PROPOSED SECIFICATION.
Design No.& Date 1250KVASLVI 3/14/2010
TransformerRating (KVA) 1250
No-Load voltage ratio (Volts) 11000/433
Connection Delta/Star-Dyn-11
No. of phases (Ph) 3
Freequency (Hz) 50
Winding Material Copper
No-Load and Load Loss(max) (Watts) 1850/11000
Impedence (%) 6.15
Max Flux Density (Tesla) 1.6
Max Current Density (A/Sqmm) 2.6
Temperature rise (Deg.C) 45/55
CORE DETAILS
Core Dia (mm) 248
Core Centre to Centre (mm) 460
Core Window Height (mm) 601
Gross Core Area (sq.cm) 461.24
Net Core Area (sq.cm) 447.4028
Stacking factor (Ks) 0.97
CoreWeight (kg) 1388.15
TANK DETAILS & WEIGHTS
Core & Winding (kg) 2077.68
Oil (kg) 803
Tank & Fittings (kg) 1160
Insulation (kg) 80
Tank Sheet Size (mm) SIDE: 5 BOTTOM: 6 TOP: 6
Tank Size (mm) LENGTH: 1445 BREADTH: 560 HEIGHT: 1351
Colling Area & Cooling tubes (Mtrs)/(Nos254.25 Mtrs @ 38.1mm Dia
Elliptical Tube Radiators (Nos) 209 @ 878mm length
Pressed Steel Radiators (Nos) PSR: 230, 900mm 67 Fins
Oil Volume (Litres) 944
Total Transformer Weight (kg) 4097
PERFORMANCE
No-Load Loss (Watts) 1814
Load Loss (Watts) 10793
Current density-LV & HV (A/Sqmm) 2.58 , 2.49
Resistance (%) 0.86344
Reactance (%) 5.4
Impedence (%) 5.47
No Load Current at 100% (A) 0.725 ,2.832
%No Load Current at 100% (%) 12.09 ,47.203
Flux Density (Tesla) 1.57
Maximum Efficiency (%) 99.3
SPECIFICATIONS
Rated KVA (kva) 1250
Type of Cooling ONAN
Vector Group Delta/Star-Dyn-11
Test Voltage HV = 28/75KV LV = 3.0KV
Tap Range + 8%To - 8%@2% In Step
Tap Changer Steps (Nos) 8
Tapposition Tapping Step Turns Position StepTurns Tapping At Voltage Ratio Turns Ratio %Error
1 8 63 Finish 14 760 47.52 47.5 0.042
2 6 49 746 46.64 46.625 0.032
3 4 35 732 45.76 45.75 0.022
4 2 21 718 44.88 44.875 0.011
5 0 7 Normal 704 44 44 0
6 -2 -7 690 43.12 43.125 -0.012
7 -4 -21 676 42.24 42.25 -0.024
8 -6 -35 662 41.36 41.375 -0.036
9 -8 -49 648 40.48 40.5 -0.049