Anda di halaman 1dari 3

SELECTION AND SIZING OF CONTROL VALVES FOR

NATURAL GAS
Carol L. Nolte
The C.J. Nolte Co.

The purpose of this paper is to help the user understand can loosen fittings and damage other pieces of equip-
the information needed to properly select and size a con- ment.
trol valve for natural gas service. With so many different
manufactures of control valves we wont focus on one; Not knowing the minimum flow rate or maximum inlet
however the information listed is required by all manu- pressure can cause us to oversize a regulator. If you
factures in order to provide you with the best valve for oversize a flexible element regulator it may cause the
the application. Most manufactures will assist you in regulator to open unevenly and destroy the flexible ele-
sizing your application. ment. Over sizing globe, ball or plug valves causes
cycling which can cause the internals to wear out. High
The first step in sizing a control valve is to determine the cycling can also cause high vibration which again can
required Cv or capacity required through the control loosen fittings and damage other pieces of equipment.
valve at different operating conditions. It is not enough to
size for one condition, rather all the conditions must be Proper sizing doesnt sacrifice good control for future
considered. flow. Instead look at using valves with better rangeability
as well as considering using additional runs.
Once you have completed sizing a valve for the given
conditions you need to determine if that valve will oper- 3. WILL THE INLET PRESSURES AND/OR FLOWS
ate and control well over all of those conditions. Most FLUCTUATE?
valves have an optimum control range. For instance a Flexible element regulators are subject to droop. Droop
manufacture may only guarantee good control if the is caused by the pilot. If pressure and flow rates are
valves is operated between 10-85% of its capacity. Its constant than droop isnt an issue. Some pilots are less
important to know those limits. Keep in mind that that susceptible to droop than other pilots.
information may not be part of sizing tables or programs.
4. DOES THE DESIGN CALL FOR A MONITOR
Besides the basic information for sizing there are sever- REGULATOR, AND IF SO WILL IT BE PASSIVE OR
al factors to weigh when sizing and selecting a control WORKING?
valve. A control valve is part of a large system and can If the monitor regulator is passive or wide open then the
affect numerous aspects of that system. Lets look at the control valve should be sized as having a passive moni-
questions and information needed to properly size and tor regulator. Having a monitor regulator can reduce the
select a control valve and why. capacity of the regulator run depending on what type of
valve will be used as a monitor.
The questions to consider and why:
If a working monitor (two pressure cut with a monitor
1. WILL THE VALVE BE USED FOR PRESSURE OR override)will be used both valves need to be sized sepa-
FLOW CONTROL? rately as independent valves taking separate cuts. What
Some instrumentation is better suited for flow control you choose as an intermediate pressure is very impor-
verses pressure control. If youre doing flow control will tant here.
you have pressure overrides? Again this choice will effect
the instrumentation you will use. Normally flow control is Lets look at an example of sizing passive verses work-
done with a combination of a positioner and controller ing monitor regulators. In this example well size for a
whereas pressure control can often be accomplished flexible element regulator for pressure control with an
with a simpler pilot scheme. inlet pressure of 500 psi and an outlet of 60 psi. If we
look at a 2 regulator the capacity is 1537 MSCFH. If we
2. WHAT ARE THE MINIMUM AND MAXIMUM INLET add a passive monitor the capacity is 1224 MSCFH. If
AND OUTLET PRESSURES AS WELL AS THE MINI- we have a working monitor with 500 psi in 200 psi out on
MUM AND MAXIMUM FLOW RATES? the first cut and 200 in and 60 out on the second cut my
Not knowing the minimum inlet pressure or maximum capacity is 628 MSCFH, because the capacity of the first
flow rate can cause us to undersize a regulator. This can cut is 1537 MSCFH, but the second cut is only 628
cause you to have a valve that doesnt get enough gas MSCFH. If we change our intermediate pressure from
through the line. This can also cause high vibration which 200 psi to 300 psi our capacity increases to 927 MSCFH.

167
500 psi in to 300 psi out is 1489 MSCFH and 300 psi in Another way to reduce the noise at one location is to use
to 60 psi out is 927 psi. Different regulator brands and a working monitor installation and have the control
types will have different capacities, but the rule is the valves separated so you can not hear the noise generat-
same; the greater the pressure drop the greater the ed from one regulator while located at the other one. The
capacity. noise generated by each regulator will be less that if the
total pressure reduction was done on one regulator.
A working monitor installation may not respond fast
enough for a fast acting system, such as a power plant Also, keep in mind that using low noise trims can trans-
trip. fer the noise from the audible range to the ultrasonic
range. If the station has an ultrasonic meter that ultra-
5. IS PRESSURE DROP A FACTOR? sonic noise could severely effect the operation of the
In some areas of the system you may have a situation meter.
where the inlet to the control valve may fluctuate. If there
are going to be times when the inlet pressure is close to 9. HOW TIGHT DOES THE CONTROL NEED TO BE?
the desired outlet pressure, than you have to size for If you are feeding a large system you may not care if your
these cases. You may want to go with a single cut regu- control fluctuates a bit. If youre feeding a short system
lator and a wide open monitor valve that has a minimal control may be critical to the equipment downstream.
pressure drop such as a ball valve regulator. You can also Youll have to choose a valve that can meet your criteria.
choose to size the application such that the monitor is
working when the inlet pressure is sufficient, and passive 10. WHAT IS THE SIZE AND CONFIGURATION OF
when the differential is too small. THE INLET AND OUTLET PIPING?
Velocities of over 100 fps in above grade pipe can cause
6. IF THERE IS A MONITOR, HOW CLOSE IS IT TO ultrasonic and audible noise as well a pipe vibration.
THE PRIMARY REGULATOR? Velocities of over 200 fps in below grade pipe can create
Certain types of control valves are not quick responding noise that can be heard in above grade pipe, and inter-
and if placed to close to the down stream regulator, may nal erosion.
cycle.
Reducers and increases, elbows, tees, and flow restrict-
7. WILL THERE BE A RELIEF VALVE, AND IF SO, HOW ing lock valves will create turbulence, affecting capacity
CLOSE WILL IT BE SET TO THE CONTROL VALVES and velocity.
SET POINT?
Its often desirable in some systems to operate as close Youll need to be able to sense the pressure that is being
to the lines maximum operating pressure as possible but controlled. Your control is only as good as the signal you
if the regulator doesnt have tight control or doesnt lock give the controller. Sense lines connections should be
off well the relief will weep. placed in straight laminar pipe and be located 10 pipe
diameters downstream, and 5 pipe diameters upstream,
8. ARE THERE NOISE CONCERNS? of any turbulence creating piping configuration.
Most sizing programs can give you predicted noise
levels. Please keep in mind these predictions dont take 11. WILL THE STATION BE IN A VAULT?
into consideration surrounding structures; youll have to If the station is located in a vault youll need to consider
figure that in yourself. If noise is an issue you have many such issues as water infiltration, can the valve and instru-
options to choose from such as low noise trim, burying mentation needed to control it be submerged or will you
the valves and even adding diffusers and silencers. All of have to make other provisions? Youll also need to make
these options have pluses and minuses. sure that the valve and instrumentation can be serviced
in that size space.
Low noise trim may reduce capacity but increase range-
ability. 12. WILL THERE BE REMOTE CONTROL?
One thing youll need to consider is the range of the con-
Burying control valves will allow you to lessen the foot- trol device. For instance if you want to add a motor drive
print of the station, increase the velocity through the to a pilot on a control valve, if the spring in the pilot has
valve (many companies allow 100 fps velocity - approxi- a control range of 200-600 psi and it takes 15 turns of
mately 68 MPH through above grade valves and 200 fps the adjustment screw to achieve that range you would
through buried valves), but if you need to work on the need to make sure the motor can give you 15 turns.
valve you have to get to it.
You also need to consider what type of signal the remote
Diffusers and silencers can be sized for a particular noise control devise will output. If the signal requires power do
reduction and pressure drop, but they have to be used you have power available and how reliable is it?
with clean gas or in conjunction with a filter because they
can catch debris. Furthermore, how will the remote control devise affect
the devise its controlling? If its constantly tweaking a set
point can that valve and instrumentation take it?

168
13. IS BLEED GAS AN ISSUE?
If you are concerned about bleed gas for reasons such
as call outs or reducing fugitive emission reduction youll
need to select a valve that can be combined with instru-
mentation to eliminate or reduce bleed. Flexible element
style regulators can be operated with pilots that bleed
into the downstream system. Control valves such as
globe, plug and ball valves can be operated with instru-
mentation with no or low bleed and some equipment can
be bleed into the downstream piping.

14. WHAT IS YOUR DESIRED MODE OF FAILURE?


All valves can fail. If they do, do you want them to fail in
the full open, full closed or last position? For instance a
flexible element style regulator in most cases will fail
open. If youve chosen that style valve youll need to
insure that you have overpressure protection if neces-
sary.

15. WILL THERE BE TEMPERATURE


CONDITIONING?
Approximately, a 15 PSI (1 atmosphere) pressure drop
= 1 degree Fahrenheit temperature drop. Low tempera-
tures can cause ice build up around outlet piping, this
can cause cracks in foundations or heaves in the high-
way. It can also reduce the maximum operating pressure
of steel pipe. For instance, class 600 pipe below 20F is
no longer rated to 1480 psi. Also, the reduced gas tem-
perature may create water and hydrocarbon condensate.

Low and high temperatures can affect soft goods in


valves and instrumentation as well as high temperatures.
Make sure you know what the acceptable temperature
ranges for the media and atmospheric temperatures are
for the valve.

CONCLUSION
Selecting and sizing control valves is not as simple as
calculating capacity. Many factors have to be taken into
consideration. Over looking even one aspect of an instal-
lation can lead to costly mistakes. Since many situations
and experiences in our industry arent documented its
important to draw from the experience of people with
first hand field experience. Give as much information as
possible to vendors in order to help you make the right
choice in proper valve selection. Also, make sure to con-
sider your operating personnel and the type of equip-
ment they prefer.

169

Anda mungkin juga menyukai