ALL WORKS SHALL COMPLY WITH THE PROVISION OF THE LATEST APPROVED EDITION OF THE PHILIPPINE

ELECTRICAL CODE, WITH THE RULES AND REGULATIONS OF THE NATIONA AND LOCAL AUTHORITY
CONCERNED IN THE ENFORCEMENT OF ELECTRICAL LAWS AND ORDINANCES AND WITH THE RULES AND
REGULATIONS OF THE UTILITY COMPANY CONCERNED. WORK SHALL NOT BE STARTED UNLESS A VALID
WIRING PERMIT HAS BEEN SECURED.

1. SERVICE VOLTAGE SHALL BE COME FROM EXISTING 480 VOLTS 3 PHASE POWER SUPPLY AND
TRANSFORM TO 230 VOLTS 3 PHASE THRU DRY TYPE TRANSFORMER
2. WIRING METHOD SHALL BE AS FOLLOWS:

A. FEEDERS AND RISERS - POLYVINLY CONDUIT


B. LIGHTING, POWER, RECEPTACLE BRANCH CIRCUIT, & FIRE ALARM SYSTEM. POLYVINLY
CONDUIT.
3. SMALLEST CONDUCTOR FOR POWER AND LIGHTING SHALL BE 3.5 MM 2 TW AND SMALLEST
RACEWAY SHALL BE IN 15 DIA. EXCEPT TRADE SIZE. CONDUCTOR SHALL BE TYPE THHN EXCEPT
AS OTHERWISE REQUIRED BY THE DRAWINGS AND INSULATED FOR 600 VOLTS.
4. NO BRANCH CIRCUIT SHALL HAVE A LOAD OF MORE THAN 80% OF ITS RATING
5. GENERAL USE RECEPTACLES SHALL BE RATED 15 A, 230 VOLTS GROUNDING TYPE PARALLEL
SLOTS.
6. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND APPROVED TYPE FOR THE PARTICULAR
LOCATION AND PURPOSE USAGE.
7. ALL LIGHT CONTROL SWITCHES SHALL BE RATED 15 A, 120-277 VOLTS AC ONLY.
8. ALL FLUORESCENT LAMPS
9. CIRCUIT BREAKER SHALL BE U.S MADE QE OR SQUARE D OR JAPAN MADE FUJI BRAND, BUT
ONLY ONE BRAND THRU-OUT, ALL CIRCUIT BREAKERS FOR ONLY LIGHTING AND C.O. SHALL BE
COMMERCIAL BOLT-O TYPE, 10 KAIC FOR BRANCHES AND INDUSTRIAL TYPE 18 KAIC FOR MANIN
AND MOTOR LOADS.
10. PRESSSED STEEL OUTLET BOXES SHALL BE GALVANIZED, GA #16 MINIMUM, AS FOLLOWS:
A. CEILING LIGHT OUTLET 40 MM DEEP, 100 MM OCTAGONAL BOX FOR 1 OR 2
RACEWAY ENTRIES
B. WALL SWITCHES 55 MM DEEP UTILITY BOX FOR 1 OR 2 RACEWAY ENTRIES 40 MM
DEEP, 100 MM SQ. BOX WITH 1-GANG RAISED COVER FOR 3 SWITCHES ON STRAP.
C. WALL RECEPTACLE 55 MM DEEP UTILITY BOX FOR 1 OR 2 RACEWAY ENTRIES
11. MOUNTING HEIGHT SHALL BE AS FOLLOWS:
A. LIGHT CONTROL SWITCH 1.40 M ABOVE FLOOR AT CENTER
B. CONVENIENCE OUTLET - .30 M ABOVE FLOOR AT CENTER. FOR NON-WEATHER
PROOF OUTLET .20M ABOVE COUNTER AT CENTER FOR PANTRY
C. SPECIAL PURPOSE OUTLET AS REQUIRED BY EQUIPMENT SERVED
D. WALL TELEPHONE 30 M ABOVE FLOOR AT CENTER UNLESS OTHERWISE REQUIRED
BY FIELD CONDITION
E. PANELBOARDS, FIRE ALARM SUPERVISORY AND CONTROL PANEL CABINETS, NON-
FUSIBLE DISCONNECT SWITCH 1.40 M ABOVE FLOOR AT CENTER