ROOF MOUNTED FANS

HCTB - HCTT Series, Axial Flow Fans


Description Applications
AIR EXTRACTION
The HCTB-HCTT range of axial roof fans The HCTB-HCTT range are suitable for many
incorporate a horizontal air discharge roof extract or supply ventilation applications
configuration and are available in two versions including: commercial office, shopping malls,
for either air extract or supply operation: leisure facilities, kitchens and agricultural
buildings ventilation. The range incorporates the
The HCTB-HCTT axial roof fan range is following standard features and specifications:
supplied as standard suitable for air extract Thermal Overload Protection (except model 800)
operation. (On request models can be IP-65 Protection (except model 800 which is
provided as air supply fans). IP-55)
The range comprises of 9 nominal fan sizes Class F Motor Insulation.
with 52 model variations in total. Models are Sealed For Life, ball bearings assemblies.
available with 4 or 6 pole motors suiatble for Motors suitable for speed control in single*
single or three-phase electrical supplies. All and three phase.
three-phase motors can be operated with a Three-phase motors can be operated in
connection at 380-415V enabling the connection with 380-415V 50 Hz electrical
possibility of two speed operation. supplies enabling to speeds of operation.
HCTB / - / B HCTT / - / B * Except models HCTB/4-560 and HCTB/4-630.

Technical characteristics Extract air configuration (type B)


"

Model Type Speed Maximum Maximum current Maximum duty Sound pressure* Weight
power absorbed (m3/h) level at 1,5 meters
absorbed (A) (dB(A))
High Low
(r.p.m.) (W) at 230 V at 400 V speed speed Inlet Outlet (kg)
SINGLE PHASE 4 POLE
HCTB/4-315-B 1300 100 0,59 1930 62 61 14,4
HCTB/4-355-B 1225 200 0,96 2680 59 58 15,8
HCTB/4-400-B 1290 340 1,64 3700 62 61 16,5
HCTB/4-450-B 1290 480 2,30 5600 65 64 23,5
HCTB/4-500-B 1290 650 3,00 7100 72 70 25,4
HCTB/4-560-B 1200 980 4,90 9820 76 72 40,0
HCTB/4-630-B 1290 1700 7,60 13000 77 73 42,6
SINGLE PHASE 6 POLE
HCTB/6-450-B 835 220 1,15 3900 56 55 23,5
HCTB/6-500-B 840 290 1,60 4600 59 57 25,4
HCTB/6-560-B 900 420 2,40 6850 63 61 40,0
HCTB/6-630-B 800 510 2,56 8400 67 64 42,6
THREE PHASE 4 POLE
HCTT/4-315-B 1300 150 0,34 1930 1500 62 61 14,4
HCTT/4-355-B 1260 200 0,46 2680 2000 59 58 15,8
HCTT/4-400-B 1350 300 0,80 3700 2900 62 61 16,5
HCTT/4-450-B 1230 500 1,00 5600 4500 65 64 23,5
HCTT/4-500-B 1350 660 1,60 7100 5850 72 70 25,4
HCTT/4-560-B 1320 1210 2,30 9820 7600 76 72 40,0
HCTT/4-630-B 1290 1600 3,20 13000 9800 77 73 42,6
HCTT/4-710-B 1300 2200 4,00 18400 81 77 60,0
HCTT/4-800-B 1400 3 kW ** 7,30 23800 87 83 67,0
HCTT/4-900-B 1400 4 kW ** 9,50 30000 92 88 77,0
HCTT/4-1000-B 1450 5,5 kW ** 12,00 38500 95 91 123,0
THREE PHASE 6 POLE
HCTT/6-450-B 835 190 0,48 3900 3000 56 55 23,5
HCTT/6-500-B 830 250 0,57 4600 3500 59 57 25,4
HCTT/6-560-B 850 410 0,93 6850 5400 63 61 40,0
HCTT/6-630-B 810 600 1,18 8400 6400 67 64 42,6
HCTT/6-710-B 900 1100 3,30 12700 72 69 54,0
HCTT/6-800-B 930 0,75 kW ** 2,50 15800 78 75 57,0
HCTT/6-900-B 930 1,1 kW ** 3,50 20000 83 80 67,0
HCTT/6-1000-B 930 1,5 kW ** 4,50 24700 86 83 108,0
THREE PHASE 8 POLE
HCTT/8-710-B 670 370 1,20 9500 66 68 52,0
HCTT/8-800-B 700 370 1,90 11900 72 68 57,0
HCTT/8-900-B 700 550 2,30 15000 77 73 67,0
HCTT/8-1000-B 700 750 2,80 18600 80 76 108,0

* Fan installed on a roof. ** Absorbed.

96
Construction Specification data
AIR SUPPLY
Base Roof Axial Extract or Supply Air Fans
Manufactured from galvanised sheet steel. Type: HCTB-HCTT
Cowl Models:
Manufactured from spun aluminium. Extraction HCTT/-B (three-phase)
HCTB/-B (single-phase)
Impellers Supply Air HCTT/-A (three-phase)
The impellers for models 315 to 560 are manu- HCTB/-A (single-phase)
factured from one piece injection moulded
plastic, reinforced with chemically anchored Air stream temperature limits:
fibreglass for additional strength. Models 630 -40 C to +700 C
to 800 incorporate separate plastic blades Motor: IP 65, Class F Insulation.
locked within a die cast aluminium hub.
Motors
Asynchronous induction motors with squirrel NEW
7 1 0 -1 0 0 0
cage rotor in die-cast aluminium:
Single-phase 230 V 50 Hz
Three-phase 400 V 50 Hz HCTB / - / A HCTT / - / A

Technical characteristics supply air configuration (type A)


"

Model Type Speed Maximum Maximum current Maximum duty Sound pressure* Weight
power absorbed (m3/h) level at 1,5 meters
absorbed (A) High Low
(dB(A))
(r.p.m.) (W) at 230 V at 400 V speed speed Inlet Outlet (kg)
SINGLE PHASE 4 POLE
HCTB/4-315-A 1300 100 0,54 2150 67 61 14,4
HCTB/4-355-A 1225 200 0,96 3250 64 62 15,8
HCTB/4-400-A 1200 340 1,64 4720 71 67 16,5
HCTB/4-450-A 1290 480 2,30 6670 74 71 23,5
HCTB/4-500-A 1290 650 3,10 8440 79 75 25,4
HCTB/4-560-A 1250 980 4,90 11400 83 78 40,0
HCTB/4-630-A 1200 1700 7,60 15300 87 82 42,6
SINGLE PHASE 6 POLE
HCTB/6-450-A 835 220 1,10 4400 63 59 23,5
HCTB/6-500-A 840 290 1,50 5500 66 63 25,4
HCTB/6-560-A 900 420 2,30 7900 71 67 40,0
HCTB/6-630-A 900 510 2,50 9900 73 69 42,6
THREE PHASE 4 POLE
HCTT/4-315-A 1360 150 0,34 2150 1820 67 61 14,4
HCTT/4-355-A 1350 200 0,46 3250 2520 64 62 15,8
HCTT/4-400-A 1380 300 0,80 4720 3900 71 67 16,5
HCTT/4-450-A 1350 500 0,95 6670 5250 74 71 23,5
HCTT/4-500-A 1380 660 1,60 8440 7000 79 75 25,4
HCTT/4-560-A 1380 1210 2,30 11400 9800 83 78 40,0
HCTT/4-630-A 1360 1600 3,00 15300 12500 87 82 42,6
HCTT/4-710-A 1300 2200 4,00 20500 90 85 60,0
HCTT/4-800-A 1400 3 kW ** 7,30 26600 96 91 67,0
HCTT/4-900-A 1400 4 kW ** 9,50 35900 101 96 77,0
HCTT/4-1000-A 1400 5,5 kW ** 12,00 44900 104 99 123,0
THREE PHASE 6 POLE
HCTT/6-450-A 835 190 0,48 4400 3600 63 59 23,5
HCTT/6-500-A 830 250 0,57 5500 4500 66 63 25,4
HCTT/6-560-A 850 410 0,93 7900 6700 71 67 40,0
HCTT/6-630-A 810 600 1,18 9900 7800 73 69 42,6
HCTT/6-710-A 900 1100 3,30 14200 81 74 54,0
HCTT/6-800-A 930 0,75 kW** 2,50 17700 87 82 57,0
HCTT/6-900-A 930 1,1 kW** 3,50 23800 92 87 67,0
HCTT/6-1000-A 930 1,5 kW** 4,50 28800 95 90 108,0
THREE PHASE 8 POLE
HCTT/8-710-A 670 370 1,20 10600 75 70 52,0
HCTT/8-800-A 700 0,37 kW** 1,90 13300 81 76 57,0
HCTT/8-900-A 700 0,55 kW** 2,30 18000 86 81 67,0
HCTT/8-1000-A 700 0,75 kW** 2,80 21700 89 84 105,0

* Fan installed on a roof. ** Absorbed.

97
Performance curves Extract air configuration (type B)
Q = Air volume in, m3/hr and m3/s Pe = Static pressure in mmWG and Pa.
Dry air at 20 C and 760 mmHg.
Air flow data in accordance with the following standards: UNE 100-212-89, BS 848, Part 1, AMCA 210-85 and ASHRAE 51-1985.

315-355 - 4 pole 400 - 4 pole

450 - 4 and 6 pole 500 - 4 and 6 pole

560 - 4 and 6 pole


630 - 4 and 6 pole

* Low speed: only for three-phase models.

98
Performance curves Extract air configuration (type B)
Q = Air volume in, m3/hr and m3/s Pe = Static pressure in mmWG and Pa.
Dry air at 20 C and 760 mmHg.
Air flow data in accordance with the following standards: UNE 100-212-89, BS 848, Part 1, AMCA 210-85 and ASHRAE 51-1985.

710 - 4, 6 and 8 pole

900 - 4, 6 and 8 pole 1000 - 4, 6 and 8 pole

* Low speed: only for three-phase models.

Acoustic characteristics Extract air configuration (type B)


Sound power spectrum: To obtain the sound power level spectrum, subtract the correction value shown below from the value given in the
technical characteristics table:

Inlet 63 125 250 500 1000 2000 4000 8000 Discharge 63 125 250 500 1000 2000 4000 8000
4-315 -21 -6 -12 10 1 1 -4 -12 4-315 -20 -9 -8 11 1 -1 -5 -11
4-355 -14 -3 -3 1 5 7 4 -3 4-355 -12 -2 4 3 5 6 3 -4
4-400 -12 -3 -4 3 4 7 5 -3 4-400 -10 -1 2 4 4 5 5 -4
4-450 -13 -5 -5 2 7 6 4 -4 4-450 -12 -2 0 4 6 5 3 -4
4-500 -17 -8 -1 2 8 6 1 -7 4-500 -14 -4 2 5 6 5 2 -6
4-560 -18 -11 -1 6 7 6 0 -7 4-560 -15 -3 1 4 6 6 2 -5
4-630 -14 -6 -5 3 6 7 4 -4 4-630 -11 -1 2 3 6 5 3 -2

99
Performance curves Extract air configuration (type A)
Q = Air volume in, m3/hr and m3/s Pe = Static pressure in mmWG and Pa.
Dry air at 20 C and 760 mmHg.
Air flow data in accordance with the following standards: UNE 100-212-89, BS 848, Part 1, AMCA 210-85 and ASHRAE 51-1985.

315-355 - 4 pole 400 - 4 pole

450 - 4 and 6 pole 500 - 4 and 6 pole

560 - 4 and 6 pole 630 - 4 and 6 pole

* Low speed: only for three-phase models.

100
Performance curves Supply air configuration (type A)
Q = Air volume in, m3/hr and m3/s Pe = Static pressure in mmWG and Pa.
Dry air at 20 C and 760 mmHg.
Air flow data in accordance with the following standards: UNE 100-212-89, BS 848, Part 1, AMCA 210-85 and ASHRAE 51-1985.

710 - 4, 6 and 8 pole 800 - 4, 6 and 8 pole

900 - 4, 6 and 8 pole 1000- 4, 6 and 8 pole

Acoustic characteristiques Supply air configuration (type A)


Sound power spectrum: To obtain the sound power level spectrum, subtract the correction value shown below from the value given in the
technical characteristics table:

Discharge 63 125 250 500 1000 2000 4000 8000 Inlet 63 125 250 500 1000 2000 4000 8000
4-315 -28 -6 -4 10 2 1 -4 -15 4-315 -23 -1 5 8 4 0 -6 -11
4-355 -24 -4 0 4 7 7 4 -9 4-355 -23 -1 4 5 7 4 -2 -11
4-400 -24 -3 1 5 7 7 5 -12 4-400 -21 -1 2 5 7 4 -2 -13
4-450 -24 -3 1 5 8 6 4 -11 4-450 -24 -1 1 6 7 2 -4 -12
4-500 -22 -4 1 6 8 6 1 -11 4-500 -19 -1 4 6 7 3 -4 -10
4-560 -24 2 1 4 7 6 0 -11 4-560 -21 -2 5 4 6 4 -4 -13
4-630 -23 0 3 4 7 7 4 -13 4-630 -18 -1 6 4 6 3 -5 -14

101
Installation


or or




Type Sealing Flat roof insulated Acoustic Accessory Back draft Flange with Flexible Circular
of fan frame up-stand up-stand adapter plate shutter spigot coupling adapter
315 JMS-560 JBS-560 JAA-560 JPA-560 JCA-560 JBR-560 JAE-560 JCC-560

355
JMS-630 JBS-630 JAA-630 JPA-630 JCA-630 JBR-630 JAE-630 JCC-630
400
450
JMS-710 JBS-710 JAA-710 JPA-710 JCA-710 JBR-710 JAE-710
500
560
JMS-905 JBS-905 JAA-905 JPA-905 JCA-905 JBR-905 JAE-905
630
710
JMS-1100 JBS-1100 JAA-1100 JPA-1100 JCA-1100 JBR-1100 JAE-1100
800

 Mounting accessories

Sealing Frame JMS Back-Draft Shutter JAC


For mounting a roof fan on an Prevents backdraught when the
up-stand or base fan is not in operation.
Supplied with screws and gasket To be mounted at the fan inlet
for a complete weatherproof with the JPA plate or fixed
seal. directly to the fan base (rivets or
screws not supplied).

Flat Roof Up-Stand JBS Flange JBR


For mounting a fan on a flat roof For use when a circular
without up-stands connection is required directly to
For use on horizontal roofs the fan or through a flexible
Internal insulation to prevent connection (by others)
condensation To be mounted at the fan inlet
Supplied with screws and gasket with the JPA plate or fixed
for a complete weather seal. directly to the fan base (rivets or
screws not supplied).

Accessory Adapter Plate JPA Flexible Coupling JAE


Used when mounting the Reduces the transmission of
accessories (JCA, JBR, JAE) vibrations when the duct is
The adapter plate allows the fan connected directly to the fan
to be disconnected from the up- To be mounted at the fan inlet
stand without having to remove with the JPA plate or fixed
the duct. directly to the fan base (rivets or
screws not supplied).

102
Adapter For Circular Duct JCC Acoustic Up-Stand JAA
For use when fitting the models Reduces sound levels
up to 400, directly to a spirally For use when mounting a fan on
wound circular duct. a flat roof without up-stands
Supplied with screws and
gasket for a complete weather
seal.

Attenuation insertion loss dB at octave average frequencies Attenuator pressure drops for JAA Up-Stand
(for JAA Up-Stand)

Type 125 250 500 1000 2000 4000 8000 15


mm.
mmCEc.d.a.

JAA-560 2 8 16 29 32 26 17
10
JAA-630 2 8 14 24 27 19 13

JAA-710 2 8 14 24 28 16 11 300 435 560 630 710 905 1100


5

JAA-905 2 7 14 26 30 19 12

JAA-1100 2 7 16 27 32 20 13 500 1000 1500 2000 3000 4000 5000 10000 15000 20000 m3/h

 Electrical accessories

REB RMB / RMT


Single-phase electronic speed Auto-transformer speed controllers
controllers. For single-phase and three-phase
For use with the single-phase roof fans roof fans.

On/Off isolation switch IP55 Switch


Enables disconnection of electrical Enables two speed commutattion for
supply at roof level when installed close supplied fans.
to the fan.
3 pole model for single speed operation
(with or without speed regulator)
6 pole model for operation in
connection.

 Dimensions (mm)

Type A B C D E F G H
315 640 560 450 315 12 40 70 341
355 760 630 535 355 12 40 80 361
C
B

400 760 630 535 400 12 40 80 361


E

450 895 710 590 450 14 40 110 410


500 895 710 590 500 14 40 110 410
A 560 1150 905 750 560 14 50 165 488
630 1150 905 750 630 14 50 165 488
G

710 1350 1100 840 710 14 50 200 551


H

800 1350 1100 840 800 14 50 200 732


900 1580 1250 950 900 14 50 200 756
F

D
1000 1580 1250 950 1000 14 50 200 756

103
Recommendations for installing S&P roof extract or supply fans
The adjoining ducting should always be the same size (or larger) than the fan inlet section / diameter.

The base and ducting should be properly sealed to prevent air leakage and re-circulation.

Where possible, the roof fan should be installed to minimise the effects of strong cross winds. i.e. on a pitched roof at a point lower than the roof
top camber.