This comparison is based on earthing conductor sizing on different materials such as copper and steel.
Conductor sizing
Minimum size of earthing conductor can be found from Equation (1) (IEEE Std 80)
1
2 = (1)
104 0+
( )( )
0 +
TCAP is the thermal capacity per unit volume from table 1, in J/(cm3*0C)
Ig=4.199kA
1
2 = = 81.55 mm2
104 0+
( )( )
0 +
Ig=4.199kA
1
2 = = 13.81 mm2
104 0+
( )( )
0 +
Conclusion
It can be seen from the conductor sizing, if using steel conductor for grounding its cross sectional area
should be higher than 81.55mm2. 113mm2 steel used in TSWF project. It is satisfying calculated
minimum cross section of conductor.