An Overview Of Short Circuit Current (part 1)

An Overview Of Short Circuit Current (part 1)

Basic concept
There are essentially four types of faults: three-phase, single line-to-ground, double line-to-ground, and line-to-line.

Each of these types of faults can result in different magnitudes of fault current.

In all types, however, there is a common element: an abnormally low-impedance path or shorted path for current to flow,
hence the name short circuit current. Such a condition can lead to extremely high currents.

By Ohms Law, voltage equals current times impedance (resistance). Therefore, when the impedance
becomes very low and the voltage does not change, the current becomes very high. Large electrical currents
produce a lot of heat transfer, which increases the temperature of cables, transformers, etc.

The increase in temperature can cause insulation damage. These currents also produce high magnetic forces, which
can actually bend buses in switchgear.

High fault currents cause magnetic forces that are proportional to the square of the fault current.

Mathematical background, X/R ratio and type of fault current

The treatment of electrical faults should be carried out as a function of time, from the start of the event at time t = 0+ until
stable conditions are reached, and therefore it is necessary to use differential equations when calculating these currents.
http://electrical-engineering-portal.com/an-overview-of-short-circuit-current-part-1 1/5
10/14/2017 An Overview Of Short Circuit Current (part 1)

In order to illustrate the transient nature of the current, consider an RL circuit as a simplified equivalent of the
circuits in electricity distribution networks.

This simplification is important because all the system equipment must be modeled in some way in order to quantify the
transient values which can occur during the fault condition.

For the circuit shown in Figure, the mathematical expression which defines the behavior of the current is:

e(t) = L di + Ri(t)

RL circuit as a simplified
equivalent of the circuits in
electricity-distribution networks

This is a differential equation with constant coefficients, of which the solution is in two parts:

ia (t): ih (t) + ip(t)

Where:

ih(t) is the solution of the homogeneous equation corresponding to the transient period.
ip(t) is the solution to the particular equation corresponding to the steady-state period.

By the use of differential equation theory, the complete solution can be determined and expressed in the following form:

Where:

http://electrical-engineering-portal.com/an-overview-of-short-circuit-current-part-1 2/5
10/14/2017 An Overview Of Short Circuit Current (part 1)

the closing angle which defines the point on the source sinusoidal voltage when the fault occurs

= tan-1(L/R) or = tan-1(X/R)
The second term in the equation for fault current is recognized as the DC component of the current, and has an initial
maximum value when:

= / 2, and zero value when = .

Notes:

Here we introduce the concept of X/R ratio. We can very well see that since L = XL or simply X hence DC
component of fault current to large extent depends upon = tan-1(X/R) or simply X/R ratio.
The X/R ratio is important because it determines the peak asymmetrical fault current.
In X/R ratio when X equals zero, there is only symmetrical current with no DC component. With R equals
zero, the DC component would never decay. One can say there will always be both resistance and reactive
components in the system.
The resistance and reactance of a circuit establishes a power factor.
The power factor (p.f.) is given by the following equation: p.f. = cos(tan-1(X/R)) this equation means that the
power factor and X/R ratio are related.
Therefore, system power factor and system X/R ratio are different ways of saying the same thing.
Please note that as power factor decreases, the X/R ratio increases.

It is impossible to predict a that is at what point the fault will be applied or take place on the sinusoidal cycle and
therefore it is not possible to determine exactly what magnitude the DC component will reach.

Symmetrical fault current

If in a circuit mainly containing reactance a short circuit occurs at the peak of the voltage wave, the short-circuit current
would start at zero and trace a sine wave which would be symmetrical about the zero axis.

This is known as a symmetrical short circuit current.

Asymmetrical fault current


http://electrical-engineering-portal.com/an-overview-of-short-circuit-current-part-1 3/5
10/14/2017 An Overview Of Short Circuit Current (part 1)

Right after a fault occurs, the current waveform is no longer a sine wave.

Instead, it can be represented by the sum of a sine wave and a decaying exponential. Figure below illustrates this
phenomenon. Please note that the decaying exponential added to the sine wave causes the current to reach a much
larger value than that of the sine wave alone.

The waveform that equals the sum of the sine wave and the decaying exponential is called the asymmetrical current
because the waveform does not have symmetry above and below the time axis.

The sine wave alone is called the symmetrical current because it does have symmetry above and below the time axis.

Sine wave, decaying exponential and their sum

Hence we can define asymmetrical fault current in the following way: If, in a circuit containing only reactance, the short
circuit occurs at any point at the peak of the voltage wave, there will be some offset of the current.

The amount of offset depends upon the point on the voltage wave at which the short circuit occurs.

This is known as asymmetrical short circuit current. Maximum asymmetry occurs when short circuit takes
place when voltage is zero.

Asymmetrical fault remains only for few cycles after which it becomes symmetrical fault. Decay of asymmetrical
component depends on the value of X/R. More the value of R, faster is the decay of asymmetrical fault current.

Magnitude of asymmetrical fault current is more than that of symmetrical fault current.

If the short circuit current does not include DC component it is called symmetrical short circuit current. If the
short circuit current contains DC component it is called as asymmetrical component.

Figure above represents the short circuit current with and without DC component.
http://electrical-engineering-portal.com/an-overview-of-short-circuit-current-part-1 4/5
10/14/2017 An Overview Of Short Circuit Current (part 1)

Will be continued soon

About Author

Asif Eqbal

Asif Eqbal - Bachelor of Engineering in Electrical & Electronics engineering, from Manipal University, (Karnataka), India
in 2006. Presently involved in the design of EHV outdoor substation and coal fired thermal power plants for more than
seven years. Motto of joining EEP as a contributor is to share my little engineering experience and help the budding
engineers in bridging the conspicuous gap between academics and Industrial practice. If you have knowledge, let others
light their candles with it, so that people who are genuinely interested in helping one another develop new capacities for
action; it is about creating timeless learning processes".

http://electrical-engineering-portal.com/an-overview-of-short-circuit-current-part-1 5/5

Anda mungkin juga menyukai