Anda di halaman 1dari 4

APAR INDUSTRIES LIMITED

(UNIT : UNIFLEX CABLES) GTP - 01/7.2.0/DGN/COM


REV 00 DATED 12/10/2012

TECHNICAL PARTICULAR
1.1 KV (1.5 KV DC) ALUMINIUM XLPE POWER CABLE (ARMOURED)

CUSTOMER : M/s GREENKO ENERGY PROJECTS PVT.LTD.


REF NO : E-MAIL DATED 16/02/2017.
REV NO : 00 DATED 18/02/2017.

S.No. Technical Description UOM 1.1 KV (1.5 KV DC) 1C X 300 A2XFaY

1 Name of the Manufacturer APAR INDUSTRIES LTD (UNIT:UNIFLEX CABLES)

2 Applicable Standards IS : 7098 (PART-1) 1988

3 Cable Description ( Cable Code) A2XFaY

4 Max. Operating Temperature C 90

5 No. of Cores 1

6 Rated Voltage 1100 V (1500 V DC)

7 Voltage Grade 1100 V (1500 V DC)

8 Suitable for Earthed/Unearthed Systems SUITABLE FOR BOTH SYSTEMS

9 Conductor

a. Material Only H4 grade to be used H2/H4 GRADE ALUMINIUM

b. Nom. Area Sq.mm 300

c. Type STRANDED CIRCULAR COMPACTED

d. Min. No. of Wires/Strands No 30


Calculated value to be DIA OF EACH STRANDS TO BE CHOOSEN TO MEET
e. Dia of each strand before stranding mm
provided MAX.C.R.VALUE
f. Max DC Resistance at 20C Ohm/Km 0.100

g. Max DC Resistance at 90C Ohm/Km 0.128

h. Max AC Resistance at 90C Ohm/Km 0.128

i. Approx. Reactance at 50Hz Ohm/Km 0.087

j. Approx. Capacitance mFd/Km 0.69

k. Elongation of strand
Strand size, tensile strength before and after stranding
NOT APPLICABLE
to be provided
l. Short circuit withstand capacity and duration (Conductor) kA/s 28.32 for 1 sec.

10 Insulation

a. Material XLPE AS PER IS 7098(Pt-1) 1988

b. Nom/Min Thickness mm 2.1/1.79

c. Colour BLACK
S.No. Technical Description UOM 1.1 KV (1.5 KV DC) 1C X 300 A2XFaY

f. Filled / unfilled UNFILLED

g. Type of curing SIOPLAS CURING


Minimum tensile strength without ageing
h. 12.5 /25
(N/mm2) and maximum % variation after ageing
Minimum elongation at break without ageing
1 200/25
(%) and maximum % variation after ageing.
2 Minimum Volume resistivity of insulation at

k. 27 DegC Ohm-Cm 1 X 1014

l. Max.rated temperature of 90 Deg.C Ohm-Cm 1 X 1012

m. Minimum insulation resistance constant at 90C 3.67

1 27 DegC Ohm-Cm TO BE MEET MIN.VOLUME RESISTIVITY 1 X 1014 AT 20C

2 Max.rated temperature of 90 Deg.C Ohm-Cm TO BE MEET MIN.VOLUME RESISTIVITY 1 X 1012 AT 90C


Whether application of insulation is by way of
3 YES
extrusion
11 Inner Sheath

a. Material PVC ST2 type


b. Thickness (Min.) mm 0.3
Whether method of application is by way of
c. YES
extrusion
d. Interstices(or fillers) N/A BEING SINGLE CORE CABLES

1 Whether used in the formation of cable

2 Material

e. Binder tape(Over the laid up cores) N/A BEING SINGLE CORE CABLES

1 Material

2 Thickness

12 Armouring

a. Material ALUMINIUM

b. Type of armouring Flat strip

c. Nominal size of armour 4.0 x 0.8

d. Fault current carrying capacity of Armouring for 0.12 sec. KA 13.34

13 Outer Sheath

a. Material FR-LSH PVC TYPE ST-2

b. Thickness (Min.) mm 1.56

c. Colour BROWN

d. Anti-Rodent & Anti Termite YES


Minimum tensile strength without ageing
e. (N/mm2) and maximum % variation after 12.5 /25
ageing
S.No. Technical Description UOM 1.1 KV (1.5 KV DC) 1C X 300 A2XFaY

Minimum elongation of break (%) and


f. 150/25
maximum variation after ageing (%)

Whether method of application is by way of


g. YES
extrusion

Are the inner and outer sheaths extruded in a


h. N/A BEING ARMOURED CABLES
single operation out of the material intended for outer sheaths

Whether the PVC suitably treated for


i. YES
withstanding the working conditions.

14 Approx. Overall Diameter of Cable mm 31.5

15 Max. Tensile Strength

a. For cables pulled with stackings N 8930

b. For cables pulled with pulling eyes N 9000

16 Fire Retardant Properties


Max Conductor temperature under normal
a. Deg C 90
operating conditions
b. Max. Short circuit temperature Deg C 250
Short Circuit rating of conductor for the
c. KA 28.32
duration of 1sec
c. Halogen Free NOT APPLICABLE

d. Smoke Density (ASTM D 2843) % max 60

e. Oxygen Index % 29

f. Fire performance AS PER IS 7098(P-1)

g. UV Resistance To be confirmed NOT APPLICABLE

h. Ozone Resistance To be confirmed NOT APPLICABLE

17 Continuous Current Carrying Capacities (Flat touching)

a. In Ground at 30 deg C A 463

b. In Duct at 30 deg C A 377

c. In air at 40 deg C A 561

18 Recommended minimum bending radius mm 15 x CABLE O.D.

19 Approx. weight of the Cable Kg/Km 1380

Gross weight of the complete drum with


20 Kg 915
cable
21 Drum Type WOODEN

22 Dimensions

a. Flange diameter can be provided for 500 meter drums.

b. Barrel diameter SHALL BE SELECTED AS PER FINAL PACKING LENGTH

c. Transverse dimension
S.No. Technical Description UOM 1.1 KV (1.5 KV DC) 1C X 300 A2XFaY

23 Drum Length and tolerance Mtrs. 500 5%


Whether core/cable identification/marking as
CONFIRM
specified shall be carried out.
AIL/UNIT-UNIFLEX CABLES - INDIA 'UNICAB' 1100 VOLTS
24 (1500 VOLTS DC)' ELECTRIC XLPE FR-LSH CABLE' 'CABLE
Cable identification (Embossing/Printing) SIZE' 'A2XFaY 'YEAR OF MFG'. & Sequential length marking
shall be provided at every one meter on outer sheath by
hot foil indenting/Printing.

Deration factors and DC current ratings to be shared.