INSPECTION & TESTING REQUIREMENTS REVISION: 09/11/2009 CODE NUMBER: PAGE:

SAUDI ARAMCO FORM-175 -007 REPLACES: 175-SPECIAL -007 1 of 1


SCOPE: Low Voltage Panelboard PURCHASE ORDER NUMBER:

TEST and INSPECTION PER:16-SAMSS-518 & Specifications As Noted ITEM NUMBER(s):


Below.

(1) VISUAL INSPECTION / WITNESSING BY BUYER REPRESENTATIVE (Note 1 )

(2) CERTIFICATES / RECORDS TO BE CHECKED BY BUYER REPRESENTATIVE


LINE
NO (3) CERTIFICATES / DATA TO BE PROVIDED BY VENDOR / SUPPLIER / MANUFACTURER
Pre-Fabrication / Pre-Production Requirements Specification Details / Notes:
01
02 X Certified Design / Test Reports
03
In-Process Inspection & Testing Requirements
04
05 X X Workmanship, Components and Dimensions: Per 16-SAMSS-518 and P.O requirements.
06
07
08
09
10
11
12
13
14
15
16
Final Inspection & Testing Requirements
17
18 X Production Tests As per UL 67 and NEMA PB1

19 X X DI-electric Tests Using Megger test with 1000V

20 X Fully Type test As per UL 67 and NEMA PB1


They shall be performed on each switching assembly at the switchboard
21 X Routine Tests
manufacturers premises.
A complete set of special tools, which is required for contractor maintenance and a
22 X Accessories lifting/handling device (if required and/or necessary), shall be provided for assembly
within a substation.
All unpainted hardware shall be of a non-oxidizing or non-corrosive material or shall
23 X Painting and coating
be planted with zinc, cadmium, chromium etc.. Color shall be P.O. requirements.
24
25
26
27
28 X Nameplates & Marking Per 16-SAMSS-518 and as per UL 67
29
30 X Preparation for Shipping Equipment shall be shipped completely assembled.
31
32

Notes:
(1) May only be waived by the responsible Saudi Aramco, ASC, AOC Inspection Offices.
(2) See form SA175 000003 (page 2 of 2) for instructions on using this form.