POINTTYPE

NOOF Typeof Supplyof Testingand


SYSTEM DETAILSOFTHEPOINT Installation
ITEMS DI DO AI AO SW Interface Equipment Commissioning

WasteSumpNo:1112 2
HighAlarm 2 VF BMS BMS BMS
VeryHighAlarm 2 VF BMS BMS BMS

WasteSumpNo:1112Pump 4
On/OffStatus 4 VF Plumbing Plumbing Plumbing/BMS
TripStatus 4 VF Plumbing Plumbing Plumbing/BMS

EjectorNo:1Tank 2
HighAlarm 2 VF BMS BMS BMS
VeryHighAlarm 2 VF BMS BMS BMS

EjectorNo:1Pump 1
On/OffStatus 1 VF Plumbing Plumbing Plumbing/BMS
TripStatus 1 VF Plumbing Plumbing Plumbing/BMS

EjectorNo:2Tank 4
HighAlarm 4 VF BMS BMS BMS
VeryHighAlarm 4 VF BMS BMS BMS

EjectorNo:2Pump 1
On/OffStatus 1 VF Plumbing Plumbing Plumbing/BMS
TripStatus 1 VF Plumbing Plumbing Plumbing/BMS

EjectorNo:2Tank 1
HighAlarm 1 VF BMS BMS BMS
VeryHighAlarm 1 VF BMS BMS BMS

SewerageHoldingTank 1
LowAlarm 1 VF BMS BMS BMS
HighAlarm 1 VF BMS BMS BMS

SewarageHoldingPump 2
On/OffStatus 2 VF Plumbing Plumbing Plumbing/BMS
TripStatus 2 VF Plumbing Plumbing Plumbing/BMS

FireServicesTransferPumps 5
On/OffStatus 5 VF Fire Fire Fire/BMS
Check and confirm the quantity of TripStatus 5 VF Fire Fire Fire/BMS
IncomingPowerSupplyOn/Off 5 VF Fire Fire Fire/BMS
pumps NumberofPonits 245 18 0 0 0
Spare(20%) 49 4 0 0 0
DDCB105 294 22 0 0 0

DieselStorageTank 3
VeryLowAlarm 3 VF BMS BMS BMS
LowAlarm 3 VF BMS BMS BMS
HighAlarm 3 VF BMS BMS BMS
VeryHighAlarm 3 VF BMS BMS BMS
SmokeDetectionStatus 3 VF BMS BMS BMS
FuelLeakAlarm 3 VF Fire Fire Fire/BMS

DieselStoragePump 6
On/OffStatus 6 VF Generator Generator Generator/BMS
TripStatus 6 VF Generator Generator Generator/BMS
BMS@ColomboCityCentre,CopyRightsNosters(Pvt)Ltd. Revision1 4of31
POINTTYPE

NOOF Typeof Supplyof Testingand


SYSTEM DETAILSOFTHEPOINT Installation
ITEMS DI DO AI AO SW Interface Equipment Commissioning

VeryHighAlarm 2 VF BMS BMS BMS

GeneratorSet 4
On/OffStatus 4 VF Generator Generator Generator/BMS
Trip/FaultAlarm 4 VF Generator Generator Generator/BMS
As per the contract spec., trend FaultAlarm 4 VF Generator Generator Generator/BMS
FuelLeakeAlarm 4 VF BMS BMS BMS
logging,run/off status etc. OverflowAlarm 4 VF BMS BMS BMS
HighLevelAlarm 4 VF BMS BMS BMS
Kwh 4 ModbusRTU Generator Generator Generator/BMS
Voltage(3Phase) 12 ModbusRTU Generator Generator Generator/BMS
Current(3Phase) 12 ModbusRTU Generator Generator Generator/BMS
VAR 4 ModbusRTU Generator Generator Generator/BMS
PowerFactor 4 ModbusRTU Generator Generator Generator/BMS
Frequency 4 ModbusRTU Generator Generator Generator/BMS
kW 4 ModbusRTU Generator Generator Generator/BMS

GeneralMVFans:FAF81,2,3 3
Check integration On/OffStatus 3 VF HVAC HVAC HVAC/BMS
Start/StopCommand 3 VF HVAC HVAC HVAC/BMS
requirements with TripAlarm 3 VF HVAC HVAC HVAC/BMS
AutoManualStatus 3 VF HVAC HVAC HVAC/BMS
FD system??
GeneralMVFans:EAF83,4,5,6 4
On/OffStatus 4 VF HVAC HVAC HVAC/BMS
Start/StopCommand 4 VF HVAC HVAC HVAC/BMS
TripAlarm 4 VF HVAC HVAC HVAC/BMS
AutoManualStatus 4 VF HVAC HVAC HVAC/BMS
NumberofPonits 61 7 0 0 44
Spare(20%) 12 1 0 0 0
DDCL903 73 8 0 0 44

KitchenMVFans:KEAF/9/1,2(Hotel) 2
On/OffStatus 2 VF HVAC HVAC HVAC/BMS
Start/StopCommand 2 VF HVAC HVAC HVAC/BMS
Check integration TripAlarm 2 VF HVAC HVAC HVAC/BMS
AutoManualStatus 2 VF HVAC HVAC HVAC/BMS
requirement with VSDControl 2 010VDC HVAC HVAC HVAC/BMS
FD system?? StaticPressure 2 420mA HVAC HVAC BMS

KitchenMVFans:KSAF/9/1,2(Hotel) 2
On/OffStatus 2 VF HVAC HVAC HVAC/BMS
Start/StopCommand 2 VF HVAC HVAC HVAC/BMS
TripAlarm 2 VF HVAC HVAC HVAC/BMS
AutoManualStatus 2 VF HVAC HVAC HVAC/BMS
VSDControl 2 010VDC HVAC HVAC HVAC/BMS
StaticPressure 2 420mA HVAC HVAC BMS
NumberofPonits 12 4 4 4 0
Spare(20%) 2 1 1 1 0
DDCL904 14 5 5 5 0

DigitalPowerMeters(compatiblewithBMS) 5
(Residential1,Hotel2,Retail2) Kwh 5 ModbusRTU Elec Elec Elec/BMS
kW 5 ModbusRTU Elec Elec Elec/BMS
Voltage(3Phase) 15 ModbusRTU Elec Elec Elec/BMS
Current(3Phase) 15 ModbusRTU Elec Elec Elec/BMS
BMS@ColomboCityCentre,CopyRightsNosters(Pvt)Ltd. Revision1 20of31
POINTTYPE

NOOF Typeof Supplyof Testingand


SYSTEM DETAILSOFTHEPOINT Installation
ITEMS DI DO AI AO SW Interface Equipment Commissioning

On/OffStatus 1 VF HVAC HVAC HVAC/BMS


Start/StopCommand 1 VF HVAC HVAC HVAC/BMS
TripAlarm 1 VF HVAC HVAC HVAC/BMS
AutoManualStatus 1 VF HVAC HVAC HVAC/BMS
VSDControl 1 010VDC HVAC HVAC HVAC/BMS
StaticPressure 1 420mA HVAC HVAC BMS

Elevators 12
CarPosition 12 ModbusRTU Elevator Elevator Elevator/BMS
DoorOpen/CloseStatus 12 ModbusRTU Elevator Elevator Elevator/BMS
Up/DownDirection 12 ModbusRTU Elevator Elevator Elevator/BMS
FireEmergencyIndication 12 ModbusRTU Elevator Elevator Elevator/BMS
PowerFailureIndication 12 ModbusRTU Elevator Elevator Elevator/BMS
Fault/Breakdown 12 ModbusRTU Elevator Elevator Elevator/BMS

RainSensor
RainStatus 2
NumberofPonits 9 3 3 3 72 ModbusRTU Elevator Elevator Elevator/BMS
Spare(20%) 2 1 1 1 0 ModbusRTU Elevator Elevator Elevator/BMS
DDCL5001 11 4 4 4 72

TotalPoints 2178 493 364 281 3504

Note.
1. Chiller plant ( CTs, pumps, chillers etc.) direct or indirect(via CMS) control steps
and sequences shall be indicated.
2. Residential area- Power meter, gas meter and water meters shall be
incorporated.
3. Check the possibility of integration of Escalators and high level interface with Lift
management system.
4. Rearrange BMS- DDC s accordingly.
5.Interface gateways of energy, gas and water meters shall be provided?
6.Each Fire distribution system static pressures?
7.Generator high level interface details must be incorporated?
8. BTU meters have missed out for retail and Hotel has missed out.