D60

Transmission Line Protection


LINE DISTANCE
PROTECTION SYSTEM
High-speed transmission line
protection with three/single pole tripping
KEY BENEFITS
High-speed cost effective five zone quad or mho, phase and Simplified teleprotection interfaces with Direct I/O
ground distance protection communications hardware for Transfer Trip and Pilot-Aided
Reliable and secure protection on series compensated lines distance schemes
Superior phase selection algorithm ensures secure high speed Reduced installation space requirements through integration
single pole tripping of multiple devices including protection, control functions,
pushbuttons, status LEDS, and communication interfaces
Supports multiple standard pilot schemes for fast fault
clearance within the protected zone Phasor Measurement Unit - Synchronised phasor information
according to IEEE C37.118 standard
Flexible programmable logic for building customized schemes
Embedded IEC61850 Protocol
Reduced relay to relay wiring and associated installation
costs through high-speed inter-relay communications

APPLICATIONS
Overhead lines including series compensated lines and Circuits with in-zone power transformers and tapped
underground cables of different voltage levels transformer feeders
Single and dual-breaker circuits requiring single pole/ Secure application with Capacitively-Coupled Voltage
three-pole autoreclosing and independent synchrocheck Transformers (CCVTs)
supervision Backup protection for generators, transformers and reactors

FEATURES
Protection and Control Monitoring and Metering
Phase Distance (five zones) with independent compensation Synchronised measurement of voltage & current and
settings for in-zone power transformers sequence component phasors - 1 to 60 phasors/sec
Ground distance (five zones) with independent self and Metering - current, voltage, power, energy, frequency
mutual zero sequence compensation
Oscillography analog and digital parameters at
Out-of-step tripping and power swing blocking 64 samples/cycle
Line pickup Event Recorder - 1024 time tagged events with 0.5ms scan of
Directional overcurrent: Phase, neutral and negative digital inputs
sequence Data Logger - 16 channels with sampling rate up to
Synchronism check for dual breaker applications 1 sample / cycle
Four-shot dual breaker auto-recloser Advanced device health diagnostics
VT fuse failure detector Setting Security Audit Trail for tracking changes to D60
configuration
Customize protection and control functions with FlexLogic,
FlexCurves, and FlexElements EnerVista Software
Communications State of the art software for configuration and
commissioning GE Multilin products
Networking interfaces 100Mbit Fiber Optic Ethernet, RS485,
RS232, RS422, G.703, C37.94 Graphical Logic Designer and Logic Monitor to simplify
designing and testing procedures
Multiple Protocols - IEC61850, DNP 3.0 Level 2, Modbus RTU,
Modbus TCP/IP, IEC60870-5-104, Ethernet Global Data (EGD) Document and software archiving toolset to ensure reference
material and device utilities are up-to-date
Direct I/O secure, high-speed exchange of data between URs
for Direct Transfer Trip and pilot-Aided schemes EnerVista Integrator providing easy integration of data in
the D60 into new or existing monitoring and control systems

g Multilin
181
D60 Line Distance Protection System

Protection & Control D60 - Protection, Metering, Monitoring and Control


The D60 is a high-end, cost effective distance
protection relay intended for protecting
transmission lines and cables providing
reliable and secure operation even under
the worst case power system conditions.
Transmission Line Protection

Part of the Universal Relay family, the D60


comes with a variety of versatile features
truly integrating protection, monitoring,
metering, communication and control in
one easy-to-use device. The Universal Relay
family offers a high degree of modularity
in its design and functionality providing
superior performance in protection and
control meeting the toughest requirements
of the marketplace.

Distance Protection
The D60 is the single point for protection, control, metering, and monitoring in one integrated device that
The core of the D60 relay is the distance can be easily connected directly to HMI or SCADA monitoring and control systems.
function providing high degree of sensitivity
used to block the distance elements under
and selectivity for all types of faults. The The advanced comparator based distance
voltage source fuse failure conditions.
distance function comes with five zones elements provide utmost security, sensitivity
of phase distance and ground distance and selectivity for different types of faults. In-Zone Transformer Compensation
providing the user maximum flexibility Superior digital filtering techniques provide
Phase distance protection in the D60
to cater for different applications which secure and optimum reach accuracy even
can be used to detect faults through
include primary line protection and back- under worst-case CVT transients. Secure
different types of three-phase wye/delta
up protection for busbars generators, directional discrimination is achieved by
transformer, allowing application of the
transformers and reactors. The relay using positive sequence memory voltage
D60 for backup protection on generators.
can be applied to power systems with polarization providing reliable directionality
VTs and CTs can be installed independent
different earthing conditions, lines with in- for worst-case close-in faults. The D60
of each other on either side of the power
zone transformers or tapped transformer employs a well-proven algorithm for phase
transformer. The relay automatically
feeders, and overhead lines with series selection which provides faster, secure
compensates for transformer connections,
compensation. Each zone element for and reliable faulted phase identification
to guarantee accurate reach for any type
the phase and ground distance can for single pole tipping and proper fault
of fault.
be independently set as Quad or Mho distance calculation for a variety of power
characteristics with the flexibility of system conditions. An additional voltage
designing different characteristic shapes to monitoring function provides extra security
suit for different power system conditions. to the distance element, which can be

ANSI Device Numbers & Functions


Functional Block Diagram
Device
Number Function
21G Ground Distance
21P Phase Distance
25 Synchronism Check
52 52
27P Phase Undervoltage
27X Auxiliary Undervoltage
50BF Breaker Failure
50DD Current Disturbance Detector
CLOSE TRIP 50G Ground Instantaneous Overcurrent
Monitoring 50N Neutral Instantaneous Overcurrent
59X 27X 25 (2)
50P Phase Instantaneous Overcurrent
79 50_2 Negative Sequence Instantaneous Overcurrent
51G Ground Time Overcurrent
50DD 50P (2) 50_2 (2) 51P (2) 51_2 (2) 50BF (2) 21P (4) 67P (2) 67_2 (2) 68 78 50N (2) 51N (2) 67N/G (2) 21G (4) 51N Neutral Time Overcurrent
51P Phase Time Overcurrent
Data From/To Remote End Pilot TM
Transducer
59P 51_2 Negative Sequence Time Overcurrent
FlexElement Metering
(via Communications) Schemes Inputs
52 AC Circuit Breaker
50G (2) 51G (2)
27P (2) 59N Neutral Overvoltage
59P Phase Overvoltage
59N
59X Auxiliary Overvoltage
59_2 Negative Sequence Overvoltage
D60 Line Distance Protection System 67N Neutral Directional Overcurrent
67P Phase Directional Overcurrent
67_2 Negative Sequence Directional Overcurrent
68 Power Swing Blocking
78 Out-of-Step Tripping
79 Automatic Recloser

182 www.GEMultilin.com
D60 Line Distance Protection System

(line end open). Three instantaneous Hybrid Permissive Overreach Transfer


overcurrent elements are used to identify Trip (HYB POTT) permissive echo and
a previously de-energized line that has transient blocking logic incorporated
been closed on to a fault.
Directional comparison blocking
scheme
Power Swing Detection
Directional comparison unblocking
Z3 Z1 Dynamic transients in the power system

Transmission Line Protection


scheme (DCUB)
Z1 looking through a transformer due to short-circuits, circuit switching,
or load unbalance changes can travel
across the power network as power swings All communication-aided schemes can be
characterized by fluctuating currents and programmed for one, two or four-bit user
voltages. This can result in unwanted communications. This allows transmission
tripping since distance elements can of phase selective information for reliable
respond to these power swings as faults. single pole tripping if required.
The D60 power swing detection element
Undervoltage & Overvoltage
provides both power swing blocking and
Z3 Z1 Protections
out-of-step tripping functions. The element
Z1 & Z3 looking through a transformer Long lines under lightly loaded conditions or
measures the positive sequence apparent
impedance and traces its locus with respect no-load may experience voltages exceeding
Load Encroachment the rated insulation voltage level of the
to either a two or three step user selectable
The load encroachment feature offers mho or quad operating characteristics. line. Use the phase overvoltage element
discrimination between line loading of the D60 to initiate a local trip as well
conditions and fault conditions especially Series Compensated Lines as a remote trip using direct transfer trip.
for long lines under heavy loads by D60 provides enhanced stability and The D60 also provides additional voltage
supervising the distance elements or security by employing an adaptive functions including neutral overvoltage,
any overcurrent element. This prevents distance reach control to cope with the negative sequence overvoltage and phase
unwanted tripping under heavy line overreaching and sub-synchronous undervoltage
load conditions and enables optimum oscillations when applied to, or in the
operation of the line while meeting Overcurrent Functions
vicinity of series compensated lines. For
regulatory requirements for line loading. directional integrity the relay uses memory The D60 provides overcurrent functions for
voltage polarization and a multi-input phase, neutral and ground which can run
comparator to deal with current inversion parallel with distance protection or can be
issues in series compensated lines. programmed to provide primary protection
under conditions when distance elements
Single-Pole Tripping are blocked during fuse-failure conditions.
The D60 relay uses an advanced phase
selection algorithm that provides fast Instantaneous and timed overcurrent
and accurate fault type identification elements for phase, neutral, ground and
even under weak-infeed conditions. negative sequence protection
A convenient trip function is built-in to Directional supervision is available for
coordinate actions of the key elements of phase neutral and negative sequence
Distance relay quadrilateral characteristics the single-pole tripping package elements
supervised by Load Encroachment function
Time O/C elements can individually
Communication Aided (Pilot)
be set to use IEEE, IEC or custom
Schemes
Fault Locator FlexCurvesTM
D60 supports different teleprotection
The integrated fault locator provides functions for fast fault clearance for Autorecloser
distance to fault in km or miles. Parallel any faults within the protected line. The
line zero-sequence current compensation The D60 provides multi shot autoreclosing
following types of pilot-aided schemes are
and load current compensation enables for single pole or three pole autoreclose
available in the D60:
the D60 to provide improved accuracy for on all types of faults with independently
fault distance measurement. settable dead time for each shot.
Direct Under reach Transfer Trip (DUTT)
Autoreclosing also can be dynamically
Line Pickup (Switch-on-to Fault) Permissive Under reach Transfer Trip blocked by user programmable logic. Four
(PUTT) different autoreclose modes are available
The Line Pickup feature uses a combination
of undercurrent and undervoltage to Permissive Overreach Transfer Trip enabling the users to select the reclosing
identify a line that has been de-energized (POTT) mode to suit specific applications.

www.GEMultilin.com 183
D60 Line Distance Protection System

Synchronism Check Custom Programmable Logic Designer


The D60 monitors voltage difference,
phase angle difference and slip frequency
to ensure proper breaker closure as per
user defined settings. The D60 provides
additional enhancements in synchronizing
Transmission Line Protection

by checking dead source conditions


for synchronism bypass under these
conditions.

Multiple Breaker Configurations


The D60 supports dual-breaker busbar
configurations such as breaker-and-a-half
or ring bus arrangements, providing dual
breaker auto reclose, dual synch-check
elements, and dual independent Breaker
Failure elements. The design provides
secure operation during external faults
with possible CT saturation.

Breaker Failure FlexLogicTM allows customizing the D60 for custom protection, control and automation allowing users
to build line protection schemes and applications for their equipment.
The D60 is able to provide fully independent
breaker failure protection for the breakers
Scalable Hardware optional circuit continuity monitoring
associated to the line when connected to
The D60 is available with a multitude of I/O and current detection to verify
a substation with a breaker-and-a-half or
configurations to suit the most demanding continuity and health of the associated
ring bus arrangement. The D60 provides
application needs. The expandable modular circuitry
the elements to perform two independent
design allows for easy configuration and Mechanically latching outputs
breaker failure functions.
future upgrades. can be used to develop secure
interlocking applications and replace
Advanced Automation Flexible, modular I/O covering a broad electromechanical lockout relays
The D60 incorporates advanced automation range of input signals and tripping RTDs and DCmA inputs are available to
features including powerful FlexLogic schemes monitor equipment parameters such as
programmable logic, communication, and Types of digital outputs include trip- temperature & pressure
SCADA capabilities that far surpass what is rated Form-A and Solid State Relay
found in the average line protection relay. (SSR) mechanically latching, and
The D60 integrates seamlessly with other Form-C outputs
Monitoring and Metering
UR relays for complete system protection, The D60 includes high accuracy metering
Form-A and SSR outputs available with
including the unit and auxiliary transformers, and recording for all AC signals. Voltage,
and Balance of Plant protection. current, and power metering are built into
D60 Breaker-and-Half Configuration
the relay as a standard feature. Current
FlexLogic and voltage parameters are available
FlexLogic is the powerful UR-platform as total RMS magnitude, and as
programming logic engine that provides the fundamental frequency magnitude and
ability of creating customized protection angle.
and control schemes thereby minimizing
the need, and the associated costs, of Fault and Disturbance Recording
auxiliary components and wiring. The advanced disturbance and event
Using FlexLogic, the D60 can be recording features within the D60 can
programmed to provide required tripping significantly reduce the time needed for
logic along with custom scheme logic for postmortem analysis of power system
breaker control (including interlocking with events and creation of regulatory reports.
external synchronizers), transfer tripping Recording functions include:
schemes for remote breakers and dynamic
setting group changes. D60 supports Breaker-and-Half configuration. Two CTs Sequence of Event (SOE)
can be brought in individually and summed off at each - 1024 time stamped events
terminal.

184 www.GEMultilin.com
D60 Line Distance Protection System

Oscillography, Settings Security & Device Status Reports


- 64 digital & up to 40 Analog channels
Data Logger, disturbance recording
16 channels up to 1 sample / cycle /
channel
Fault Reports

Transmission Line Protection


- Powerful summary report of pre-fault
and fault values

The very high sampling rate and large


amount of storage space available for
data recording in the D60 can eliminate
the need for installing costly standalone
recording equipment.

Advanced Device Health


Diagnostics
The D60 performs comprehensive device
health diagnostic tests during startup and
continuously at runtime to test its own major
functions and critical hardware. These
diagnostic tests monitor for conditions that
Track changes of settings to your D60 & view health and operating status by generating a report at the
could impact security and availability of click of a button
protection, and present device status via
SCADA communications and front panel IEC61850 Direct I/O Messaging
display. Providing continuous monitoring Direct I/O allows for sharing of high-speed
DNP3.0
and early detection of possible issues helps digital information between multiple UR
improve system uptime. Ethernet Global Data (EGD)
relays via direct back-to-back connections
IEC60870-5-104 or multiplexed through a standard DS0
Comprehensive device health Modbus RTU, Modbus TCP/IP multiplexer channel bank. Regardless of
diagnostic performed during startup the connection method, Direct I/O provides
Monitors the CT/VT input circuitry to Interoperability with Embedded continuous real-time channel monitoring
validate the integrity of all signals IEC61850 that supplies diagnostics information on
Use the D60 with integrated IEC61850 to channel health.
lower costs associated with protection, Direct I/O provides superior relay-to-relay
Communications control and automation. GE Multilins communications that can be used in
The D60 provides advanced commun- leadership in IEC61850 comes from advanced interlocking and other special
ications technologies for remote data and thousands of installed devices and follows protection schemes.
engineering access, making it easy and on seven years of development experience
flexible to use and integrate into new and with UCA 2.0. Communication with up to 16 UR relays
existing infrastructures. Direct support in single or redundant rings rather
for fiber optic Ethernet provides high- Replace expensive copper wiring than strictly limited to simplistic point-
bandwidth communications allowing for between devices with direct transfer of to-point configurations between two
low-latency controls and high-speed file data using GOOSE messaging devices
transfers of relay fault and event record Configure systems based on IEC61850 Connect to standard DS0 channel
information. The available redundant and also monitor and troubleshoot banks through standard RS422, G.703
Ethernet option provides the means of them in real-time with EnerVista or IEEE C37.94 interfaces or via direct
creating fault tolerant communication Viewpoint Engineer fiber optic connections
architectures in an easy, cost-effective No external or handheld tester
Integrate GE Multilin IEDs and generic
manner without the need for intermediary required to provide channel diagnostic
IEC61850-compliant devices seamlessly
communication hardware. information
in EnerVista Viewpoint Monitoring

The D60 supports the most popular industry


standard protocols enabling easy, direct
integration into DCS and SCADA systems.

www.GEMultilin.com 185
D60 Line Distance Protection System

Multi-Language all of the setup and support tools needed systems. Viewpoint Monitoring provides a
The D60 supports English, French, Russian, for configuring and maintaining GE Multilin complete HMI package with the following
and Chinese languages on the front panel, products. The setup software within functionality:
EnerVista setup software, and product Launchpad allows configuring devices in
manual. Easily switch between English real-time by communicating using serial, Plug-&-Play Device Monitoring
and an additional language on the local Ethernet, or modem connections, or offline
System Single-Line Monitoring & Control
Transmission Line Protection

displays without uploading new firmware. by creating setting files to be sent to


Annunciator Alarm Screens
devices at a later time.
Trending Reports
EnerVistaTM Software Included in Launchpad is a document Automatic Event Retrieval
The EnerVista Suite is an industry-leading archiving and management system
Automatic Waveform Retrieval
set of software programs that simplifies that ensures critical documentation is
up-to-date and available when needed.
every aspect of using the D60 relay. The Viewpoint Engineer
EnerVista suite provides all the tools Documents made available include:
Viewpoint Engineer is a set of powerful
to monitor the status of the protected tools that will allow the configuration and
asset, maintain the relay, and integrate Manuals
testing of UR relays at a system level
information measured by the D60 into Application Notes in an easy-to-use graphical drag-and-
DCS or SCADA monitoring systems. Guideform Specifications drop environment. Viewpoint Engineer
Convenient COMTRADE and Sequence provides the following configuration and
Brochures
of Events viewers are an integral part commissioning utilities:
of the UR Setup software included with Wiring Diagrams
every UR relay, to carry out postmortem FAQs
Graphical Logic Designer
event analysis to ensure proper protection Service Bulletins
system operation. Graphical System Designer

Viewpoint Monitoring Graphical Logic Monitor


EnerVista Launchpad
Viewpoint Monitoring is a simple-to-use Graphical System Monitor
EnerVista Launchpad is a powerful
and full-featured monitoring and data
software package that provides users with
recording software package for small

Power System Troubleshooting


The D60 contains many tools and reports that simplify and reduce the amount of time required for troubleshooting power system events.

Graphically view zone settings for ground


Analyse transmission line faults using system phase distance elements for the selected
voltage, current and appropriate pickup flags that zones and the power swing detection
are measured & recorded up to 64 samples/cycle. element.

Record the operation of the internal D60 elements and external


connected devices with 1ms time-stamped accuracy to identify
the Sequence of Operation of station devices during faults and
disturbances.

186 www.GEMultilin.com
D60 Line Distance Protection System

Viewpoint Maintenance Typical Wiring


TRIPPING DIRECTION
TYPICAL CONFIGURATION
Viewpoint Maintenance provides tools that THE AC SIGNAL PATH IS CONFIGURABLE

will create reports on the operating status A (5 Amp)

of the relay, simplify the steps to download B


52 52
fault and event data, and reduce the work C

required for cyber-security compliance


audits. Tools available in Viewpoint

Transmission Line Protection


A B C

Maintenance include: CURRENT


POLARIZATION
SOURCE

Settings Security Audit Report


Device Health Report

F 5a

F 6a

F 7a
F 1a

F 1b

F 2a

F 2b

F 3a

F 3b

F 4a

F 4b

F 8a
F 2c

F 3c

F 5c

F 6c

F 7c
F 1c

F 4c

F 8c
Single Click Fault Data Retrieval

VB

VC

VX
VA
IG5

IG1
IG
IB

IC

VB

VC
IC5

IC1

VX
IA5

IA1

VA
IB5

IB1
IA
EnerVista Integrator

CURRENT SUPV.
VOLT &
CURRENT INPUTS VOLTAGE INPUTS
EnerVista Integrator is a toolkit that allows 8F / 8G
H 7a CONTACT IN 7a H DIGITAL I/O 6H I H 1a TC 1
seamless integration of GE Multilin devices H 7c CONTACT IN 7c H
CONTACT IN 8a H
H1
V
H 1b
H 8a H 1c
into new or existing automation systems. H 8c
H 7b
CONTACT IN 8c H
COMMON 7b H H2
I H 2a
H 2b
V

VOLTAGE SUPV.
Included in EnerVista Integrator is: H 8b SURGE
I
H 2c
H 3a
H3 H 3b TC 2
H 3c
I H 4a
OPC/DDE Server H4 H 4b

g Multilin D60 V
H 4c
I H 5a
GE Multilin Drivers Line Distance Protection System H5 H 5b
V
H 5c
Automatic Event Retrieval H6
I H 6a
H 6b
V
H 6c
Automatic Waveform Retrieval W 5a CONTACT IN 5a W DIGITAL I/O 6A I W 1a
W 5c CONTACT IN 5c W W1 W 1b
V
W 6a CONTACT IN 6a W W 1c
W 6c CONTACT IN 6c W I W 2a
W 5b COMMON 5b W W2 W 2b

User Interface
V
W 2c
W 7a CONTACT IN 7a W
W 3a
W 7c CONTACT IN 7c W
W3 W 3b
W 8a CONTACT IN 8a W
W 3c
The D60 front panel provides extensive W 8c CONTACT IN 8c W
W 4a
W 7b COMMON 7b W
W4 W 4b
local HMI capabilities. The local display W 8b SURGE W 4c
P 1a
is used for monitoring, status messaging,
6C
( DC ONLY )

P1 P 1b
P 1c
fault diagnosis, and device configuration. P 2a
P2 P 2b
User configurable messages that combine U 1a CONTACT IN 1a U P 2c
6D

U 1c CONTACT IN 1c U P 3a
text with live data, can be displayed when U 2a CONTACT IN 2a U P3 P 3b
U 2c CONTACT IN 2c U P 3c
user-defined conditions are met. U 1b COMMON 1b U
P4
P 4a
U 3a CONTACT IN 3a U
P 4b
U 3c CONTACT IN 3c U
P 4c
U 4a CONTACT IN 4a U
P 5a
P5 P 5b
U 4c CONTACT IN 4c U
U 3b COMMON 3b U
P 5c
P 6a
U 5a CONTACT IN 5a U P6 P 6b
U 5c CONTACT IN 5c U P 6c
U 6a CONTACT IN 6a U P 7a
U 6c CONTACT IN 6c U P7 P 7b
DIGITAL I/O

U 5b COMMON 5b U P 7c
U 7a CONTACT IN 7a U P 8a
U 7c CONTACT IN 7c U P8 P 8b PERSONAL
COMPUTER
DIGITAL I/O

U 8a CONTACT IN 8a U P 8c
U 8c CONTACT IN 8c U
M 1a
6K

U 7b COMMON 7b U
M1 M 1b
U 8b SURGE
RS-232 M 1c
M 2a 9 PIN 25 PIN
DB-9 CONNECTOR
B 1b M2 M 2b CONNECTOR
1

CRITICAL
B 1a (front) M 2c 1 1 8
FAILURE
B 2b M 3a TXD 2 2 3 RXD
B 3a 48 VDC M3 M 3b RXD 3 3 2 TXD
B 3b OUTPUT M 3c 4 4 20
POWER SUPPLY

DC
B 5b HI M 4a SGND 5 5 7 SGND
CONTROL M4
B 6b LO CONTACTS SHOWN M 4b 6 6 6
AC or DC POWER
B 6a WITH NO M 4c 7 7 4
Shielded B 8a SURGE CONTROL POWER M 5a 8 8 5
twisted pairs B 8b FILTER M5 M 5b 9 9 22
M 5c
UR COMPUTER
D2a M 6a
RS485
9E

D3a M6 M 6b
CO M 1
D4a COM M 6c
D3b M 7a
RS485
D4b M7 M 7b
CO M 2
DIGITAL I/O

D5b COM M 7c
D5a M 8a
IRIG-B M8
D6a M 8b
CPU

Ground at D7b SURGE M 8c


Device end
No. 10AWG GROUND BUS MODULE ARRANGEMENT
Minimum
X W V U T S R P N M L K J H G F D B
6 6 6 6 6 8 9 1
MODULES MUST BE
GROUNDED IF
I/O I/O I/O I/O I/O CT/VT CPU Power
TERMINAL IS
* * * * Supply
PROVIDED
(Rear View)
* Optional

www.GEMultilin.com 187
D60 Line Distance Protection System

Ordering
D60 - * ** - H * * - F ** - H**- M** - P ** - U**-W** For Full Sized Horizontal Mount
Base Unit D60 Base Unit
CPU E RS485 & RS485 (IEC61850 option not available)
G RS485 + Multi-mode ST 10BaseF
H RS485 + Mutli-mode ST Redundant 10BaseF
J RS485 + Multi-mode ST 100BaseFX
K RS485 + Multi-mode ST Redundant 100BaseFX
Transmission Line Protection

N RS485 + 10/100 BaseT


Software Options 00 No Software Options
02 Breaker & Half
03 IEC61850
05 Breaker and Half + IEC61850
06 Phasor Measurement Unit (PMU)
07 IEC61850 + Phasor Measurement Unit (PMU)
08 Breaker and Half + Phasor Measurement Unit (PMU)
09 Breaker and Half + IEC61850 + Phasor Measurement Unit (PMU)
Mount H Horizontal (19" rack) - Standard
A Horizontal (19" rack) - Harsh Chemical Environment Option
V Vertical (3/4 size) - Standard
B Vertical (3/4 size) - Harsh Chemical Environment Option
User Interface K Enhanced English Front Panel
L Enhanced English Front Panel with User-Programmable Pushbuttons
M Enhanced French Front Panel
N Enhanced French Front Panel with User-Programmable Pushbuttons
Q Enhanced Russian Front Panel
T Enhanced Russian Front Panel with User-Programmable Pushbuttons
U Enhanced Chinese Front Panel
V Enhanced Chinese Front Panel with User-Programmable Pushbuttons
F Vertical Front Panel with English display
Power Supply H RH 125/250 V AC/DC w/ redundant 125/250 V AC/DC power supply
H 125/250 V AC/DC
CT/VT DSP 8L 8L Standard 4CT/4VT w/ enhanced diagnostics
8M 8M Sensitive Ground 4CT/4VT w/ enhanced diagnostics
Digital I/O XX XX XX XX XX No module
4A 4A 4A 4A 4A 4 Solid State (No Monitoring) MOSFET Outputs
4C 4C 4C 4C 4C 4 Solid State (Current w/opt Voltage) MOSFET Outputs
4D 4D 4D 4D 4D 16 Digital Inputs with Auto-Burnish
4L 4L 4L 4L 4L 14 Form-A (No Monitoring) Latchable Outputs
67 67 67 67 67 8 Form-A (No Monitoring) Outputs
6C 6C 6C 6C 6C 8 Form-C Outputs
6D 6D 6D 6D 6D 16 Digital Inputs
6E 6E 6E 6E 6E 4 Form-C Outputs, 8 Digital Inputs
6F 6F 6F 6F 6F 8 Fast Form-C Outputs
6K 6K 6K 6K 6K 4 Form-C & 4 Fast Form-C Outputs
6L 6L 6L 6L 6L 2 Form-A (Current w/ opt Voltage) & 2 Form-C Outputs, 8 Digital Inputs
6M 6M 6M 6M 6M 2 Form-A (Current w/ opt Voltage) & 4 Form-C Outputs, 4 Digital Inputs
6N 6N 6N 6N 6N 4 Form-A (Current w/ opt Voltage) Outputs, 8 Digital Inputs
6P 6P 6P 6P 6P 6 Form-A (Current w/ opt Voltage) Outputs, 4 Digital Inputs
6R 6R 6R 6R 6R 2 Form-A (No Monitoring) & 2 Form-C Outputs, 8 Digital Inputs
6S 6S 6S 6S 6S 2 Form-A (No Monitoring) & 4 Form-C Outputs, 4 Digital Inputs
6T 6T 6T 6T 6T 4 Form-A (No Monitoring) Outputs, 8 Digital Inputs
6U 6U 6U 6U 6U 6 Form-A (No Monitoring) Outputs, 4 Digital Inputs
Transducer I/O 5A 5A 5A 5A 5A 4 dcmA Inputs, 4 dcmA Outputs
5F 5F 5F 5F 5F 8 dcmA Inputs
Inter-Relay Communications 7A 820 nm, multi-mode, LED, 1 Channel
7B 1300 nm, multi-mode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7H 820 nm, multi-mode, LED, 2 Channels
7I 1300 nm, multi-mode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7S G.703, 2 Channels
7W RS422, 2 Channels
73 1550 nm, single-mode, LASER, 2 Channels
77 IEEE C37.94, 820 nm, multimode, LED, 2 Channel
2B C37.94SM, 1300nm Singlemode, ELED, 2 Channel Single mode

Accessories for the D60 Visit www.GEMultilin.com/D60 to:


UR Applications I Learning CD TRCD-URA1-C-S-1 View Guideform specifications
Multilink Ethernet Switch ML2400-F-HI-HI-A2-A2-A6-G1 Download the instruction manual
Viewpoint Engineer VPE-1 Review applications Notes and support documents
Viewpoint Maintenance VPM-1 Buy a D60 online
Viewpoint Monitoring IEC61850 VP-1-61850 View the UR Family brochure

Ordering Note: To view the latest options available for the D60, or to order the UR Classic Front Panel, please visit our online store for more details.