System Psychrometrics for CORRIDOR 4a

Project Name: 21014 BARKA MALL R4 08/01/2017


Prepared by: Amjaad 07:56AM

July DESIGN COOLING DAY, 1800

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 44.3 0.02037 0 400 0 0
Vent - Return Mixing Outlet 26.2 0.00981 2359 4975 - -
Central Cooling Coil Outlet 13.3 0.00876 2359 4975 36870 7303
Supply Fan Outlet 13.3 0.00876 2359 4975 218 -
Cold Supply Duct Outlet 13.4 0.00876 2335 4975 - -
Zone Air - 21.6 0.00982 2335 4977 23105 7302
Return Plenum Outlet 26.4 0.00982 2335 4977 13308 -
Duct Leakage Air Outlet 13.3 0.00876 24 4975 - -
Return Duct Outlet 26.2 0.00981 2359 4975 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2942.3 W/(L/s)
Site Altitude = 14.9 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (C) (L/s) (ppm) (W) (W)
Zone 1 23886 Cooling 23105 21.6 2335 4977 0 0

Hourly Analysis Program v4.50 Page 1 of 2


System Psychrometrics for CORRIDOR 4a
Project Name: 21014 BARKA MALL R4 08/01/2017
Prepared by: Amjaad 07:56AM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 12.0 0.00682 0 400 0 0
Vent - Return Mixing Outlet 18.5 0.01100 2359 800 - -
Central Cooling Coil Outlet 18.4 0.01100 2359 800 0 0
Supply Fan Outlet 18.5 0.01100 2359 800 218 -
Cold Supply Duct Outlet 18.5 0.01100 2335 800 - -
Zone Air - 18.5 0.01100 2335 800 -141 0
Return Plenum Outlet 18.5 0.01100 2335 800 0 -
Duct Leakage Air Outlet 18.5 0.01100 24 800 - -
Return Duct Outlet 18.5 0.01100 2359 800 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2942.3 W/(L/s)
Site Altitude = 14.9 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (C) (L/s) (ppm) (W) (W)
Zone 1 -2538 Deadband -141 18.5 2335 800 0 0

Hourly Analysis Program v4.50 Page 2 of 2