i START HERE - CAN YOU USE THIS CHECKLIST?

You MUST assess your operation before using this checklist. IF ONLY Non-Combustible particulate Solids are at this location, or specific area, this checklist
CANNOT be used for COMBUSTIBLE WOOD DUST at the location or specific area. Answer the questions below to determine your status.

Question DETERMINATION, REQUIREMENT, STATUS Y


Number OBSERVATION, MEASUREMENT CRITICAL NOTE(S): for YES, N WHAT NEXT?
for NO

1 Wood Dust IS COMBUSTIBLE. If


Does this location have ONLY Non-
A N
you generate Wood Dust, and you
MUST answer Question A as IF NO - CONTINUE to Question B
Combustible particulate Solids? "NO". You must also answer
Question B.
NFPA 91

1 Doing anything with wood


ANSWER ALL the questions below first to
B determine IF your location can use this Combustible qualifies
N
as a "process". DON'T
Dust Checklist. The overall answer will appear for
enter this value - It appears IF NO - STOP HERE - You dont qualify for this checklist
automatically based on question
you in the STATUS column. responses.
NFPA 664

ANSWER ALL - Does this location: 1 Overall response is: Y


B.1 Process wood? N 0
B.2 Manufacture wood products? n 0
B.3 Use wood or cellulosic fiber as a substitute for or additive to wood fiber? N 0
B.4 Create wood chips, particles, or dusts? N 0
B.5 Make wood flour? N 0
B.6 Do industrial woodworking? N 0
B.7 Make furniture? N 0
B.8 Make plywood? N 0
B.9 Make composite board? N 0
B.10 A lumber mill? Y 1
Do production woodworking and carpentry that is incidental to the
B.11 operation that would not otherwise fall under NFPA 664? N 0
1 Doing anything with wood
ANSWER ALL the questions below to determine IF
C Y
your location can use this Combustible Dust qualifies as a "process". DON'T
Checklist. The overall answer will appear for you in
enter this value - It appears Check the MY STATUS box below
automatically based on question
the STATUS column. responses.
NFPA 664

ANSWER ALL - Does ANY condition apply at your location? 1 Overall response is: Y
This location conducts woodworking operations that occupy areas which
C.1 equal or exceed 5000 square feet (Ft 2) which is equivalent to 465 square
meters (M2). (Length X Width = 5,000 f2 OR 465 M2)
Y 1 You are Subject to NFPA 664-Proceed to Question C.2

This location operates production equipment requiring a total dust collection IF you have no dust collection equipment OR
C.2 air flow rate of 1500 cubic feet per minute (Ft3/Min) which is equal to 2549
cubic meters per hour (M3/Hr).
N 0 have reduced design flow, you may STILL be
subject to NFPA 664 & OSHA requirements

i 0
MY LOCATION IS NOT COVERED BY NFPA
MY 664 (Regarding Wood Dust). IT MAY BE MY LOCATION IS COVERED BY NFPA 664
COVERED BY THE COMBUSTIBLE DUST AND THE COMBUSTIBLE DUST
MY
STATUS COMPLIANCE DIRECTIVE AS SOME OTHER
TYPE OF DUST. I CANNOT USE THIS OR COMPLIANCE DIRECTIVE. I CAN USE THIS
CHECKLIST. I will complete the sections X STATUS
CHECKLIST FOR WOOD DUST. I will need
to Check NFPA 91 and 654 for applicable
requirements.
below to identify my percent readiness
for minimizing Combustible Wood Dust.

i START HERE - This is The BEGINNING of the Initial Self-Assessment CHECKLIST

RESULTS SECTION - 1
Initial: 50% 10
CAUTION! The following NFPA Codes are extensive and cannot be adequately summarized within this checklist. As an
alternative, common electrical problems that can generate or become ignition sources will be summarized. Their code compliant
solution MUST be retrieved and MUST meet the applicable code requirements in the applicable NFPA code.

NFPA 77 - RECOMMENDED PRACTICE ON STATIC ELECTRICITY


NFPA 79 - ELECTRICAL STANDARD FOR INDUSTRIAL MACHINERY
F1.1 F1.1 F1.3 F1.4 F1.5 F1.6 F1.7 F1.8 F1.9 F1.10
10 500%
100% 100% 100% 100% 100% 100% 100% 100% 100% 100% FOLLOW-UP
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 SCORES
50%
Follow-Up: 100% 10 100% 0% 0% 0% 100% 100% 100% 100% 0% 0%
100%
Question
Number FOCUS on STATIC ELECTRICITY and MACHINERY FIX WHAT? When? Who?
10 1000%

i 1 ANY UNGROUNDED, CONDUCTIVE objects? When? Who?

100% NO FIX NEEDED N 100%


1.1 Where?
N 100% NO FIX NEEDED N 100%

NFPA 77

1 ANY evidence of STATIC Electricity (e-) accumulation? When? Who?

1.2 Where?
Y 0% Find static e
sources & Minimize N 100%

NFPA 77

1 ANY suspended (wood) dust in air? When? Who?


Control
1.3 Where?
Y 0% accomulation and
apply N 100%
Housekeeping
NFPA 77

1 ALL conductive bag house parts always grounded? When? Who?

N
Check and fix ground
1.4 Where?
0% on conductive
baghouses
Y 100%

NFPA 77

1 When? Who?
NON-NFPA - Has a qualified electrician been consulted for
1.5 ways to reduce or prevent static e-discharge(s)? Y 100% NO FIX NEEDED Y 100%

NFPA 77

1 Is the design and e- power supply correct for all machinery? When? Who?

1.6 Where?
Y 100% NO FIX NEEDED Y 100%

i NFPA 79

1 Are ground terminals & enclosed local disconnects present for machinery? When? Who?
List ONLY if missing:
1.7 Y 100% NO FIX NEEDED Y 100%

NFPA 79

1 Are LIVE electrical parts at or above 50 Volts guarded against contact When? Who?
(including by insulation)?
1.8 List ONLY if missing: Y 100% NO FIX NEEDED Y 100%

NFPA 79

1 Are over current protection devices in place? When? Who?


List ONLY if missing:
1.9 N 0% Install overcurrent
devices as needed Y 100%

NFPA 79

1 Is ALL equipment electrically grounded? When? Who?


Test & Ground all
N 0% electrical
equipment as Y 100%
Test & Ground all
List ONLY if missing:
1.10 N 0% electrical
equipment as Y 100%
needed
NFPA 79

RESULTS SECTION - 2
Initial: 63% 8 CAUTION! NFPA 70 & 70E Codes are extensive and cannot be adequately summarized within this checklist. Equivalently, look for common electrical problems that are ignition
sources. Code compliant solution MUST be retrieved and meet the applicable NFPA requirements.

NFPA 70 - NATIONAL ELECTRIC CODE


NFPA 70E - STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE
NFPA 499 - RECOMMENDED PRACTICE FOR THE CLASSIFICATION OF COMBUSTIBLE DUSTS AND OF HAZARDOUS (CLASSIFIED) LOCATIONS FOR ELECTRICAL
INSTALLATIONS IN CHEMICAL PROCESS AREAS

F2.1 F2.2 F2.3 F2.4 F2.5 F2.6 F2.7 F2.8 F2.9


8 500%
0% 0% 0% 0% 0% 100% 100% 100% 0% Follow-Up
2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 Scores
63%
Follow-Up: 38% 8 0% 100% 100% 100% 0% 0% 0% 200% 0%
38%
Question
Number FOCUS on GENERAL ELECTRICAL HAZARDS - Conduit, Electrical Panels, etc. FIX WHAT? When? Who?
8 300%

1 ANY energized damaged electrical conduits? When? Who?


List ONLY if missing:
2.1 y 0% Repair or Replace Y 0%

NFPA 70

1 ANY exposed breakers within a breaker panel? When? Who?


List ONLY if missing:
2.2 N 100% NO FIX NEEDED Y 0%

NFPA 70

1 ANY SUBSTANDARD electrical repairs? When? Who?


List ONLY if missing:
2.3 N 100% NO FIX NEEDED Y 0%

NFPA 70

1 ANY exposed wiring that could short, or cause a spark? When? Who?
List ONLY if missing:
2.4 N 100% NO FIX NEEDED Y 0%

NFPA 70
ANY electrical conditions that can cause material ignition? (consult
1 When? Who?
electrician)
Y 0% Repair and Upgrade
to Code Y 0%
List ONLY if missing:
2.5 Y 0% Repair and Upgrade
to Code Y 0%

NFPA 70

1 When? Who?
At hazardous locations (in hazardous Atmospheres) are there ARE equipment breaks
that void effectiveness? (IF NO hazardous locations, answer NO) SEE OSHA 1910.307
2.6 Y 0% Repair-Upgrade-
Check against Code N 100%
List ONLY if effectiveness voided:
NFPA 70E

1 When? Who?
Is HOT WORK controlled by a permit system? (Both NFPA & OSHA 1910.252 apply) Implement written

2.7 N
program-Formulate
0% procedures-Acquire
equipment & Train
Y 100%
employees
NFPA 70E

1 When? Who?
Answer the Questions below FIRST to DETERMINE your location's
i
2.8 Y
status under NFPA 499. It ONLY APPLIES IF the area under review is Don't 499 Applies-REFER to
ALSO A CHEMICAL PROCESS AREA. Is your location subject to NFPA
ENTER this
value
200% NFPA for Specific
Requirements
N 100%

499?
NFPA 499

ANSWER ALL - Do ANY of the following exist? 1 Overall response is: 200% When? Who? 1 100%

2.8.1
is there a DUST that is produced, processed, handled, or likely to be at this area
that's under review? N 0% 499 Does Not Apply N 0%

1
Y
499 May Apply if area is

2.8.2
Can or is the dust released into the atmosphere or accumulated on surfaces? 100% also a Chemical Process
Area
N 0%

1
Y
499 May Apply if area is

2.8.3
Are there sources of ignition, such as electrical systems or equipment? 100% also a Chemical Process
Area
N 0%

1 Is this area ALSO A CHEMICAL PROCESS AREA? (IF YES, Consult NFPA 499 for code
2.8.4
specifics. Also answer Question 2.9. (NOTE: Chemical Process Areas are not
common, and go significantly beyond the scope of this checklist)
Y 0% 499 Applies-CHECK
Specific Requirements N 100%

2.9 IF NFPA 499 APPLIES, is this location meeting ALL REQUIRMENTS? N 0% 499 Does Not Apply N 0%

NFPA 499

i
DETERMINATION - EXIT CHECKLIST OR FIRE TRIANGLE CONDITIONS?
DETERMINATION - EXIT CHECKLIST OR FIRE TRIANGLE CONDITIONS?
IF sufficient conditions DO NOT EXIST, FIRE, DEFLAGRATION, or EXPLOSION CANNOT result. However, Oxygen, Heat, and Fuel results in a FIRE
HAZARD.

X
Cumulative "Percent
Prepared" & Hazard
Condition Indicated 56%
by "X" is:

X
FOLLOW-UP
Cumulative "Percent
Prepared" & Hazard 69%
Condition Indicated
by "X" is:

RESULTS SECTION - 3
Initial: 21% 11
NFPA 68 - EXPLOSION PROTECTIONS BY DEFLAGRATION VENTING

NFPA 69 - STANDARD ON EXPLOSION PREVENTION SYSTEMS

NFPA 654 - STANDARDS FOR THE PREVENTION OF FIRE AND DUST EXPLOSIONS FROM THE MANUFACTURING, PROCESSING, AND HANDLING
OF COMBUSTIBLE PARTICULATE SOLIDS

NFPA 664 - STANDARD FOR THE PREVENTION OF FIRES AND EXPLOSIONS IN WOOD PROCESSING AND WOODWORKING FACILITIES
Follow-Up: 50% 11
i F3.1 F3.2 F3.3 F3.4 F3.5 F3.6 F3.7 F3.8 F3.9 F3.10 F3.11
11% 63% 60% 60% 20% 29% 70% 80% 100% 54% Follow-Up
3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 3.10 3.11 Scores
33% 13% 80% 60% 0% 6% 9% 0% 33% 0%
1 When? Who?
The following questions apply to NFPA 68, 69, and 664. IF you produce WOOD DUST,
3.1 Answer the questions below FIRST to determine if NFPA
68 specifics apply, then continue through the questions.
AND you have a bag house or
ANY OTHER type of enclosure, 33% Percentage for
this Question 11%
You MUST answer YES.
NFPA 68

ANSWER ALL - Do ANY of the following exist? 9 Overall response is: 300% When? Who? 9 100%
ANSWER ALL - Do ANY of the following exist? 9 Overall response is: 300% When? Who? 9 100%

1
N
Are there any ENCLOSURES where combustible wood dust is present? (If NO, NFPA 68 Does not apply.
NFPA 68 does not apply. Skip to NFPA 69, AT QUESTION #5) 100% OTHER NPFA Codes may N 100%
3.1.1 apply

1
N
Are there ANY IGNITION SOURCES that can possibly reach the inside of a NFPA 68 Does not apply.
process enclosure? 100% OTHER NPFA Codes may Y 0%
3.1.2 apply

3.1.3
Prior to today, was there a deflagration or explosion event involving
combustible wood dust? N 100% VERIFY requirements
met Y 0%

1
N
Implement controls
Were engineering controls IN PLACE during the event? 0% specified under NFPA Y 0%
3.1.4 664 and other codes

1
N
Determine reason for
Did the engineering controls activate during the event? 0% non-activation and N 0%
3.1.5 correct it

1 Implement periodic

3.1.6
Are the engineering controls on a periodic maintenance and testing
schedule? N 0% maintenance and testing
schedule &
doucmentation
N 0%

1 IF Engineering Controls ARE NOT CURRENTLY IN PLACE, was NFPA 68


3.1.7
reviewed in detail by representatives of your company? (If already in place,
answer Y for YES)
N 0% Review NFPA 68 in detail
as required. N 0%

3.1.8
Were enclosures evaluated for needed engineering controls per NFPA 68? n 0% Evaluate enclosures per
NFPA N 0%

1 Determine an

3.1.9
IF Engineering Controls ARE NOT CURRENTLY IN PLACE, has an installation
date for them been scheduled? N 0% installation date after
review with AHJ and
others
N 0%

1 When? Who?
Don't Enter this value -
ANSWER the questions below to determine your location's
3.2 status. NFPA 69 ONLY APPLIES IF you have listed conditions.
it automatically appears
based on question
responses
13% Percentage for
this Question 63%

NFPA 69

ANSWER ALL - Do ANY of the following exist? 8 100% When? Who? 8 500%
1
Does a DEFLAGRATION hazard exist? (IF you produce WOOD DUST, and it can
3.2.1
become airborne, you MUST answer YES. IF YES, continue. IF NO, STOP HERE!
NFPA 69 DOES NOT APPLY. Skip to Question 3.3)
Y 0% NFPA 69 Applies Y 100%

1
Has the design basis of the deflagration scenario been identified and
N
MUST identify &
documented? 0% document design basis N 0%
3.2.2 of deflagration scenario

3.2.3
Are there ENGINEERING CONTROLS present? N 0% ALL controls MUST be
either or both-specify N 0%

3.2.4
Were the controls acceptance tested? N 0% Controls MUST be
acceptance tested Y 100%

1
Are the controls on a periodic inspection & maintenance schedule
N
Controls MUST be
(Additional requirement under NFPA 664) 0% periodically inspected Y 100%
3.2.5 and maintained

1
Is location aware of required housekeeping under NFPA 654 or 664?
N
Housekeeping under
(detailed elsewhere in this checklist) 0% NFPA 654 OR 664 MUST Y 100%
3.2.6 be applied

3.2.7
Has the engineering control system been checked against NFPA
requirements for Operation, Maintenance, and Safety requirements? Y 100% Maintain as required N 0%

N
Automatic system
Does the system allow for automatic shutdown? 0% shutdown MUST be Y 100%
3.2.8 required

1 When? Who?
Don't Enter this value -
3.3 Do the ENGINEERING CONTROLS use ANY of the following
detection system(s) or methods?
it automatically appears
based on question
responses
80% Percentage for
this Question 60%
Don't Enter this value -
3.3 Do the ENGINEERING CONTROLS use ANY of the following
detection system(s) or methods?
it automatically appears
based on question
responses
80% Percentage for
this Question 60%

NFPA 69

ANSWER ALL - Do ANY of the following exist? 5 Overall response is: 400% When? Who? 5 300%

1
Are DEFLAGRATION SUPPRESSION AND EXPLOSION VENTING
Y
Component indicated as
components also used? 100% present-verify its Y 100%
3.3.1 appropriate

1
Y
Component indicated as
Is there a DEFLAGRATION PASSIVE ISOLATION SYSTEM in place? 100% present-verify its Y 100%
3.3.2 appropriate

1
Y
Component indicated as
Is there a DEFLAGRATION PRESSURE CONTAINMENT SYSTEM in place? 100% present-verify its Y 100%
3.3.3 appropriate

1
Y
Component indicated as
Is there a DEFLAGRATION PRESSURE CONTAINMENT SYSTEM in place? 100% present-verify its N 0%
3.3.4 appropriate

3.3.5
Does the CONTROL SYSTEM use Oxidant Reduction Concentration to
prevent combustion? (see comment notes) N 0% Check NFPA 69 to verify
if component is needed N 0%

1 NFPA 664 Chapter 4 - General Requirements When? Who?


Don't Enter this value -
3.4 These questions assess the design of the fire and deflagration
safety provisions at the location. Consult NFPA 664 for definitions
it automatically appears
based on question
responses
60% Percentage for
this Question 60%

NFPA 664 and specific details.

ANSWER ALL - Do ANY of the following exist? 10 Overall response is: 600% When? Who? 10 600%

1 PROCESS ANALYSIS - is the design, physical and chemical properties, and


3.4.1
documented results, maintained for the life of the process & and on
location?
N 0% Implement PROCESS
ANALYSIS Y 100%

1 MANAGEMENT of CHANGE (MOC) - Are there written procedures to


3.4.2
manage the change of process materials, technology, equipment,
procedures, and facilities?
Y 100% Requirement Met Y 100%

1 Does (MOC) Include - Technical basis of Changes, Safety & Health Implications,
3.4.3
Temporary-Permanent, Procedure Modifications, Employee Training, Authorization
requirements for proposed change?
n 0% UPGRADE to meet all
requirements Y 100%

1
DESIGNER & INSTALLER QUALIFICATIONS - Are systems designed and
installed under the supervision of a knowledgeable, Qualified Engineer? Y 100% Requirement Met Y 100%
3.4.4
DESIGNER & INSTALLER QUALIFICATIONS - Are systems designed and
installed under the supervision of a knowledgeable, Qualified Engineer? Y 100% Requirement Met Y 100%

3.4.5
LIFE SAFETY - Is the design, construction, & equipment maintained to
prevent building occupants from Fire / Deflagration / Explosion? Y 100% Requirement Met Y 100%

3.4.6
LIFE SAFETY - Is the structure located, designed, constructed, & maintained
to prevent propagation of Fire / Deflagration? Y 100% Requirement Met Y 100%

1 UPGRADE to meet all

3.4.7
LIFE SAFETY - Is structure designed, constructed, & equipped to maintain
Structural Integrity in spite of the effects of Fire / Deflagration? N 0% LIFE SAFETY
requirements-SEE NFPA
101
N 0%

3.4.8
MITIGATION of FIRE SPREAD & EXPLOSIONS - are there sufficient safeguards
to prevent failure of adjacent building compartments? Y 100% Requirement Met N 0%

1 COMPLIANCE OPTIONS - PERFORMANCE BASED - Is the design documented


N
ACQUIRE missing items
with calculations, references and sources, per NFPA 101 (Life Safety Code) 0% and create N 0%
3.4.9 and NFPA 664 (Chapter 5)? documentation

3.4.10
COMPLIANCE OPTIONS - PRESCRIPTIVE BASED - does the design meet the
requirements of NFPA 664 - Chapters 6 through 11? Y 100% Requirement Met N 0%

1 IF NO-This location MUST be a


N
This location has a Performance
REVIEWER(S) - EITHER Based System - I want questions 0% Prescriptive System-ONLY ANSWER the N 10%
Performance based system What in 3.5 to apply. Questions at 3.6 & skip 3.5
questions at 3.5 OR type of
i
Prescriptive based system
questions at 3.6 APPLIES - system does 0% total
value cell 20%

CHOOSE one then ONLY this location


ANSWER the questions in have? DO NOT manually enter value - it will
that section! automatically appear OR remain the 0% 10%
same based on your responses

1 NFPA 664 Chapter 5 - Performance-Based Design Option When? Who?


Don't Enter this value -
3.5 These questions assess the Performance Based Design Option at
it automatically appears
based on question 0% Percentage for
this Question
10%
the location. Consult NFPA 664 for definitions and specific details. responses
NFPA 664
ANSWER ALL - Do ANY of the following exist? 10 0% When? Who? 10 100%

1
N
APPROVED QUALIFICATIONS & INDEPENDENT REVIEW - Was design VERIFY acceptability with
prepared by a person acceptable to the Authority Having Jurisdiction (AHJ)? 0% Authority Having Y 100%
3.5.1 Jurisdiction-AHJ

1
N
INDEPENDENT REVIEW - IF REQUIRED by the AHJ, was the design REVIEWED VERIFY requirement with
by an independent 3rd Party? (If NOT REQUIRED, answer Y for YES) 0% Authority Having N 0%
3.5.2 Jurisdiction-AHJ

1 VERIFY Data Sources &

3.5.3
DATA SOURCES - Have data sources for design aspects been identified? N 0% Design Aspects with
Authority Having
Jurisdiction-AHJ
N 0%

1
N
DESIGN FEATURES MAINTAINED - Are they maintained for operation as Maintain design features
originally designed, or modified with AHJ approval? 0% or obtain AHJ approval N 0%
3.5.4 for change

3.5.5
PREVENTION of IGNITION - Has the NFPA criteria been met? N 0% Prevent ignition per
NFPA criteria N 0%

1
N
Implement controls to
PREVENTION of FIRE EXTENSION - Has the NFPA criteria been met? 0% prevent fire from N 0%
3.5.6 spreading

1 Implement controls to

3.5.7
EFFECTS of DEFLAGRATION - Has the NFPA criteria been met? N 0% prevent effects of
deflagration-SEE NFPA
664
N 0%

3.5.8
DESIGN FIRE SCENARIOS - Has the NFPA criteria been met? N 0% Perform Design Fire
Scenarios per NFPA 664 N 0%

3.5.9
DEFLAGRATION SCENARIOS - Has the NFPA criteria been met? N 0% Perform Deflagration
Scenarios per NFPA 664 N 0%

1
N
EVALUATION of PROPOSED DESIGN - Did the AHJ approve all items identified Obtain AHJ Evaluation of
by NFPA 5.4? 0% proposed design NFPA N 0%
3.5.10 664- at 5.4

1 NFPA 664 Chapter 6 - Building Construction When? Who?


Don't Enter this value -
3.6 These questions assess the Prescriptive Based Design Option for
Building Construction at the location. Consult NFPA 664 for
it automatically appears
based on question
responses
0% Percentage for
this Question
10%

definitions and specific details.


These questions assess the Prescriptive Based Design Option for Percentage for
it automatically appears
based on question 0% this Question
10%
Building Construction at the location. Consult NFPA 664 for responses
NFPA 664 definitions and specific details.

ANSWER ALL - Do ANY of the following exist? 10 Overall response is: 0% When? Who? 10 100%

1
N
COMPARTMENTATION - are there passive fire protection features in place to Possible location
prevent the spread of FIRE / DEFLAGRATIONS? 0% UPGRADE may be Y 100%
3.6.1 needed - Consult AHJ

1
N
COMPARTMENTATION - are there Fire Walls, Fire Partitions, & Fire Barrier Possible location
Walls? 0% UPGRADE may be N 0%
3.6.2 needed - Consult AHJ

1
N
PROTECTION of OPENINGS & PENETRATIONS - are listed systems or Possible location
approved materials used that conform to NFPA 221? 0% UPGRADE may be N 0%
3.6.3 needed - Consult AHJ

1 OCCUPANT LIFE SAFETY SYSTEMS MEANS OF EGRESS - does the design,


N
Possible location
construction, installation, & maintenance of Life Safety Systems meet NFPA 0% UPGRADE may be N 0%
3.6.4 101 - Life Safety Code? needed - Consult AHJ

3.6.5
SPECIAL REQUIREMENTS - SURFACES & LEDGES IN DUST AREAS - are
interior areas designed to minimize dust accumulation? N 0% MINIMIZE dust at these
locations N 0%

1 SPECIAL REQUIREMENTS - DAMAGE LIMITING CRITERIA - are enclosed areas


N
Possible location
designed to prevent breach, provide explosion resistance, and include 0% UPGRADE may be N 0%
3.6.6 venting to a safe outside location? needed - Consult AHJ

1
N
SPECIAL REQUIREMENTS - DRAFT CURTAINS - where required, are they Possible location
made of noncombustible materials? 0% UPGRADE may be N 0%
3.6.7 needed - Consult AHJ

1
N
SPECIAL REQUIREMENTS - DRAFT CURTAINS - are they made of a minimum Possible location
of 26 gauge steel, and NOT made of Aluminum? 0% UPGRADE may be N 0%
3.6.8 needed - Consult AHJ

1 SPECIAL REQUIREMENTS - DRAFT CURTAINS - do they fit tightly against the


N
Possible location
roof deck, and extend downward a minimum of 10 Percent of the total 0% UPGRADE may be N 0%
3.6.9 height? needed - Consult AHJ

1
SPECIAL REQUIREMENTS - BEAMS, PURLINS & OTHER STRUCTURAL MEMBERS -
N
Does this location have these structures that extend downward equal to or greater Possible location
than 10 Percent of floor to ceiling height (IF YES - they are a substitute for DRAFT 0% UPGRADE may be N 0%
3.6.10 needed - Consult AHJ
CURTAINS)
1 NFPA 664 Chapter 7 - Prevention of Ignition & Control of Ignition Sources When? Who?
Don't Enter this value -
3.7 `These questions assess the Prevention of Ignition and Control of
Ignition Sources at the location. Consult NFPA 664 for definitions
it automatically appears
based on question
responses
6% Percentage for
this Question
29%

NFPA 664 and specific details.

ANSWER ALL - Do ANY of the following exist? 17 Overall response is: 100% When? Who? 17 500%

3.7.1
HOT WORK - Is Hot Work controlled according to NFPA 51B? (Also consult 29
CFR 1910.276 - Welding, Cutting, Burning) N 0% HOT WORK must be
controlled N 0%

1 ELECTRICAL SYSTEMS

3.7.2
ELECTRICAL SYSTEMS - Do electrical systems meet NFPA 70? (Also see OSHA
29 CFR 1910.303 and the following) N 0% must meet code
requirements-SEE NFPA
70
Y 100%

1
Wood exposed to HOT
HOT SURFACES - Are exterior surfaces of heated process equipment in
N
SURFACES exceeding the
contact with wood prevented from a MAXIMUM allowable temperature of 0% auto-ignition N 0%
3.7.3 500 degrees (500 *F) [260 *C]? temperature of wood at
399 degrees may ignite

1
Inadequate lubrication &

3.7.4
BEARINGS - Are they monitored for adequate lubrication and excessive
wear? N 0% wear leads to frictional
heating and auto-
ignition of wood dust
N 0%

1 Powered Industrial

3.7.5
POWERED INDUSTRIAL TRUCKS - IF they operate in areas with a deflagration
hazard, are they the correct classification? (See NFPA 505) N 0% Trucks are sources of
ignition-CHECK
Classification
N 0%

1 Evaluate & Upgrade

3.7.6
LIGHTING - Are they designed, installed, & maintained so they aren't an
ignition hazard during normal operation OR catastrophic failure? N 0% lighting to low
temperature & enclosed
devices
N 0%

1 FUEL FIRED EQUIPMENT - Are they designed, installed, & maintained so they
N
CHECK fuel fired
aren't an ignition hazard? (See NFPA 31-Oil Burning, NFPA 54-Fuel Gas, NFPA 0% equipment against NFPA N 0%
3.7.7 85-Boilers Combustion)? 31 requirements

1 STATIC ELECTRICITY - Does equipment contain design features that include -


N
Consult electrician for
Conductivity, bonding & grounding, grounded metal combs, other effective 0% Static Electricity N 0%
3.7.8 means approved by the AHJ? minimizations

1 MACHINES & PROCESSING EQUIPMENT - Are they operated per


N
Look for equipment
manufacturer's specifications, at a condition of sharpness to minimize heat, 0% generation of sparks and N 0%
3.7.9 and abrasives used within design life? ignition
1
Inspect for and minimize

3.7.10
FOREIGN MATERIAL - Is wood stock inspected for nails and other objects
prior to processing? N 0% foreign material that can
generate sparks and
cause ignition
Y 100%

1
FOREIGN MATERIAL - Is fugitive (A.K.A "tramp") metal prevented from
3.7.11
entering wood and dust process equipment? (These are materials capable of
creating a spark that could ignite materials)
Y 100% Determine materials
sources and minimize Y 100%

N
FRICTION - Is all equipment designed, installed, and operated to maintain CHECK equipment to
alignment and lubrication to avoid frictional heat ignition? 0% minimize frictional N 0%
3.7.12 heating

3.7.13
FANS - Is combustible residue on fans, fan shrouds, and drive mechanisms
prevented to avoid frictional heat ignition of the deposits? N 0% Schedule and maintain
cleaning of these parts N 0%

1 SPONTANEOUS IGNITION & CHEMICAL ACTION - Has the storage of wood


3.7.14
particulates been evaluated to determine any spontaneous ignition hazards
due to chemical reaction(s)?
N 0% Evaluate hazards and
minimize Y 100%

1 PROPELLANT ACTUATED TOOLS - Is their use PROHIBITED, UNLESS - dust


N
DON'T use propellant
producing machinery is shut down AND, Equipment / Floors / Walls are 0% actuated tools unless Y 100%
3.7.15 cleaned, AND dust accumulations are removed? conditions are met

1 SMOKING - Is smoking restricted to designated areas having devices for


3.7.16
smoking material disposal that is free of combustible / flammable hazards or
storage?
N 0% Restrict smoking as
specified N 0%

1 PORTABLE ELECTRIC EQUIPMENT & APPLIANCES - Is their use LISTED for the Equipment MUST be

3.7.17
areas where they're used? (Example - Space heaters approved for use in
dusty areas)
N 0% either UL or FM listed
and only sed where
allowed
N 0%

1 NFPA 664 Chapter 8 - Processes, Operations, & Special Systems When? Who?
Don't Enter this value -
3.8 These questions apply to SYSTEMS, such as pneumatic, dust control, mechanical conveyors, it automatically appears
and all other equipment types used to convey, re-size, dry, or otherwise process wood, wood based on question
responses
9% Percentage for
this SECTION
70%

particles, & cellulosic material.


NFPA 664

1 T-percent T-Count Q-Count Q-Sect% FTpercent FTCount FQCount FQSect%


ANSWER ALL - Do ANY of the following exist? 20% 60%
120% 13 10 200% 911% 13 10 600%
1 PARTICULATE CONVEYING & DUST COLLECTION SYSTEMS - Was a HAZARD
3.8.1
ANALYSIS done to determine if the materials was GREEN, DRY NON-
DEFLAGRABLE, or DEFLAGRABLE?
N 0% A Hazard Analysis must
be conducted Y 100%

1 FIRE & DEFLAGRATION HAZARD - Is ONLY GREEN MATERIAL collected or


N
IF green & dry material
conveyed in A SPECIFIC area? (IF YES, Fire & Deflagration hazards are 0% present - NFPA 664 N 0%
3.8.2 deemed non-exist in that area) controls required

1 FIRE & DEFLAGRATION HAZARD - Is DRY WOOD PARTICULATE collected or


3.8.3
conveyed in A SPECIFIC area? (IF YES, A Fire hazard is deemed to exist in that
area)
Y 100% NFPA 664 controls
required N 0%

1 FIRE & DEFLAGRATION HAZARD - Is OR Could DRY WOOD PARTICULATE be


3.8.4
suspended in air? (IF YES, A Deflagration hazard is deemed to exist in that
area)
N 0% NFPA 664 controls NOT
required N 0%

1 VERIFY-Non

3.8.5
PNEUMATIC CONVEYING & DUST COLLECTION SYSTEMS - Are all such
systems designed per NFPA 654? Y 100% professionally
engineered systems
WILL NOT qualify
Y 100%

1 PNEUMATIC CONVEYING & DUST COLLECTION SYSTEMS - Are ANY OTHER NFPA 664 PROHIBITS

3.8.6
spark producing systems tied into the woodworking particle conveying
system?
Y 0% THIS CONDITION.
Separate systems As
Soon As Possible
Y 0%

1
Y
PNEUMATIC CONVEYING & DUST COLLECTION SYSTEMS - Were ANY system System may need
modifications made (capture points, etc) WITHOUT system rebalancing? 0% rebalancing to assure N 100%
3.8.7 capture velocity

1
N
PNEUMATIC CONVEYING & DUST COLLECTION SYSTEMS - Is (Are) Dust MUST operate system
collection systems operated whenever wood stock is being processed? 0% when wood stock Y 100%
3.8.8 processed

1
N
DUCT SYSTEMS - GENERAL REQUIREMENTS - Are Duct systems METALLIC, MAXIMIZE METAL -
and NOT made of plastic(s)? 0% MINIMIZE PLASTIC - See Y 100%
3.8.9 comment for specifics

1
N
DUCT SYSTEMS - GENERAL REQUIREMENTS - Are Duct systems protected Provide corrosion
from corrosion AND bonded and grounded? 0% protection and-or bond Y 100%
3.8.10 & ground

1 DUCTS WITH A FIRE HAZARD - Answer the questions below FIRST - Don't Enter value it
Are ducts conveying DRY MATERIAL where equipment generates automatically appears
based on question 0% Percentage for this
Question 100%
3.8.11 sparks protected by one of the following? responses

Count SubCount SubSect% SubCount SubSect%


WHAT TYPE of CONTROL SYSTEM for 3.8.11? 0% 100%
1 0% 1 100%
1
N
System A: 1-Material Entry Point > 2-Listed Spark Detection & Extinguishing Provide corrosion
System > 3-Collection Equipment 0% protection and-or bond
& ground
Y 100%
N
System A: 1-Material Entry Point > 2-Listed Spark Detection & Extinguishing Provide corrosion
0% protection and-or bond Y 100%
3.8.11.1 System > 3-Collection Equipment & ground

1 System B: 1-LiSTED spark Detection & Extinguishing System > 2-Actuating a


N
Provide corrosion
High Speed Abort Gate > 3-Diversion to Atmosphere before entry to 0% protection and-or bond N 0%
3.8.11.2 collection or storage equipment & ground

1
N
System C: 1-Conveying to location with minimal personnel and personnel Provide corrosion
0% protection and-or bond N 0%
3.8.11.3 risk > 2-Acceptable Risk Analysis to the Authority Having Jurisdiction. & ground

1 DUCTS WITH A DEFLAGRATION HAZARD - Answer the questions below Don't Enter value it
FIRST -Are ducts having a deflagration hazard designed, constructed, and automatically appears
based on question 0% Percentage for this
Question 100%
3.8.12 installed by at least ONE of the following? responses

Count SubCount SubSect% SubCount SubSect%


WHAT TYPE of CONTROL SYSTEM for 3.8.12? 0% 100%
1 0% 1 100%
1 Provide corrosion
Control System A: 1-Ducts and all metal hatches constructed of metal; 2-
3.8.12.1 Able to withstand maximum deflagration pressures. N 0% protection and
ELECTRICALLY bond &
ground
Y 100%

1 Control System B: 1-Metal Ducts protected by a LISTED EXPLOSION


N
Provide corrosion
SUPPRESSION SYSTEM that is able to withstand maximum deflagration 0% protection and-or bond N 0%
3.8.12.2 pressures. & ground

1 Control System C: 1-Metal Ducts located INDOORS; 2-Equipped with


N
Provide corrosion
DEFLAGRATION RELIEF PIPES less than 20 feet length; 3-Extending to safe areas 0% protection and-or bond N 0%
3.8.12.3 outside of building; 4-Able to withstand maximum deflagration pressures. & ground

1
Control System D: 1-Metal Ducts located INDOORS; 2-equipped with
N
Provide corrosion
deflagration relief vents EXHAUSTING THROUGH LISTED FLAME QUENCHING 0% protection and-or bond N 0%
3.8.12.4 DEVICES; 3-Able to withstand maximum deflagration pressures. & ground

1 Control System E: 1-Metal Ducts located OUTDOORS; 2-equipped with


N
Provide corrosion
deflagration relief vents; 2-Able to withstand maximum deflagration 0% protection and-or bond N 0%
3.8.12.5 pressures. & ground

1
N
Control System F: 1-Metal Ducts located OUTDOORS; 2-Having weaker Provide corrosion
0% protection and-or bond N 0%
3.8.12.6 construction permitted IF subject to a RISK ANALYSIS acceptable to the AHJ. & ground

1
Check system
HOODS & ENCLOSURES - Do hoods & enclosures capture wood dusts and
N
performance against
particulates? (The air flow rate must be sufficient to capture & carry it into 0% design specifications- Y 100%
3.8.13 the ductwork) check for leaks or
material plugs
Check system
HOODS & ENCLOSURES - Do hoods & enclosures capture wood dusts and
N
performance against
particulates? (The air flow rate must be sufficient to capture & carry it into 0% design specifications- Y 100%
3.8.13 the ductwork) check for leaks or
material plugs

1 HOODS & ENCLOSURES - Are hoods & enclosures made of NON- NFPA 13-Standard for

3.8.14
COMBUSTIBLE MATERIALS? (IF NO, they MUST be protected by sprinklers
described by NFPA 13)
N 0% the Installation of
Sprinkler Systems-
applies
Y 100%

1 Don't Enter value it


DUST COLLECTORS - GENERAL REQUIREMENTS - CAUTION! NFPA 664
Specifies permitted dust collector placement based on SPECIFIC automatically
requirements. Pick the system placement at your location and consult
appears based on 0% Percentage for this
Question 100%
3.8.15 question responses
NFPA for detail. A SUMMARY of conditions appears below.

Count SubCount SubSect% SubCount SubSect%


NFPA ALLOWABLE DUST COLLECTOR LOCATIONS: 0% 100%
1 0% 1 100%
1
Check system

N
performance against
OUTSIDE OF BUILDINGS 0% design specifications- Y 100%
3.8.15.1 check for leaks or
material plugs

1
Check system

N
performance against
INDOORS - ONLY IF NO fire hazard or deflagration is deemed to exist. 0% design specifications- N 0%
3.8.15.2 check for leaks or
material plugs

1
N
INDOORS - Because ONLY A FIRE HAZARD exists AND it is PROTECTED by the Provide corrosion
0% protection and-or bond N 0%
3.8.15.3 design requirements of NFPA 664 & ground

1
N
INDOORS - Because A DEFLAGRATION HAZARD exists BUT it is PROTECTED by Provide corrosion
0% protection and-or bond N 0%
3.8.15.4 deflagration relief vents or pipes per the design requirements of NFPA 664 & ground

1
INDOORS - Because it is an ENCLOSURELESS device that MEETS the following: 1-
Used ONLY for wood processing machinery; 2-NOT used on Sanders or abrasive
N
Provide corrosion
planers; 3-Each collector has maximum air flow rate of 5000 cfm; 4-Fan motor is 0% protection and-or bond N 0%
3.8.15.5 totally enclosed and fan cooled; 5-Daily or greater removal of collected dust; 6- & ground
Collector located 20 ft or more from persons or other collectors.

1 DUST COLLECTORS WITH FIRE or DEFLAGRATION HAZARDS - Don't Enter value it


CAUTION! NFPA 664 requires specific construction methods. automatically appears
based on question 0% Percentage for this
Question 50%
3.8.16 Consult NFPA for requirements. responses
DUST COLLECTORS WITH FIRE or DEFLAGRATION HAZARDS - Don't Enter value it
CAUTION! NFPA 664 requires specific construction methods. automatically appears
based on question 0% Percentage for this
Question 50%
3.8.16 Consult NFPA for requirements. responses

Count SubCount SubSect% SubCount SubSect%


ANSWER ALL - Do ANY of the following exist? 0% When? Who? 50%
2 0% 2 100%
1
Do Dust collectors WITH FIRE HAZARDS meet the design requirements in
3.8.16.1 NFPA? N 0% Review NFPA 664 and
corrrect Y 100%

1
Do Dust collectors WITH DEFLAGRATION HAZARDS meet the design
3.8.16.2 requirements in NFPA? N 0% Review NFPA 664 and
corrrect N 0%

1
RECYCLED EXHAUST AIR - CAUTION! NFPA 664 prohibits recycling air UNLESS Don't Enter value it
certain equipment is installed based on the air flow rate of the system. Choose the automatically appears
based on question 0% Percentage for this
Question 100%
3.8.17 air flow rate at your location and consult NFPA for detail. responses

Count SubCount SubSect% SubCount SubSect%


ANSWER The Question that applies to your system: 0% When? Who? 100%
1 0% 1 100%
1
Do RECYCLED AIR SYSTEMS less than or equal to 5000 cubic feet per minute
3.8.17.1 (CFM) meet the design requirements in NFPA 664? N 0% Review NFPA 664 and
corrrect Y 100%

1
Do RECYCLED AIR SYSTEMS greater than 5000 cubic feet per minute (CFM)
3.8.17.2 meet the design requirements in NFPA 664? N 0% Review NFPA 664 and
corrrect N 0%

1 Don't Enter value it


MECHANICAL CONVEYING SYSTEMS - GENERAL REQUIREMENTS - automatically Percentage for
CAUTION! NFPA 664 has specific requirements for mechanical appears based on 0% this Question
71%
3.8.18 conveying system design. question responses

What design features does your system have? Answer all that Count SubCount SubSect% SubCount SubSect%
apply: 0% When? Who? 71%
7 0% 7 500%
1
Designed, Installed, & Operated to maintain alignment and minimize
3.8.18.1 excessive heat build-up? N 0% Review NFPA 664 -
Minimize heat build-up Y 100%

1
N
Review NFPA 664 and
Fugitive dust emissions minimized? 0% Minimize fugitive dust Y 100%
3.8.18.2 emissions
1
N
Review NFPA 664 and
Dust tight ball or roller bearings used wherever practical? 0% UPGRADE bearings N 0%
3.8.18.3 where possible

1
Bearings and bushings located outside of equipment UNLESS there's no
3.8.18.4 other alternative? N 0% Review NFPA 664 and
correct where needed N 0%

3.8.18.5
Shaft seals provided where rotating shafts penetrate equipment walls? N 0% Review NFPA 664 and
correct where needed Y 100%

3.8.18.6
Access hatches & covers tightly fitted & fastened for dust tight operation? N 0% Review NFPA 664 and
UPGRADE as required Y 100%

1
Do Mechanical Conveying Systems with a FIRE or DEFLAGRATION Hazard
3.8.18.7 meet NFPA 664 sprinkler & isolation requirements? N 0% Review NFPA 664 and
UPGRADE as required Y 100%

1 Don't Enter value it


THERMAL OIL HEATING SYSTEMS - CAUTION! NFPA 664 has
specific requirements for thermal oil heating systems. Inspect your automatically Percentage for
location's equipment based on the specific requirements below.
appears based on 0% this Question
30%
3.8.19 question responses
Consult NFPA for detail.

Count SubCount SubSect% SubCount SubSect%


ANSWER ALL - Do ANY of the following exist? 0% When? Who? 30%
10 0% 10 300%
1
N
Designed, Operated, & Maintained to minimize thermal oil spills, fires, & Review NFPA 664
0% requirements and N 0%
3.8.19.1 explosions? corrrect

1
N
Review NFPA 664
Physically separated from a manufacturing area? 0% requirements and N 0%
3.8.19.2 corrrect

1
N
Review NFPA 664
Discharged to a safe location? 0% requirements and N 0%
3.8.19.3 corrrect

1
NON-WELDED piping

3.8.19.4
Uses a WELDED piping system? N 0% systems are NOT
acceptable-Review NFPA
664 and corrrect
Y 100%

1
Are piping systems INSULATED if routed through production areas? N 0% Review NFPA 664 and
corrrect N 0%
3.8.19.5
Are piping systems INSULATED if routed through production areas? N 0% Review NFPA 664 and
corrrect N 0%

1
N
Review NFPA 664
Do expansion or storage tanks meet design requirements? 0% requirements and N 0%
3.8.19.6 corrrect

3.8.19.7
Are there SAFETY CONTROLS & INTERLOCKS? N 0% Review NFPA 664 and
corrrect N 0%

3.8.19.8
Has FUEL BURNER CONTROLS & INTERLOCKS? N 0% Review NFPA 664 and
corrrect N 0%

1
Review NFPA 664
Have OPERATIONAL CONSIDERATIONS been completed? (Procedures,
3.8.19.9 operator training, etc) N 0% requirements-Create
procedures and conduct
operator training
Y 100%

1
N
Is FIRE PROTECTION provided, IF REQUIRED, for areas where a hot oil spill Review NFPA 664
0% requirements and Y 100%
3.8.19.10 could accumulate? (SEE NFPA 664 8.3.2.10) corrrect

1 Don't Enter value it


PARTICULATE SIZE REDUCTION EQUIPMENT - CAUTION! NFPA 664 has
specific requirements for particulate size reduction equipment. These automatically Percentage for
requirements apply to operations that include specific types of products
appears based on 0% this Question
0%
3.8.20 question responses
or production equipment. Consult NFPA for detail.

Count SubCount SubSect% SubCount SubSect%


ANSWER ALL - Have the following been completed? 0% When? Who? 0%
3 0% 3 0%
1
N
Review NFPA 664-Hazard
Was the HAZARD ANALYSIS based on particle size? 0% Analysis MUST be based N 0%
3.8.20.1 on particle size

1
Is foreign material (AKA, Tramp metal), removed by self-cleaning magnets,
3.8.20.2 air separators, or BOTH? N 0% Review NFPA 664 and
corrrect N 0%

1
Does equipment meet NFPA requirements for FIRE or DEFLAGRATION
3.8.20.3 hazards? (SEE NFPA 664 beginning at 8.4.2.3) N 0% Review NFPA 664
requirements N 0%
1 Does the reviewed location
N
IF NO - SPECIAL REQUIREMENTS DON'T APPLY to
MAKE Panel Products like 100% you. You've been FULLY CREDITED. SKIP Questions
3.8.21 & 3.8.22 & 3.8.23
N 100%
PLYWOOD or MDF?
REVIEWER(S) - SPECIAL
REQUIREMENTS APPLY TO Provide a
i
Average F-Average Q-Total F-Total F3.8.21 F3.8.22 F3.8.23
PANEL MANUFACTURERS - response to 0% 0% 3
100% total
value cell
0% 0% 0%
100%
CHOOSE Either A or B and this question 3
follow the instructions 3.8.21 3.8.22 3.8.23
DO NOT manually enter value - it will
automatically appear OR remain the 0% 0% 0% 0% 0%
same based on your responses

1 Don't Enter value it


PANEL PRODUCT MANUFACTURING EQUIPMENT - CAUTION! automatically Percentage for
NFPA 664 has specific requirements for panel product appears based on 0% this Question
0%
3.8.21 manufacturing equipment. Consult NFPA for detail. question responses

Count SubCount SubSect% SubCount SubSect%


ANSWER ALL - Do ANY of the following exist? 0% When? Who? 0%
4 0% 4 0%
1
N
Review NFPA 664 -
Is dust controlled within enclosures? 0% Provide enclosures to N 0%
3.8.21.1 control dust

1
Designed, Installed, & Operated to maintain alignment and minimize
3.8.21.2 excessive heat build-up? N 0% Review NFPA 664 and
corrrect N 0%

1
Foreign material is removed by self-cleaning magnets, air separators, or
3.8.21.3 BOTH? N 0% Review NFPA 664 and
corrrect N 0%

3.8.21.4
Designed, Installed, & Operated for dust tight operation? N 0% Review NFPA 664 and
corrrect N 0%

1 Don't Enter value it


DRYER SYSTEMS - CAUTION! NFPA 664 has specific requirements automatically Percentage for
for dryer systems. Consult NFPA 664 for detail.
appears based on 0% this Question
0%
3.8.22 question responses

Count SubCount SubSect% SubCount SubSect%


ANSWER ALL - Do ANY of the following exist? 0% When? Who? 0%
6 0% 6 0%
1
IF PRESENT, does my location meet requirements for VENEER and/or
FIBERBOARD DRYERS? N 0% Review NFPA 664 and
corrrect N 0%
IF PRESENT, does my location meet requirements for VENEER and/or
3.8.22.1 FIBERBOARD DRYERS? N 0% Review NFPA 664 and
corrrect N 0%

3.8.22.2
IF PRESENT, does my location meet requirements for ROTARY DRYERS? N 0% Review NFPA 664 and
corrrect N 0%

3.8.22.3
IF PRESENT, does my location meet requirements for CONVEYOR DRYERS? N 0% Review NFPA 664 and
corrrect N 0%

3.8.22.4
IF PRESENT, does my location meet requirements for FLASH TUBE DRYERS? N 0% Review NFPA 664 and
corrrect N 0%

3.8.22.5
IF PRESENT, does my location meet requirements for KILN DRYERS? N 0% Review NFPA 664 and
corrrect N 0%

3.8.22.6
IF PRESENT, does my location meet requirements for FINISH ROOM DRYERS? N 0% Review NFPA 664 and
corrrect N 0%

1 Schedule installation

N
POLLUTION CONTROL EQUIPMENT - Does pollution control equipment meet date and verify
NFPA 664 requirements? (SEE NFPA 8.9 for detail). 0% requirements with N 0%
3.8.23 Authority Having
Jurisdiction-AHJ

1 Don't Enter value it


FIRE CONTROL SYSTEMS - CAUTION! NFPA 664 has specific automatically Percentage for
requirements for fire control that vary by system type and location. appears based on 0% this Question
0%
3.8.24 Assess the presence of systems and check local requirements. question responses

Q-Count SubCount SubSect% SubCount SubSect%


ANSWER ALL - Do ANY of the following exist? 0% When? Who? 0%
6 0% 6 0%
1
IF REQUIRED, are fire control systems in place for DRY LUMBER storage? (If
3.8.24.1 not required, ANSWER YES) N 0% CHECK requirements and
VERIFY if needed N 0%

1
IF REQUIRED, are fire control systems in place for FLAMMABLE LIQUID
3.8.24.2 storage? (If not required, ANSWER YES) N 0% CHECK requirements and
VERIFY if needed N 0%

1
IF REQUIRED, are fire control systems in place for SILOS and/or STORAGE
BINS? (If not required, ANSWER YES) N 0% CHECK requirements and
VERIFY if needed N 0%
IF REQUIRED, are fire control systems in place for SILOS and/or STORAGE
3.8.24.3 BINS? (If not required, ANSWER YES) N 0% CHECK requirements and
VERIFY if needed N 0%

1
IF REQUIRED, are fire control systems in place for Indoor DRY, FINE
3.8.24.4 PARTICULATE storage? (If not required, ANSWER YES) N 0% CHECK requirements and
VERIFY if needed N 0%

1
IF REQUIRED, are fire control systems in place for HOT PRESSES - Continuous
3.8.24.5 or MULTI-OPENING Batch-Type? (If not required, ANSWER YES) N 0% CHECK requirements and
VERIFY if needed N 0%

1
IF REQUIRED, are fire control systems in place for WOOD SCRAP PROCESSING
3.8.24.6 & DISPOSAL? (If not required, ANSWER YES) N 0% CHECK requirements and
VERIFY if needed N 0%

1 NFPA 664 Chapter 9 - Fire Protection Systems Don't Enter value it


When? Who?
automatically
3.9 These questions apply to FIRE PROTECTION SYSTEMS. appears based on
question responses
0% Percentage for
this Question
80%
Requirements may vary and may not apply in every location.
NFPA 664

ANSWER ALL - Are the following items, IF REQUIRED, present


and properly designed?
5 0% When? Who? 5 400%

3.9.1
Automatic sprinklers? (SEE NFPA 13 or 15) N 0% Item NOT REQUIRED or
Exempt, or Not in Place Y 100%

3.9.2
Detection and Extinguishing systems? (SEE NFPA 11, 12, 15, 17, 25, 69, 72,
750, 2001) N 0% Item NOT REQUIRED or
Exempt, or Not in Place N 0%

3.9.3
Inside Hose Stations? (SEE NFPA 14) N 0% Item NOT REQUIRED or
Exempt, or Not in Place Y 100%

3.9.4
Water Supply? (SEE NFPA 20, 22, 24) N 0% Item NOT REQUIRED or
Exempt, or Not in Place Y 100%

3.9.5
Portable Fire Extinguishers? (SEE NFPA 10) N 0% Item NOT REQUIRED or
Exempt, or Not in Place Y 100%

1 NFPA 664 Chapter 10 - Human Element Don't Enter value it


When? Who?
automatically Percentage for
appears based on 33% this Question
100%
question responses
Don't Enter value it
automatically
3.10 These questions apply to the HUMAN ELEMENT under the NFPA appears based on
question responses
33% Percentage for
this Question
100%
664 definition.
NFPA 664

ANSWER ALL - Do ANY of the following exist? 12 400% When? Who? 12 1200%

3.10.1
Is there an INSPECTION, TESTING, & MAINTENANCE program for Fire &
Explosion protection systems? Y 100% Maintain as needed Y 100%

3.10.2
Does the INSPECTION, TESTING, & MAINTENANCE program also cover Dust
Collection systems? Y 100% Maintain as needed Y 100%

3.10.3
Are RECORDS for INSPECTION, TESTING, & MAINTENANCE kept for their
useful life? N 0% Ensure records are kept
for their useful life Y 100%

N
Conduct general & job-
Is GENERAL & JOB SPECIFIC Employee Training being done? 0% specific employee Y 100%
3.10.4 training

1
Ensure contractors are

N
Are CONTRACTORS properly trained, qualified, and their documentation properly trained,
retained on-site? 0% qualified, and their Y 100%
3.10.5 documentation is
retained on-site

N
Establish written policy
Is PORTABLE APPLIANCE use regulated by a written policy? 0% & regulate portable Y 100%
3.10.6 appliance use

N
Is EVERY INCIDENT that results in a FIRE or EXPLOSION INVESTIGATED & Investigate and record
RECORDED? 0% every incident involving Y 100%
3.10.7 fire or explosion

N
Establish a procedure for
Is there a procedure for Fire & Explosion System Impairments? 0% fire & explosion system Y 100%
3.10.8 impairment
N
Establish a procedure for
Is there a procedure for Fire & Explosion System Impairments? 0% fire & explosion system Y 100%
3.10.8 impairment

3.10.9
Is the procedure being used? N 0% Determine why and
implement procedures Y 100%

1
SMOKING - Is smoking restricted to designated areas having devices for
smoking material disposal that is free of combustible / flammable hazards or
3.10.10 storage? Y 100% Maintain as needed Y 100%

1
HOT WORK - Is Hot Work controlled according to NFPA 51B? (Also consult 29
3.10.11 CFR 1910.276 - Welding, Cutting, Burning) Y 100% Maintain as needed Y 100%

N
EMERGENCY PLANNING & RESPONSE - Does it meet the requirements of Meet requirements for
0% Emergency Planning & Y 100%
3.10.12 NFPA 600? (Also consult 29 CFR 1910.38 - Emergency Action Plan) Response

1 NFPA 664 Chapter 11 - Housekeeping Don't Enter value it


When? Who?
automatically
3.11 These questions apply to HOUSEKEEPING requirements under the appears based on
question responses
0% Percentage for
this Question 54%
NFPA 664 definition.
NFPA 664

CHECK and VERIFY the following conditions: 13 0% When? Who? 13 700%

1
N
Is the Housekeeping & Inspection program is DEVELOPED, MAINTAINED, & Develop, maintain &
DOCUMENTED? 0% document Housekeeping Y 100%
3.11.1 & Inspection program

1 Immediately remove

3.11.2
Are large quantities of waste or debris that impede energized or moving
equipment removed immediately? N 0% waste accumulation that
impedes equipment
operation
N 0%

1 Place combustible waste

3.11.3
Is combustible waste placed in metal covered receptacles until removed for
daily disposal? N 0% in metal covered
receptacles for daily
disposal
N 0%

1
Place non-reusable

N
Is non-reusable combustible waste placed in metal covered receptacles until combustible waste in
removed for daily disposal? 0% metal covered N 0%
3.11.4 receptacles for daily
disposal
Place non-reusable

N
Is non-reusable combustible waste placed in metal covered receptacles until combustible waste in
removed for daily disposal? 0% metal covered N 0%
3.11.4 receptacles for daily
disposal

1
N
Is collected Fugitive (Tramp) metal SEPARATED so it can't re-enter the Collect & separate
process? 0% fugitive metal to prevent Y 100%
3.11.5 system re-entry

1
N
Is Production Equipment maintained and operated to minimize debris & dust Collect & separate
escape? 0% fugitive metal to prevent Y 100%
3.11.6 system re-entry

1
N
Seal unreachable areas
If an area can't be reached for housekeeping purposes, is it sealed? 0% to prevent dust Y 100%
3.11.7 accumulation & ignition

1
Consider an assessment

3.11.8
If an area can't be reached TO ASSESS OPERATING TEMPERATURE, is a
remote detection method considered? N 0% method - surfaces
exceeding 399*F are an
ignition hazard
Y 100%

1
N
Cleanup combustable &
Are Combustible or Flammable liquid spills cleaned up without delay? 0% flammable liquid spills as N 0%
3.11.9 soon as possible

1 Cleanup Volatile oil &


Are volatile oil & resin residues removed from areas such as Ovens, Dryers,
3.11.10 Fume Extraction, or Ventilation systems? N 0% resin residues - they are
combustable or
flammable
Y 100%

1
Are volatile oil & resin residues that are removed STORED near sources of RELOCATE STORAGE-
ignition or areas such as Ovens, Dryers, Fume Extraction, or Ventilation
3.11.11 systems? N 0% Manage and Dispose of
volatile oil & resin
residues per regulations
N 0%

1
N
Are OILY soaked cloths or waste material stored in approved metal Provide approved metal

3.11.12 receptacles with self closing lids?


0% receptacles having self-
closing lids
Y 100%

1 Review NFPA 30 for


Are FLAMMABLE LIQUIDS, IF PRESENT, stored per the requirements of NFPA
3.11.12 30? (Flammable & Combustible Liquids Code) N 0% specific requirements
and UPGRADE storage
methods as needed
N 0%

1 Don't Enter value it


CLEAN-UP METHODS - CAUTION! NFPA 664 has specific automatically Percentage for
requirements for clean-up methods. Several procedures are appears based on 0% this Question
50%
3.11.13 allowed if other procedures are followed question responses

ANSWER ALL - Are the following conditions met? 4 0% When? Who? 4 200%

1 Floor & Equipment areas are vacuumed with a the correct equipment?
(Equipment MUST be approved for CLASS II, Division 1, Group G Per NFPA 70,
3.11.13.1 Article 502)(National Electrical Code) N 0% Review NFPA 664 and
corrrect Y 100%

1
Electrical and other Ignition Sources are either 1-SHUT DOWN or REMOVED
3.11.13.2 from the area, OR, 2-Classified for use in dusty areas. N 0% Review NFPA 664 and
corrrect N 0%

3.11.13.3
ONLY LOW Gauge air pressure of 15 Pounds Per Square Inch (PSI) is used. N 0% Review NFPA 664 and
corrrect N 0%

1
There are NO open flames, sparks from spark producing equipment, or hot
3.11.13.4 surfaces that can ignite a dust cloud or layer. N 0% Review NFPA 664 and
corrrect Y 100%

i
RESULTS SECTION - 4
Initial: 0% 1

This item is based on the OSHA Compliance Directive.

4.1 F4.1
Follow-Up: 0% 1 0% 0%
Follow-Up
STATUS Y Scores
Question
Number DETERMINATION, REQUIREMENT, OBSERVATION, MEASUREMENT for YES, N FIX WHAT? When? Who?
for NO

1 When? Who?
Is DUST ACCUMULATION equal to or greater than 1/32 of an inch?
4.1 Y
Control dust
0% accumulation to less
than 1/32 inch
N 100%

OSHA CPL Where?


RESULTS SECTION - 5
Initial: 0% 1

This item is based on the OSHA Compliance Directive.

5.1 F5.1
Follow-Up: 0% 1 0% 0%
Follow-Up
STATUS Y Scores
Question
Number DETERMINATION, REQUIREMENT, OBSERVATION, MEASUREMENT for YES, N FIX WHAT? When? Who?
for NO

1 Don't Enter value it


When? Who?
automatically
5.1 Is there VISIBLE DUST ACCUMULATION at the following areas? appears based on
question responses
0% PERCENTAGE 40%

OSHA CPL

ANSWER ALL - Do ANY of the following exist? 5 Overall response is: 0% When? Who? 5 200%

1 Control
5.1.1
Slopes Y 0% accumulation on
Slopes
Y 100%

1 Control
5.1.2
Overhead beams Y 0% accumulation on
Overhead Beams
Y 100%

1 Control
5.1.3
Joists Y 0% accumulation on
Joists
N 0%

1 Control
5.1.4
Ducts Y 0% accumulation on
Ducts
N 0%

1 Control
5.1.4
Equipment tops Y 0% accumulation on
Equipment Tops
N 0%
Control
5.1.4
Equipment tops Y 0% accumulation on
Equipment Tops
N 0%

RESULTS SECTION - 6
Initial: 0% 1

This item is based on the OSHA Compliance Directive.

6.1 F6.1
Follow-Up: 100% 1 0% 100%
Follow-Up
STATUS Y Scores
Question
Number DETERMINATION, REQUIREMENT, OBSERVATION, MEASUREMENT for YES, N FIX WHAT? When? Who?
for NO

1 When? Who?
Are DUST ACCUMULATIONS on all surfaces GREATER THAN Calculate area
6.1 5% of surface area? Y 0% square footage and
control to less than N 100%
5%
OSHA CPL Where?

RESULTS SECTION - 7
Completed: 0% 1

This item is based on the OSHA Compliance Directive.

7.1 F7.1
Follow-Up: 100% 1 0% 100%
Follow-Up
STATUS Y Scores
Question
Number DETERMINATION, REQUIREMENT, OBSERVATION, MEASUREMENT for YES, N FIX WHAT? When? Who?
for NO
Follow-Up
STATUS Y Scores
Question
Number DETERMINATION, REQUIREMENT, OBSERVATION, MEASUREMENT for YES, N FIX WHAT? When? Who?
for NO

1 When? Who?
Are DUST ACCUMULATIONS CONTROLLED under the Consult OSHA
7.1 Housekeeping standard (FED 29 CFR 1910.22) N 0% standard and
minimize dust N 100%
accumulation
OSHA CPL

RESULTS SECTION - 8
Initial: 13% 1

This item is based on the OSHA Compliance Directive.

8.1 F8.1
Follow-Up: 88% 1 13% 88%
Follow-Up
STATUS Y Scores
Question
Number DETERMINATION, REQUIREMENT, OBSERVATION, MEASUREMENT for YES, N FIX WHAT? When? Who?
for NO

1 Don't Enter value it


When? Who?
automatically
8.1 DETERMINE if IGNITION SOURCES are present anywhere in
the inspection area. Complete the questions below:
appears based on
question responses
13% PERCENTAGE 88%
OSHA CPL

ANSWER ALL - Are ANY of the following devices present? 8 Overall response is: 100% When? Who? 8 700%

8.1.1
Space heaters (electrical, gas, etc)? N 0% Controlled Y 100%

8.1.2
Heat Guns, Soldering irons, other electrical heat producing items? N 0% Controlled Y 100%
1
Remove or prohibit HOT

8.1.3
HOT WORK - Welding, Burning, Cutting in area? Y 100% WORK in area when
deflagration or explosion
conditions exist
Y 100%

8.1.4
Camp stoves or gas lanterns or other flame sources? N 0% Controlled N 0%

8.1.5
Hot Plates or other appliances? N 0% Controlled Y 100%

1
Halogen or Metal Halide lamps near the auto-ignition temperature of
8.1.6
wood (At approximately 399 *F) as verified by DIRECT MEASUREMENT
or Thermographic Imagery?
N 0% Controlled Y 100%

1
Metal surfaces such as bearings, drive motors, etc. near the auto-
8.1.7
ignition temperature of wood (approx 399 *F) as verified by DIRECT
MEASUREMENT or Thermographic Imagery?
N 0% Controlled Y 100%

1 OTHER Heat or Ignition causing SOURCES? (IF YES, LIST)

8.1.8 N 0% Controlled Y 100%

i
DETERMINATION - FIRE TRIANGLE OR DEFLAGRATION CONDITIONS?
DEFLAGRATION results from Oxygen, Heat, Fuel (wood dust) with DISPERSION IN AIR without confinement that results in a subsonic explosion
(A slow expanding pressure wave).

X
Cumulative "Percent
Prepared" & Hazard
Condition Indicated 6%
by "X" is:
Prepared" & Hazard
Condition Indicated
by "X" is:
6%
X
X
FOLLOW-UP
Cumulative "Percent
Prepared" & Hazard 56%
Condition Indicated
by "X" is:

RESULTS SECTION - 9
Initial: 0% 2

This item is based on the OSHA Compliance Directive.

9.1 9.2 F9.1 F9.1


Follow-Up: 50% 2 0% 0% 100% 0%
Follow-Up
STATUS Y Scores
Question
Number DETERMINATION, REQUIREMENT, OBSERVATION, MEASUREMENT for YES, N FIX WHAT? When? Who?
for NO

1 When? Who?
Could wood dust become dispersed in air due to vibration, other Control by
9.1 disturbances, OR a primary explosion? Y 0% minimizing
accumulation
N 100%

OSHA CPL Where?

1 Don't Enter value it


When? Who?
Determine if ANY of the following processes are occurring WHEN
9.2
automatically
dust could become dispersed in air due to vibration, other appears based on 0% PERCENTAGE 0%
disturbances, OR a primary explosion. ANSWER ALL conditions: question responses

OSHA CPL

ANSWER ALL - Are ANY of the following processes performed


WHILE MACHINERY IS OPERATING?
8 Overall response is: 0% When? Who? 8 0%

1
Control by procedure
that shuts down

9.2.1
Uncontrolled DUST BLOW DOWN operations on process equipment? Y 0% equipment-removes
IGNITION SOURCES and
requires immediate
Y 0%
Control by procedure
that shuts down

9.2.1
Uncontrolled DUST BLOW DOWN operations on process equipment? Y 0% equipment-removes
IGNITION SOURCES and
requires immediate
Y 0%

clean-up

1
Control by procedure

9.2.2
Uncontrolled AIR LANCING (at greater than 15 Pounds per Square Inch
[psi]) of equipment or areas? Y 0% that removes IGNITION
SOURCES and requires
immediate clean-up
Y 0%

1
Control by procedure

9.2.3
Uncontrolled FLOOR SWEEPING? Y 0% that removes IGNITION
SOURCES and requires
immediate clean-up
Y 0%

1
Control by procedure

9.2.4
Vibrating, moving, or milling equipment CAUSING DUST TO BE
AIRBORNE? Y 0% that removes IGNITION
SOURCES and requires
immediate clean-up
y 0%

1
Shut down system-

9.2.5
Has the Dust collection system failed OR been turned off? Y 0% Inspect-Repair unit-
Start-up and check
operation.
y 0%

1
Control by procedure
that isolates and-or

9.2.6
Is Excessive dust accumulation subjected to wind or other
environmental conditions? Y 0% minimizes dust
accumulation and
controls all IGNITION
y 0%

SOURCES

1
Control by procedure

9.2.7
Are Mechanical conveying systems in use, and CAUSING DUST TO BE
AIRBORNE? Y 0% that removes IGNITION
SOURCES and requires
immediate clean-up
y 0%

1 OTHER Conditions or equipment that CAUSE DUST TO BE AIRBORNE?


(IF YES, LIST) Control by procedure

9.2.8 Y 0% that removes IGNITION


SOURCES and requires
immediate clean-up
y 0%
Control by procedure

9.2.8 Y 0% that removes IGNITION


SOURCES and requires
immediate clean-up
y 0%

RESULTS SECTION - 10
Initial: 0% 1

This item is based on the OSHA Compliance Directive.

10.1 F10.1
Follow-Up: 100% 1 0% 100%
Follow-Up
DETERMINATION, REQUIREMENT, OBSERVATION, JUSTIFY PARTICLE STATUS Y Scores
Question SIZE for YES, N FIX WHAT? When? Who?
Number MEASUREMENT DETERMINATIONS for NO

1 When? Who?
Is the material explosible under the OSHA Lab test? (You MUST assume
10.1 Y
the answer is YES, UNLESS the particle size is too large OR the OSHA Control by applying
lab result is known. Randomly generated particles will include less 0% Housekeeping methods
and engineering controls
N 100%
than 420 micron size)
OSHA CPL

RESULTS SECTION - 11
Initial: 14% 2

This item is based on the OSHA Compliance Directive.

11.1 11.2 F11.2 F11.1


Follow-Up: 93% 2 29% 0% 100% 86%
Follow-Up
STATUS Y Scores
Question
Number DETERMINATION, REQUIREMENT, OBSERVATION, MEASUREMENT for YES, N FIX WHAT? When? Who?
for NO
Follow-Up
STATUS Y Scores
Question
Number DETERMINATION, REQUIREMENT, OBSERVATION, MEASUREMENT for YES, N FIX WHAT? When? Who?
for NO

1 Don't Enter value it


When? Who?
automatically
11.1 ANSWER the questions BELOW to determine if your location has
wood dust suspended in air, AND under confinement.
appears based on
question responses
29% PERCENTAGE 86%

OSHA CPL

ANSWER ALL - Does this location have any of the following process
equipment that has wood dust in air AND under confinement, AND 7 Overall response is: 200% FIX WHAT? When? Who? 7 600%
unprotected?

N
NFPA Engineering
Silos, Bunkers, Cyclones? 100% Controls NOT Needed Y 100%
11.1.1 OR already in place

N
NFPA Engineering
Covered screw conveyors? 100% Controls NOT Needed Y 100%
11.1.2 OR already in place

1
Review & Select NFPA

Y
engineering control
Air Ducts and associated piping? 0% options and VERIFY with Y 100%
11.1.3 Authority Having
Jurisdiction - AHJ

1
Review & Select NFPA

Y
engineering control
Dust Bins? 0% options and VERIFY with Y 100%
11.1.4 Authority Having
Jurisdiction - AHJ

1
Review & Select NFPA

Y
engineering control
Bag houses, either in-doors or outside areas? 0% options and VERIFY with Y 100%
11.1.5 Authority Having
Jurisdiction - AHJ

1
Review & Select NFPA
engineering control
options and VERIFY with N 0%
Review & Select NFPA

Y
engineering control

11.1.6
Intermediate stage collection vessels? 0% options and VERIFY with
Authority Having
N 0%
Jurisdiction - AHJ

1 OTHER - List:
Review & Select NFPA

Y
engineering control

11.1.7
0% options and VERIFY with
Authority Having
Y 100%
Jurisdiction - AHJ

1 Are there WORKING ENGINEERING CONTROLS that are currently protecting When? Who?
ALL of these systems from prevention or mitigation of Deflagrations And/or
11.2 N
NFPA Engineering
Explosions? 0% Controls NOT Needed
OR already in place
Y 100%

OSHA CPL List areas where NOT working:

i
DETERMINATION - DEFLAGRATION OR EXPLOSION CONDITIONS?
EXPLOSION is a DEFLAGRATION resulting from Oxygen, Heat, Fuel (wood dust) with dispersion in air WHICH IS UNDER CONFINEMENT, that
results in a Supersonic Explosion (a rapidly expanding pressure wave).

X
Cumulative "Percent
Prepared" & Hazard
Condition Indicated 5%
by "X" is:

X
FOLLOW-UP
Cumulative "Percent
Prepared" & Hazard 81%
Condition Indicated
by "X" is:

STOP HERE! This is The END of the Initial Self-Assessment CHECKLIST - Schedule a FOLLOW-UP
Assessment in 2 months to assess Performance after Corrective Action has been applied
2 MONTH FOLLOW-UP Percent
INITIAL Self-Assessment
CHECKLIST RESULT (in
Cumulative %)
15% Self-Assessment
CHECKLIST RESULT (in 65% PERFORMANCE
INCREASE (or 51%
Cumulative %) DECREASE)

2 MONTH FOLLOW-UP - DETERMINATION of CHECKLIST EFECTIVENESS, COMBUSTIBLE WOOD DUST INFORMATION, & CORRECTIVE ACTION

This Checklist is a Self-Assessment, Self-Scoring tool to determine percent compliance on Combustible Wood Dust Issues. As a measure of percent
effectiveness, a SECOND LOOK at identical issues AFTER the first look should result in the following: #1-Corrected Conditions, AND, #2-An
increased Self assessment score relative to the baseline. Comparative percentages is the best method to QUANTIFY RESULTS after information on
combustible wood dust has been presented, reviewed, and opportunities for corrective action have had a chance to be implemented.

1 WAS TRAINING & ASSESSMENT EFFECTIVE?- Provide SUMMARY EXPLANATION of PERFORMANCE Increase or Decrease

2 Provide DETAILED ANALYSIS for ANY QUESTION not resulting in PERFORMANCE Increase Duplicate rows as needed.

Question
Number

Question
Number
Question
Number

Question
Number

Question
Number

Question
Number

Question
Number

Question
Number

Question
Number

Question
Number
Question
Number