Anda di halaman 1dari 5

Paper accepted for presentation at PPT 2001

2001 IEEE Porto Power Tech Conference


loth-13'h September, Porto, Portugal .

High-speed Fault Identification and Protection


for HVDC Line Using Wavelet Technique
L. Shang, G. Herold, Senior Member, IEEE, J. Jaeger, R. Krebs, A. Kumar

In AC power system, the amplitude of fault generated


Abstract-This paper describes a new high-speed HVDC line traveling waves changes with the voltage angles. There is
protection using wavelet technique, Based on the representation always a problem for the travelling wave protection when
of the tavelling waves through wavelet modulus maxima, the faults occur during voltage zerocrossing. However, for DC
protection criterions for HVDC line are proposed. Simulations power systems there is no such problems so that travelling
are carried out for testing the criterions. And the influences of
similar faults are discussed. The protection can detect the HVDC wave protection is preferably applied to HVDC systems.
line fault well and identify the HVDC line fault clearly from the By the travelling wave protection at the present, how to
similar transients, such as commutation failure and AC single detect a fault fast and reliable is still remaining big
phase fault. challenging. Fault generated travelling waves are varied with
time and frequency. Pure frequency domain based methods are
Index Terms-Edge detection, HVDC Fault, HVDC line, not suitable for such transient signals. The pure time domain
identification, protection, wavelet, wavelet modulus maxima. based methods are very easy influenced by noise. Therefore,
the travelling wave protection still has the difficulty in practice
I. INTRODUCTION
applications.
OR a safe operation of HVDC systems, ihe detection and
F fast clearance of faults in the HVDC lines are important.
The protection principle based on travelling wave theory gives
In HVDC systems, commutation failures in the converter
station and single phase short circuit faults at AC side are
similar to HVDC line faults. It is not easy to identify them by
the possibility of fastest protection. Particularly HVDC lines using pure frequency domain based methods or pure time
are mostly long distance transmission lines. They cannot be domain based methods. However, it is an important
sufficiently modeled with concentrated parameters as assumed requirement on HVDC line protections that different fault
in traditional protection systems. Therefore, long HVDC lines types should be identified and the correct decision should be
have to be taken as distributed elements in the principle and a made as fast as possible.
protection for long HVDC lines should be developed based on Wavelet transform, a rather new signal analysis method, is
travelling wave theory. particularly suitable for analyzing transient signals. It has the
According to travelling wave theory, voltage and current capability of time location as well as frequency location
travelling waves appear through the line when fault occurs. simultaneously during signal analysis. Moreover, it can adjust
The fault generated travelling waves contain sufficient fault analysis windows automatically according to frequency,
information that can be used to construct high-speed fault namely, there are shorter windows for higher frequency and
identification and line protection. The use of travelling wave vice visa. So it is naturally to use it for fault identification and
theory for fault detection was initially proposed in 1978 [l]. the travelling wave protection [3-51. However, wavelet based
Since then a lot of work on it has been done. An overview of fast identification and protection in HVDC systems is a rather
travelling wave protection in AC power systems can be found undeveloped area.
in [ 2 ] . In this paper, the behaviors of different faults in HVDC
power systems will be analyzed through wavelet transform and
L. Shang is at the Institute of Electrical Power Systems in the University of
the protection criterions based on wavelet technique will be
Erlangen, Cauerstr. 4, 91058 Erlangen, Germany (email: shang@eev.e- proposed. The criterions will be tested through the simulations
technik.uni-erlangen.de). under different conditions. The influences of similar faults
G. Herold is at the Institute of Electrical Power Systems in University of such as commutation failure and AC single phase fault will be
Erlangen, Cauerstr. 4, 91058 Erlangen, Germany (email: herold@eev.e-
technik.uni-erlangen.de). discussed. The simulations are carried out through
J. Jaeger is at the Power Transmission and Distribution Group in Siemens MATLAB@.The results will show that the wavelet technique
AG, P.O.Box 3220, 91050 Erlangen, Germany (email: leads to a new way to the fault detection and protection in
johann.jaeger@ptd.siemens.de)
R. Krebs is at the Power Transmission and Distribution Group in Siemens HVDC system.
AG, P.O.Box 3220, 91050 Erlangen, Germany (email:
rainer.krebs@ptd.siemens.de) 11. TRANSIENTS
IN HVDC SYSTEM
A. Kumar is at the Power Transmission and Distribution Group in Siemens
AG, P.O.Box 3220, 91050 Erlangen, Germany (email: Figure 1 shows the voltages and currents of DC line at the
anil.kumar@ptd.siemens.de)

0-7803-7 139-9/01/$10.00 0200 1 IEEE


rectifier terminal when (a) DC line short circuit, (b) frequency automatically. Such multiresolution property is
commutation failure at the inverter station, (c) signal phase particularly suitable for analyzing transient signals. Another
short circuit on the AC side of inverter station, and (d) normal important reason that wavelet transform is attractive for
operation condition as a reference case. engineers is there are fast calculation algorithms based on filter
bank.
DC Current (kA) DC Voltage (kV) There are different algorithm structures for wavelet
4 500 transform. Considering a better time location and a better
information keeping, we use the atrous structure but without
2 0
down-sampling block after high-pass filters. Fig. 2 shows our
0 -500 filter bank where Hoand H, are low-pass filters and high-pass
0.45 0.5 055 0.6 0.65 0.7 0.45 0.5 0.55 0.6 0.65 0.7 filters respectively. The output of high-pass filters are the
time (s) time (s) wavelet transform of the original signal, called as wavelet
(a) DC line short circuit coefficients.

4 600
400
2
200
0 0
-200
0.45 0.5 0.55 0.6 0.65 0.7 0.45 0.5 0.55 0.6 0.65 0.7
time (s) time (s)
(b) Commutation failure at the inverter station

4 600
400 Fig. 2. Wavelet filter bank-atrous algorithm
2
200
0 0
-200
B. Wavelet Modulus Maxima
0.45 0.5 0.55 0.6 0.65 0.7 0.45 0.5 0.55 0.6 0.65 0.7 The absolute local maximum values of wavelet coefficients
time (s) time (s)
are called wavelet modulus maxima. If the mother wavelet is
(c) AC signal phase short circuit at the inverter station
the first derivative of a smooth function, the edge of a signal
4 600 can be represented well by its wavelet modulus maxima [ 6 ] .
400 Under above condition, the wavelet modulus maxima occur at
2
200 an edge point, the polarity of the maxima shows the change
0 0 direction of the edge, and the amplitude represents the change
-200 intensity of the edge. It is proved that the wavelet modulus
0.45 0.5 0.55 0.6 0.65 0.7 0.45 0.5 0.55 0.6 0.65 0.7
maxima satisfy the following relation.
time (s) time (s)
(d) Normal operation condition

Fig. 1. Transients in HVDC system


Where, Wmmx(t)is the wavelet modulus maxima of signal
x(t), A is a constant, s is scale and a is Lipschitz exponent.
From Fig. 1 we can see that the different type of faults lead This relation means that the wavelet modulus maxima of an
to similar transient processes. It is difficult to identify the
edge (a = 0 or a > 0) keep unchanged or increase in value
faults and to make protection decision fast within 3-5ms by
while the wavelet modulus maxima caused by white noise (a <
using traditional methods. It is even more difficult if there is
0 ) decrease in value when scale increases. Additionally, the
noise.
number of wavelet modulus maxima caused by white noise
Wavelet transform give us a new possibility for the fast fault
decrease sharply when scale increase. This make an edge
detection and for the development of new protection criterions.
detector with strong denoising function possible [7]. Fig. 3
shows the effect of edge detection based on wavelet modulus
111. PROTECTION CRITERIONS BASED ON WAVELET TECHNIQUE
maxima when signal with 15% noise. It can be see that the
A . Wavelet Transform edge detector works well under heavy noisy condition.
Wavelet transform transfers a time varying signal into a
time-scale domain and thus can represent the original signal
with time as well as frequency information. Each scale in
wavelet transform corresponding to a certain frequency band
and the time window widths are changed with scale or
Travelling wave with 15% noise RESULTS
IV. SIMULATION

A. Simulation Model
Fig. 4 shows the simulation model in which a 1000 MW
-?.5 3 3.5 4 4.5 5 (500 kV, 2kA) DC line is used to transmit power from a 500
Time (ms) kV, 5000 MVA, 60 Hz network to a 345 kV, 10 000 MVA, 50
Output of edge detector (wavelet modulus maxima) Hz network. The DC line is 300 km long and the speed of the
10, I
travelling wave is 2961 12 Ms. It is the standard model of 12-
pulse HVDC system under the MALLAF3' environment.
-101 I
2.5 3 3.5 4 4.5 5
Time (ms)

e
Fig. 3. Effect of edge detector based on wavelet modulus maxima (WMM)
U I-
Rectifier Inverter
C. Protection Criterions
a
Following a fault, travelling waves propagate along the line
and are reflected at discontinues point of surge impedance. Fig. 4. Simulation model
This leads to an abrupt change on the voltages and currents.
Such sudden changes in voltages and currents are just edges in The study cases are: (a) DC line short circuit fault, (b)
signal processing. Based on above wavelet theory, the sudden commutation failure, (c) AC signal phase short circuit at
change can be detected with the help of wavelet modulus inverter station. Each case is sampled at 80 kHz and 100
maxima. samples are taken for wavelet transform. Mallat wavelet is
The one terminal protection scheme is used in this paper so used as mother wavelet. Reverse traveling waves are used as
that there is no requirement to the communication and the input signals of the edge detector.
synchronized timer as in the case of two terminal protection B. Response to DC Line Fault
scheme. We use the reverse voltage travelling wave as the To investigate the discrimination of the proposed protection
input signal for the wavelet transform. The criterions for fault criterion to DC line faults, the faults at different locations and
detection and fault location are based on the corresponding with different fault resistances are implemented in the
wavelet modulus maxima. simulation.
I ) Fault detection Fig. 5 shows the response to a DC line fault: at 100 km from
Two criterions for fault detection are proposed in this paper. terminal M and with zero fault resistance. The first modulus
The first criterion is that the amplitude of the first wavelet maxima is 1091, larger than the setting (100) and the
modulus maxima, denoted as I w,,, u r I , should be larger corresponding polarity is negative so that DC line fault is
than the setting value K . ~ ~ r r i n p. The setting can be take as 100 detected. The time delay between the first two modulus
for 500 kV HVDC lines. maxima with different polarities (here corresponding to the
first and the second modulus maxima) is 0.000675 s, thus the
fault is located 99.93 km away from terminal M. The fault is
The second criterion is the polarity of the first wavelet detected and located correctly.
modulus maxima. It should be negative for the HVDC line
operating with positive voltage. Reverse voltage travelling wave
- 5001 1

Polarity = negative (3)


2) Fault Location
The Fault location is calculated according to the equation 4.
- I YYY
The key is the measurement of the timer delay At. Considering 0.5 0.5005 0.501 0.5015 0.502 0 5025
Time (s)
that the reflection from the fault point (reflection factor is Output of edge detector (Wavelet Mudulus maxia)
negative) is different with the reflection from the line terminal 2000, 1

(reflection factor is positive), we measure the time delay E O A A


between the first two modulus maxima with different 5
I/ V
polarities, namely the first is negative, the next positive one
should be taken.
L=-vxAt (4)
2
Where L is fault distance in km from the measuring point,
A t is the time delay in s and v is travelling wave speed in Fig 5. Response to DC line fault: lOOkm from terminal M
W S . WMM: wavelet modulus maxima
Fig. 6 shows the response to another DC line fault: at 200 D. Response to Commutation Failure
km from terminal M and with 60 ohm fault resistance. The Fig. 8 shows the response to the commutation failure at the
first modulus maxima is 723, larger than the setting (100) and inverter station. All modulus maxim are less than 10, much
the corresponding polarity is negative so that the DC line fault smaller than the setting (100). The polarities of modulus
is detected. In this case, the reflected travelling wave fiom the maxima are same after disturbance arriving at the terminal M.
terminal N arrives at the terminal M earlier than the reflection It can be seen that the protection can detect the commutation
from fault location. With the help of the polarity, it is easy to failure and tell the difference between DC line fault and
identify them. The time delay between the first two modulus commutation failure.
maxima with different polarities (here corresponding to the
first and the third modulus maxima) is 0.0013 s, thus the fault Reverse voltage travelling wave
801
is located 199.87 km away fiom terminal M. The fault is h

detected and located correctly.

500
Reverse voltage travelling wave
20'
0.5 0.5005 0.501 0.5015 0.502
I
0.5025
Time (s)
Output of edge detector (Wavelet Mudulus maxia)
P 1 I
-500
0.5 0.5005 0.501 0.5015 0.502 0.5025
Time (s)
Output of edge detector(Wavelet Mudulus maxia) -10 ' I

-
0.5 0.5005 0.501 0.5015 0.502 0.5025
z Time (s)
s o A
-10ogj5
V V

I Fig 8. Response to commutation failureat the inverter station


0.5005 0.501 0.5015 0.$2 0.5025 WMM: wavelet modulus maxima
Time (s)
i f
-123 +59 1
E. Response to AC Single Phase Fault
At = 0.0013s e L,, = 199.87km Fig. 9 shows the response to the AC single phase fault at the
inverter station. Similar as the commutation failure, all
Fig 6. Response to DC line fault: 2 0 0 h from terminal M modulus maxima in AC fault are less than 10, much smaller
WMM: wavelet modulus maxima
than the setting (100). The polarities of modulus maxima are
same after the disturbance arriving at the terminal M, so that
It can be seen that the proposed criterions lead to a clear the protection can also detect the AC fault and tell the
identification and decision for DC line fault.

5rz%
difference between AC fault and DC line fault.
C. Response to Normal Operation Condition Reverse voltage travelling wave
Fig. 7 shows the response to the normal operation condition
at the terminal M. All modulus maxim are less than 10, much
smaller the setting (100). The polarities of modulus maxima
are positive and negative in turns.
3 -500.5 0.5005 0.501 0.5015 0.502 0.5025

Time (s)
Reverse voltage travelling wave

i3 E O _ - I
$ i
60

40
IO,
Output of edge detector (Wavelet Mudulus maxia)
I

-101
200.5 0.5005 0.501 0.5015 0.502 0.5025 0.5 0.5005 0.501 0.5015 0.502 0.5025
Time (s) Time (s)
Output of edge detector (Wavelet Mudulus maxia)
:4AC single phase fault

Fig 9. Response to AC single phase fault


WMM: wavelet modulus maxima
-101 I
0.5 0.5005 0.bOl 0.5015 0.502 0.5025
j Time(s)
V. CONCLUSION
Commutation failure
For high-speed HVDC line protection based on travelling
Fig 7. Response to normal operation condition wave, the methods regarding transient signal analysis are
WMM: wavelet modulus maxima necessary; the edge detection and identification fiom the
similar transients are decisive. The wavelet transform Systems Group. Since 1993 he is Professor and Director of the Institute of
Electrical Power Systems at the Friedrich-Alexander-University of Erlangen-
technique provides new possibility for this. The proposed Nuernberg. He is a senior member of the IEEE.
protection criterions based on wavelet modulus maxima can
make a definite HVDC line fault detection and the .-- - Johann Jager was born in Erlangen, Germany,
-:

identification fiom the similar faults such as commutation on January 19, 1964. He studied Electrical
failure and AC single phase fault. The simulation results has Engineering at the Friedrich-Alexander
University Erlangen-Nurnberg. He received his
shown that the application of wavelet technique leads to a Dip1.-Ing. degree in 1990. He joined the
faster, easier and more reliable solution for the fault detection Institute for Electric Power Systems in 1991
and protection of HVDC lines. and received his Dr.-Ing. degree in 1996.
Since 1996 he works in the Siemens AG in
Erlangen, Power Transmission and Distribution
VI. REFERENCES Group - System Planning Department. Now he
H. W. Dommel and J. M. Michels, High speed relaying using travelling works at protection design and protection
[l]
wave transient analysis, in 1978 IEEE PES Winter Power Meeting, coordination in power systems as a senior
78CH1295-5 PWR, 1-7. consultant.
He is member of VDE and its associated section ETG..
[2] A. T. Johns, and S. K. Salman, Digital protection f o r power systems,
IEE Power Series 15, Peter Peregrinus Ltd.E., 1995.
Rainer Krebs was born in Pfedelbach,
[31 L. Shang, G. Herold, and J. Jaeger, A new approach to high-speed Germany on January 19, 1958. He received his
protection for transmission line based on transient signal analysis using
Dip1.-Ing. degree in Electrical Engineering and
wavelets, in Proc. 7th International Conference on Developments in
Power Systems in 1982 and the Dr.-Ing. degree
Power System Protecfion,pp. 173-176, April 2001, Amsterdam.
in 1990 from the Friedrich-Alexander
[41 F.H. Magnago, and A. Abur, Fault location using wavelets, IEEE Universityjn Erlangen.
Trans. on Power Deliveiy, vol. 13. pp. 1475-1480, Apr. 1998.
He joined the Institut Gr Elektrische
t51 X. Zh. Dong, Y Zh. Ge, and B. Y. Xu,, Fault position relay based on Energieversorgung at the same University in
current travelling waves and wavelets, in IEEE PES 2000 Winter
1983, working on calculation and
Meeting, pp. 23-27, Jan. 2000, Singapore.
S. Mallat, A Wavelet Tour of Signal Processing, Academic Press, 1998, measurement of power-system disturbances
pp. 165-198. and unbalances, using space-phasor theory. In
L. Shang, G. Herold, and J. Jaeger, A new approach to high-speed 1990 he joined the Siemens AG in Erlangen as
protection for transmission line using wavelet technique, in Proc. 12h a member of the System Planning Department.
He started his work in the fields of power-system planning, power-system
International Con$ PSP 2000, pp. 85-90, Sept. 2000, Bled.
relaying, system and protection real-time simulation and fault analysis. Since
1998 he is director of the department Protection Systems and PC-Tools.
VII. BIOGRAPHIES He is member of VDE and its associated section ETG.

Shang, Li was born in Shandong Province, Ani1 Kumar (M64) received his B. Tech, ME
China, on October IO, 1961. She received her and Ph. D from the Indian Institute of Science
Bachelor degree in 1982, Master degree in 1991 Bangalore in 1962, 1964 and 1969
from the Department of Electrical Engineering respectively. From 1970 to 1972, he was a post
in China Agriculture University, Beijing, doctoral fellow of the Alexander von
China. She worked as a lecturer during 1982- Humboldt Foundaton at the technical
1993 and is an associate professor since 1994 university of Braunschweig, Germany. From
in China Agriculture University where her main 1973 to 1995 he was with the Protection
research fields are the analysis and automation Department of Siemens, Germany. Since 1995
of MV and LV distribution power system. Since he has been with the high voltage department
1998, she is working at her doctor dissertation as a senior project manager for HV AC and
in the Institute of Electrical Power Systems in DC innovations. He has been involved in the
the University of Erlangeu, Germany. Now her - .,.
desim and develoDment of dieital orotection
research area is the applicittions of wavelet transform in analysis of power systems from the beginning. In his 26 years service with Siemens, he has also
transients, protection and pc)wer quality. carried out design and sales work for EHV line protection and customer
oriented design tests of protection schemes on the AC/DC Simulator.
From 1980 to 1990; Dr. Kumar was a member of the CIGRE Working
Gerhard Herold was born in Beesedau, Groups 34.01 and 34.02 dealing with digital protection and control of power
Germany, on July 20, 1947. He received his systems. He is a member of the IEEE and PES.
Dipl.-Ing. degree in 1971 from the Technische
Hochschule Ilmenau, Department of Electrical
Power Apparatus and Systems. From 1971 to
1984 he joined TH Ilmenau as a scientific
assistant, where he received his Dr.-Ing degree
in 1976 and his Dr.sc.techn. degree in 1982.
From 1986 to 1990 he was supervisor of the
department on CAD-technique and power
system planning in the Starkstrom-Anlagenbau
GmbH Leipzig-Halle. In 1991 he joined the
Siemens AG as a head of a department on
Engineering and Softwaredelrelopment in the Siemens Industrial and Building

Anda mungkin juga menyukai