LOAD SCHEDULE / CABLE SIZING / VOLTAGE DROP

VOLTAGE SYSTEM : 200


: WIRE : 3W + E
: ENCLOSURE : NEMA-1

CABLE AMPACITY
CONDUIT / CABLE
System RATING LOAD DISTRIBUTION, KVA % BREAKER SIZE GROUND WIRE PF DF K L Full Load CV SERVICE WIRE System % PERMIT VOLTAGE DROP
CKT. NO. LOAD DESCRIPTION Full Load MCCB TRAY Cond/ Voltage REMARKS
Voltage KW KVA AB BC CA AN BN CN 3 Multiplie Pole AT AF mm Type mm Type Current Sets mm Type Voltage allowabl e(V) %V
Current Rating set Drop
1 4-Prong C.O., 3, 200V 3 200 0.80 1.00 1.00 r
1.25 3 2.89 3.61 20 50 3.5 TW 20 PVC 1 1 30.8 2.89 1000 1 3 3.5 THHN 200 e
3% 6 0.00 0.00% OK
2 4-Prong C.O., 3, 200V 3 200 0.80 1.00 1.00 1.25 3 2.89 3.61 20 50 3.5 TW 20 PVC 1 1 30.8 2.89 1000 1 3 3.5 THHN 200 3% 6 0.00 0.00% OK
3 4-Prong C.O., 3, 200V 3 200 0.80 1.00 1.00 1.25 3 2.89 3.61 20 50 3.5 TW 20 PVC 1 1 30.8 2.89 1000 1 3 3.5 THHN 200 3% 6 0.00 0.00% OK
4 4-Prong C.O., 3, 200V 3 200 0.80 1.00 1.00 1.25 3 2.89 3.61 20 50 3.5 TW 20 PVC 1 1 30.8 2.89 1000 1 3 3.5 THHN 200 3% 6 0.00 0.00% OK
5 4-Prong C.O., 3, 200V 3 200 0.80 1.00 1.00 1.25 3 2.89 3.61 20 50 3.5 TW 20 PVC 1 1 30.8 2.89 1000 1 3 3.5 THHN 200 3% 6 0.00 0.00% OK
6 4-Prong C.O., 3, 200V 3 200 0.80 1.00 1.00 1.25 3 2.89 3.61 20 50 3.5 TW 20 PVC 1 1 30.8 2.89 1000 1 3 3.5 THHN 200 3% 6 0.00 0.00% OK
7 4-Prong C.O., 3, 200V 3 200 0.80 1.00 1.00 1.25 3 2.89 3.61 20 50 3.5 TW 20 PVC 1 1 30.8 2.89 1000 1 3 3.5 THHN 200 3% 6 0.00 0.00% OK
8 SPACE
9
10
11
12

TOTAL 5.60 7.00 0.00 0.00 0.00 0.00 0.00 0.00 7.00
TOTAL PANEL LOAD = 7.00 kVA 3 NOTE: MAIN PROTECTION: 30 AT 50 AF MCCB NOTE:
DEMAND FACTOR = 80.00 % System Voltage (V) 230 Apply 125% for Lighting and Receptacle Loads MAIN FEEDER SIZE: 1 sets - 3 x 5.5 mm THHN VOLTAGE DROP PERMISSIBLE PERCENTAGE
TOTAL DEMAND LOAD = 5.60 kVA Transformer (kVA) Apply 125% for Power & Motor Loads 5.5 mm TW in 20 mm IMC 3% FOR BRANCH PROTECTION
TOTAL CURRENT LOAD = 14.06 A 2% FOR MAIN PROTECTION

COMPUTATION: Ref.: PEC 2009 Part 1 APPENDIX C - CONDUIT & TUBING FILL TABLE TABLE 3.10.1.16: ALLOWABLE AMPACITIES
TYPE COND. EMT TYPE COND. PVC (SCH. 80) THHN 90C 31-40C INDOOR USE
FULL LOAD CURRENT: 15 20 25 32 40 50 65 80 90 100 15 20 25 32 40 50 65 80 90 100 CABLE
CAPACITY CORRECTION FACTORS
= 5.60 kVA SIZE
1.732 X 230 V THHN 2.0 (1.6) 12 22 35 61 84 138 241 364 476 608 THHN 2.0 (1.6) 9 17 28 51 70 118 170 265 358 464 3.5 30 A 91 % 27.3 A
FLC = 14.06 A 3.5 (2.0) 9 16 26 45 61 101 176 266 347 443 3.5 (2.0) 6 12 20 37 51 86 124 193 261 338 5.5 40 A 91 % 36.4 A
5.5 (2.6) 5 10 16 28 38 63 111 167 219 279 5.5 (2.6) 4 7 13 23 32 54 78 122 164 213 8 55 A 91 % 50.1 A
CB RATING = 14.06 X 1.25 = 17.57 A 8.0 (3.2) 3 6 9 16 22 36 64 96 126 161 8.0 (3.2) 2 4 7 13 18 31 45 70 95 123 14 70 A 91 % 63.7 A
14 2 4 7 12 16 26 46 69 91 116 14 1 3 5 9 13 22 32 51 68 89 22 90 A 91 % 81.9 A
USE: 30 AT PHASE: 3 WIRE: 3 22 1 2 4 7 10 16 28 43 56 71 22 1 1 3 6 8 14 20 31 42 54 30 115 A 91 % 104.7 A
50 AF MCCB 30 1 1 3 5 7 11 20 30 40 51 30 1 1 2 4 6 10 14 22 30 39 38 130 A 91 % 118.3 A
CABLE SIZE AMPACITY: 38 1 1 1 4 5 8 15 22 29 37 38 0 1 1 3 4 7 10 16 22 29 50 150 A 91 % 136.5 A
CHECK TABLE 3.10.1.16 / 3.10.1.17 FOR ALLOWABLE AMPACITIES. 50 1 1 1 3 4 7 12 19 25 32 50 0 1 1 2 3 6 9 14 18 24 60 170 A 91 % 154.7 A
14.06 36.4 WITH CORRECTION FACTOR (0.91) @ 40C 60 0 1 1 2 3 6 10 16 20 26 60 0 1 1 1 3 5 7 11 15 20 80 205 A 91 % 186.6 A
USE: 1 SET/S 3- 5.5 mm THHN 80 0 1 1 1 3 5 8 13 17 22 80 0 1 1 1 2 4 6 9 13 17 100 225 A 91 % 204.8 A
100 0 1 1 1 2 4 7 11 14 18 100 0 0 1 1 1 3 5 8 10 14 125 265 A 91 % 241.2 A
VOLTAGE DROP CALCULATION: 125 0 0 1 1 1 3 6 9 11 15 125 0 0 1 1 1 3 4 6 8 11 150 295 A 91 % 268.5 A
VD = 30.8 X 14.06 X 13 LM 150 0 0 1 1 1 3 5 7 10 13 150 0 0 0 1 1 2 3 5 7 9 200 355 A 91 % 323.1 A
1000 X 5.5 X 1 SET/S 175 0 0 1 1 1 2 4 6 9 11 175 0 0 0 1 1 1 3 5 6 8 250 400 A 91 % 364.0 A
VD = 1.02 Volts 200 0 0 0 1 1 1 4 6 8 10 200 0 0 0 1 1 1 3 4 6 7 325 470 A 91 % 427.7 A
250 0 0 0 1 1 1 3 5 6 8 250 0 0 0 1 1 1 2 3 5 6 400 515 A 91 % 468.7 A
%V = 1.02 THW 2.0 (1.6) 6 10 16 28 39 64 112 169 221 282 THW 2.0 (1.6) 4 8 13 23 32 55 79 123 166 215 500 580 A 91 % 527.8 A
230 3.5 (2.0) 4 8 13 23 31 51 90 136 177 227 3.5 (2.0) 3 6 10 19 26 44 63 99 133 274
%V = 0.44 3 % 5.5 (2.6) 3 6 10 18 24 40 70 106 138 177 5.5 (2.6) 2 5 8 15 20 34 49 77 104 135 TABLE 3.10.1.16: ALLOWABLE AMPACITIES
USE: 1 SET/S 3- 5.5 mm THHN 8.0 (3.2) 1 4 6 10 14 24 42 63 83 106 8.0 (3.2) 1 3 5 9 12 20 29 46 62 81 THW 75C 31-40C OUTDOOR USE
FOR SERVICE WIRE: 14 1 3 4 8 11 18 32 48 63 81 14 1 1 3 7 9 16 22 35 48 62 CABLE
CAPACITY CORRECTION FACTORS
USE: 1 SET/S 3- 5.5 mm THHN 22 1 1 3 6 8 13 24 36 47 60 22 1 1 3 5 7 12 17 26 35 46 SIZE
FOR GROUND WIRE: 30 1 1 2 4 6 10 17 26 34 44 30 1 1 1 3 5 8 12 19 26 33 3.5 25 A 88 % 22.0 A
CHECK TABLE 2.50.6.13: 38 1 1 1 3 4 7 12 18 24 31 38 0 1 1 2 3 6 8 13 18 23 5.5 35 A 88 % 30.8 A
USE: 1- 5.5 mm TW 50 0 1 1 2 3 6 10 16 20 26 50 0 1 1 1 3 5 7 11 15 20 8 50 A 88 % 44.0 A
FOR CONDUIT SIZING: 60 0 1 1 1 3 5 9 13 17 22 60 0 1 1 1 2 4 6 10 13 17 14 65 A 88 % 57.2 A
CHECK APPENDIX C FOR THE MAXIMUM NUMBER OF CONDUCTORS AND FIXTURE WIRES, 80 0 1 1 1 2 4 7 11 15 19 80 0 0 1 1 1 3 5 8 11 14 22 85 A 88 % 74.8 A
ALL OF THE SAME SIZES (TOTAL CROSS-SECTIONAL AREA INCLUDING INSULATION) PERMITTED 100 0 0 1 1 1 3 6 9 12 16 100 0 0 1 1 1 3 4 7 9 12 30 110 A 88 % 96.8 A
IN TRADE SIZES OF THE APPLICABLE CONDUIT OR TUBING. 125 0 0 1 1 1 3 5 7 10 13 125 0 0 0 1 1 2 3 5 7 9 38 125 A 88 % 110.0 A
USE: 20 mm IMC 150 0 0 1 1 1 2 4 6 8 11 150 0 0 0 1 1 1 3 5 6 8 50 145 A 88 % 127.6 A
175 0 0 0 1 1 1 4 6 7 10 175 0 0 0 1 1 1 2 4 6 7 60 160 A 88 % 140.8 A
200 0 0 0 1 1 1 3 5 7 9 200 0 0 0 1 1 1 2 4 5 7 80 185 A 88 % 162.8 A
VOLTAGE DROP CALCULATION: 250 0 0 0 1 1 1 3 4 6 7 250 0 0 0 1 1 1 1 3 4 5 100 220 A 88 % 193.6 A
1, VD CALCULATION: 3, 3W VD CALCULATION: 3, 4W VD CALCULATION: TYPE COND. IMC TYPE COND. LTFMC 125 255 A 88 % 224.4 A
35.6 x L x I 30.8 x L x I 17.8 x L x I 15 20 25 32 40 50 65 80 90 100 15 20 25 32 40 50 65 80 90 100 150 280 A 88 % 246.4 A
eV = eV = eV =
1000 x S 1000 x S 1000 x S 200 330 A 88 % 290.4 A
THHN 2.0 (1.6) 14 24 39 68 91 149 211 326 436 562 THHN 2.0 (1.6) 13 22 36 63 81 133 201 308 401 523 250 375 A 88 % 330.0 A
% VD = eV / V x 1000 3.5 (2.0) 10 17 29 49 67 109 154 238 318 410 3.5 (2.0) 9 16 26 46 59 97 146 225 292 381 325 435 A 88 % 382.8 A
5.5 (2.6) 6 11 18 31 42 68 97 150 200 258 5.5 (2.6) 6 10 16 29 37 61 92 141 184 240 400 485 A 88 % 426.8 A
e (V) = Voltage Drop, (volts) 8.0 (3.2) 3 6 10 18 24 39 56 86 115 149 8.0 (3.2) 3 6 9 16 21 35 53 81 106 138 500 540 A 88 % 475.2 A
% VD = Voltage Drop, (%) 14 2 4 7 13 17 28 40 62 83 107 14 2 4 7 12 15 25 38 59 76 100
L = Single Length of Conductor, (meters) 22 1 3 4 8 10 17 25 38 51 66 22 1 2 4 7 9 15 23 36 47 61 TABLE 2.50.6.13: EQUIPMENT GROUNDING CONDUCTORS
I = Current, (amperes) 30 1 1 3 5 7 12 17 27 36 47 30 1 1 3 5 7 11 17 26 33 44 Size
S = Single Conductor Cross Section multiplied by the number of sets, (mm) 38 1 1 2 4 5 9 13 20 27 35 38 1 1 1 4 5 8 12 19 25 32 Rating or Setting of Automatic
Aluminum or Copper-
Overcurrent Device in Circuit Copper
V = System Voltage, (volts) 50 1 1 1 3 4 8 11 17 23 29 50 1 1 1 3 4 7 10 16 21 27 Clad Aluminum*
Ahead of Equipment, Conduit,
60 1 1 1 3 4 6 9 14 19 24 60 0 1 1 2 3 6 8 13 17 23 mm
etc., mm AWG/MCM AWG/MCM
80 0 1 1 2 3 5 7 12 16 20 80 0 1 1 1 3 5 7 11 14 19
ARTICLE 2.4 - OVERCURRENT PROTECTION 100 0 1 1 1 2 4 6 9 13 17 100 0 1 1 1 2 4 6 9 12 15 15 2.0 14 3.5 12
2.40.1.3 125 0 0 1 1 1 3 5 8 10 13 125 0 0 1 1 1 3 5 7 10 12 20 3.5 12 5.5 10
(b) Devices Rated 800 Amperes or Less. 150 0 0 1 1 1 3 4 7 9 12 150 0 0 1 1 1 3 4 6 8 11 30 5.5 10 8 8
The next higher standard overcurrent device rating (above the ampacity 175 0 0 1 1 1 2 4 6 8 10 175 0 0 1 1 1 2 3 5 7 9 40 5.5 10 8 8
of the conductors being protected) shall be permitted to be used, provided 200 0 0 1 1 1 2 3 5 7 9 200 0 0 0 1 1 1 3 5 6 8 60 5.5 10 8 8
all of the following conditions are met. 250 0 0 0 1 1 1 3 4 6 7 250 0 0 0 1 1 1 2 4 5 7 100 8.0 8 14 6
0 (1) The conductors being protected are not part of the multioutlet branch THW 2.0 (1.6) 6 11 18 31 42 69 98 151 202 261 THW 2.0 (1.6) 6 10 16 29 38 62 93 143 186 243 200 14 6 22 4
circuit supplying receptacles for cord-and plug-connected portable loads. 3.5 (2.0) 5 9 14 25 34 56 79 122 163 209 3.5 (2.0) 5 8 13 23 30 50 75 115 149 195 300 22 4 30 2
(2) The ampacity of the conductors does not correspond with the standard 5.5 (2.6) 4 7 11 19 26 43 61 95 127 163 5.5 (2.6) 3 6 10 18 23 39 58 89 117 152 400 30 3 38 1
ampere rating of a fuse or a circuit breaker without overload trip 8.0 (3.2) 2 4 7 12 16 26 37 57 76 98 8.0 (3.2) 1 4 6 11 14 23 35 53 70 91 500 30 2 50 1/0
adjustments above its rating (but that shall be permitted to have 14 1 3 5 9 12 20 28 43 58 75 14 1 3 5 8 11 18 27 41 53 70 600 38 1 60 2/0
other trip or rating adjustments). 22 1 2 4 6 9 15 21 32 43 56 22 1 1 3 6 8 13 20 30 40 52 800 50 1/0 80 3/0
(3) The next higher standard rating selected does not exceed 800 amperes. 30 1 1 3 5 6 11 15 23 31 41 30 1 1 2 4 6 9 14 22 29 38 1000 60 2/0 100 4/0
38 1 1 1 3 4 7 11 16 22 28 38 1 1 1 3 4 7 10 15 20 26 1200 80 3/0 125 250
(c) Devices Rated Over 800 Amperes. 50 1 1 1 3 4 6 9 14 19 24 50 0 1 1 2 3 6 8 13 17 23 1600 100 4/0 150 350
Where the overcurrent device is rated over 800 amperes, the ampacity of the 60 0 1 1 2 3 5 8 12 16 20 60 0 1 1 2 3 5 7 11 15 19 2000 125 250 200 400
conductors it protects shall be equal or greater than the rating of the overcurrent 80 0 1 1 1 3 4 6 10 13 17 80 0 1 1 1 2 4 6 9 12 16 2500 150 350 300 600
device as defined in Section 2.40.1.6. 100 0 1 1 1 2 4 5 8 11 14 100 0 0 1 1 1 3 5 8 10 13 3000 200 400 300 600
125 0 0 1 1 1 3 4 7 9 12 125 0 0 1 1 1 3 4 6 8 11 4000 250 500 400 800
150 0 0 1 1 1 2 4 6 8 10 150 0 0 1 1 1 2 3 5 7 9 5000 375 700 500 1200
175 0 0 0 1 1 1 3 4 6 8 175 0 0 0 1 1 1 3 5 6 8 6000 400 800 500 1200
200 0 0 0 1 1 1 2 4 5 7 200 0 0 0 1 1 1 3 4 6 7
250 250 0 0 0 1 1 1 2 3 5 6

file:///conversion/tmp/scratch/366822312.xls Page 1
LOAD SCHEDULE / CABLE SIZING / VOLTAGE DROP

PANEL DESIGNATION : MOUNTING LOCATION : VOLTAGE SYSTEM :


AREA/EQPT.SERVED : MOUNTING METHOD : WIRE :
FEED FROM : FEED TYPE : ENCLOSURE :

CABLE AMPACITY
CONDUIT / CABLE
System RATING LOAD DISTRIBUTION, KVA % BREAKER SIZE GROUND WIRE PF DF K L Full Load CV SERVICE WIRE System % PERMIT VOLTAGE DROP
CKT. NO. LOAD DESCRIPTION Full Load MCCB TRAY Cond/ Voltage REMARKS
Voltage KW KVA AB BC CA AN BN CN 3 Multiplie Pole AT AF mm Type mm Type Current Sets mm Type Voltage allowabl e(V) %V
Current Rating set Drop
1 10 - D.C.O. (1FL Parking area) 1 1.44 1.80 1.80 r
1.25 2 #VALUE! #VALUE! 20 50 3.5 TW 20 PVC 0.8 1 35.6 80 #VALUE! 1000 1 2 3.5 THW e
3% #VALUE! #VALUE! #VALUE! #VALUE!
2 7 - D.C.O. (New Welding Area) 1 1.01 1.26 1.26 1.25 2 #VALUE! #VALUE! 20 50 3.5 TW 20 PVC 0.8 1 35.6 53 #VALUE! 1000 1 2 3.5 THW 3% #VALUE! #VALUE! #VALUE! #VALUE!
3 1FL Traffic loop Supply 1 0.80 1.00 1.00 1.25 2 #VALUE! #VALUE! 20 50 3.5 TW 15 EMT 0.8 1 35.6 44 #VALUE! 1000 1 2 3.5 THW 3% #VALUE! #VALUE! #VALUE! #VALUE!
4 17 - 2x36W FL, 1 - 1x36W FL (Parking) 1 1.26 1.58 1.58 1.25 2 #VALUE! #VALUE! 20 50 3.5 TW 15 EMT 0.8 1 35.6 50 #VALUE! 1000 1 2 3.5 THW 3% #VALUE! #VALUE! #VALUE! #VALUE!
5 21 - 2x36W FL (New Welding Area) from LPP-WORKSHOP 1 1.51 1.89 1.89 1.25 2 #VALUE! #VALUE! 20 50 TW 15 EMT 0.8 1 35.6 50 8.22 1000
6 18 - 2x36W FL, 1 - 1x36W FL (Parking) 1 1.33 1.67 1.67 1.25 2 #VALUE! #VALUE! 20 50 3.5 TW 15 EMT 0.8 1 35.6 56 #VALUE! 1000 1 2 3.5 THW 3% #VALUE! #VALUE! #VALUE! #VALUE!
7 4 - 2x10W EML, 4 - 1x8W EXL (Stairs, Workshop, EE & Pump 1 0.11 0.14 0.14 1.25 2 #VALUE! #VALUE! 20 50 3.5 TW 15 EMT 0.8 1 35.6 110 #VALUE! 1000 1 2 3.5 THW 3% #VALUE! #VALUE! #VALUE! #VALUE!
8 SPACE
9
10
11
12

TOTAL 7.46 9.33 3.20 3.56 2.58 0.00 0.00 0.00 0.00
TOTAL PANEL LOAD = 10.67 kVA 3 NOTE: MAIN PROTECTION: 30 AT 50 AF MCCB NOTE:
DEMAND FACTOR = 80.00 % System Voltage (V) 230 Apply 125% for Lighting and Receptacle Loads MAIN FEEDER SIZE: 1 sets - 3 x 5.5 mm THHN VOLTAGE DROP PERMISSIBLE PERCENTAGE
TOTAL DEMAND LOAD = 8.53 kVA Transformer (KVA) Apply 1.25% for Power & Motor Loads 5.5 mm TW in 20 mm IMC 3% FOR BRANCH PROTECTION
TOTAL CURRENT LOAD = 21.42 A 2% FOR MAIN PROTECTION

COMPUTATION: Ref.: PEC 2009 Part 1 APPENDIX C - CONDUIT & TUBING FILL TABLE TABLE 3.10.1.16: ALLOWABLE AMPACITIES
TYPE COND. EMT TYPE COND. PVC (SCH. 80) THHN 90C 31-40C INDOOR USE
FULL LOAD CURRENT: 15 20 25 32 40 50 65 80 90 100 15 20 25 32 40 50 65 80 90 100 CABLE
CAPACITY CORRECTION FACTORS
= 8.53 kVA SIZE
1.732 X 230 V THHN 2.0 (1.6) 12 22 35 61 84 138 241 364 476 608 THHN 2.0 (1.6) 9 17 28 51 70 118 170 265 358 464 3.5 30 A 91 % 27.3 A
FLC = 21.42 A 3.5 (2.0) 9 16 26 45 61 101 176 266 347 443 3.5 (2.0) 6 12 20 37 51 86 124 193 261 338 5.5 40 A 91 % 36.4 A
5.5 (2.6) 5 10 16 28 38 63 111 167 219 279 5.5 (2.6) 4 7 13 23 32 54 78 122 164 213 8 55 A 91 % 50.1 A
CB RATING = 21.42 X 1.25 = 26.77 A 8.0 (3.2) 3 6 9 16 22 36 64 96 126 161 8.0 (3.2) 2 4 7 13 18 31 45 70 95 123 14 70 A 91 % 63.7 A
14 2 4 7 12 16 26 46 69 91 116 14 1 3 5 9 13 22 32 51 68 89 22 90 A 91 % 81.9 A
USE: 30 AT PHASE: 3 WIRE: 3 22 1 2 4 7 10 16 28 43 56 71 22 1 1 3 6 8 14 20 31 42 54 30 115 A 91 % 104.7 A
50 AF MCCB 30 1 1 3 5 7 11 20 30 40 51 30 1 1 2 4 6 10 14 22 30 39 38 130 A 91 % 118.3 A
CABLE SIZE AMPACITY: 38 1 1 1 4 5 8 15 22 29 37 38 0 1 1 3 4 7 10 16 22 29 50 150 A 91 % 136.5 A
CHECK TABLE 3.10.1.16 / 3.10.1.17 FOR ALLOWABLE AMPACITIES. 50 1 1 1 3 4 7 12 19 25 32 50 0 1 1 2 3 6 9 14 18 24 60 170 A 91 % 154.7 A
21.42 36.4 WITH CORRECTION FACTOR (0.91) @ 40C 60 0 1 1 2 3 6 10 16 20 26 60 0 1 1 1 3 5 7 11 15 20 80 205 A 91 % 186.6 A
USE: 1 SET/S 3- 5.5 mm THHN 80 0 1 1 1 3 5 8 13 17 22 80 0 1 1 1 2 4 6 9 13 17 100 225 A 91 % 204.8 A
100 0 1 1 1 2 4 7 11 14 18 100 0 0 1 1 1 3 5 8 10 14 125 265 A 91 % 241.2 A
VOLTAGE DROP CALCULATION: 125 0 0 1 1 1 3 6 9 11 15 125 0 0 1 1 1 3 4 6 8 11 150 295 A 91 % 268.5 A
VD = 30.8 X 21.42 X 13 LM 150 0 0 1 1 1 3 5 7 10 13 150 0 0 0 1 1 2 3 5 7 9 200 355 A 91 % 323.1 A
1000 X 5.5 X 1 SET/S 175 0 0 1 1 1 2 4 6 9 11 175 0 0 0 1 1 1 3 5 6 8 250 400 A 91 % 364.0 A
VD = 1.56 Volts 200 0 0 0 1 1 1 4 6 8 10 200 0 0 0 1 1 1 3 4 6 7 325 470 A 91 % 427.7 A
250 0 0 0 1 1 1 3 5 6 8 250 0 0 0 1 1 1 2 3 5 6 400 515 A 91 % 468.7 A
%V = 1.56 THW 2.0 (1.6) 6 10 16 28 39 64 112 169 221 282 THW 2.0 (1.6) 4 8 13 23 32 55 79 123 166 215 500 580 A 91 % 527.8 A
230 3.5 (2.0) 4 8 13 23 31 51 90 136 177 227 3.5 (2.0) 3 6 10 19 26 44 63 99 133 274
%V = 0.68 3 % 5.5 (2.6) 3 6 10 18 24 40 70 106 138 177 5.5 (2.6) 2 5 8 15 20 34 49 77 104 135 TABLE 3.10.1.16: ALLOWABLE AMPACITIES
USE: 1 SET/S 3- 5.5 mm THHN 8.0 (3.2) 1 4 6 10 14 24 42 63 83 106 8.0 (3.2) 1 3 5 9 12 20 29 46 62 81 THW 75C 31-40C OUTDOOR USE
FOR SERVICE WIRE: 14 1 3 4 8 11 18 32 48 63 81 14 1 1 3 7 9 16 22 35 48 62 CABLE
CAPACITY CORRECTION FACTORS
USE: 1 SET/S 3- 5.5 mm THHN 22 1 1 3 6 8 13 24 36 47 60 22 1 1 3 5 7 12 17 26 35 46 SIZE
FOR GROUND WIRE: 30 1 1 2 4 6 10 17 26 34 44 30 1 1 1 3 5 8 12 19 26 33 3.5 25 A 88 % 22.0 A
CHECK TABLE 2.50.6.13: 38 1 1 1 3 4 7 12 18 24 31 38 0 1 1 2 3 6 8 13 18 23 5.5 35 A 88 % 30.8 A
USE: 1- 5.5 mm TW 50 0 1 1 2 3 6 10 16 20 26 50 0 1 1 1 3 5 7 11 15 20 8 50 A 88 % 44.0 A
FOR CONDUIT SIZING: 60 0 1 1 1 3 5 9 13 17 22 60 0 1 1 1 2 4 6 10 13 17 14 65 A 88 % 57.2 A
CHECK APPENDIX C FOR THE MAXIMUM NUMBER OF CONDUCTORS AND FIXTURE WIRES, 80 0 1 1 1 2 4 7 11 15 19 80 0 0 1 1 1 3 5 8 11 14 22 85 A 88 % 74.8 A
ALL OF THE SAME SIZES (TOTAL CROSS-SECTIONAL AREA INCLUDING INSULATION) PERMITTED 100 0 0 1 1 1 3 6 9 12 16 100 0 0 1 1 1 3 4 7 9 12 30 110 A 88 % 96.8 A
IN TRADE SIZES OF THE APPLICABLE CONDUIT OR TUBING. 125 0 0 1 1 1 3 5 7 10 13 125 0 0 0 1 1 2 3 5 7 9 38 125 A 88 % 110.0 A
USE: 20 mm IMC 150 0 0 1 1 1 2 4 6 8 11 150 0 0 0 1 1 1 3 5 6 8 50 145 A 88 % 127.6 A
175 0 0 0 1 1 1 4 6 7 10 175 0 0 0 1 1 1 2 4 6 7 60 160 A 88 % 140.8 A
200 0 0 0 1 1 1 3 5 7 9 200 0 0 0 1 1 1 2 4 5 7 80 185 A 88 % 162.8 A
VOLTAGE DROP CALCULATION: 250 0 0 0 1 1 1 3 4 6 7 250 0 0 0 1 1 1 1 3 4 5 100 220 A 88 % 193.6 A
1, VD CALCULATION: 3, 3W VD CALCULATION: 3, 4W VD CALCULATION: TYPE COND. IMC TYPE COND. LTFMC 125 255 A 88 % 224.4 A
35.6 x L x I 30.8 x L x I 17.8 x L x I 15 20 25 32 40 50 65 80 90 100 15 20 25 32 40 50 65 80 90 100 150 280 A 88 % 246.4 A
eV = eV = eV =
1000 x S 1000 x S 1000 x S 200 330 A 88 % 290.4 A
THHN 2.0 (1.6) 14 24 39 68 91 149 211 326 436 562 THHN 2.0 (1.6) 13 22 36 63 81 133 201 308 401 523 250 375 A 88 % 330.0 A
% VD = eV / V x 1000 3.5 (2.0) 10 17 29 49 67 109 154 238 318 410 3.5 (2.0) 9 16 26 46 59 97 146 225 292 381 325 435 A 88 % 382.8 A
5.5 (2.6) 6 11 18 31 42 68 97 150 200 258 5.5 (2.6) 6 10 16 29 37 61 92 141 184 240 400 485 A 88 % 426.8 A
e (V) = Voltage Drop, (volts) 8.0 (3.2) 3 6 10 18 24 39 56 86 115 149 8.0 (3.2) 3 6 9 16 21 35 53 81 106 138 500 540 A 88 % 475.2 A
% VD = Voltage Drop, (%) 14 2 4 7 13 17 28 40 62 83 107 14 2 4 7 12 15 25 38 59 76 100
L = Single Length of Conductor, (meters) 22 1 3 4 8 10 17 25 38 51 66 22 1 2 4 7 9 15 23 36 47 61 TABLE 2.50.6.13: EQUIPMENT GROUNDING CONDUCTORS
I = Current, (amperes) 30 1 1 3 5 7 12 17 27 36 47 30 1 1 3 5 7 11 17 26 33 44 Size
S = Single Conductor Cross Section multiplied by the number of sets, (mm) 38 1 1 2 4 5 9 13 20 27 35 38 1 1 1 4 5 8 12 19 25 32 Rating or Setting of Automatic
Aluminum or Copper-
Overcurrent Device in Circuit Copper
V = System Voltage, (volts) 50 1 1 1 3 4 8 11 17 23 29 50 1 1 1 3 4 7 10 16 21 27 Clad Aluminum*
Ahead of Equipment, Conduit,
60 1 1 1 3 4 6 9 14 19 24 60 0 1 1 2 3 6 8 13 17 23 mm
etc., mm AWG/MCM AWG/MCM
80 0 1 1 2 3 5 7 12 16 20 80 0 1 1 1 3 5 7 11 14 19
ARTICLE 2.4 - OVERCURRENT PROTECTION 100 0 1 1 1 2 4 6 9 13 17 100 0 1 1 1 2 4 6 9 12 15 15 2.0 14 3.5 12
2.40.1.3 125 0 0 1 1 1 3 5 8 10 13 125 0 0 1 1 1 3 5 7 10 12 20 3.5 12 5.5 10
(b) Devices Rated 800 Amperes or Less. 150 0 0 1 1 1 3 4 7 9 12 150 0 0 1 1 1 3 4 6 8 11 30 5.5 10 8 8
The next higher standard overcurrent device rating (above the ampacity 175 0 0 1 1 1 2 4 6 8 10 175 0 0 1 1 1 2 3 5 7 9 40 5.5 10 8 8
of the conductors being protected) shall be permitted to be used, provided 200 0 0 1 1 1 2 3 5 7 9 200 0 0 0 1 1 1 3 5 6 8 60 5.5 10 8 8
all of the following conditions are met. 250 0 0 0 1 1 1 3 4 6 7 250 0 0 0 1 1 1 2 4 5 7 100 8.0 8 14 6
0 (1) The conductors being protected are not part of the multioutlet branch THW 2.0 (1.6) 6 11 18 31 42 69 98 151 202 261 THW 2.0 (1.6) 6 10 16 29 38 62 93 143 186 243 200 14 6 22 4
circuit supplying receptacles for cord-and plug-connected portable loads. 3.5 (2.0) 5 9 14 25 34 56 79 122 163 209 3.5 (2.0) 5 8 13 23 30 50 75 115 149 195 300 22 4 30 2
(2) The ampacity of the conductors does not correspond with the standard 5.5 (2.6) 4 7 11 19 26 43 61 95 127 163 5.5 (2.6) 3 6 10 18 23 39 58 89 117 152 400 30 3 38 1
ampere rating of a fuse or a circuit breaker without overload trip 8.0 (3.2) 2 4 7 12 16 26 37 57 76 98 8.0 (3.2) 1 4 6 11 14 23 35 53 70 91 500 30 2 50 1/0
adjustments above its rating (but that shall be permitted to have 14 1 3 5 9 12 20 28 43 58 75 14 1 3 5 8 11 18 27 41 53 70 600 38 1 60 2/0
other trip or rating adjustments). 22 1 2 4 6 9 15 21 32 43 56 22 1 1 3 6 8 13 20 30 40 52 800 50 1/0 80 3/0
(3) The next higher standard rating selected does not exceed 800 amperes. 30 1 1 3 5 6 11 15 23 31 41 30 1 1 2 4 6 9 14 22 29 38 1000 60 2/0 100 4/0
38 1 1 1 3 4 7 11 16 22 28 38 1 1 1 3 4 7 10 15 20 26 1200 80 3/0 125 250
(c) Devices Rated Over 800 Amperes. 50 1 1 1 3 4 6 9 14 19 24 50 0 1 1 2 3 6 8 13 17 23 1600 100 4/0 150 350
Where the overcurrent device is rated over 800 amperes, the ampacity of the 60 0 1 1 2 3 5 8 12 16 20 60 0 1 1 2 3 5 7 11 15 19 2000 125 250 200 400
conductors it protects shall be equal or greater than the rating of the overcurrent 80 0 1 1 1 3 4 6 10 13 17 80 0 1 1 1 2 4 6 9 12 16 2500 150 350 300 600
device as defined in Section 2.40.1.6. 100 0 1 1 1 2 4 5 8 11 14 100 0 0 1 1 1 3 5 8 10 13 3000 200 400 300 600
125 0 0 1 1 1 3 4 7 9 12 125 0 0 1 1 1 3 4 6 8 11 4000 250 500 400 800
150 0 0 1 1 1 2 4 6 8 10 150 0 0 1 1 1 2 3 5 7 9 5000 375 700 500 1200
175 0 0 0 1 1 1 3 4 6 8 175 0 0 0 1 1 1 3 5 6 8 6000 400 800 500 1200
200 0 0 0 1 1 1 2 4 5 7 200 0 0 0 1 1 1 3 4 6 7
250 250 0 0 0 1 1 1 2 3 5 6

file:///conversion/tmp/scratch/366822312.xls Page 2
LOAD SCHEDULE / CABLE SIZING / VOLTAGE DROP

: VOLTAGE SYSTEM :
: WIRE :
: ENCLOSURE :

CABLE AMPACITY
CONDUIT / CABLE
System RATING LOAD DISTRIBUTION, KVA % BREAKER SIZE GROUND WIRE PF DF K L Full Load CV SERVICE WIRE System % PERMIT VOLTAGE DROP
CKT. NO. LOAD DESCRIPTION Full Load MCCB TRAY Cond/ Voltage REMARKS
Voltage KW KVA AB BC CA AN BN CN 3 Multiplie Pole AT AF mm Type mm Type Current Sets mm Type Voltage allowabl e(V) %V
Current Rating set Drop
1 M-20 Grinding Machine 3 230 8.00 10.00 10.00 r
1.25 3 25.10 31.38 20 50 3.5 TW 15 IMC 0.8 1 30.8 20 25.10 1000 1 3 3.5 THW 230 e
3% 6.9 3.53 1.54% OK
2 M-20 Grinding Machine 3 230 8.00 10.00 10.00 1.25 3 25.10 31.38 20 50 3.5 TW 15 IMC 0.8 1 30.8 23 25.10 1000 1 3 3.5 THW 230 3% 6.9 4.06 1.77% OK
3 SPARE 3 230 0.00 0.00 1.25 3 0.00 0.00 20 50 3.5 TW 15 IMC 0.8 1 30.8 23 0.00 1000 1 3 3.5 THW 230 3% 6.9 0.00 0.00% OK
4 ECB NEMA-1, 50A, 3, 200V (Near M41 @ Washing/Etching) 3 230 8.80 11.00 11.00 1.25 3 27.61 34.52 20 50 3.5 TW 15 IMC 0.8 1 30.8 27.61 1000 1 3 3.5 THW 230 3% 6.9 0.00 0.00% OK
5 ECB NEMA-1, 50A, 3, 200V (Pyro Polarization Area) 3 230 8.80 11.00 11.00 1.25 3 27.61 34.52 20 50 15 IMC THW
6 P34 & P45 Dicer Filter (2 - Twistlock C.O. 4 Prong) 3 230 6.40 8.00 8.00 1.25 3 20.08 25.10 20 50 3.5 TW 15 IMC 0.8 1 30.8 20.08 1000 1 3 3.5 THW 230 3% 6.9 0.00 0.00% OK
7 P46 & P47 Dicer Filter (2 - Twistlock C.O. 4 Prong) 3 230 4.80 6.00 6.00 1.25 3 15.06 18.83 20 50 3.5 TW 15 IMC 0.8 1 30.8 15.06 1000 1 3 3.5 THW 230 3% 6.9 0.00 0.00% OK
8 ECB NEMA-1, 30A, 3, 200V (Near M28 @ Washing/Etching) 3 230 5.12 6.40 6.40 1.25 3 16.07 20.08 20 50 3.5 TW 15 IMC 0.8 1 30.8 16.07 1000 1 3 3.5 THW 230 3% 6.9 0.00 0.00% OK
9 T05 & M05 Dicer Pyro & UT (2 - Twistlock C.O. 4 Prong) 3 230 4.00 5.00 5.00 1.25 3 12.55 15.69 20 50 3.5 TW 15 IMC 0.8 1 30.8 12.55 1000 1 3 3.5 THW 230 3% 6.9 0.00 0.00% OK
10 SPARE 3 230 0.00 0.00 1.25 3 0.00 0.00 20 50 15 IMC THW
11 M-16 Slicer 3 230 4.40 5.50 5.50 1.25 3 13.81 17.26 20 50 3.5 TW 15 IMC 0.8 1 30.8 13.81 1000 1 3 3.5 THW 230 3% 6.9 0.00 0.00% OK
12 0.00 0.00
13 0.00 0.00
14 0.00 0.00
15 0.00 0.00
16 0.00 0.00
17 0.00 0.00
18 0.00 0.00
19 0.00 0.00
20 0.00 0.00
21 0.00 0.00
22 0.00 0.00
23 0.00 0.00
24 0.00 0.00
25 0.00 0.00
26 0.00 0.00

TOTAL 58.32 72.90 0.00 0.00 0.00 0.00 0.00 0.00 72.90
TOTAL PANEL LOAD = 72.90 kVA 3 NOTE: MAIN PROTECTION: 30 AT 50 AF MCCB NOTE:
DEMAND FACTOR = 80.00 % System Voltage (V) 230 Apply 125% for Lighting and Receptacle Loads MAIN FEEDER SIZE: 1 sets - 3 x 5.5 mm THHN VOLTAGE DROP PERMISSIBLE PERCENTAGE
TOTAL DEMAND LOAD = 58.32 kVA Transformer (KVA) Apply 125% for Power & Motor Loads 5.5 mm TW in 20 mm IMC 3% FOR BRANCH PROTECTION
TOTAL CURRENT LOAD = 146.40 A 2% FOR MAIN PROTECTION

COMPUTATION: Ref.: PEC 2009 Part 1 APPENDIX C - CONDUIT & TUBING FILL TABLE TABLE 3.10.1.16: ALLOWABLE AMPACITIES
TYPE COND. EMT TYPE COND. PVC (SCH. 80) THHN 90C 31-40C INDOOR USE
FULL LOAD CURRENT: 15 20 25 32 40 50 65 80 90 100 15 20 25 32 40 50 65 80 90 100 CABLE
CAPACITY CORRECTION FACTORS
= 58.32 kVA SIZE
1.732 X 230 V THHN 2.0 (1.6) 12 22 35 61 84 138 241 364 476 608 THHN 2.0 (1.6) 9 17 28 51 70 118 170 265 358 464 3.5 30 A 91 % 27.3 A
FLC = 146.40 A 3.5 (2.0) 9 16 26 45 61 101 176 266 347 443 3.5 (2.0) 6 12 20 37 51 86 124 193 261 338 5.5 40 A 91 % 36.4 A
5.5 (2.6) 5 10 16 28 38 63 111 167 219 279 5.5 (2.6) 4 7 13 23 32 54 78 122 164 213 8 55 A 91 % 50.1 A
CB RATING = 146.40 X 1.25 = 182.99 A 8.0 (3.2) 3 6 9 16 22 36 64 96 126 161 8.0 (3.2) 2 4 7 13 18 31 45 70 95 123 14 70 A 91 % 63.7 A
14 2 4 7 12 16 26 46 69 91 116 14 1 3 5 9 13 22 32 51 68 89 22 90 A 91 % 81.9 A
USE: 30 AT PHASE: 3 WIRE: 3 22 1 2 4 7 10 16 28 43 56 71 22 1 1 3 6 8 14 20 31 42 54 30 115 A 91 % 104.7 A
50 AF MCCB 30 1 1 3 5 7 11 20 30 40 51 30 1 1 2 4 6 10 14 22 30 39 38 130 A 91 % 118.3 A
CABLE SIZE AMPACITY: 38 1 1 1 4 5 8 15 22 29 37 38 0 1 1 3 4 7 10 16 22 29 50 150 A 91 % 136.5 A
CHECK TABLE 3.10.1.16 / 3.10.1.17 FOR ALLOWABLE AMPACITIES. 50 1 1 1 3 4 7 12 19 25 32 50 0 1 1 2 3 6 9 14 18 24 60 170 A 91 % 154.7 A
146.40 36.4 WITH CORRECTION FACTOR (0.91) @ 40C 60 0 1 1 2 3 6 10 16 20 26 60 0 1 1 1 3 5 7 11 15 20 80 205 A 91 % 186.6 A
USE: 1 SET/S 3- 5.5 mm THHN 80 0 1 1 1 3 5 8 13 17 22 80 0 1 1 1 2 4 6 9 13 17 100 225 A 91 % 204.8 A
100 0 1 1 1 2 4 7 11 14 18 100 0 0 1 1 1 3 5 8 10 14 125 265 A 91 % 241.2 A
VOLTAGE DROP CALCULATION: 125 0 0 1 1 1 3 6 9 11 15 125 0 0 1 1 1 3 4 6 8 11 150 295 A 91 % 268.5 A
VD = 30.8 X 146.40 X 13 LM 150 0 0 1 1 1 3 5 7 10 13 150 0 0 0 1 1 2 3 5 7 9 200 355 A 91 % 323.1 A
1000 X 5.5 X 1 SET/S 175 0 0 1 1 1 2 4 6 9 11 175 0 0 0 1 1 1 3 5 6 8 250 400 A 91 % 364.0 A
VD = 10.66 Volts 200 0 0 0 1 1 1 4 6 8 10 200 0 0 0 1 1 1 3 4 6 7 325 470 A 91 % 427.7 A
250 0 0 0 1 1 1 3 5 6 8 250 0 0 0 1 1 1 2 3 5 6 400 515 A 91 % 468.7 A
%V = 10.66 THW 2.0 (1.6) 6 10 16 28 39 64 112 169 221 282 THW 2.0 (1.6) 4 8 13 23 32 55 79 123 166 215 500 580 A 91 % 527.8 A
230 3.5 (2.0) 4 8 13 23 31 51 90 136 177 227 3.5 (2.0) 3 6 10 19 26 44 63 99 133 274
%V = 4.63 3 % REQUIRES BIGGER SIZE OF CONDUCTOR 5.5 (2.6) 3 6 10 18 24 40 70 106 138 177 5.5 (2.6) 2 5 8 15 20 34 49 77 104 135 TABLE 3.10.1.16: ALLOWABLE AMPACITIES
USE: 1 SET/S 3- 5.5 mm THHN 8.0 (3.2) 1 4 6 10 14 24 42 63 83 106 8.0 (3.2) 1 3 5 9 12 20 29 46 62 81 THW 75C 31-40C OUTDOOR USE
FOR SERVICE WIRE: 14 1 3 4 8 11 18 32 48 63 81 14 1 1 3 7 9 16 22 35 48 62 CABLE
CAPACITY CORRECTION FACTORS
USE: 1 SET/S 3- 5.5 mm THHN 22 1 1 3 6 8 13 24 36 47 60 22 1 1 3 5 7 12 17 26 35 46 SIZE
FOR GROUND WIRE: 30 1 1 2 4 6 10 17 26 34 44 30 1 1 1 3 5 8 12 19 26 33 3.5 25 A 88 % 22.0 A
CHECK TABLE 2.50.6.13: 38 1 1 1 3 4 7 12 18 24 31 38 0 1 1 2 3 6 8 13 18 23 5.5 35 A 88 % 30.8 A
USE: 1- 5.5 mm TW 50 0 1 1 2 3 6 10 16 20 26 50 0 1 1 1 3 5 7 11 15 20 8 50 A 88 % 44.0 A
FOR CONDUIT SIZING: 60 0 1 1 1 3 5 9 13 17 22 60 0 1 1 1 2 4 6 10 13 17 14 65 A 88 % 57.2 A
CHECK APPENDIX C FOR THE MAXIMUM NUMBER OF CONDUCTORS AND FIXTURE WIRES, 80 0 1 1 1 2 4 7 11 15 19 80 0 0 1 1 1 3 5 8 11 14 22 85 A 88 % 74.8 A
ALL OF THE SAME SIZES (TOTAL CROSS-SECTIONAL AREA INCLUDING INSULATION) PERMITTED 100 0 0 1 1 1 3 6 9 12 16 100 0 0 1 1 1 3 4 7 9 12 30 110 A 88 % 96.8 A
IN TRADE SIZES OF THE APPLICABLE CONDUIT OR TUBING. 125 0 0 1 1 1 3 5 7 10 13 125 0 0 0 1 1 2 3 5 7 9 38 125 A 88 % 110.0 A
USE: 20 mm IMC 150 0 0 1 1 1 2 4 6 8 11 150 0 0 0 1 1 1 3 5 6 8 50 145 A 88 % 127.6 A
175 0 0 0 1 1 1 4 6 7 10 175 0 0 0 1 1 1 2 4 6 7 60 160 A 88 % 140.8 A
200 0 0 0 1 1 1 3 5 7 9 200 0 0 0 1 1 1 2 4 5 7 80 185 A 88 % 162.8 A
VOLTAGE DROP CALCULATION: 250 0 0 0 1 1 1 3 4 6 7 250 0 0 0 1 1 1 1 3 4 5 100 220 A 88 % 193.6 A
1, VD CALCULATION: 3, 3W VD CALCULATION: 3, 4W VD CALCULATION: TYPE COND. IMC TYPE COND. LTFMC 125 255 A 88 % 224.4 A
35.6 x L x I 30.8 x L x I 17.8 x L x I 15 20 25 32 40 50 65 80 90 100 15 20 25 32 40 50 65 80 90 100 150 280 A 88 % 246.4 A
eV = eV = eV =
1000 x S 1000 x S 1000 x S 200 330 A 88 % 290.4 A
THHN 2.0 (1.6) 14 24 39 68 91 149 211 326 436 562 THHN 2.0 (1.6) 13 22 36 63 81 133 201 308 401 523 250 375 A 88 % 330.0 A
% VD = eV / V x 1000 3.5 (2.0) 10 17 29 49 67 109 154 238 318 410 3.5 (2.0) 9 16 26 46 59 97 146 225 292 381 325 435 A 88 % 382.8 A
5.5 (2.6) 6 11 18 31 42 68 97 150 200 258 5.5 (2.6) 6 10 16 29 37 61 92 141 184 240 400 485 A 88 % 426.8 A
e (V) = Voltage Drop, (volts) 8.0 (3.2) 3 6 10 18 24 39 56 86 115 149 8.0 (3.2) 3 6 9 16 21 35 53 81 106 138 500 540 A 88 % 475.2 A
% VD = Voltage Drop, (%) 14 2 4 7 13 17 28 40 62 83 107 14 2 4 7 12 15 25 38 59 76 100
L = Single Length of Conductor, (meters) 22 1 3 4 8 10 17 25 38 51 66 22 1 2 4 7 9 15 23 36 47 61 TABLE 2.50.6.13: EQUIPMENT GROUNDING CONDUCTORS
I = Current, (amperes) 30 1 1 3 5 7 12 17 27 36 47 30 1 1 3 5 7 11 17 26 33 44 Size
38 1 1 2 4 5 9 13 20 27 35 38 1 1 1 4 5 8 12 19 25 32 Rating or Setting of Automatic
S = Single Conductor Cross Section multiplied by the number of sets, (mm) Aluminum or Copper-
Overcurrent Device in Circuit Copper
V = System Voltage, (volts) 50 1 1 1 3 4 8 11 17 23 29 50 1 1 1 3 4 7 10 16 21 27 Clad Aluminum*
Ahead of Equipment, Conduit,
60 1 1 1 3 4 6 9 14 19 24 60 0 1 1 2 3 6 8 13 17 23 mm
etc., mm AWG/MCM AWG/MCM
80 0 1 1 2 3 5 7 12 16 20 80 0 1 1 1 3 5 7 11 14 19
ARTICLE 2.4 - OVERCURRENT PROTECTION 100 0 1 1 1 2 4 6 9 13 17 100 0 1 1 1 2 4 6 9 12 15 15 2.0 14 3.5 12
2.40.1.3 125 0 0 1 1 1 3 5 8 10 13 125 0 0 1 1 1 3 5 7 10 12 20 3.5 12 5.5 10
(b) Devices Rated 800 Amperes or Less. 150 0 0 1 1 1 3 4 7 9 12 150 0 0 1 1 1 3 4 6 8 11 30 5.5 10 8 8
The next higher standard overcurrent device rating (above the ampacity 175 0 0 1 1 1 2 4 6 8 10 175 0 0 1 1 1 2 3 5 7 9 40 5.5 10 8 8
of the conductors being protected) shall be permitted to be used, provided 200 0 0 1 1 1 2 3 5 7 9 200 0 0 0 1 1 1 3 5 6 8 60 5.5 10 8 8
all of the following conditions are met. 250 0 0 0 1 1 1 3 4 6 7 250 0 0 0 1 1 1 2 4 5 7 100 8.0 8 14 6
0 (1) The conductors being protected are not part of the multioutlet branch THW 2.0 (1.6) 6 11 18 31 42 69 98 151 202 261 THW 2.0 (1.6) 6 10 16 29 38 62 93 143 186 243 200 14 6 22 4
circuit supplying receptacles for cord-and plug-connected portable loads. 3.5 (2.0) 5 9 14 25 34 56 79 122 163 209 3.5 (2.0) 5 8 13 23 30 50 75 115 149 195 300 22 4 30 2
(2) The ampacity of the conductors does not correspond with the standard 5.5 (2.6) 4 7 11 19 26 43 61 95 127 163 5.5 (2.6) 3 6 10 18 23 39 58 89 117 152 400 30 3 38 1
ampere rating of a fuse or a circuit breaker without overload trip 8.0 (3.2) 2 4 7 12 16 26 37 57 76 98 8.0 (3.2) 1 4 6 11 14 23 35 53 70 91 500 30 2 50 1/0
adjustments above its rating (but that shall be permitted to have 14 1 3 5 9 12 20 28 43 58 75 14 1 3 5 8 11 18 27 41 53 70 600 38 1 60 2/0
other trip or rating adjustments). 22 1 2 4 6 9 15 21 32 43 56 22 1 1 3 6 8 13 20 30 40 52 800 50 1/0 80 3/0
(3) The next higher standard rating selected does not exceed 800 amperes. 30 1 1 3 5 6 11 15 23 31 41 30 1 1 2 4 6 9 14 22 29 38 1000 60 2/0 100 4/0
38 1 1 1 3 4 7 11 16 22 28 38 1 1 1 3 4 7 10 15 20 26 1200 80 3/0 125 250
(c) Devices Rated Over 800 Amperes. 50 1 1 1 3 4 6 9 14 19 24 50 0 1 1 2 3 6 8 13 17 23 1600 100 4/0 150 350
Where the overcurrent device is rated over 800 amperes, the ampacity of the 60 0 1 1 2 3 5 8 12 16 20 60 0 1 1 2 3 5 7 11 15 19 2000 125 250 200 400
conductors it protects shall be equal or greater than the rating of the overcurrent 80 0 1 1 1 3 4 6 10 13 17 80 0 1 1 1 2 4 6 9 12 16 2500 150 350 300 600
device as defined in Section 2.40.1.6. 100 0 1 1 1 2 4 5 8 11 14 100 0 0 1 1 1 3 5 8 10 13 3000 200 400 300 600
125 0 0 1 1 1 3 4 7 9 12 125 0 0 1 1 1 3 4 6 8 11 4000 250 500 400 800
150 0 0 1 1 1 2 4 6 8 10 150 0 0 1 1 1 2 3 5 7 9 5000 375 700 500 1200
175 0 0 0 1 1 1 3 4 6 8 175 0 0 0 1 1 1 3 5 6 8 6000 400 800 500 1200
200 0 0 0 1 1 1 2 4 5 7 200 0 0 0 1 1 1 3 4 6 7
250 250 0 0 0 1 1 1 2 3 5 6