Check List for Chilled Water Primary Pump No.

Sl. No Description YES NO REMARKS


1 Isolate the incoming source and apply LOTO.
2 Make sure that supply is not available at the i/p terminal of the equipment
3 Check for leakage in pipelines
4 Check for abnormal noise or heating of pump and motors
5 Check foundation bolts tightness
6 Check shaft guards are secure
7 Observe pressure gauges are functioning
8 Clean the exterior of the pump and motor
9 Check for leakage in gland / Seal
Remove coupling guard and inspect motor and pump coupling it should be free from
10
damange and with proper alignment
11 Check the Remote off and the tightness of earthing wire
Ensure suction and discharge valves are operating with ease and shut off / open in chilled
12
water line of the pump
Check for any cable colour change in motor cable terminations and loose ness of the
13
termination and if so rectify.( Termination at both ends).
Check for any cable colour change in starter panel ( Chiller pump panel) and loose ness
14
of the termination and if so rectify.
15 Check foundation plinth/base for rigidness
16 Remove the Motor fan guard and clean the fan with a clean damp cloth
17 Clean the pump and insulated pipe lines externally with cotton cloth.
Switch OFF the power supply and ensure pump shaft rotates freely by hand and Switch
18
ON the Power Supply
19 Clean pump suction strainer.
Check the Over load relay setting.(It should be setted as 17A).Ensure the O/L operation
20
by pressing the "Test" Button.
21 Check and Record the Motor load current and Winding resistance Value

22 Check and Record the suction and discharge pressure

Done by : Spares Used


PM done On :
Start Time :
End time :
Next PM due on :