00 mV -
DC current 0.00 to 20.00 mA -

All Rights Reserved. Copyright 2009-2013, Yokogawa Electric Corporation GS 05P01D31-01EN Jun. 28, 2013-00
<<Contents>> <<Index>> 5
Analog Output Specifications UT35A: Two 1a-contact points , 3 A at 250 V
Number of points AC or 3A at 30 V DC (resistance load)
Control output (heating-side output): 1 point UT32A: Two 1a-contact points , 3 A at 240 V
(standard), which is shared with transmission AC or 3A at 30 V DC (resistance load)
output *: This should always be used with a load of 10 mA or more.
Cooling-side output: 1 point, which is Retransmission Output Specifications
shared with transmission output Number of points: 1 point (standard), which is shared
Output functions with 15 V DC loop power supply
Current output or voltage pulse output Additional 1 points when analog control output are
Current output not used
4 to 20 mA DC or 0 to 20 mA DC/load resistance Output function: current output
600 or less 4 to 20 mA DC or 0 to 20 mA DC/load
Current output accuracy resistance 600 or less
0.1% of span (however, 5% of span for 1 mA Current output accuracy (conversion accuracy from
or less) PV display on the set scale): 0.1% of span (how-
The accuracy is that in the standard operating ever, 5% of span for 1 mA or less)
conditions: 23 2C, 55 10%RH, and power The accuracy is that in the basic operating
frequency at 50/60 Hz conditions: 23 2C, 55 10%RH, and power
Voltage pulse output frequency at 50/60 Hz
Application: time proportional output This is not conversion accuracy through input
ON voltage: 12 V or more/load resistance of 600 and output but the performance of transmission
or more output itself.
OFF voltage: 0.1 V DC or less
Time resolution: 10 ms or 0.1% of output value, 15V DC Loop Power Supply Specifications
whichever is larger Number of points: 1 point (standard), which is shared
with retransmission output
Relay Contact Output Specifications Control output (1 point) can also be used.
Types of contact and number of points Supply voltage: 14.5 to 18.0 V DC
Control relay output: one 1c-contact point Maximum supply current: about 21 mA (with short-
Control output of heating and cooling control: circuit current limiting circuit)
2 1a-contact points
Alarm output: 3 1a-contact points (Common is Contact Input Specifications
separated) Number of points: 2 points (standard)
Contact rating For the maximum number of points, see the
1c-contact: 3 A at 250 V AC or 3 A at 30 V DC model and suffix code table.
(resistance load) Input type: no-voltage contact input or transistor con-
1a-contact: tact input
For alarm output: 1 A at 240 V AC or 1 A at Input contact capacity: 12 V DC, 10 mA or more
30 V DC (resistance load) Be sure to use a contact with a minimum ON
For output of heating and cooling control current of 1 mA or more
relay output: 3 A at ON/OFF detection
240 V AC or 3 A at 30 V DC (resistance load) For no-voltage contact input:
*: The control output should always be used with a load Contact resistance 1 k or less in ON state
of 10 mA or more. Contact resistance 50 k or more in OFF state
The alarm output should always be used with a load Transistor contact input:
of 1 mA or more. 2 V or less in ON state
Application: time proportional output, alarm output, Leak current 100 A or less in OFF state
FAIL output, etc. Status detection minimum hold time: control period
Time resolution for control output: 10 ms or 0.1% of + 50 ms
output value, whichever is larger Application: SP switching, operation mode switching,
Step Response Time Specifications event input
1s Transistor Contact Output Specifications
(Response time at 63% of transmission output when a Number of points: see the model and suffix code table
change is made stepwise in the range between 10 and Output form: open collector (sink current)
90% of input span) Output contact capacity: Up to 24 V DC, 50 mA
Output time resolution: min 200 ms
Position Proportional Output Specifications
Position signal input
Heater Break Alarm Specifications (for /HA Option)
Slide resistance: 100 to 2.5 k of total resistance Function: Measures the heater current using an
100% side and slide line: with disconnection external current transformer (CT) and generates a
detection heater break alarm when the measured value is less
0% side: without disconnection detection than the disconnection detection value.
Current input: 4 to 20 mA DC (with disconnection Number of input points: 2 points
detection) Number of output points: 2 points (transistor contract
Input resistance: about 330 output)
Sampling period: 50 ms CT input resistance: about 9.4
Measurement resolution: 0.1% of input span CT input range: 0.0 to 0.1 Arms (0.12 Arms or more
Position proportional relay output cannot be applied)

All Rights Reserved. Copyright 2009-2013, Yokogawa Electric Corporation GS 05P01D31-01EN Jun. 28, 2013-00
<<Contents>> <<Index>> 6
Heater current alarm setting range: OFF, 0.1 to 300.0 Withstanding voltage
Arms 2300 V AC for 1 minute between primary and
Heater current measured value display range: 0.0 to secondary terminals (UL, CSA)
360.0 Arms 3000 V AC for 1 minute between primary and
*: The CT ratio can be set. CT ratio setting range: 1 to 3300 secondary terminals (CE)
Recommended CT: CT from URD Co. Ltd. 1500 V AC for 1 minute between primary terminals
CTL-6-S-H: CT ratio 800, measurable current 500 V AC for 1 minute between secondary
range: 0.1 to 80.0 Arms terminals
CTL-12L-30: CT ratio 3000, measurable current (Primary terminals = Power (*) and relay output
range: 0.1 to 180.0 Arms terminals, Secondary terminals = Analog I/O signal
Heater current measurement period: 200 ms terminals, contact input terminals, communication
Heater current measurement accuracy: 5% of CT terminals, and functional grounding terminals.)
input range span 1 digit (CT error is not included) *: Power terminals for 24 V AC/DC models are the
Heater current detection resolution: Within 1/250 of secondary terminals.
CT input range span Insulation resistance
Disconnection detection ON time: Minimum 200 ms. Between power supply terminals and a grounding
(for time proportional output) terminal: 20 M or more at 500 V DC
Isolation specifications
24 V DC Loop Power Supply Specifications
(for /LP Option) PV (universal) input terminal
Application: Power is supplied to the 2-wire transmitter. Control and transmission (analog) output terminal
Supply voltage: 21.6 to 28.0 V DC (not isolated between the analog output terminals)
Valve position (feedback) input terminal
Rated current: 4 to 20 mA DC
Maximum supply current: About 30 mA (with short- Control relay (c-contact or 2 a-contact) output terminal

circuit current limiting circuit) Alarm-1 relay (a-contact) output terminal

Safety and EMC Standards Alarm-2 relay (a-contact) output terminal

Safety: Alarm-3 relay (a-contact) output terminal Internal Power


Compliant with IEC/EN61010-1 (CE), IEC/EN61010- Position proportional relay output terminal
circuits supply

2-030 (CE), approved by CAN/CSA C22.2 No. Contact input terminal (All)
61010-1 (CSA), approved by UL61010-1. RS485 communication terminal (2 ports)
Installation category: II 24 V DC loop power supply terminal
Pollution degree: 2 Contact output (transistor) terminal
Measurement category: I (CAT I) (UL, CSA)
Ethernet/PROFIBUS-DP/CC-Link/DeviceNet
O (Other) (CE) communication terminal
Rated measurement input voltage: Max. 10 V DC
Current transformer input terminal
Rated transient overvoltage: 1500 V (*)
*: This is a reference safety standard value for measure- The circuits divided by lines are insulated mutually.
ment category I of IEC/EN/CSA/UL61010-1. This value is
not necessarily a guarantee of instrument performance. Environmental Conditions
EMC standards: Normal operating conditions
Compliant with Ambient temperature: -10 to 50C (-10 to 40C for
CE marking side-by-side mounting of controllers)
EN 61326-1 Class A, Table 2 (For use in industrial For the CC-Link option, 0 to 50 C (0 to 40 C for
locations), side-by-side close mounting)
EN 61326-2-3 Ambient humidity: 20 to 90% RH (no condensation)
*: The instrument continues to operate at a measurement
Magnetic field: 400 A/m or less
accuracy of within 20% of the range during testing.
Continuous vibration (at 5 to 9 Hz) Half amplitude of
EN 55011 Class A, Group 1
1.5 mm or less
EN 61000-3-2 Class A
(at 9 to 150 Hz) 4.9 m/s2 or less, 1 oct/min for 90 min-
EN 61000-3-3
utes each in the three axis directions
EMC Regulatory Arrangement in Australia and New Zealand
Rapid vibration: 14.7 m/s2, 15 s or less
EN 55011 Class A, Group 1
Impact: 98 m/s2 or less, 11 msec.
KC marking: Electromagnetic wave interference
Installation altitude: 2,000 m or less above sea level
prevention standard, electromagnetic wave protection
Warm-up time: 30 minutes or more after the power is
standard compliance
turned on
Power Supply Specifications and Isolation Start-up time within 10 s
Power supply
Rated voltage: 100 to 240 V AC (+10%/-15%), 50/60 Hz
24 V AC/DC (+10%/-15%) (When the
/DC option is specified)
Power consumption: UT35A: 18 VA (For the /DC
option. DC: 9 VA, AC: 14 VA)
UT32A: 15 VA (For the /DC
option. DC: 7 VA, AC: 11 VA)
Storage: Nonvolatile memory
Allowable power interruption time: 20 ms (at 100 V AC)

All Rights Reserved. Copyright 2009-2013, Yokogawa Electric Corporation GS 05P01D31-01EN Jun. 28, 2013-00
<<Contents>> <<Index>> 7
Transportation and Storage Conditions For RTD input:
Temperature: -25 to 70C 0.05C/C (ambient temperature) or less
Temperature change rate: 20C per hour or less For current input:
Humidity: 5 to 95%RH (no condensation) 0.01% of F.S. (instrument range)/C
For analog output:
Effects of Operating Conditions 0.02% of F.S./C or less
Effect of ambient temperature Effect of power supply fluctuation:
For voltage or TC input: For analog input: 0.05% of F.S. (instrument range)
1 V/C or 0.01% of F.S. (instrument or less
range)/C, whichever is greater For analog output: 0.05% of F.S. or less
(Each within rated voltage range)

n Block Diagram
Single Loop Control
Equipped as standard
Equipped as standard.
PV input Contact inputs

PV DI1 DI2

Input type IN

Input unit UNIT

Input range/scale RH, RL SDP SH, SL

Input ladder calculation program (signal goes to the control computation as is when without ladder program). For ladder program, see the LL50A Parameters Setting Software Users Manual.

PV input bias BS Communication


SPNO SP
PV input filter FL
Ratio bias computation RT RBS Target setpoints 1 to 4
REMOTE LOCAL
R/L

SP limiter SPH, SPL

SP ramp rate UPR, DNR TMU

PV display SP display
Control computation

CNT ALG

Output limiter OH, OL


Input error preset output EPO
Normal
When sensor burnout occurs
Manual preset output MPON

Manual operation

Output limiter OH, OL OLMT


MAN AUTO
A/M AUTO (ON)/MAN (OFF) switch
Preset output PO

STOP RUN
S/R STOP (ON)/RUN (OFF) switch

* After the control output terminal is specified by the parameter OT,


Output terminal assignment OT other current output terminals can be used as retransmission output.

OUT retransmission output Equipped as standard Equipped as standard


O1RS RET retransmission output Alarm
RTS

Output ladder calculation program (signal goes to the output as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software Users Manual.

For optional suffix code /LP For optional suffix code /HA
24 V loop Heater break alarm
power supply
(PV high limit)

(PV high limit)


(PV low limit)
Alarm 1

Alarm 3
Alarm 2

LPS OUT OUT RET AL1 AL2 AL3 HAL1 HAL2

Heater break Heater break


Relay Current or voltage pulse Current alarm 1 alarm 2
(Current when retransmission output)
Terminal Parameter Function
Legend
Analog signal Contact signal Front panel key

All Rights Reserved. Copyright 2009-2013, Yokogawa Electric Corporation GS 05P01D31-01EN Jun. 28, 2013-00
<<Contents>> <<Index>> 8
n Terminal Arrangement
Terminal Arrangement for UT35A Single Loop Control
(Equipped
Control output OUT PV input PV as standard) Retransmission output RET (Equipped as standard)
(Suffix code: Type1=-0)
Relay contact output Factory default: PV input TC input RTD input Retransmission output 15 V DC loop power supply Can be used for 15 V DC loop
type is undefined. power supply when not used for
Terminal wiring differs in Heating/cooling Default: PV
NC 101 A 201 retransmission retransmission output.
control and Position proportional control.
+ 202 + 205 + 205
Refer to the terminals of Position 4-20 mA DC or 14.5-18.0 V DC
NO 102 b 202 0-20 mA DC (Max. 21 mA DC)
proportional control output and - 203 - 206 - 206
Heating/cooling control output below. Load resistance 600 or less
COM 103 B 203
Factory default: Control output is relay. Default: 4-20 mA DC
Contact rating: 250 V AC, 3 A Current (mA) input Voltage (mV, V) input
30 V DC, 3 A (resistance load)
Cooling-side control output RET/OUT2
- 203 + 202 (Suffix code: Type 1=-2)
Current/voltage pulse output
Can not be used for retransmission output or
Heating/cooling control output + 204 - 203
+ 205 15 V DC loop power supply when
0-20 mA DC, current/voltage pulse output is used.
Heating/cooling relay contact output (Suffix code: Type 1=-2) 4-20 mA DC,
Voltage pulse (12V) Can be used for retransmission output or 15 V
OUT2 Cooling NO
-side 101 E4-terminal area E1-terminal area - 206 DC loop power supply when control output is
101 501 401 301 201 not used.
Heating NO Current output range can be changed.
OUT -side 102 -112 -512 -412 -306 -212
101 501 401 301 201
COM 103
Contact rating: 240 V AC, 3 A 102 502 302 202
30 V DC, 3 A (resistance load)
103 503 303 203
Control output OUT (Suffix code: Type1=-0, -1 or -2)
Current/voltage pulse output Retransmission output 15 V DC loop power supply
104 504 304 204
Default: Undefined
105 505 305 205 + 207
0-20 mA DC, + 207 + 207
4-20 mA DC, 0-20 mA DC, 14.5-18.0 V DC
106 506 306 206 Voltage pulse (12 V) 4-20 mA DC (Max. 21 mA DC)
- 208 - 208 - 208
107 507 407 207
Default: 4-20 mA DC
108 508 408 208
(Equipped Can be used for retransmission output or 15 V DC loop power supply when
Contact output ALM as standard) 109 509 409 current/voltage pulse output is not used for control output.
Current output range can be changed.
External contact output (relay) 110 510 410 210 In Position proportional type, can be used for retransmission output or 15 V
Alarm-3 output UT DC loop power supply.
(PV high limit) 104 111 511 411 211
AL3
112 512 412 212
105 Contact input
Common
DI (Equipped as standard)
Alarm-2 output
( PV low limit)
106 External contact input
AL2 E3-terminal area No-voltage
contact UT Transistor UT
+5V
Common 107 contact DI2
STOP when DI2=ON 210 DI2 210
Alarm-1 output RUN when DI2=OFF +5V
108
(PV high limit) DI1
AL1 AUTO when DI1=ON 211 DI1 211
109 MAN when DI1=OFF
Common COM
Relay contact rating: 240 V AC, 1 A
Position proportional control output VALV Common
212 COM 212
30 V DC, 1 A (resistance load) Relay contact output Feedback input (Suffix code: Type1=-1) Contact rating: 12 V DC, 10 mA or more
HIGH 100% Function can be assigned to the terminals with no function.
(direct) 507 510

Power supply LOW


(reverse) 508 511
100-240 V AC power supply 24 V AC/DC power supply COM 509 0% 512
Heater break alarm HBA (Optional suffix code /HA)
N N Heater current detection input
110 - 110 Contact rating: 250 V AC, 3A Resistance: 100 to 2.5 k External contact output (transistor)
30 V DC, 3 A UT
L L
+ 111 (resistance load) Feedback input Heater break alarm-1 HAL1 507 510
111 output
Current (mA) CT1
input + 510 Heater break alarm-2
511
112 112 HAL2 508 CT2
output
Allowable range: (24 V AC/DC power supply: Optional suffix code /DC) 511 512
Common COM 509 COM
100-240 V AC (+10%/-15%)
(free voltage) - 512
50/60 Hz shared Transistor contact rating: 24 V DC, 50 mA
When feedback input is current

All Rights Reserved. Copyright 2009-2013, Yokogawa Electric Corporation GS 05P01D31-01EN Jun. 28, 2013-00
<<Contents>> <<Index>> 9
E4-terminal area E1-terminal area
301-306 E1-Terminal Area 501-506 E4-Terminal Area
101 501 401 301 201
-112 -512 -412 -306 -212
101 501 401 301 201 Contact input DI (Suffix code: Type 2=2) Contact output DO (Suffix code: Type 2=2)
102 502 302 202 External contact input External contact output
No-voltage UT UT UT
103 503 303 203 contact Transistor contact
COM Factory default: No function DO45 501
104 504 304 204 Common 301 COM 301
+5V
DI11 Factory default: No function DO44 502
105 505 305 205 Factory default: No function 302 DI11 302
+5V
106 506 306 206 DI12 Factory default: No function DO43 503
Factory default: No function 303 DI12 303
+5V
107 507 407 207 DI13
Factory default: No function 304 DI13 304 Factory default: No function DO42 504
108 508 408 208 +5V
DI14
Factory default: No function 305 DI14 305 Factory default: No function DO41 505
109 509 409 +5V
DI15
110 510 410 210 Factory default: No function 306 DI15 306 Common COM 506
111 511 411 211 Contact rating: 12 V DC, 10 mA or more Function can be assigned to the Transistor contact rating: 24 V DC, 50 mA
112 terminals with no function. Function can be assigned
512 412 212
to the terminals with no
function.

E3-terminal area Contact input / Contact output DI/DO (Suffix code: Type 2=1)
External contact input
No-voltage
contact
UT Transistor contact UT 24 V DC loop power supply
COM
Common 301 COM 301
+5V
24 V DC loop power supply
LPS24
DI11 (Optional suffix code /LP)
Factory default: No function 302 DI11 302
+5V + 505
DI12 21.6-28.0 V DC
Factory default: No function 303 DI12 303 (Max. 30 mA DC)
506
Contact rating: 12 V DC, 10 mA or more

External contact output Function can be


assigned to the
UT terminals with no
Factory default: No function DO12 304
function.

Factory default: No function DO11 305

Common COM 306

Transistor contact rating: 24 V DC, 50 mA

401-412 E3-Terminal Area

RS-485 communication RS485 Ethernet communication (with gateway function)


RS-485 (Suffix code: 10BASE-T/100BASE-TX ETHR
Type 3=1) RJ45 connector (Suffix code: Type 3=2)
SDB(+) 407

SDA(-) 408
Upper side LED (baud rate)
SG 409 Color Amber
Lit 100M bps
RDB(+) 410 Unlit 10M bps RS-485
Lower side LED (link activity)
RDA(-) 411 RSB(+) 407
Color Green
Lit Linked RSA(-) 408
Blink Active
Unlit Link failure SG 409

PROFIBUS-DP communication (with Modbus master) CC-Link communication (with Modbus master) DeviceNet communication (with Modbus master)
VP
PROF DA CC-L CAN_H DNET
1 Data 390 1 1
CHK line (Suffix code: Type 3=4) CHK 110 (Suffix code: Type 3=3) 121 (Suffix code: Type 3=5)
2 RxD/TxD-P 2 2
RDY DB CHK CAN_L
3 Data 220 If the UT is located at the end 3 If the UT is located at 3 If the UT is located at
ERR line RxD/TxD-N of a segment for the L ERR the end of a segment the end of a segment
4 4 4
PROFIBUS
390 L RUN for the CC-Link 5
MNS for the DeviceNet
5 5
communication wiring,
DGND communication wiring, communication wiring,
terminating resistors are terminating resistors terminating resistors
Pin Signal name Description Pin Signal name Description Pin Signal name Description
separately needed. are separately needed. are separately needed.
1 VP +5V bus power These are to be prepared by 1 FG Flame ground These are to be 1 V+ DeviceNet power supply 24V These are to be
Data signal users. (390 : 2 pcs. 220 : 2 SLD Shield prepared by users. 2 CAN_H RX/TX + signal prepared by users.
2 RxD/TxD-P
(positive data receive/transmit) 1 pc., or an active 3 DG RX/TX signal ground (110 : 1 pc.) 3 DRAIN Shield/Drain wire (121 : 1 pc.)
Data signal terminator.) 4 DB RX/TX - signal 4 CAN_L RX/TX - signal
3 RxD/TxD-N
(negative data recive/transmit) 5 DA RX/TX + signal 5 DeviceNet power supply common
V-
4 DGND Signal ground
LED Lit Unlit LED Lit/flashing Unlit
5 SHIELD Shield ground
CHK User profile error/ CHK
(red) Normal (red) User profile error Normal
LED Lit Unlit Address error
RS-485 RS-485 RS-485
CHK Normal, communicating
(red) User profile error Normal L ERR Communication failure successfully (green, lit).
RSB(+) 407 Normal RSB(+) 407 RSB(+) 407
Normal No power, or (red) (CRC error) Not connected (green, flashing).
RDY Communicating MNS
Communication (green Critical link failure (red, lit). No electricity
(green) successfully failure RSA(-) 408 RSA(-) 408 RSA(-) 408
No carrier /red) Connection timeout (red, flashing)
L RUN Normal detected/
ERR Not connected, or
communication Normal SG 409 (green) Communicating successfully Communication SG 409 At power-on/Communication SG 409
(red)
failure (flashing) timeout faulted (green/red, flashing)

All Rights Reserved. Copyright 2009-2013, Yokogawa Electric Corporation GS 05P01D31-01EN Jun. 28, 2013-00
<<Contents>> <<Index>> 10
Terminal Arrangement for UT32A Single Loop Control
Control output OUT PV input PV (Equipped
as standard) Retransmission output RET (Equipped as standard)
(Suffix code: Type1=-0) Factory default:
Relay contact output TC input RTD input Retransmission output 15 V DC loop power supply Can be used for 15 V DC loop
Terminal wiring differs in Heating/cooling PV input type is power supply when not used for
Default:
NC 101 control and Position proportional control. undefined. A 201 PV retransmission retransmission output.
Refer to the terminals of Position + 202 + 205 + 205
NO 102 b 202 4-20 mA DC or 14.5-18.0 V DC
proportional control output and 0-20 mA DC (Max. 21 mA DC)
- 203 - 206 - 206
Heating/cooling control output below.
COM 103 B 203 Load resistance 600 or less
Factory default: Control output is relay. Default: 4-20 mA DC
Contact rating: 250 V AC, 3 A Current (mA) input Voltage (mV, V) input
30 V DC, 3 A (resistance load)
Cooling-side control output RET/OUT2
- 203 + 202 (Suffix code: Type 1=-2)
Current/voltage pulse output
+ 204 - 203 Can not be used for retransmission output or 15 V
+ 205 DC loop power suppy when current/voltage pulse
0-20 mA DC,
4-20 mA DC, output is used for control output.
Heating/cooling control output E1-terminal area Voltage pulse (12 V)
- 206
Can be used for retransmission output or 15 V DC
loop power suppy when control output is not used.
Heating/cooling relay contact output (Suffix code: Type 1=-2) 101 301 201 Current output range can be changed.
Cooling NO -112 -312 -212
OUT2 -side 101
101 301 201
Heating NO
OUT -side 102
102 302 202
COM 103 103 303 203 Control output OUT (Suffix code: Type1=-0, -1 or -2)
Contact rating: 240 V AC, 3 A 104 304 204 Current/voltage pulse output Retransmission output 15 V DC loop power supply
30 V DC, 3 A (resistance load)
Default: Undefined
105 305 205 + 207
0-20 mA DC, + 207 + 207
106 306 206 4-20 mA DC, 0-20 mA DC, 14.5-18.0 V DC
Voltage pulse (12 V) 4-20 mA DC (Max. 21 mA DC)
- 208 - 208
107 307 207 - 208
Default: 4-20 mA DC
108 308 208
Can be used for retransmission output or 15 V DC loop power suppy when
Contact output ALM (Equipped
as standard)
109 309 current/voltage pulse output is not used for control output.
Current output range can be changed.
External contact output (relay) 110 310 210
In Position proportional type, can be used for retransmission output or 15 V DC
Alarm-3 output UT 111 311 211 loop power supply.
(PV high limit) 104
AL3 112 312 212
Common 105
Alarm-2 output Contact input DI (Equipped as standard)
(PV low limit) 106
AL2 External contact input
Common 107 No-voltage
UT Transistor UT
contact contact +5V
Alarm-1 output STOP when DI2=ON DI2
108 210 DI2 210
(PV high limit) RUN when DI2=OFF +5V
AL1 DI1
AUTO when DI1=ON 211 DI1 211
Common 109 Position proportional control output VALV MAN when DI1=OFF
COM
Relay contact rating: 240 V AC, 1 A Relay contact output Feedback input (Suffix code: Type1=-1) 212 COM 212
30 V DC, 1 A (resistance load) Common
HIGH 100%
(direct) 101 310
Contact rating: 12 V DC, 10 mA or more
Power supply LOW
(reverse) 102 311 Function can be assigned to the terminals with no function.

100-240 V AC power supply 24 V AC/DC power supply (24 V AC/DC power supply: COM 103 0% 312
N N
Optional suffix code /DC) Heater break alarm HBA (Optional suffix code /HA)
- 110 Contact rating: 240 V AC, 3A Resistance: 100 to 2.5 k
110
30 V DC, 3 A External contact output (transistor) Heater current detection input
L L (resistance load)
111 + 111 Feedback input UT
Current (mA) Heater break alarm-1 HAL1 307 310
input + 310 output CT1
112 112
Heater break alarm-2
311
HAL2 308 CT2
Allowable range: 311 output
100-240 V AC (+10%/-15%) 312
(free voltage) Common COM 309 COM
- 312
50/60 Hz shared
When feedback input is current Transistor contact rating: 24 V DC, 50 mA

301-306 E1-Terminal Area

RS-485 communication RS485 24 V DC loop power supply


RS-485 (Suffix code: 24 V DC loop power supply
LPS24
Type 2=1) (Suffix code: Type 2=0 and
SDB(+) 301
+ 305 optional suffix code /LP)
21.6-28.0 V DC
SDA(-) 302 (Max. 30 mA DC)
306
SG 303

RDB(+) 304

RDA(-) 305

Contact input / Contact output DI/DO (Suffix code: Type 2=2)


External contact input
No-voltage UT Transistor UT
contact contact
COM
Common 301 COM 301
+5V
DI11
Factory default: No function 302 DI11 302
+5V
DI12
Factory default: No function 303 DI12 303
Contact rating: 12 V DC, 10 mA or more

External contact output Function can be


assigned to the
UT terminals with no
Factory default: No function DO12 304
function.

Factory default: No function DO11 305

Common COM 306

Transistor contact rating: 24 V DC, 50 mA

RS-485 communication/24 V DC loop power supply


RS-485 24 V DC loop power supply RS485/LPS24
RSB(+) 301
(Suffix code: Type 2=1 and
21.6-28.0 V DC
+ 305 optional suffix code /LP)
RSA(-) 302 (Max. 30 mA DC)
306
SG 303

All Rights Reserved. Copyright 2009-2013, Yokogawa Electric Corporation GS 05P01D31-01EN Jun. 28, 2013-00
<<Contents>> <<Index>> 11
n External Dimensions and Panel Cutout Dimensions
UT35A
Unit: mm
11
96 65 Bracket
Terminal cover (option)
20

105.2
91.6
94.6
96
Bracket
1 to 10 mm (panel thickness)
General mounting Side-by-side close mounting
117 min. [(N-1)96+92] +0.8
0

92 +0.8
0

(53) 145
min.
N stands for the number of controllers to be
installed.
92+0.8
0 However, the measured value applies if N5.
Normal tolerance:
92+0.8
0 (25) (value of JIS B 0401-1998 tolerance class IT18)/2

UT32A
Unit: mm
11
48 65 Bracket Terminal cover (option)
20
105.2
91.6
94.6
96

Bracket
1 to 10 mm (panel thickness)
General mounting Side-by-side close mounting
70 min. [(N-1)48+45] +0.6
0
+0.8
92 0

145
(53) min.
N stands for the number of controllers to be
installed.
92 +0.8
0
However, the measured value applies if N5.
Normal tolerance:
45+0.6
0 (25) (value of JIS B 0401-1998 tolerance class IT18)/2

n Construction, Mounting, and Wiring UT32A: 48 (width) x 96 (height) x 65 (depth from the
Dust-proof and drip-proof: IP66 (Front panel) (Except panel surface)
for side-by-side close mounting)/NEMA4 * Mounting: Direct panel mounting; mounting bracket,
*: Hose down test only one each for upper and lower mounting
Material: Polycarbonate resin (Flame retardancy: UL94 V-0) Panel cutout dimensions (mm):
Case color: White (Light gray) or Black (Light Char- UT35A: 92+0.8/0 (width) x 92+0.8/0 (height)
coal gray) UT32A: 45+0.6/0 (width) x 92+0.8/0 (height)
Weight: 0.5 kg or less Mounting position: Up to 30 degrees above the hori-
External dimensions (mm): zontal. No downward titling allowed.
UT35A: 96 (width) x 96 (height) x 65 (depth from the Wiring: M3 screw terminal with square washer (signal
panel surface) wiring and power)

All Rights Reserved. Copyright 2009-2013, Yokogawa Electric Corporation GS 05P01D31-01EN Jun. 28, 2013-00
<<Contents>> <<Index>> 12
n Model and Suffix Code
Optional
Model Suffix code suffix Description
code
Digital Indicating Controller (provided with retransmission output or 15 V DC loop power
UT35A
supply, 2 DIs, and 3 DOs) (Power supply: 100-240 V AC)
-0 Standard type
Type 1:
-1 Position proportional type
Basic control
-2 Heating/cooling type
0 None
Type 2:
1 2 additional DIs, 2 additional DOs
Functions
2 5 additional DIs, 5 additional DOs
0 None
1 RS-485 communication (Max.38.4 kbps, 2-wire/4-wire)
Type 3: 2 Ethernet communication (with serial gateway function)
Open networks 3 CC-Link communication (with Modbus master function)
4 PROFIBUS-DP communication (with Modbus master function)
5 DeviceNet communication (with Modbus master function)
-1 English
-2 German
Display language (*1)
-3 French
-4 Spanish
0 White (Light gray)
Case color
1 Black (Light charcoal gray)
Fixed code -00 Always "-00"
/LP 24 V DC loop power supply (*2)
/HA Heater break alarm (*3)
Optional suffix codes
/DC Power supply 24 V AC/DC
/CT Coating (*4)
*1: English, German, French, and Spanish can be displayed as the guide display.
*2: The /LP option can be specified in the combination of Type 2 code (any of "0" or "1") and Type 3 code (any of "0" or "1".)
*3: The /HA option can be specified when the Type 1 code is "-0" or "-2."
*4: When the /CT option is specified, the UT35A does not conform to the safety standards (UL and CSA) and CE marking.

Optional
Model Suffix code suffix Description
code
Digital Indicating Controller (provided with retransmission output or 15 V DC loop power
UT32A
supply, 2 DIs, and 3 DOs) (Power supply: 100-240 V AC)
-0 Standard type
Type 1:
-1 Position proportional type
Basic control
-2 Heating/cooling type
0 None
Type 2:
1 RS-485 communication (Max. 38.4 kbps, 2-wire/4-wire) (*2)
Functions
2 2 additional DIs and 2 additional DOs
Type 3:
0 None
Open networks
-1 English
-2 German
Display language (*1)
-3 French
-4 Spanish
0 White (Light gray)
Case color
1 Black (Light charcoal gray)
Fixed code -00 Always "-00"
/LP 24 V DC loop power supply (*2)
/HA Heater break alarm (*3)
Optional suffix codes
/DC Power supply 24 V AC/DC
/CT Coating (*4)
*1: English, German, French, and Spanish can be displayed as the guide display.
*2: The /LP option can be specified in the combination of Type 1 code (any of "-0" or "-1") and Type 2 code (any of "0" or "1.") Ad-
ditionally, when the Type 2 code is "1", the RS-485 communication is 2-wire system.
*3: The /HA option can be specified when the Type 1 code is "-0" or "-2."
*4: When the /CT option is specified, the UT32A does not conform to the safety standards (UL and CSA) and CE marking.

n Items to be specified when ordering Name Model

Model and suffix codes, whether Users Manual and Terminal cover (for UT35A) UTAP001
Terminal cover (for UT32A) UTAP002
QIC required.
Users Manual (CD) UTAP003

n Standard accessories Users Manual


Brackets (mounting hardware), Unit label, Operation Product users manuals can be downloaded or viewed
Guide at the following URL. To view the users manual, you
need to use Adobe Reader 7 or later by Adobe Sys-
n Special Order Items tems.
Model code Suffix code Description URL: http://www.yokogawa.com/ns/ut/im/
LL50A -00 Parameter Setting Software
X010 See the General Specifications (*) Resistance Module

*: Necessary to input current signal to voltage input


terminal.

All Rights Reserved. Copyright 2009-2013, Yokogawa Electric Corporation GS 05P01D31-01EN Jun. 28, 2013-00
Subject to change without notice.