05.11.2003
1.0 Data
1.1 Lighting : 112.50KW *
1.2 Air-Conditioning : 867.00KW *
1.3 Power Load : 15.00KW *
1.4 Computer Load : 160.00KW *
1.5 Lift : 30.00KW *
1.6 Miscellaneous (Assumed)
1.6.1 Water Pump : 7.50KW
1.6.2 Jockey Pump : 11.00KW
1.6.3 Ventilation : 7.50KW
1.6.4 Cafeteria : 25.00KW
---------------
Total : 1235.5KW
Demand Factor : 0.9
Power Factor : 0.92 (0.8 for DG Selection)
Max. Demand : 1111.95KW = 1208.64KVA
Selected Rating of Transformer : 1 x 1250KVA
/conversion/tmp/scratch/369175730.doc
S.M.ENGINEERS & CONSULTANTS
Annexure - A
Assumptions
Lighting
150Sq.ft = 1 workstation
1 Workstation = 350VA